ConcreteSpecifications.pdf

PDF 11 KB Posted

Attached to
Restroom Repair and Fire Suppression Federal contract opportunity
Solicitation number
W912GY16B0006
Issued by
Department of the Army Materiel Command Contracting Command Detroit Arsenal

About this file

Concrete Specifications

View the file

Other files for this federal contract opportunity

Other files attached to Restroom Repair and Fire Suppression, newest first.
File Type Posted
OF_1419_Restroom_and_Fire_Suppression_201.xls XLS spreadsheet
Question_and_Answer_Set_7.doc DOC document
Questions_and_Answers_Set_6.doc DOC document
Questions_Set_5.doc DOC document
IMG_9203.JPG JPG image
IMG_9202.JPG JPG image
IMG_9200.JPG JPG image
IMG_9198.JPG JPG image
IMG_9201.JPG JPG image
IMG_9205.JPG JPG image
IMG_9199.JPG JPG image
IMG_9204.JPG JPG image
Questions_and_Answers_Set_4_201.doc DOC document
Amendment_0001_-_Extension_of_Closing_Date.pdf PDF
Questions_and_Answers_201_Set_3.doc DOC document
BLDG._201_1st_FLR_PLN-11x17.pdf PDF
BLDG._201_2nd_FLR_PLN-Layout1.pdf PDF
Scope_of_Work_Fire_Suppression_Revision.doc DOC document
Site_Visit_Sign_In_Sheet.pdf PDF
Questions_and_Answers_Set_2.doc DOC document
Question_and_Answer_Set_1_Fire_Suppression_System.doc DOC document
Drawing_-_Sheet_A-4.pdf PDF
Solicitation_16-B-0006.pdf PDF
Drawing_-_Sheet_A-6.pdf PDF
Drawing_-_Sheet_A-7.pdf PDF
Show all 25

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sierra Army Depot Concrete Specifications r’c (Min. 28- Maximum Range Water- Day Comp. Nominal of Cement Air Entr.

Strength) Aggregate Slump

Ratio

Location (psi) (Size No.) (inches) (by weight) (percent) Location (psi) (Size No.) (inches) (by weight) (percent)

All interior areas 3000 67 4 0.50 6

Concrete Exposed To weather 4000 57 6 0.50 6

Maximum slump shown above may be increased 1 inch for methods o£ consolidation other than vibration. Slump may be increased to 8 inches when superplasticizers are used.

Proportion concrete mixes for strength at 20 days.

2.3.1.1 Mix Proportions for Normal Weight Concrete

Trial design batches, mixture proportioning studies, and testing requirements for various classes and types of concrete specified are the responsibility of the Contractor. Base mixture proportions on compressive strength as determined by test specimens fabricated in accordance with ASTM C 192/C 192M and tested in accordance with ASTM C 39/C39 M. Samples of all materials used in mixture proportioning studies must be representative of those proposed for use in the project and must be accompanied by the manufacturer's or producer's test report indicating compliance with these specifications. Base trial mixtures having proportions, consistencies, and suitable for the work on methodology described in ACI/MCP-1. In the trial mixture, use at least three different water-cement ratios for each type of mixture, which must produce a range of strength encompassing those required for each class and type of concrete required on the project. The maximum water-cement ratio required must be based on equivalent water-cement ratio calculations as determined by the conversion from the weight ratio of water to cement by weight equivalency method. Design laboratory trial mixture for maximum permitted slump and air content. Each combination of material proposed for use must have separate trial mixture, except for accelerator or retarder use can be provided without separate trial mixture. Report the temperature of concrete in each trial batch. For each water-cement ratio, at least three test cylinders for each test age must be made and cured in accordance with ASTM C 192/C 192M and tested in accordance with ASTM C 39/C 39M for 7 and 28 days. From these results, plot a curve showing the relationship between water-cement ratio and strength for each set of trial mix studies. In addition, plot a curve showing the relationship between 7 and 28 day strengths.

2.3.1.2 Required Average Strength of Mix Design

The selected mixture must produce an average compressive strength exceeding the specified strength by the amount indicated in ACI/MCP-2. When a concrete production facility has a record of at least 15 consecutive tests, the standard deviation must be calculated and the required average compressive strength must be determined in accordance with ACI/MCP-2. When a concrete production facility does not have a suitable record of tests to establish a standard deviation, the required average strength must follow ACI/MCP-2 requirements.

2.3.2 Ready-Mix Concrete

Provide concrete that meets the requirements of ASTH C 94/C 94M.

Ready-mixed concrete manufacturer must provide duplicate delivery tickets with each load of concrete delivered. Provide delivery tickets with the following information in addition to that required by ASTM C 94/C 94M:

Type and brand cement

Cement content in 95-pound bags per cubic yard of concrete

Maximum size of aggregate

Amount and brand name of admixtures

Total water content expressed by water/cement ratio

2.3.3 Concrete Curing Materials

2.3.3.1 Absorptive Cover

Provide burlap cloth cover for curing concrete made from jute or kenaf, weighing 10 ounces plus or minus percent per square yard when clean and dry, conforming to ASTM C 171, Class 3; or cover may be cotton mats as approved.

2.3.3.2 Moisture·~Retaining Cover

Provide waterproof paper cover for curing concrete conforming to ASTM C 171, regular or white1 or polyethylene sheeting conforming to ASTM C 171, or polyethylene-coated burlap consisting of a laminate of burlap and a white opaque polyethylene film permanently bonded to the burlap; burlap must conform to ASTM C 171, Class 3, and polyethylene film must conform to ASTM C

171. When tested for water retention in accordance with ASTM C 156, weight of water lost 72 hours after application of moisture retaining covering material· must not exceed 0.039 gram per square centimeter of the mortar specimen surface.

2.3.3.3 Membrane-Forming Curing Compound

Provide liquid type compound conforming to ASTM C 309, Type 1, clear, Type 1D with fugitive dye for interior work and Type 2, white, pigmented for exterior work.

2 4 MATERIALS

2.4.1 Cement

ASTM C 309/C 150M, Type II, low alkali except as modified herein. Provide blended cement that consists of a mixture of ASTM C 150/C 150M, Type II cement and one of the following materials: ASTM C 618 pozzolan or fly ash, ASTM C 989. For Portland cement manufactured in a kiln fueled by hazardous waste, maintain a record of source for each batch. For exposed concrete, use one manufacturer for each type of cement and fly ash.

2.4.1.1 Fly Ash and Pozzolan

ASTM C 618, Type F. The maximum allowable loss on ignition must be 6 percent for Type F. Add with cement. The use of class F Fly ash is mandatory to mitigate the potential of Alkali Silica Reactivity (ASR) in concrete. Fly ash shall be used at a rate between 15 and 35 percent of the total cementitious material by weight. Fly ash content must be a minimum of 15 percent by weight of cementitious material, provided the fly ash does not reduce the amount of cement in the concrete mix below the minimum requirements of local building codes. Where the use of fly ash cannot meet the minimum level, provide the maximum amount of fly ash permittable that meets the code requirements for cement content. Report the chemical analysis of the fly ash in accordance with ASTM C 311. Evaluate and classify fly ash in accordance with ASTM D 5759.

High contents of supplementary cementitious materials can have some detrimental effects on the concrete properties, such as slowing excessively the strength gain rate, and delaying and increasing the difficulty of finishing. The recommended maximum content (by weight of the total cementitious material) for these materials are:

1. For fly ash or natural pozzolan: 35 percent (25 percent in cold climates)

2.4.1.2 Portland Cement

Provide cement that conforms to ASTM C 150/C 150M, Type 1, IA, II, or IIA.

Use one brand and type of cement for formed concrete having exposed-to-view finished surfaces.

2.4.2 Water

Minimize the amount of water in the mix. The amount of water must not exceed 45 percent by weight of cementitious materials (cement plus pozzolans), and in general, improve workability by adjusting the grading rather than by adding water. Water must be fresh, clean, and potable; free from injurious amounts of oils, acids, alkalis, salts, organic materials, or other substances deleterious to concrete.

2.4.3 Aggregates

ASTM C 33/C 33M, except as modified herein. Furnish aggregates for exposed concrete surfaces from one source. Provide aggregates that do not contain any substance which may be deleteriously reactive with the alkalies in the cement.

2.4.3.1 Aggregates/Combined Aggregate Gradation (Floor Slabs Only)

ASTM C 33/C 33M, uniformly graded and as follows: Nominal maximum aggregate size of 1 inch.