Amendment_3_-_KC46_Body_Tank_Storage_-_Plans.pdf
PDF 1 MB Posted
- Attached to
- KC-46A Body Tanks Storage Federal contract opportunity
- Solicitation number
- W912DS18B0020
About this file
Plans
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Bid_Abstract.pdf | ||
| AE601.pdf | ||
| Amendment_0006.pdf | ||
| Amendment__0005.pdf | ||
| Amendment_0004.pdf | ||
| Appendix_A_-_B1837_As-Builds.pdf | ||
| Appendix_C_-_JB_MDL_Soil_Contamination.pdf | ||
| Appendix_A_-_B1837_As-Builds.pdf | ||
| Appendix_B_-_Burlington_Co_Exemption_Notice_Bldg_1837.pdf | ||
| Amendment_3_-_KC46_Body_Tank_Storage_-_Specs.pdf | ||
| Amendment_0003_SF-30.pdf_Final.pdf | ||
| Amendment_0002.pdf | ||
| Site_Visit.pdf | ||
| Amendment_0001_final.pdf | ||
| Amendment_0001.pdf | ||
| Package_2_-_JB_MDL_-_Fuel_Body_Tanks_-_Specifications.pdf | ||
| W912DS18B0020.pdf | ||
| Package_3_-_JB_MDL_-_Fuel_Body_Tanks_-_CID.pdf | ||
| Package_1_-_JB_MDL_-_Fuel_Body_Tanks_-_Plans.pdf |
Show all 19
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GWH-1
A3
P-101
A3
P-101
FUEL SYSTEMS
MAINTENANCE
DOCK
ESEW-1
3/4" CA
3/4" CA
45100E
47900E
10000N 28
BODY TANKS
STORAGE
1/2" G
1" HW
1 1/4" CW
GROUND LEVEL
0' - 0"
ESEW-1
1" CW
1" HW
TMV-1
K C
-4
A A
D D
T O
B
F
O R
B O
D Y
T A
N K
S S
T O
R A
G E
P R
O J E
C T
N U
M B
E R
P
T F
L
J o in t B a s e
M c G u ir e
-D ix
-L a k e h u rs t, N e w
J e rs e y
P O
N D
-F S
B J oi nt
V en tu re
P ar kw ay
L an e, S ui te
P ea ch tr ee C or ne rs , G
A
P ho ne : 6
.3
.7 w w w .p on dc o.
co m
M A
Y
N
Y D
A /E
B O
R D
E R
F
IL
E N
A M
E
S u b m it te d b y
P lo t D a te
F
S B
A N
S I D
U S
A
R M
Y E
N G
IN
E
E R
D
IS
T R
IC
T
N E
W Y
O R
K h tt p /w w w
.n a n .u s a c e .a rm y .m il
F S
B
- W D
S O
L
IC
IT
A
T
IO
N N
O
F
IL
E N
A M
E
D W
N B
Y
C K
D B
Y
D E
S
IG
N E
D B
Y
D A
T E
S
IZ
E
S U
B M
IT
T
E D
B Y
P L O
T D
A T
E
C O
N T
R A
C T
N O
P L O
T T
E D
B Y
US Army Corps of Engineers
New York District
D E
S C
R
IP
T
IO
N M
A R
K A
P P
R
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
D
2 3
C
4 5
A
B
SHEET
REFERENCE
NUMBER
0 1"
THIS BAR IS ONE INCH ON
ORIGINAL DRAWING
IF NOT ONE INCH ON THIS
SHEET, ADJUST SCALES
ACCORDINGLY
xx xx c -x xx .d w g
95% SUBMITTAL
C U s e rs
\B o ri b o u n e S
\D o c u m e n ts
\1 -B
T S v M
E P n a iz e rj .r v t
/3
/2
:2
:5
A
M
/3
/2
:2
:5
A
M
P-101
F
IR
S T
F L O
O R
D O
M E
S T
IC
W
A T
E R
P
IP
IN
G
P L A
N
J L N
A P
M D
K H
A P
M
SCALE: = 1'-0"3/16"
0 4 8 124
SCALE: 3/16" = 1'-0"A1
FIRST FLOOR DOMESTIC WATER PIPING PLAN
CONNECT TO EXISTING COMPRESSED AIR LINES
IN HANGAR.
3/4" BREATHING COMPRESSED AIR DOWN TO
HOSE REEL. PROVIDE SHUTOFF VALVE AT MAIN.
3/4" SHOP COMPRESSED AIR DOWN TO HOSE
REEL. PROVIDE SHUTOFF VALVE AT MAIN.
CONNECT TO HANGAR DOMESTIC WATER LINE.
PROVIDE SHUTOFF VALVE AT MAIN.
PROVIDE GUARDIAN 3800LF SERIES
THERMOSTATIC MIXING VALVE OR EQUIVALENT.
1-1/4" TEMPERED WATER TO ESEW-1.
CONNECT TO EXISTING NATURAL GAS SYSTEM IN
HANGAR.
EXPANSION JOINT. PROVIDE +/- 2" MOTION.
PROVIDE SHUTOFF VALVE.
ROUTE PIPING TIGHT TO WALL. SHOWN ON
DRAWING FOR CLARITY ONLY.
ROUTE PIPING ABOVE OVERHEAD DOOR. MINIMUM
20' AFF.
PROVIDE HEAT TRACING (5 W/LF) ON EXTERIOR
PIPING. SEE ELECTRICAL.
ROUTE GWH-1 CONDENSATE DRAIN, FULL SIZE OF
UNIT DISCHARGE, TO SITE DRAIN. SEE C-120 FOR
CONTINUATION.
1. SEE SHEET P-001 FOR GENERAL PLUMBING NOTES
AND ABBREVIATIONS.
SCALE: 3/16" = 1'-0"A3
DOMESTIC WATER PIPING SECTION
N
GENERAL NOTES
SHEET KEYNOTES
A
M E
N D
M E
N T
-3 -1
M
.O
5/8"Ø
EXPANSION BOLTS
TYP. FOR SIX
UNIT HEATER SHALL BE
SECURED TO WALL
WITH A MINIMUM OF
TWO BRACKETS.
BRACKETS PER
MANUFACTURERS
RECOMMENDATIONS
SEISMIC BRACE
UNIT HEATER
TWO 5/8"Ø BOLTS,
EACH SIDE OF
FRAME WITH LOCK
WASHERS
FLEX CONNECTION
AIR FLOW
SPRING VIBRATION
ISOLATORSBASE MOUNT WITH STANDING SPRING ISOLATORS
K C
-4
A A
D D
T O
B
F
O R
B O
D Y
T A
N K
S S
T O
R A
G E
P R
O J E
C T
N U
M B
E R
P
T F
L
J o in t B a s e
M c G u ir e
-D ix
-L a k e h u rs t, N e w
J e rs e y
P O
N D
-F S
B J oi nt
V en tu re
P ar kw ay
L an e, S ui te
P ea ch tr ee C or ne rs , G
A
P ho ne : 6
.3
.7 w w w .p on dc o.
co m
M A
Y
N
Y D
A /E
B O
R D
E R
F
IL
E N
A M
E
S u b m it te d b y
P lo t D a te
F
S B
A N
S I D
U S
A
R M
Y E
N G
IN
E
E R
D
IS
T R
IC
T
N E
W Y
O R
K h tt p /w w w
.n a n .u s a c e .a rm y .m il
F S
B
- W D
S O
L
IC
IT
A
T
IO
N N
O
F
IL
E N
A M
E
D W
N B
Y
C K
D B
Y
D E
S
IG
N E
D B
Y
D A
T E
S
IZ
E
S U
B M
IT
T
E D
B Y
P L O
T D
A T
E
C O
N T
R A
C T
N O
P L O
T T
E D
B Y
US Army Corps of Engineers
New York District
D E
S C
R
IP
T
IO
N M
A R
K A
P P
R
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
D
2 3
C
4 5
A
B
SHEET
REFERENCE
NUMBER
0 1"
THIS BAR IS ONE INCH ON
ORIGINAL DRAWING
IF NOT ONE INCH ON THIS
SHEET, ADJUST SCALES
ACCORDINGLY
xx xx c -x xx .d w g
95% SUBMITTAL
C U s e rs
\B o ri b o u n e S
\D o c u m e n ts
\1 -B
T S v M
E P n a iz e rj .r v t
/3
/2
:3
:4
P
M
/3
/2
:3
:4
P
M
M-601
M E
C H
A N
IC
A
L S
C H
E D
U L E
S A
N D
D E
T A
IL
S
J L N
A P
M D
K H
A P
M
EXHAUST FAN SCHEDULE
MARK LOCATION SERVICE TYPE CFM
MINIMUM ESP
(IN. WG.)
DRIVE STARTER
FAN DATA MAX
SONES
BASIS OF DESIGN
WEIGHT
(LBS)
REMARKS
POWER (HP) VOLTS PHASE
EF-1 BODY TANKS STORAGE
GENERAL /
EMERGENCY
IN-LINE
CENTRIFUGAL
2700 0.50 BELT
MAGNETIC
EXPLOSION PROOF
1.00 208 1 12.2 GREENHECK TCB-2-16 252 1-5
LOUVER SCHEDULE
MARK LOCATION AREA / EQUIPMENT SERVED SERVICE
AIR FLOW
CFM
MIN FREE
AREA (SQ. FT.)
MIN
WIDTH
(FT.)
MIN
HEIGHT
(FT.)
NOMINAL
SIZE IN X IN
FACE
VELOCITY
(FPM)
MAXIMUM
PRESSURE
DROP (IN. WG.)
REMARKS
L-1 BODY TANKS STORAGE BODY TANKS STORAGE INTAKE 2900 6.4 SF 3' - 4" 3' - 4" 40" X 40" 455 0.03 1-7
REMARKS:
1. EXPLOSION PROOF, SPARK TYPE B.
2. PROVIDE NEMA PREMIUM EFFICIENCY MOTORS.
3. PROVIDE EC MOTOR.
4. DISCONNECT TO BE PROVIDED AND INSTALLED BY ELECTRICAL.
5. PROVIDE MANUFACTURER'S STARTER.
HOT WATER UNIT HEATER SCHEDULE
UNIT NO.
AIR FLOW
(CFM)
MOTOR
(HP)
HEATING DATA ELECTRICAL DATA BASIS OF DESIGN
WEIGHT
(LBS)
REMARKSHEATING
CAPACITY (BTUH)
LWT (°F) EWT (°F) GPM
MAX WPD
(FT. WG)
VOLTS PHASE MCA MANUFACTURER MODEL
HWUH-1 730 1/12 16.0 160 °F 190 °F 1.1 0.1 208 1 1.7 MODINE HC 47SB01SA 136 1-4
HWUH-2 730 1/12 16.0 160 °F 190 °F 1.1 0.1 208 1 1.7 MODINE HC 47SB01SA 136 1-4
HWUH-3 730 1/12 16.0 160 °F 190 °F 1.1 0.1 208 1 1.7 MODINE HC 47SB01SA 136 1-4
HWUH-4 730 1/12 16.0 160 °F 190 °F 1.1 0.1 208 1 1.7 MODINE HC 47SB01SA 136 1-4
REMARKS:
1. EXPLOSION PROOF.
2. 10' MINIMUM MOUNTING HEIGHT.
3. PROVIDE MANUFACTURER'S DISCONNECT SWITCH.
4. PROVIDE WALL MOUNTING KIT.
REMARKS:
1. SEE ARCHITECTURAL PLANS FOR LOUVER ELEVATIONS.
2. UNIT SHALL BE MADE OF ALUMINUM WITH AN ALLOY.
3. PROVIDE BIRDSCREENS. SCREENS SHALL BE CONTAINED WITHIN A REMOVABLE FRAME.
4. UNIT SHALL BE AMCA LICENSED.
5. FINISH TO BE SELECTED BY ARCHITECTURAL. PROVIDE ARCHITECT WITH COLOR WHEEL PER MANUFACTURER.
6. PROVIDE EXPLOSION PROOF MOTOR OPERATED DAMPER.
7. LOUVERS PROVIDED BY DIV. 23. COORDINATE WITH ARCHITECTURE.
SCALE: N.T.S.B1
WALL-HUNG ELECTRIC UNIT HEATER DETAIL
SCALE: N.T.S.A1
INLINE EXHAUST FAN DETAIL
FAN COIL UNIT SCHEDULE
MARK UNIT LOCATION
FAN DATA HEATING ELECTRICAL
BASIS OF DESIGN REMARKSTOTAL OA
CFM
ESP (IN WG)
MIN FAN
POWER (HP)
HEAT (MBH)
HEAT EAT
(°F) DB
HEAT LAT
(°F) DB
EWT
(°F)
LWT
(°F)
GPM
MAX WPD
(FT. WG)
VOLTS PHASE MCA (A) MOCP (A)
FCU-1 BODY TANKS STORAGE 2700 0.25 1.5 221.9 16.0 86.6 190 160 5.0 0.5 208 V 3 2.3 15 A CARRIER 42BHE 1 - 9
ROOF HOOD SCHEDULE
MARK SERVES CFM ESP (IN WG)
THROAT
WIDTH
THROAT
LENGTH
BASIS OF DESIGN
REMARKS
MAKE MODEL
RH-1 EF-1 2700 0.23 1' - 8" 1' - 8" GREENHECK FGR-20X20 1 - 5
REMARKS:
1. FINAL COLOR SELECTION SHALL BE MADE BY ARCHITECT AT TIME OF SHOP DRAWING APPROVAL. SUBMIT COLOR CHART
WITH SHOP DRAWINGS.
2. MATERIAL TO BE GALVANIZED STEEL OR ALUMINUM.
3. FURNISH PREFABRICATED, INSULATED CURB. COORDINATE ROOF CURB INSTALLATION WITH ROOFING CONTRACTOR.
4. HOOD TO HAVE 0.5” BIRD SCREEN AND 12” TALL BASE.
5. PROVIDE WITH AUTOMATIC BACKDRAFT DAMPER.
REMARKS:
1. DISCONNECT AND STARTER PROVIDED BY ELECTRICAL.
2. FILTER BOX WITH HIGH EFFICIENCY MERV 8 FILTERS.
3. EC MOTOR WITH SPEED CONTROLLER.
4. BUILDING AUTOMATION SYSTEM (BAS) INTERFACE.
5. SUSPENDED FROM STRUCTURE ABOVE WITH SPRING ISOLATORS.
6. EXTERNAL STATIC PRESSURE DOES NOT INCLUDE COIL, CASING, OR FILTER LOSSES.
7. PROVIDE DIRECT DRIVE FAN.
8. INTERNAL FILTER OR FILTER RACK BY FAN COIL UNIT MANUFACTURER WITH 1” THROWAWAY FILTERS.
9. EXPLOSION PROOF
A
M E
N D
M E
N T
-3 -1
M
.O
E
D E
S C
R I P
T I O
N M
A R
K A
P P
R
D A
T E
M A
R K
D E
S C
R I P
T I O
N D
A T
E A
P P
R
D
2 3
C
4 5
A
B
S O
L I C
I T
A T
I O
N
N
O
F I L
N
A M
E
D W
N
B
Y
C K
D
B
Y
D E
S I G
N E
D
B
Y
D A
T E
S I Z
E
S U
B M
I T
T E
D
B
Y
P L O
T
D
A T
E
C O
N T
R A
C T
O
A N
S I
D
P L O
T T
B
Y
U
S
A
R M
Y
E
N G
I N
E E
R
D
I S
T R
I C
T
N E
W
Y
O R
K h t t p w w w n a n u s a c e a r m y m i l
F S
B
- W
D
SHEET
REFERENCE
NUMBER
0 1"
K C
B
F
R
B
D
Y
T
A N
K S
S
O
R A
G E
P R
O J E
C
U M
B E
R
P
F
L
J o i n t
B a s e
M c G u i r e
D i x L a k e h u r s t
N w
J r s e y
C D
M
C D
M J B
B
THIS BAR IS ONE INCH ON
ORIGINAL DRAWING
IF NOT ONE INCH ON THIS
SHEET, ADJUST SCALES
ACCORDINGLY
PO
ND
-F
SB
Jo int
V en tur e
P ar kw ay
La ne
, S uit e 5
Pe ac htr ee
C or ne rs, G A
Ph on e:
8.3
.77 ww w.
po nd co
.co m
US Army Corps of Engineers
New York District
95% SUBMITTAL
C-502
C O
N S
T R
U C
T I O
N
D
E T
A I L
S
C
PCC
SUBGRADE
(SEE PAVEMENT
SECTION NOTES)
PAVEMENT NOTES:
1. PCC - 650 PSI FLEXURAL STRENGTH CONCRETE
PAVEMENT PER SPECIFICATION 32 13 13.06
SUBGRADE NOTES:
1. COMPACT TOP 12" TO 95% MAXIMUM DRY DENSITY
PER ASTM D-1557
JOINT NOTES
1. LONGITUDINAL AND TRANSVERSE JOINTS SHALL BE SAWED AS INDICATED.
2. TOP OF SEAL SHALL BE BELOW THE PAVEMENT SURFACE AS SPECIFIED.
3. TRANSVERSE CONSTRUCTION JOINTS SHALL BE PERMITTED ONLY WHERE
PAVING OPERATIONS STOP FOR THE DAY.
4. JOINT CONFIGURATION SHALL MEET JOINT SEAL MANUFACTURER'S
SPECIFICATIONS. (EXCEPT AS NOTED ON PLANS AND IN SPECIFICATIONS.)
5. THE WIDTH OF THE JOINTS SHALL BE CORRECTED FOR 68°F.
6. SEE TYPICAL SECTIONS FOR PAVEMENT THICKNESS.
7. SEE JOINT LAYOUT PLANS FOR LOCATIONS WHERE WELDED WIRE
REINFORCEMENT IS REQUIRED.
8. SEE SPECIFICATION SECTION 32 01 19 FOR CLEANING AND SEAL
INSTALLATION PROCEDURES.
9. ALL REINFORCEMENT SHALL BE FREE FROM LOOSE, FLAKY RUST, LOOSE
SCALE, OIL, GREASE, MUD, OR OTHER COATINGS THAT MIGHT REDUCE
THE BOND WITH CONCRETE.
10. "T" = THICKNESS OF NEW CONCRETE PAVEMENT. EXISTING CONCRETE
MAY BE THICKER THAN NEW CONCRETE. SAWCUT FULL-DEPTH VERTICAL
FACE IN EXISTING CONCRETE WHERE NEW CONCRETE IS PLANNED.
11. IF CONTRACTOR ELECTS TO PAVE DOUBLE LANES, THE DOWEL BARS AT
THE MID POINT JOINT ARE STILL REQUIRED.
12. IRREGULAR, UN-EVEN, OR ROUNDED JOINTS THAT ARE TOO WIDE TO BE
100% SHAPED BY SAW CUT DIMENSION IN DETAIL SHALL HAVE A LARGER
SEAL INSTALLED. CONTRACTOR SHALL FIRST DETERMINE THE NEW
RESERVOIR DIMENSIONS, SIZE OF THE SEAL TO BE APPROXIMATELY
TWICE THE JOINT WIDTH, THEN MAKE SUBMITTAL TO THE CONTRACTING
OFFICER PRIOR TO SHAPING THE RESERVOIR. LARGER SEAL
INSTALLATION SHALL BE FULL LENGTH
OF THE EFFECTED SLABS, TERMINATING
AT INTERSECTING JOINTS.
13. SEALS WITHOUT PROPER RECESS, OR
OTHERWISE IMPROPERLY INSTALLED,
SHALL BE REPLACED WITH NEW SEAL
FROM PLANNED JOINT TO PLANNED
JOINT.
INITIAL
FILL IN
T
T = THICKNESS OF PAVEMENT
d = DOWEL DIAMETER
1/2"
1/2 LENGTH ±
T
3/4" MIN.
5' MIN. (TYP)
C3
DOWELED CONTRACTION JOINT
AT EXISTING PAVEMENT - TYPE X
SCALE: N.T.S.
B2
THICKENED EDGE
EXPANSION JOINT - TYPE B2
SCALE: N.T.S.
A3
BITUMINOUS/ PCC
PAVEMENT JOINT - TYPE S
C-502
B1
C-502
D1
C-502
D3
T d/2T/2
X
SYMBOL:
S
SYMBOL:
COAT EXPOSED FACE OF BUTT JOINT
WITH CURING COMPOUND
NEW PORTLAND CEMENT
CONCRETE PAVEMENT
SEE SHEET A3/C-502
FOR DOWEL SIZE,
SPACING & NOTES
90° (VERTICAL AND HORIZONTAL)
TOLERANCE: 1/8" MAX PER FOOT OF
DOWEL
DRILLED HOLE W/ BAR EMBEDDED
INTO EPOXY GEL
EXISTING
PAVEMENT
NEW PORTLAND CEMENT
CONCRETE PAVEMENT
STRUCTURE OR
PAVEMENT
JOINT FILLER
ASPHALT
PAVEMENT
PORTLAND CEMENT
CONCRETE PAVEMENT
1.25 T
B2
SYMBOL:
A1
CONCRETE
PAVEMENT SECTION
SCALE: N.T.S.
D1
CONTRACTION JOINT COLD
APPLIED SEALANT DETAIL
SCALE: N.T.S.
FIELD POURED
JOINT SEALANT.
DEPTH EQUAL TO
1 - 1.5 TIMES
JOINT WIDTH (W)
BACKER ROD, NON-MOISTURE
ABSORPTIVE NON-REACTIVE
MATERIAL. DIAMETER EQUAL TO
JOINT WIDTH (W) PLUS 1/8"
COMPLETED JOINT
PCC PAVEMENT
SURFACE
D
ASPHALT PAVEMENT
SURFACEW
1/2" MIN. TO
5/8" MAX.
POURED JOINT SEALANT
RECESSED 1/4" TO 5/16"
BELOW PAVEMENT SURFACE
SAWCUT DEPTH AS
REQUIRED FOR
SEALANT RECESS
AND BACKER ROD
PROTECT
PAVEMENT FACE
B1
BITUMINOUS/ PCC PAVEMENT JOINT
HOT APPLIED SEALANT DETAIL
SCALE: N.T.S.
FIELD POURED SILICONE
JOINT SEALANT.
DEPTH EQUAL TO 0.5 X
JOINT WIDTH (W)
BUTTED JOINT
BACKER ROD, NON-MOISTURE
ABSORPTIVE NON-REACTIVE
MATERIAL. DIAMETER EQUAL TO
JOINT WIDTH (W) PLUS 1/8"
COMPLETED SAWCUT JOINT
PCC PAVEMENT
SURFACE
D
W
1/2" MIN. TO
5/8" MAX.
1/4" BEVELED
EDGE (TYP)
POURED JOINT SEALANT
RECESSED 1/4" TO 5/16"
BELOW PAVEMENT SURFACE
SAWCUT DEPTH
AS REQUIRED
FOR SEALANT
RECESS AND
BACKER ROD
FIELD POURED SILICONE
JOINT SEALANT.
DEPTH EQUAL TO 0.5 X
JOINT WIDTH (W)
BACKER ROD, NON-MOISTURE
ABSORPTIVE NON-REACTIVE
MATERIAL. DIAMETER EQUAL TO
JOINT WIDTH (W) PLUS 1/8"
PCC PAVEMENT
SURFACE
D
W
1/4" BEVELED
EDGE (TYP)
PREMOLDED JOINT FILLER
FOR FULL DEPTH OF SLAB
COMPLETED JOINT
POURED JOINT SEALANT
RECESSED 1/4" TO 5/16"
BELOW PAVEMENT SURFACE
3/4" MIN. TO
7/8" MAX.
JOINT FILLER
EXTENDS TO
PAVEMENT SURFACE
DURING INITIAL
CONSTRUCTION.
REMOVE JOINT
FILLER AS REQUIRED
FOR SEALANT
RECESS AND
BACKER ROD
D3
EXPANSION AND SLIP JOINT
COLD APPLIED SEALANT DETAIL
SCALE: N.T.S.
W=1/4" FOR SLIP JOINT
FOR EXPANTION JOINT
FIELD POURED, COLD APPLIED JOINT SEALANT NOTES:
1. DEPTH (D) AND WIDTH (W) OF JOINT SEALANT SHALL BE AS RECOMMENDED BY SEALANT MANUFACTURER.
2. FOR ALL JOINTS THE BACKER ROD MATERIAL SHALL BE COMPATIBLE WITH THE COLD POURED SEALANT AND SLIGHTLY OVERSIZED TO PREVENT
MOVEMENT DURING THE JOINT SEALANT OPERATION.
3. JOINT SEALANT MUST MEET NFGS 02522, 02562, AND ASTM 5893.
FIELD POURED, HOT APPLIED JOINT SEALANT NOTES:
1. DEPTH (D) AND WIDTH (W) OF JOINT SEALANT SHALL BE AS RECOMMENDED BY SEALANT MANUFACTURER.
2. FOR ALL JOINTS THE BACKER ROD MATERIAL SHALL BE COMPATIBLE WITH THE HOT POURED SEALANT AND SLIGHTLY OVERSIZED TO PREVENT
MOVEMENT DURING THE JOINT SEALANT OPERATION.
3. JOINT SEALANT MUST MEET ASTM D 3569.
DOWEL BAR INSTALLATION NOTES
1. DOWEL SLEEVES OR INSERTS ARE NOT PERMITTED.
2. DOWELS TO BE EPOXY COATED FULL LENGTH OF DOWEL. APPLY A LUBRICANT BOND BREAKER TO THE EPOXY COATED DOWEL IMMEDIATELY
PRIOR TO PAVING.
3. DOWEL BAR DIAMETER, LENGTH, AND SPACING TO BE AS SHOWN IN MATERIAL SCHEDULE (THIS SHEET).
4. DRILLING AND INSTALLATION METHOD SHALL BE CAPABLE OF MAINTAINING DRILL HOLES AND EMBEDDED BARS: (A) PARALLEL TO THE CONCRETE
SURFACE AND (B) NORMAL TO THE JOINT LINE, WITHIN SECTION 32 13 13.06 TOLERANCES. USE GANG DRILL WITH 3 OR MORE DRILLS. HOLE
DIAMETER TO BE APPROXIMATELY 1/8" LARGER THAN DOWEL. MINIMUM CURE TIME FOR DRILLING NEW CONCRETE PER SECTION 32 13 13.06.
5. AFTER THE DRILLING IS COMPLETE AND PRIOR TO INSTALLATION OF DOWELS, THE HOLES SHALL BE THOROUGHLY CLEANED BY HIGH PRESSURE
AIR TO REMOVE DRILLING DUST, CONCRETE CHIPS, AND ANY MATERIAL DETRIMENTAL TO BONDING.
6. INSERT EPOXY INTO BACK OF DOWEL HOLE BY INJECTION NOZZLE WITH SUFFICIENT EPOXY PLACED SO A SLIGHT AMOUNT IS FORCED OUT WHEN
DOWEL IS INSERTED AND TAPPED INTO CORRECT POSITION. EPOXY SHALL BE SOLID AROUND BARS WITH NO VOIDS. INSTALL METAL OR PLASTIC
DOWEL RINGS TO RETAIN EPOXY. SUBMIT PROPOSED EPOXY INFORMATION FOR APPROVAL PRIOR TO STARTING WORK.
7. CONTRACTOR SHALL RETAIN DRILL BIT MANUFACTURER'S REPRESENTATIVE TO TRAIN THE DRILLING CREW AND MAKE ADJUSTMENTS AS
REQUIRED TO THE COMPRESSOR AND DRILL RIG TO PRODUCE DRILL HOLES WITH MINIMAL EDGE SPALLING. MAXIMUM EDGE SPALLING ON FACE
IS PER SPECIFICATION SECTION 32 13 13.06/3.5.4 AND ACI 301.
BASKET NOTES:
1. WIRE USED IN BASKETS SHALL CONFORM TO ASTM-A1064 COLD DRAWN WIRE.
2. DOWEL BAR ATTACHMENT MAY BE FABRICATED BY ARC OR RESISTANCE TYPE WELDING.
3. WIRE FRAME MEMBERS SHALL BE RESISTANCE WELDED EXCEPT FOR SPACER BARS WHICH MAY BE ARC WELDED.
LINE
LONGITUDINAL JOINT
W
W/2
TRANSVERSE
JOINT LINE
D I R
E C
T I O
N
F
P
V
I N
G d d
10" MIN.
DOWEL (TYP)
L
NOTE:
SEE MATERIAL SCHEDULE (THIS SHEET) FOR DOWEL SIZE,
LENGTH AND DIMENSIONAL INFORMATION.
A3
DOWEL SPACING AT JOINT
CORNERS
MATERIAL SCHEDULE
ITEM
SLAB
THICKNESS
SIZE SECTION REMARKS
DOWELS 12" PCC
1" DIA. X 20"
LONG @ 15" O.C
32 13 11
EPOXY COATED, INCLUDING ENDS
T/4 (ROUNDED
UP TO NEXT
WHOLE INCH)
SCALE: N.T.S. SCALE: N.T.S.
SYMBOL:
"PCC
SUBGRADE
(SEE PAVEMENT
SECTION NOTES)
PAVEMENT NOTES:
1. PCC - 650 PSI FLEXURAL STRENGTH CONCRETE
PAVEMENT PER SPECIFICATION 32 13 13.06
AGGREGATE NOTES:
1. AGGREGATE BASE COURSE (ABC) PER
SPECIFICATION 32 11 23 AGGREGATE BASE COURSE.
SUBGRADE NOTES:
1. COMPACT TOP 12" TO 95% MAXIMUM DRY DENSITY
PER ASTM D-1557
A2
CONCRETE APRON
SCALE: N.T.S.
AGGREGATE BASE
SYMBOL:
W2.9XW2.9
WHERE INDICATED BY "R"
M E
N D
M E
I P
AutoCAD SHX Text
MAY 2010 NYD A/E BORDER
AutoCAD SHX Text FILE NAME:M:\USACE, NEW YORK DISTRICT\1180250-163008 BODY TANKS STORAGE\04.CAD_BIM\04.02.CAD\C-502.DWG
AutoCAD SHX Text Submitted by:
AutoCAD SHX Text Plot Date:8/31/2018 2:46 PM
AutoCAD SHX Text
FSB
| Sheets |
| P-101 - FIRST FLOOR DOMESTIC WATER PIPING PLAN |