PLANS_Pages_201-250.pdf

PDF 23 MB Posted

Attached to
Pershing Barracks Renovation/Modernization, West Point New York Federal contract opportunity
Solicitation number
W912DS-16-B-0010
Issued by
Department of the Army Corps of Engineers Engineering District New York

About this file

Plans 5

View the file

Other files for this federal contract opportunity

Other files attached to Pershing Barracks Renovation/Modernization, West Point New York, newest first.
File Type Posted
Bid_Abstract.pdf PDF
Amendment_0006.pdf PDF
Amendment_0005.pdf PDF
Amendment_0005_Project_Table_of_Contents_IFB_final.pdf PDF
Amendment_0005_Sections_Specsrr.pdf PDF
Amendment_0005_CD101_-_Exhibit_-_Temporary_Fence.pdf PDF
Amendment_0005_Pershing_Submittal_Register_IFB.pdf PDF
Amendment_0003_Historical_Pictures.pdf PDF
Amendment_0003_Drawings.pdf PDF
Amendment_0003_Pershing_Field_Investigation_Report.pdf PDF
Amendment_0003_EXHIBIT_-_SITE_UTILITIES.pdf PDF
B-1_Pershing_751_Framing_plbg_roof.pdf PDF
Pershing_738_740_751_Repair Shower Rooms.pdf PDF
6833.tif TIF image
Amendment_0002_Site_Visit_Sign_In_Sheet.pdf PDF
Amendment_0002.pdf PDF
7687-5942.tif TIF image
B-7_Pershing_751_painting.pdf PDF
36993_00751_01.dwg DWG drawing
Amendment_0002_Geotechnical_Evaluation.pdf PDF
36993_00751_04.dwg DWG drawing
Pages from C-6_Pershing_751_fixtures_roof plan_windows.pdf PDF
1261.tif TIF image
7687-5941.tif TIF image
A-1_Pershing_751_Maint and Repairs.pdf PDF
LIFE SAFETY Pages from A-1_Pershing_751_Maint and Repairs 1.pdf PDF
36993_00751_02.dwg DWG drawing
C-7_Pershing_751_flooring_painting.pdf PDF
36993_00751_03.dwg DWG drawing
NO. 2.tif TIF image
A-8_Pershing_751_Roof Repl and insul.pdf PDF
7687-5947.tif TIF image
B-8_Pershing_conversion_arch_plbg_HVAC_elec.pdf PDF
C-6_Pershing_751_fixtures_roof plan_windows.pdf PDF
7687-5943.tif TIF image
A-6_Pershing_751_Maint Rep_conversion.pdf PDF
C-8_Pershing_751_floor plans_roof plan.pdf PDF
7687-5939.tif TIF image
7687-5945.tif TIF image
7687-5940.tif TIF image
B-6_Pershing_751_Floor_roof plans.pdf PDF
36993_00751_L1.dwg DWG drawing
Amendment_0001_Section_28_08_10.pdf PDF
Amendment_0001_Section_28_10_05.pdf PDF
Amendment_0001.pdf PDF
PLANS_Pages_51-100rd.pdf PDF
PLANS_Pages_251-320.pdf PDF
PLANS_Pages_1-50.pdf PDF
W912DS-16-B-0010.pdf PDF
2016_0608_Pershing_IFB_Specs_Volume_2.pdf PDF
Show all 50

Pershing Barracks Renovation/Modernization, West Point New York has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BASEMENT LEVEL

FIRST LEVEL

SECOND LEVEL

THIRD LEVEL

FOURTH LEVEL

ROOF LEVEL

CEILINGFCU-4

R

FCU-4 CEILING

FCU-2 FCU-2FCU-2FCU-2FCU-3

FCU-5

HX-1

FCU-4

FCU-4

FCU-2

FCU-2 FCU-2

FCU-2 FCU-2

FCU-2 FCU-2

FCU-5

FCU-5

FCU-7

FCU-2

FCU-2

FCU-1

HWC-4A

FCU-2FCU-2

FCU-2FCU-2

FCU-2FCU-2

FCU-4FCU-2

FCU-4FCU-2

FCU-4FCU-2

FCU-5FCU-4

FCU-3

FCU-5

FCU-2 FCU-2

FCU-2 FCU-2

FCU-2 FCU-2

FCU-2 FCU-2

CEILING

CEILING

R

R

R

R

R

R

R

R

6" HWS

6" HWS

4" HWR

4" HWR

6" HWR

6" HWS

4" HWR

3" CHWR

2-1/2" CHWR2-1/2" CHWR

2" CHWR

1-1/2" CHWS

2" CHWS

2" CHWS

1-1/4" HWR

1-1/2" HWS

1-1/2" CHWS

1-1/4" HWS

1-1/2" CHWS

1-1/2" HWS

1-1/4" HWS

1-1/2" CHWS 1-1/4" HWS

1-1/2" CHWS

1-1/2" HWS

1-1/2" CHWS

1-1/4" CHWS

1-1/4" HWS

3" CHWS

2" CHWS

4" HWR

1-1/2" CHWS 2" CHWS

1-1/4" HWS

1-1/4" HWS

2" HWS 2" HWS 1-1/2" HWS 1-1/4" HWS

2" CHWS

6" HWS

4" HWR

6" HWS

2" HWS

1-1/4" HWR

1-1/2" HWR

1-1/2" CHWR

1-1/2" CHWR

1-1/4" HWR1-1/2" CHWS

1-1/2" CHWS

HX-2

HWP-2

HWP-1

CUH-1

FCU-7 CUH-1

FCU-7 CUH-1

FCU-7 CUH-2

CUH-1

1-1/2" HWS

FCU-8 FCU-8

CUH-1

1-1/2" CHWR

HWC-3A

1" HWS/R

FTR-1

HWC-2A

HWC-1A

FCU-8

CUH-1

UH-1

1-1/2" HWR

1-1/2" HWS

FCU-8 FCU-8

1-1/2" CHWR

1-1/4" HWR

2-1/2" CHWR

1-1/2" CHWR

1-1/4" HWR

FCU-7

FCU-3

FCU-7

FCU-3

FCU-7

FCU-8

FCU-7

1-1/2" CHWR

1-1/4" HWR

3" CHWR

1"

1"

1"

1"

1. MINIMUM PIPE RISER SIZE SHALL BE 1-1/4" UNLESS OTHERWISE INDICATED.

2. MINIMUM PIPE RUN-OUT SIZE SHALL BE 3/4" UNLESS OTHERWISE INDICATED.

3. MINIMUM DRAIN LINE SIZE SHALL BE 3/4" UNLESS OTHERWISE INDICATED.

GENERAL NOTES:

FTR-1

FTR-1 FTR-1

FTR-1 FTR-1

4. DASHED LINES REPRESENT HYDRONIC RETURN PIPING.

5. SUPPORT TOP OF ALL HEATING WATER RISERS (HWS) WITH SPRING TYPE HANGERS

H W

R

H W

S

C D

C H

W S

C H

W R

C H

W S

C H

W R

C D

H W

S

H W

R

H W

R

H W

S

C D

C H

W S

C H

W R

C H

W S

C H

W R

C D

H W

S

H W

R

C H

W S

C H

W R

C D

H W

S

H W

R

C H

W S

C H

W R

C D

H W

S

H W

R

C H

W S

C H

W R

C D

H W

S

H W

R

H W

R

H W

S

C D

C H

W S

C H

W R

H W

R

H W

S

C D

C H

W S

C H

W R

C H

W S

C H

W R

C D

H W

S

H W

R

H W

R

H W

S

C D

C H

W S

C H

W R

C H

W S

C H

W R

C D

H W

S

H W

R

C H

W S

C H

W R

C D

H W

S

H W

R

C H

W S

C H

W R

C D

H W

S

H W

R

C H

W S

C H

W R

C D

H W

S

H W

R

H W

R

H W

S

C D

C H

W S

C H

W R

ET-1

AS-1

H W

S

H W

R

HWS

HWR HWR

HWS

HWS

HWS HWS

CHWS

HWR

CHWSCHWS

HWS

HWR HWR

CHWR CHWR CHWR

1-1/2" HWR

MECH ROOM 002

SUPPORT WITH SPRING TYPE

HANGER AT ELBOW

MANUAL AIR VENT

4" HWR

HOSE END DRAIN VALVE W/CAP

& CHAIN AT BOTTOM OF RETURN

RISER (TYPICAL)

AIR SEPARATOR WITH AIR REMOVAL FITTING

AND BOTTOM OF ALL HEATING WATER RISERS (HWR) WITH WITH SPRING TYPE HANGERS.

1-1/4" HWS

1-1/4"CHWS

1-1/4" CHWR

1-1/4" HWR

DIFFERENTIAL

PRESSURE

TRANSMITTER

1-1/4" HWR

1-1/4" CHWS

1-1/2" HWS

1-1/4" HWS

1-1/4" CHWR

1-1/4" HWR

1-1/4" CHWR

1-1/4" CHWS

1-1/4" CHWS

1-1/4" CHWR

1-1/4" CHWR

1-1/4" CHWR

1-1/4" CHWS

HOSE END DRAIN VALVE W/CAP

& CHAIN AT BOTTOM OF RETURN

RISER (TYPICAL)

6. PROVIDE MANUAL AIR VENTS AT THE TOP OF ALL CHILLED WATER SUPPLY AND HEATING WATER SUPPLY

WATER RISERS. SEE DETAIL 13/M-603 “TYPICAL HVAC PIPE RISER BRANCH CONNECTION DETAIL”.

7. PROVIDE MANUAL AIR VENTS IN CHWS AND HWS MAINS LOCATED IN THE 4TH FLOOR CEILING NO

GREATER THAN 100 FEET APART.

D

UN RCO

UT Y

HONOR

T Y

MD

CC

CII

PO INWEST T

USM A

DRAWN BY:

U. S. ARMY

GARRISON

PROJECT:

ARCHITECTURE, INTERIORS,

CIVIL, LANDSCAPE, MECHANICAL,

PLUMBING, FIRE PROTECTION

NORTH AMERICA INC

2318 MILL ROAD,

SUITE 1040,

ALEXANDRIA, VA 22314.

TELEPHONE: (703) 535-3008

FAX: (703) 535-1031

R.G.VANDERWEIL, LLP

1001 AVENUE OF THE

AMERICAS, 21st FLOOR

NEW YORK, NY 10018

ELECTRICAL,TELECOMMUNICATION,SECURITY

212.921.4142 TEL

212.921.4616 FAX

VANDERWEIL.com

CLIENT

Revision / Submission

XXX XXX XXX XXX XXX XXX

Date

00-00-00

Rev.#Rev. By

00-00-00

WEST POINT,N.Y.

USMA, WEST POINT, NY

100% DESIGN PACKAGE

FOR THE RENOVATION

AND MODERNIZATION

OF PERSHING

BARRACKS

REVIEWED BY:

PROJECT NUMBER:

SEAL: DRAWING NO.

SHEET TITLE:

HISTORIC CONSERVATION

40 WEST 27th

STREET,

SUITE 1201

NEW YORK, NY

10001

CONTACT:

MARY JABLONSKI

TEL: 212.532.7775

FAX: 212.532.2188

1 2 3 5 6

B

C

D

E

A

STRUCTURAL

ISSUE FOR BID DATE: 06/08/16

ATKINS #100040983

/8

/2

:5

:1

P

M

M-302

REP

DLH

HVAC WATER-RISER

DIAGRAM

patr3381

THIRD LEVEL

FOURTH LEVEL

ROOF LEVEL

CEILING

CEILING

CEILING

CEILING

FCU-2 FCU-2

FCU-2

SECOND LEVEL

FCU-2FCU-2

FCU-2FCU-2

FCU-2FCU-2

FCU-2

FCU-2

FCU-2

FCU-2 FCU-2

FCU-2FCU-2

FCU-2FCU-2

FCU-2FCU-2

FCU-2FCU-2

HWC-1B

FCU-2

HWC-2B

FCU-2

HWC-3B

FCU-2

HWC-4B

FCU-2

FCU-2

FCU-2

FCU-2

FCU-2 FCU-2

FCU-2

FCU-2

FCU-2

FCU-2 FCU-2

HWC-4C

FCU-6

FCU-2FCU-2

R

R

R

R

4" HWR 3" HWR 2-1/2" HWR

1-1/2" CHWR

3" CHWR

4" CHWR

1-1/2" HWR

1-1/2" HWR

3" CHWR

4" HWR

R

R

R

R

FCU-2FCU-2

FCU-2FCU-2

FCU-2FCU-2

R

1-1/2" CHWS1-1/2" HWS 1-1/4" CHWS1-1/4" HWS 1-1/2" CHWS

1-1/4" HWS

1-1/2" CHWS

1-1/4" HWS

1-1/4" CHWS1-1/4" HWS 1-1/4" CHWS1-1/4" HWS 1-1/2" CHWS

1-1/2" HWS 1-1/2" CHWS 1-1/2" HWS 1-1/2" CHWS 1-1/2" HWS

6" HWS 6" HWS

3" CHWS 4" CHWS 4" CHWS 4" CHWS

ERU-1 ROUTE TO NEAREST

ROOF DRAIN

4" HWS

4" HWR

3" HWS6" HWS 3" HWS 3" HWS 2-1/2" HWS

4" CHWS&R

4" HWS

FCU-6

FCU-2FCU-2

CUH-1

UH-1

CUH-1

1-1/2" HWR

1-1/2" CHWR

1-1/2" CHWR

HWC-0A

1-1/4" CHWR

1-1/4" HWR

FCU-7

FCU-2

FCU-7

FCU-2 FCU-2

FCU-7

FCU-7

FCU-8

1-1/2" CHWR

1-1/2" HWR

1-1/2" CHWR

1-1/2" HWR

HWC-0B

FCU-8

UH-1

2" CHWR

2" HWR

2" HWR

1-1/2" CHWS

FCU-2

FCU-7

FCU-2

FCU-7

FCU-2

FCU-7

FCU-7

FCU-8

1-1/2" CHWR

1-1/2" HWR

1-1/2" CHWR

3" HWR3" HWR4" HWR

UH-1

3" HWS

1-1/2" HWS

FCU-2

HWC-3C

FCU-2

HWC-2C

FCU-2

HWC-1C

FCU-8 FCU-8

UH-1

CUH-1

1-1/2" HWR

FCU-2

FCU-2

FCU-2

1-1/2" CHWR

1-1/2" HWR

FCU-8

UH-1

CUH-1

FTR-1 FTR-1

FTR-1 FTR-1

FTR-1 FTR-1

FTR-1 FTR-1 FTR-1 FTR-1

FTR-1 FTR-1 FTR-1 FTR-1

FTR-1 FTR-1 FTR-1 FTR-1

1. MINIMUM PIPE RISER SIZE SHALL BE 1-1/4" UNLESS OTHERWISE INDICATED.

2. MINIMUM PIPE RUN-OUT SIZE SHALL BE 3/4" UNLESS OTHERWISE INDICATED.

3. MINIMUM DRAIN LINE SIZE SHALL BE 3/4" UNLESS OTHERWISE INDICATED.

GENERAL NOTES:

4. DASHED LINES REPRESENT HYDRONIC RETURN PIPING.

C H

W S

C H

W R

C D

H W

S

H W

R

C H

W S

C H

W R

C D

H W

S

H W

R

C H

W S

C H

W R

C D

H W

S

H W

R

C H

W S

C H

W R

C D

H W

S

H W

R

C H

W S

C H

W R

C D

H W

S

H W

R

H W

R

H W

S

C D

C H

W S

C H

W R

H W

R

H W

S

C D

C H

W S

C H

W R

H W

R

H W

S

C D

C H

W S

C H

W R

H W

R

H W

S

C D

C H

W S

C H

W R

C H

W S

C H

W R

C D

H W

S

H W

R

C H

W S

C H

W R

C D

H W

S

H W

R

C H

W S

C H

W R

C D

H W

S

H W

R

H W

R

H W

S

C D

C H

W S

C H

W R

H W

R

H W

S

C D

C H

W S

C H

W R

H W

R

H W

S

C D

C H

W S

C H

W R

H W

R

H W

S

C D

C H

W S

C H

W R

HWRHWR

HWSHWS HWS

CHWS CHWS

CHWR CHWR

CHWSCHWSCHWS

HWR HWR HWR

CHWR CHWR CHWR

HWR

1-1/2" HWR

1-1/2" CHWR

1-1/4"

HOSE END DRAIN VALVE W/CAP

& CHAIN AT BOTTOM OF RETURN

RISER (TYPICAL)

5. SUPPORT TOP OF ALL HEATING WATER RISERS (HWS) WITH SPRING TYPE HANGERS

AND BOTTOM OF ALL HEATING WATER RISERS (HWR) WITH WITH SPRING TYPE HANGERS.

1-1/2" CHWS

1-1/2" HWS

1-1/4" CHWR

1-1/4" CHWS

1-1/4" HWS

1-1/4" HWR

1-1/4"CHWS

1-1/4"CHWR

1-1/2" CHWS

1-1/2" HWR

1-1/4"CHWS

1-1/4" HWS

1-1/4" HWS1-1/4"CHWS

1-1/4" HWS

1-1/4" CHWR

1-1/4" HWR

1-1/4" CHWR

1-1/4" HWR

1-1/4" CHWR

1-1/4"CHWS

1-1/4" HWS

6. PROVIDE MANUAL AIR VENTS AT THE TOP OF ALL CHILLED WATER SUPPLY AND HEATING WATER SUPPLY

WATER RISERS. SEE DETAIL 13/M-603 “TYPICAL HVAC PIPE RISER BRANCH CONNECTION DETAIL”.

7. PROVIDE MANUAL AIR VENTS IN CHWS AND HWS MAINS LOCATED IN THE 4TH FLOOR CEILING NO

GREATER THAN 100 FEET APART.

D

UN RCO

UT Y

HONOR

T Y

MD

CC

CII

PO INWEST T

USM A

DRAWN BY:

U. S. ARMY

GARRISON

PROJECT:

ARCHITECTURE, INTERIORS,

CIVIL, LANDSCAPE, MECHANICAL,

PLUMBING, FIRE PROTECTION

NORTH AMERICA INC

2318 MILL ROAD,

SUITE 1040,

ALEXANDRIA, VA 22314.

TELEPHONE: (703) 535-3008

FAX: (703) 535-1031

R.G.VANDERWEIL, LLP

1001 AVENUE OF THE

AMERICAS, 21st FLOOR

NEW YORK, NY 10018

ELECTRICAL,TELECOMMUNICATION,SECURITY

212.921.4142 TEL

212.921.4616 FAX

VANDERWEIL.com

CLIENT

Revision / Submission

XXX XXX XXX XXX XXX XXX

Date

00-00-00

Rev.#Rev. By

00-00-00

WEST POINT,N.Y.

USMA, WEST POINT, NY

100% DESIGN PACKAGE

FOR THE RENOVATION

AND MODERNIZATION

OF PERSHING

BARRACKS

REVIEWED BY:

PROJECT NUMBER:

SEAL: DRAWING NO.

SHEET TITLE:

HISTORIC CONSERVATION

40 WEST 27th

STREET,

SUITE 1201

NEW YORK, NY

10001

CONTACT:

MARY JABLONSKI

TEL: 212.532.7775

FAX: 212.532.2188

1 2 3 5 6

B

C

D

E

A

STRUCTURAL

ISSUE FOR BID DATE: 06/08/16

ATKINS #100040983

/8

/2

:5

:2

P

M

M-303

REP

DLH

HVAC WATER-RISER

THIRD LEVEL

FOURTH LEVEL

ROOF LEVEL

CEILING

CEILING

CEILING

CEILING

SECOND LEVEL

FCU-4FCU-4

FCU-4FCU-4

FCU-5FCU-5

FCU-3FCU-4

FCU-2FCU-4

FCU-2FCU-4

FCU-2FCU-4

FCU-2

CUH-2

FCU-6

FCU-2FCU-2

CUH-2

FCU-1FCU-1

FCU-2FCU-2

FCU-3

FCU-3

FCU-3

FCU-4

R

R

R

R

R

R

R

FCU-2

FCU-2

FCU-2

3" CHWS

2" CHWS 1-1/2" CHWS

1-1/2" HWS

1-1/4" HWS

1-1/2" HWS2" HWS

2" HWS2" HWS

1-1/2" HWS

1-1/4" HWS

1-1/4" HWS

1-1/2" CHWS1-1/4" CHWS

1-1/4" CHWS1-1/4" CHWS

1-1/4" CHWS

1-1/4" CHWS3" CHWS

1-1/2" CHWS

4" CHWS&R

2-1/2" HWS

4" CHWS

1-1/4" HWS

1-1/4" HWS

4" CHWS

4" CHWR

6" CHWS

R

6" CHWS4" CHWR 4" CHWS

1-1/2" CHWR

1-1/2" HWR

UH-1

CUH-1

2-1/2" CHWR

2-1/2" HWR

2-1/2" HWR

UH-1

1-1/4" HWR 1-1/4" CHWR

FCU-7

FCU-2

FCU-7

FCU-7

FCU-7

1-1/4" CHWS

& HWS

1-1/4" CHWR

& HWR

FCU-2FCU-2

FCU-2FCU-2

2" HWS

2" CHWS

1-1/2" HWR

1-1/2" CHWR

4" CHWS

2" HWR

2-1/2" HWR

2-1/2" CHWR

FCU-2

FCU-2

FCU-2

CUH-2

1-1/4" CHWR

& HWR

1-1/2" CHWR

& HWR

2" CHWR

2" HWR

FCU-8

CUH-2

4" CHWR

2-1/2" HWR

2" HWR

2" CHWR

2" HWR

2-1/2" HWR

2" CHWR

FCU-2

CUH-2

CHWP-1 CHWP-2

6" CHWR

6" CHWS

6" CHWS 6" BYPASS

2-1/2"

UH-1

FCU-7

ET-2

1. MINIMUM PIPE RISER SIZE SHALL BE 1-1/4" UNLESS OTHERWISE INDICATED.

2. MINIMUM PIPE RUN-OUT SIZE SHALL BE 3/4" UNLESS OTHERWISE INDICATED.

3. MINIMUM DRAIN LINE SIZE SHALL BE 3/4" UNLESS OTHERWISE INDICATED.

GENERAL NOTES:

4. DASHED LINES REPRESENT HYDRONIC RETURN PIPING.

C H

W S

C H

W R

C D

H W

S

H W

R

C H

W S

C H

W R

C D

H W

S

H W

R

C H

W S

C H

W R

C D

H W

S

H W

R

H W

R

H W

S

C D

C H

W S

C H

W R

C H

W S

C H

W R

C D

H W

S

H W

R

C H

W S

C H

W R

C D

H W

S

H W

R

C H

W S

C H

W R

C D

H W

S

H W

R

C H

W S

C H

W R

C D

H W

S

H W

R

C H

W S

C H

W R

C D

H W

S

H W

R

C H

W S

C H

W R

C D

H W

S

H W

R

H W

R

H W

S

C D

C H

W S

C H

W R

C H

W S

C H

W R

C D

H W

S

H W

R

C H

W S

C H

W R

C D

H W

S

H W

R

C H

W S

C H

W R

C D

H W

S

H W

R

C H

W S

C H

W R

C H

W S

AS-2

HWR

CHWS CHWS CHWS

CHWR CHWR

CHWS CHWS CHWS

CHWS CHWS

HWS

CHWR CHWR CHWR

CHWR CHWR

HWR

ROOM 039

AIR SEPARATOR WITH

AIR REMOVAL FITTING

MANUAL AIR VENTS

HOSE END DRAIN VALVE W/CAP

& CHAIN AT BOTTOM OF RETURN

RISER (TYPICAL)

5. SUPPORT TOP OF ALL HEATING WATER RISERS (HWS) WITH SPRING TYPE HANGERS

AND BOTTOM OF ALL HEATING WATER RISERS (HWR) WITH WITH SPRING TYPE HANGERS.

1-1/4" HWS

1-1/4" CHWS

1-1/4" HWR

1-1/4" CHWR

1-1/2" HWR

1-1/2" CHWR

CHWR

CD

HWR

HWS

HWS

HWR

CHWS

1-1/2" CHWR

1-1/2" HWR

C H

W S

C H

W R

C D

H W

S

H W

R

DIFFERENTIAL

PRESSURE

TRANSMITTER

CHWR

HWS

HWR

CHWS

1-1/4" CHWR1-1/4" HWR

1-1/4" HWS

1-1/4" CHWS

6. PROVIDE MANUAL AIR VENTS AT THE TOP OF ALL CHILLED WATER SUPPLY AND HEATING WATER SUPPLY

WATER RISERS. SEE DETAIL 13/M-603 “TYPICAL HVAC PIPE RISER BRANCH CONNECTION DETAIL”.

7. PROVIDE MANUAL AIR VENTS IN CHWS AND HWS MAINS LOCATED IN THE 4TH FLOOR CEILING NO

GREATER THAN 100 FEET APART.

D

UN RCO

UT Y

HONOR

T Y

MD

CC

CII

PO INWEST T

USM A

DRAWN BY:

U. S. ARMY

GARRISON

PROJECT:

ARCHITECTURE, INTERIORS,

CIVIL, LANDSCAPE, MECHANICAL,

PLUMBING, FIRE PROTECTION

NORTH AMERICA INC

2318 MILL ROAD,

SUITE 1040,

ALEXANDRIA, VA 22314.

TELEPHONE: (703) 535-3008

FAX: (703) 535-1031

R.G.VANDERWEIL, LLP

1001 AVENUE OF THE

AMERICAS, 21st FLOOR

NEW YORK, NY 10018

ELECTRICAL,TELECOMMUNICATION,SECURITY

212.921.4142 TEL

212.921.4616 FAX

VANDERWEIL.com

CLIENT

Revision / Submission

XXX XXX XXX XXX XXX XXX

Date

00-00-00

Rev.#Rev. By

00-00-00

WEST POINT,N.Y.

USMA, WEST POINT, NY

100% DESIGN PACKAGE

FOR THE RENOVATION

AND MODERNIZATION

OF PERSHING

BARRACKS

REVIEWED BY:

PROJECT NUMBER:

SEAL: DRAWING NO.

SHEET TITLE:

HISTORIC CONSERVATION

40 WEST 27th

STREET,

SUITE 1201

NEW YORK, NY

10001

CONTACT:

MARY JABLONSKI

TEL: 212.532.7775

FAX: 212.532.2188

1 2 3 5 6

B

C

D

E

A

STRUCTURAL

ISSUE FOR BID DATE: 06/08/16

ATKINS #100040983

/8

/2

:5

:2

P

M

M-304

REP

DLH

HVAC WATER-RISER

DN

DN

3/4"CHWS&R

3/4"HWS&R

3/4" COND.

DRAIN PIPING

FCU FCU

TT

6ø

6ø

6ø

6ø x8 x8

CADET

CADET

B

A

2 3

MM

CEILING MOUNTED VACANCY SENSOR

PROVIDED UNDER DIVISION 26. WIRE TO

FAN COIL UNIT CONTROLLER. (TYP.)

EXHAUST GRILLE (TYP.) SUPPLY REGISTER (TYP.)

ROOM SENSOR (TYP.)

VFDVFD

CHWP-1 CHWP-2

MINIMUM FLOW

CONTROL VALVE

6" BYPASS

6" CHWR FROM

FCU LOOP

6" CHWS

UP TO FCU

LOOP

CONTROL

VALVE4" CHWS&R

UP TO ERU-1

BTUH

METER

CHILLED

WATER PUMP

2-1/2" CHWS

6" CHWS

6" CHWS 4" CHWR6" CHWS

FCU-7

T

DDC BAS

PANEL

PIPE WALL SLEEVE

WITH LINKSEAL (TYP.).

6" UNDERGROUND CHWS & CHWR.

PROVIDE 54" MINIMUM COVER.

FOR CONTINUATION REFER TO

CIVIL DRAWINGS

M-501

B

10 11

2-1/2" CHWR

2" CHWR

1-1/4" CHWR

1-1/2" CHWR

1-1/4" HWR

1-1/2" HWR

AS-2

CHILLED

WATER PUMP

ET-2

3/4" CHWS

3/4" HWS

CD 3/4" HWR

ISOLATION

VALVE (TYP)

2/1/2" CHW BYPASS

2-1/2" HWR

1-1/2" CHWR

UNDERGROUND STEAM

AND CONDENSATE RETURN

PIPING. LOCATE IN EXISTING

STEAM TUNNEL

M-501

AC-1

T

8" LPS

3" PCR TO

CAMPUS PLANT

4" HPS FROM

CAMPUS PLANT

RS & RL

TO AC-1

8" STEAM RELIEF

VENT UP TO ROOF

PRV-1BPRV-1ASRV-1

STEAM ROOM

B

A

ROUTE CONDENSATE

PIPING TO NEAREST

PLUMBING DRAIN (TYP.)

8"

8" LPS

HWP-1

HWP-2

HX-1 HX-2

CRU-1

AS-1

HWP CHEM

POT FEEDER

2" MIN FLOW

HW BYPASS

AND CV

FT-1

AC-2

2-1/2" CRU

VENT UP

LPR FROM

HX-1 & 2

LOW PRESSURE

STEAM RETURN

(TYP. OF 3)

4" LPR FROM

DOMESTIC HW

GENERATOR

1 1/2"ø

2" PRV VENT

ET-1

MECHANICAL

PLUMBING

PROVIDE EA LOUVER

WITH 1.0 SQFT MIN.

FREE AREA

M

MOD (HARDWIRE

INTERLOCK WITH

EF-2)

M

PROVIDE OA INTAKE

LOUVER WITH 1.0 SQFT

MIN. FREE AREA

OA INTAKE

PLENUM

12x8 MOD (HARDWIRE

INTERLOCK WITH EF-2)

DISCHARGE PLENUM

500 CFM

500 CFM

S

FAN WALL SWITCH

WIRED TO EF-2

EF-2

T

B

A

1 2

M-501

4" LPR

1 1/2"

6" HWS

6" HWR

8" LPS

6"

8" LPS

6" LPS

DWH

DWH

REFER TO

PLBG. DWGS

AC-3

6" HWR

4"

6"

6"

MECHANICAL

6" HWS

4" HWR

3" PC

6" 6"

6"

6"

6"

1-1/4" HWR

1-1/2"CHWR

2" PRV

VENT

3/4" HWS

3/4"HWR

1-1/4" HWR

D

UN RCO

UT Y

HONOR

T Y

MD

CC

CII

PO INWEST T

USM A

DRAWN BY:

U. S. ARMY

GARRISON

PROJECT:

ARCHITECTURE, INTERIORS,

CIVIL, LANDSCAPE, MECHANICAL,

PLUMBING, FIRE PROTECTION

NORTH AMERICA INC

2318 MILL ROAD,

SUITE 1040,

ALEXANDRIA, VA 22314.

TELEPHONE: (703) 535-3008

FAX: (703) 535-1031

R.G.VANDERWEIL, LLP

1001 AVENUE OF THE

AMERICAS, 21st FLOOR

NEW YORK, NY 10018

ELECTRICAL,TELECOMMUNICATION,SECURITY

212.921.4142 TEL

212.921.4616 FAX

VANDERWEIL.com

CLIENT

Revision / Submission

XXX XXX XXX XXX XXX XXX

Date

00-00-00

Rev.#Rev. By

00-00-00

WEST POINT,N.Y.

USMA, WEST POINT, NY

100% DESIGN PACKAGE

FOR THE RENOVATION

AND MODERNIZATION

OF PERSHING

BARRACKS

REVIEWED BY:

PROJECT NUMBER:

SEAL: DRAWING NO.

SHEET TITLE:

HISTORIC CONSERVATION

40 WEST 27th

STREET,

SUITE 1201

NEW YORK, NY

10001

CONTACT:

MARY JABLONSKI

TEL: 212.532.7775

FAX: 212.532.2188

1 2 3 5 6

B

C

D

E

A

STRUCTURAL

ISSUE FOR BID DATE: 06/08/16

ATKINS #100040983

/8

/2

:5

:3

P

M

M-401

REP

DLH

HVAC ENLARGED

PLANS

1/4" = 1'-0" M-401

2 TYPICAL CADET ROOM LAYOUT

1/4" = 1'-0" M-401

3 BASEMENT HVAC PLAN - CHILLED WATER PUMP ROOM

1/4" = 1'-0"

M-401

1 BASEMENT HVAC PLAN - STEAM ROOM

1/4" = 1'-0" M-401

4 BASEMENT HVAC PLAN - MECH. ROOM 002

ERU-1

26x32

20x30

20x30

AFMS

30Ø EA32Ø OA

30Ø EA34Ø OA

20x28 EA 24x24 OA 20x14 OA

14x16 OA

30ø

4 5 6 7 8

GALLERY FL. ELEV.

57' - 10 1/4"

PROVIDE SHORT

RADIUS ELBOW WITH

INTERNAL VANES

PROVIDE SHORT

RADIUS ELBOW WITH

INTERNAL VANES

26x28

ERU-1

26x28

30x20

20x30

32x26

OA INTAKE

DF E

GALLERY FL. ELEV.

57' - 10 1/4"

3" STEAM MOISTURE

SEPARATOR

GLOBE VALVE

SAFETY RELIEF

VALVE

8" STEAM VENT

TO ROOF

4" HPS

8" LPS

6"ø

4"ø

6"ø4"ø

3"ø

4"ø

4" STEAM MOISTURE

SEPARATOR

WALL

WALL

TO STEAM TUNNEL

GATE VALVE (TYP.)

FLOOR

1ST FLOOR SLAB

STRAINER (TYP.)

11' - 0 5/8"

FLANGE TO FLANGE

PRV DIMMENSIONS WILL

BE PROVIDED BY VALVE

MFR

PIPE

STAND

(TYP.)

SRV-1

SPRING HANGER

(TYP.)

PIPE CLAMP

(TYP.)

PRV-1B

PRV-1A

4' - 4 11/32"

B

6" ø 6" ø

CHWP-1

6" ø

4"ø4"ø

6"ø

4"ø1 1/4"ø

VFD

2 1/2"ø

FIRST FL. ELEV.

158' - 9"

BSMT. FL. ELEV.

148' - 1"

ABB A

HX-2

6" ø

6" ø

6" ø

3"ø

CRU-1

BOTTOM OF HX NO

LESS THAN 40" AFF

SECOND FL. ELEV.

5' - 10 1/4"

THIRD FL. ELEV.

18' - 6 1/4"

FOURTH FL. ELEV.

31' - 2 1/4"

FIFTH FL. ELEV.

43' - 2 1/4"

12ø ø

12ø

LAUNDRY

LAUNDRY

4'-0" x 4'-0"

LOUVER

10x14 ELEVATOR

VENTILATION DUCT

GALLERY

FSD

PROVIDE BLANK-OFF PANEL

ON INTERIOR SIDE OF LOUVER

OVER UN-USED AREA

WRAP ELEVATOR

HOISTWAY RELIEF

DUCT IN 2 HOUR

FIRE WRAP

D

UN RCO

UT Y

HONOR

T Y

MD

CC

CII

PO INWEST T

USM A

DRAWN BY:

U. S. ARMY

GARRISON

PROJECT:

ARCHITECTURE, INTERIORS,

CIVIL, LANDSCAPE, MECHANICAL,

PLUMBING, FIRE PROTECTION

NORTH AMERICA INC

2318 MILL ROAD,

SUITE 1040,

ALEXANDRIA, VA 22314.

TELEPHONE: (703) 535-3008

FAX: (703) 535-1031

R.G.VANDERWEIL, LLP

1001 AVENUE OF THE

AMERICAS, 21st FLOOR

NEW YORK, NY 10018

ELECTRICAL,TELECOMMUNICATION,SECURITY

212.921.4142 TEL

212.921.4616 FAX

VANDERWEIL.com

CLIENT

Revision / Submission

XXX XXX XXX XXX XXX XXX

Date

00-00-00

Rev.#Rev. By

00-00-00

WEST POINT,N.Y.

USMA, WEST POINT, NY

100% DESIGN PACKAGE

FOR THE RENOVATION

AND MODERNIZATION

OF PERSHING

BARRACKS

REVIEWED BY:

PROJECT NUMBER:

SEAL: DRAWING NO.

SHEET TITLE:

HISTORIC CONSERVATION

40 WEST 27th

STREET,

SUITE 1201

NEW YORK, NY

10001

CONTACT:

MARY JABLONSKI

TEL: 212.532.7775

FAX: 212.532.2188

1 2 3 5 6

B

C

D

E

A

STRUCTURAL

ISSUE FOR BID DATE: 06/08/16

ATKINS #100040983

/8

/2

:5

:5

P

M

M-501

REP

DLH

HVAC SECTIONS

1/4" = 1'-0" M-501

1 N/S SECTION - ROOFTOP DUCTWORK

1/4" = 1'-0" M-501

2 E/W SECTION - ROOFTOP DUCTWORK

1/4" = 1'-0" M-501

3 STEAM ROOM PRS

1/4" = 1'-0"

M-501

4 CHILLED WATER PUMP ROOM

1/4" = 1'-0" M-501

5 MECH. ROOM 002

1/4" = 1'-0" M-501

6 LAUNDRY ROOM SECTION

1/4" = 1'-0" M-501

7 SECTION THRU ELEVATOR SHAFT

EQUAL

X

X

TRANSITION

Y

Y

X

Y

1X 1Y

W

X+Y1

Y = W *1 X+Y

Y

X = W * X

X Y

X Y

W

1 1

X = W *1 X

X+Y

Y = W *1 X+Y

Y

X

X Y

Y

TYPICAL ELBOWS

SEE DETAIL

20° MAX.

MANUAL VOLUME

DAMPER (TYP.) MANUAL VOLUME

DAMPER (TYP.)

TYPICAL ELBOWS

SEE DETAIL

EQUAL

TRANSITION

MANUAL VOLUME

DAMPER (TYP.)

MANUAL VOLUME

DAMPER (TYP.)

TYPICAL ELBOWS

SEE DETAIL

TYPICAL ELBOWS

SEE DETAIL

20° MAX.

TRANSITIONEQUAL

X

X

X R =(X+Y)/2

R

Y

X

R 2

R =X+Y

X

X Y

X

TRANSITIONEQUAL

PROVIDE DOUBLE THICKNESS VANES PER SMACNA DUCT CONSTRUCTION STANDARDS.

VANE REQUIREMENTS FOR TRANSITION ELBOWS VARY FROM EQUAL ELBOWS. VANES

SHALL BE UTILIZED IN ALL MITERED ELLS 45° AND GREATER.

M A

IN

D

U C

T

W

ECCENTRIC TRANSITION

MAX = 30°

(EXCEPT 45° IS PERMITTED AT

ROUND TO FLAT OVAL)

CONCENTRIC TRANSITION MAX = 45°

DIVERGING, 60° CONVERGING

AIR FLOW

BRANCH DUCT

OR RUNOUT

MANUAL DAMPER

L = 1/4 W

MINIMUM 4"

45º

28" ABOVE ROOF

TO BOT. OF DUCT

SUPPORT AND CURB

SILICONE CAULK BETWEEN

FLASHING BY GEN. CONTRACTOR

COUNTER FLASHING BY MECH.

CONTRACTOR

MODEL ES-5 PRE-FAB EQUIPMENT

CURB AS MANUF. BY PATE OR

APPROVED EQUAL

ROOF CONSTRUCTION

FASTEN EQUIPMENT CURB TO ROOF

WITH 3/8" DIAMETER STAINLESS

STEEL HILTI HAS RODS EMBEDDED 3

1/2" INTO CONCRETE TOPPING WITH

HILTI HIT-ICE EPOXY (@ 6" O/C)

LAG SCREWS EACH SIDE

SILICONE CAULK BENEATH

HEAD BEFORE TIGHTENING.

3"x3"x1/4" GALV.

1/4" STL PLATE WELDED TO ANGLE

STL.ANGLE EACH SIDE

SHEET METAL SCREWS (6" O.C.)

PROVIDE 3 COATS OF GALV. PAINT

AFTER WELDING. (TYP.)

(2) 1/2" ZINC COATED

DUCTWORK.

NOTE:

A/E TO CONFIRM ADEQUACY OF ATTACHMENT SUBSTRATE WHEN ROOFING IS REMOVED. ATTACHMENT

METHOD MAY BE REVISED DEPENDING ON CONDITION AND MATERIAL OF ROOF STRUCTURE

14" MIN.

CURB

HEIGHT.

SCHEDULE CREATED FROM SMACNA "HVAC DUCT CONSTRUCTION STANDARDS", SECOND EDITION - 1995.

TABLE ALLOWS FOR CONVENTIONAL WALL THICKNESS, AND JOINT SYSTEMS PLUS ONE LB/SF INSULATION WEIGHT. IF HEAVIER DUCTS ARE TO BE INSTALLED, ADJUST HANGER SIZES TO BE WITHIN THEIR LOAD

TWO(2) 1" x 16 GA.

LIMITS. HANGER SPACING MAY BE ADJUSTED BY SPECIAL ANALYSIS.

FOR UPPER ATTACHMENTS, LOWER ATTACHMENTS, TRAPEZE SIZES, AND ROD/STRAP ALLOWABLE

NOTES:

61"-84"

1.

2.

4.

3.

6.

5.

LOADS, SEE SMACNA MANUAL.

STRAPS ARE TO BE GALVANIZED STEEL.

WIRE IS NOT AN APPROVED HANGER.

STRAP AND ROD SIZES ARE MINIMUM ALLOWABLE.

12' TWO(2) 3/8"

PAIR AT 8FT SPACING

ROD

1/4"

1/4"

3/8"

1/2"

1/2"

3/8"

STRAP

1" x 22" GA.

1" x 20" GA.

1" x 22" GA.

1" x 22" GA.

SCHEDULE CREATED FROM SMACNA "HVAC DUCT CONSTRUCTION STANDARDS", SECOND EDITION - 1995.

TABLE ALLOWS FOR TYPICAL DUCT WEIGHT WITH NORMAL REINFORCEMENT AND JOINTS, 1 LB/SF

ALLOWABLE LOADS FOR P/2 ASSUME THAT DUCTS ARE 16 GA MAX., EXCEPT THAT WHEN MAXIMUM

DUCT DIMENSION (W) IS OVER 60", THEN P/2 MAX. IS 1.25W.

FOR UPPER ATTACHMENTS, LOWER ATTACHMENTS, TRAPEZE SIZES, AND ROD/STRAP ALLOWABLE

TWO(2) 1" x 20 GA.

TWO(2) 1" x 18 GA.

4.

5.

6.

DIAMETER

7.

11-18"

19"-24"

25"-36"

51"-60"

37"-50"

10" & DN

12'

12'

12'

12'

MAX. SPACING

12'

12'

TWO(2) 3/8"

TWO(2) 3/8"

3/8"

1/4"

1/4"

1/4"

ROD

WIRE IS NOT AN APPROVED HANGER.

STRAP AND ROD SIZES ARE MINIMUM ALLOWABLE.

LOADS, SEE SMACNA MANUAL.

MAX. HALF

PERIMETER

P/2=30"

P/2=72"

P/2=120"

P/2=168"

P/2=192"

P/2>192"

P/2=96"

OF DUCT

NOTES:

2.

1.

3.

SPECIAL ANALYSIS REQUIRED

INSULATION WEIGHT, AND TRAPEZE WEIGHT, BUT NO EXTERNAL LOADS. IF HEAVIER DUCTS ARE TO BE

STRAPS ARE TO BE GALVANIZED STEEL.

SMACNA REQUIREMENTS GOVERN.

1.5"x16 GA

N/A

1.5"x16 GA

1.5"x16 GA

1/2"

1/2"

PAIR AT 10FT SPACING

1"x22 GA

1"x18 GA

1"x16 GA

1.5"x16 GA

STRAP

1"x22 GA

1"x20 GA

1"x18 GA

1"x16 GA1/2"

3/8"

3/8"

1/4"

STRAPROD

PAIR AT 4FT SPACING

ROD

1/4"

1/4"

3/8"

1/4"

3/8"

1/4"

3/8"

3/8"1"x16 GA

1"x16 GA

1"x18 GA

1"x16 GA

PAIR AT 5FT SPACING

ROD

1/4"

1/4"

3/8"

3/8"

1"x22 GA

1"x22 GA

1"x20 GA

1"x18 GA

STRAP

1"x22 GA

1"x22 GA

1"x22 GA

1"x20 GA

STRAP

INSTALLED (SUCH AS DOUBLE-WALL OR DENSE INSULATIONS), ADJUST HANGER SIZES TO BE WITHIN

THEIR LOAD LIMITS.

RECTANGULAR DUCT HANGER SCHEDULE

ROUND DUCT HANGER SCHEDULE

AND EXHAUST TUBE. VERIFY THAT DIFFERENTIAL PRESSURE

MEASURE DIFFERENTAL PRESSURE ACROSS INLET TUBE

INSTALL DUCT SMOKE DETECTOR ON SIDE OF DUCT AS

SUPPORT INLET TUBE IN DUCT OPENING WHEN DUCT WIDTH

ACCESS DOOR IN DUCT FOR INSPECTION AND TESTING.

INSTALL DUCT SMOKE DETECTORS IN ACCORDANCE WITH

DETECTOR MANUFACTURER'S INSTALLATION INSTRUCTIONS,

REQUIREMENTS ARE IN CONFLICT, THE MORE STRINGENT

REFER TO FIRE DAMPER DETAIL FOR ACCESS DOOR SIZE.

MANUFACTURERS INSTALLATION REQUIREMENTS.

SATISFIES MINIMUM REQUIREMENTS AS SPECIFIED IN

AND REQUIREMENTS INDICATED ABOVE. WHERE

WILL GOVERN.

INLET TUBE HOLES SHALL FACE UPSTREAM.

EXHAUST TUBE LENGTH 1/2 OF DUCT WIDTH.

SHOWN. (13852)

EXCEEDS 32".

NOTES:

DUCT ACCESS DOOR

DUCT OPENING

RECTANGULAR

W/ DAMPER

LENGTH

DIA.SIZE

ORDER

10"x16"

8"x14"

6"x12"

5"x9"

13"

13"

13"

13"

12"

10"

8"

6"

5" 13" 5"x9"

7" 13" 5"x11"

9" 13" 7"x13"

14" 13" 12"x18"

16" 13" 14"x20"

MIN. RECT.

DUCT HEIGHT

7"

14"

12"

16"

10"

7"

8"

9"

7"

8"

8"

8"

8"

8"

8"

8"

8"

8"

GASKET SEAL WHERE ROD PENETRATES COLLAR

1" WIDE FLANGE AROUND

RECTANGULAR END

"X"

"H"

"A X B"

GASKET SEAL

AROUND PERIMETER

DAMPER BLADE W/CONTINUOUS ROD

MINIMUM 26 GAUGE, G-90 GALVANIZED STEEL

FLANGE WITH DIE FORMED CORNER CLIPS

DAMPER WITH 2" INSULATION BUILD-OUT AND LOCKING HAND

QUADRANT BASIS OF DESIGN: FLEXMASTER "STO"

2" STAND-OFF

W/LOCKING

QUADRANT

PROVIDE EXTRA LENGTH

STRAP HANGER AROUND

WITH DAMPER BLADE(S).

BECAUSE THEY INTERFERE

DO NOT USE ANY SCREWS,

QUADRANT ARM

PROVIDE LOCKING

STANDOFF

& SEAL

BUTT ENDS

FOR HANGING DUCT:

OF INSULATION AT

TO AVOID "PINCHING"

CORNERS.

DUCT COMPLETELY.

TRAPEZE DUCT OR

NOTE:

HVAC EQUIPMENT, DUCTWORK AND PIPING

SHALL BE SUPPRTED FROM NEW UNISTRUT

FRAME SYSTEM. REFER TO STRUCTURAL

DWG S-207 "TYPICAL DETAIL MEP AND

PARTITION WALL HEAD UNISTRUT

FRAME SUPPORT" AND COORDINATION

NOTE "9" ON DWGS S-100 THROUGH S-107.

DECK

CURB TO

ANCHOR

ROOF DECK

INSULATION

ROOF MEMBRANE

FLASHING

SS SHEETMETAL SCREW

S-SLIP CONNECTION

STEEL DECK

TO DECK

TACK WELD CURB

(THYCURB OR EQUAL)

CURB WITH WOOD NAILOR

PREFABRICATED, INSULATED

RESISTANT SEALANT

JOINT WITH OUTDOOR, UV

COMPLETELY SEAL & COVER

CONCRETE DECK

TOP OF CURB 18

INCH MINIMUM

ABOVE ROOF

GAUGESPR (RADIUS)

SMALL

LARGE

Runner Type 1

Single Vane

Double Vane

Vane Support

Large Small

MAXIMUM UNSUPPORTED VANE LENGTH

72"

48"

LARGE DOUBLE VANE

SMALL DOUBLE VANE

45°

4-1/2"R

2-1/4"

2-1/4"R

3-1/4"

2-1/8"

1"R

1-1/8"

2"R

45°

OR 7"

4-1/2"

MIN.

1-1/2"

22 GA.

45° R

SP

45°

SINGLE VANE SCHEDULE

241-1/2"2"

(51 mm) (38 mm) (0.70 mm)

(0.85 mm)(83 mm)(114 mm)

4-1/2" 3-1/4" 22

SMALL SINGLE VANE

LARGE SINGLE VANE

36"

36"

NOTES:

VANES SHALL BE SECURELY FASTENED

TO RUNNERS.

ALL VANES SHALL BE SECURE AND

STABLE IN INSTALLED OPERATING

POSITION.

RUNNER TYPE 2

MIN. 24 GA. VANES

2-1/4"

45°

MIN. 26 GA. VANES

BOLT, SCREW OR

WELD RUNNER TO DUCT

SCREW EVERY 6TH

VANE TO TAB

45°

NOTE:

INSTALL VANES IN SECTIONS OR USE TIE

RODS

TO LIMIT THE UNBRACED VANE LENGTH.

TIE ROD

DUCT

RUNNER

RUNNER TYPE 2

RUNNER TYPE 2

TAB TAB

METAL SCREWS 12" O.C.

VANE

1.

2.

NOTE:

SEE MECHANICAL SPECIFICATIONS FOR ADDITIONAL INFORMATION.

VANE

BEAM CLAMP

ADJUSTABLE

THREADED STEEL

SUPPORT

STEEL

BOLT/NUT ASSEMBLY

WITH 3/4" SPACER

STEEL WELDLESS EYENUT

MSS SP-69 TYPE 17

ROD

NOTE:

HVAC EQUIPMENT, DUCTWORK AND PIPING

SHALL BE SUPPRTED FROM NEW UNISTRUT

FRAME SYSTEM. REFER TO STRUCTURAL

DWG S-207 "TYPICAL DETAIL MEP AND

PARTITION WALL HEAD UNISTRUT

FRAME SUPPORT" AND COORDINATION

NOTE "9" ON DWGS S-100 THROUGH S-107.

14" MIN. CURB HEIGHT

1-1/2"x1-1/2"x1/8" (MIN)

GALVANIZED ANGLE

IRON SUPPORT (TYP.)

SUPPORT CURB

ROOF EQUIPMENT

COUNTER FLASHING

SUPPORT CURB

ROOF EQUIPMENT

COUNTER FLASHING

RECTANGULAR DUCTWORK

CIRCULAR DUCTWORK

2" MINIMUM

INSULATION

THICKNESS

SLOPE INSULATION MINIMUM 1/16

INCH PER FOOT AND INCREASE

INSULATION THICKNESS TO MAINTAIN

2 INCH MINIMUM THICKNESS

1-1/2"x1-1/2"x1/8" (MIN)

GALVANIZED ANGLE

IRON SUPPORT (TYP.)

2" INSULATED DUCT

MINIMUM THICKNESS

NOTES:

1. DETAILS APPLIES TO SUPPLY, EXHAUST AND RETURN DUCTWORK.

INSULATION THICKNESS LISTED IS MINIMUM, REFER TO SPECIFICATIONS

FOR ADDITIONAL REQUIREMENTS.

2. PROVIDE ZERO PERM MULTI-PLY VAPOR BARRIER/WEATHERPROOF

JACKET AS SPECIFIED IN SECTION 23 07 00 OVER ALL DUCT INSULATION.

3. INSULATION SHALL BE CELLULAR GLASS.

14" MIN. CURB HEIGHT

D

UN RCO

UT Y

HONOR

T Y

MD

CC

CII

PO INWEST T

USM A

DRAWN BY:

U. S. ARMY

GARRISON

PROJECT:

ARCHITECTURE, INTERIORS,

CIVIL, LANDSCAPE, MECHANICAL,

PLUMBING, FIRE PROTECTION

NORTH AMERICA INC

2318 MILL ROAD,

SUITE 1040,

ALEXANDRIA, VA 22314.

TELEPHONE: (703) 535-3008

FAX: (703) 535-1031

R.G.VANDERWEIL, LLP

1001 AVENUE OF THE

AMERICAS, 21st FLOOR

NEW YORK, NY 10018

ELECTRICAL,TELECOMMUNICATION,SECURITY

212.921.4142 TEL

212.921.4616 FAX

VANDERWEIL.com

CLIENT

Revision / Submission

XXX XXX XXX XXX XXX XXX

Date

00-00-00

Rev.#Rev. By

00-00-00

WEST POINT,N.Y.

USMA, WEST POINT, NY

100% DESIGN PACKAGE

FOR THE RENOVATION

AND MODERNIZATION

OF PERSHING

BARRACKS

REVIEWED BY:

PROJECT NUMBER:

SEAL: DRAWING NO.

SHEET TITLE:

HISTORIC CONSERVATION

40 WEST 27th

STREET,

SUITE 1201

NEW YORK, NY

10001

CONTACT:

MARY JABLONSKI

TEL: 212.532.7775

FAX: 212.532.2188

1 2 3 5 6

B

C

D

E

A

STRUCTURAL

ISSUE FOR BID DATE: 06/08/16

ATKINS #100040983

/1

/2

:5

:1

A M

M-601

REP

DLH

HVAC DETAILS

NO SCALE

90 DEGREE RECTANGULAR TEES

NO SCALE

LOW VELOCITY BRANCH DUCT, ELBOWS & TRANSITIONS DETAIL

NO SCALE

TYPICAL ROOFTOP DUCT SUPPORT DETAIL

NO SCALE

RECTANGULAR & ROUND DUCT HANGER SCHEDULE

NO SCALE

DUCT SMOKE DETECTOR DETAIL

NO SCALE

RECTANGULAR TO ROUND TAKEOFF DETAIL

NO SCALE

TYPICAL DUCT INSULATION & SUPPORTS NEAR VOLUME DAMPERS

NO SCALE

DUCT PENETRATION THROUGH ROOF

NO SCALE

TURNING VANES DETAIL

NO SCALE

BEAM CLAMP DETAIL

NO SCALE

DUCTWORK ON ROOF

50"

88"

370"

131"

54"

55"

12" 148"

20" 80.5"

60"

9"5

138"

TOP VIEW

FRONT VIEW

BACK VIEW

OA

OA

EA

RA

SA

CHW

HW

SA

RA

(TYP.)

(TYP.)

(TYP.)

SA FAN WALL WITH MOTORS AND DRIVES

EA FAN WALL WITH MOTORS AND DRIVES

OA INTAKE HOOD WITH MOTORIZED DAMPER

MERV 8 PRE- AND MERV 13 FINAL FILTERS

CHILLED WATER COOLING COIL

MAIN ELECTRICAL CONNECTION PANEL

HINGED ACCESS DOORS

(TYP.)

(TYP.)

CHW COIL CONNECTION AND BOTTOM INLET

HW COIL CONNECTION AND BOTTOM INLET

STAINLESS STEEL DRAIN PANS AND CONNECTIONS

TOTAL ENERGY RECOVERY WHEEL

WRAP-AROUND HEAT PIPE

HEAT PIPE BYPASS DAMPER

HEATING HOT WATER COIL

LED SERVICE MARINE LIGHTS

MAJOR COMPONENTS GENERAL NOTES

1. ALL OUTDOOR AIR AND EXHAUST AIR DAMPERS SHALL BE LOW

DUCTED EA OUTLET WITH MOTORIZED DAMPER

LEAKAGE TYPE WITH MAXIMUM LEAKAGE RATE OF 3CFM/SF AT

1.0" DIFFERENTIAL STATIC PRESSURE.

2. PROVIDE HEAT WHEEL WITH MANUFACTURER FURNISHED

INTEGRAL HEAT WHEEL CONTROLLER.

P

P

P

O

N

M

L

K

J

I

H

O

O

G

F

E

D

C

B

A

KN

N

L L

L L

M

M

K

K

J

J

I

H

G

G G

F

F

E

E

D

DD

D

C

C

B

BA

A

HOUSEKEEPING PAD

DRAIN W/VALVE

CONNECT TO SIDE

OF MAIN PIPE

BLOWDOWN VALVE PIPE

TO FLOOR DRAIN

TANGENTIAL TYPE

AIR SEPARATOR

SUPPORT FROM

STRUCTURE

RETURN WATER

FULL SIZE

BYPASS

CHECK VALVE

BALL VALVE

(TYP.)

WATER METER

B.F.P. DRAIN TO

FLOOR DRAIN

STRAINER

EXTEND TO MAKE-UP

WATER PIPING

UNION (TYP.)

REDUCED PRESSURE

BACKFLOW PREVENTER

AUTOMATIC HIGH

CAPACITY AIR VENT

PRESSURE

REDUCING

VALVE

AUTOMATIC

AIR VENT

PRESSURE

GAUGE

DRAIN LINE

TO FLOOR

DRAIN

DIAPHRAGM TYPE

PRESSURIZED

EXPANSION

TANK

TO PUMP

SUCTION

M

NOTES;

1. THIS DETAIL SHALL BE USED AS A GUIDE. ALL SUPPORTS SHALL MEET THE REQUIREMENTS OF THE SPECIFICATIONS.

2. THE STEEL WELDLESS EYENUT SHALL BE INSTALLED TO PIVOT IN OPPOSITE DIRECTION OF ROLLER.

3. HANGERS THAT UTILIZE A TURNBUCKLE WILL REQUIRE THE INSTALLATION AND USE OF BOTH RIGHT AND LEFT HANDED

THREADS.

4. PIPE SIZE NOT INCLUDED IN THE LOAD SCHEDULE WILL NOT BE PERMISSIBLE.

5. THE THICKNESS OF THE INSERT SHALL BE AS REQUIRED TO FIT THE SUPPORT, BUT NOT LESS THAN THE PIPING SYSTEM

SUPPORTED.

MAX SPACING

7'

9'

11'

12'

14'

16'

17'

ROD SIZE

3/8"Ø

3/8"Ø

1/2"Ø

1/2"Ø

5/8"Ø

5/8"Ø

3/4"Ø

THREADED STEEL ROD (REFER TO

LOAD SCHEDULE)

STEEL TURNBUCKLE MSS SP-69

TYPE 13 (REQUIRED ON PIPING

WITH INSULATION 2" THICK AND

GREATER)

HEX NUT, ASTM A194, GRADE 2H

(TYP.)

ADJUSTABLE CLEVIS HANGER MSS

SP-69 TYPE 43

SERVICE PIPE (REFER TO PLANS

FOR SIZE)

METAL SHIELD MSS SP-69 TYPE 40

HIGH DENSITY THERMAL HANGER

INSERT, MIN 12" LONG (SEE NOTE 5)

PIPE SIZE

2"-1 1

4"Ø

1 1 2"-2"Ø

2 1 2"Ø

3"Ø

4"Ø

5"Ø

6"Ø

NOTE:

HVAC EQUIPMENT, DUCTWORK AND PIPING

SHALL BE SUPPRTED FROM NEW UNISTRUT

FRAME SYSTEM. REFER TO STRUCTURAL

DWG S-207 "TYPICAL DETAIL MEP AND

PARTITION WALL HEAD UNISTRUT

FRAME SUPPORT" AND COORDINATION

NOTE "9" ON DWGS S-100 THROUGH S-107.

MAX SPACING

11'

12'

14'

16'

17'

PIPE SIZE

2 1 2"Ø

3"Ø

4"Ø

5"Ø

6"Ø

ROD SIZE

2"Ø

2"Ø

8"Ø

8"Ø

4"Ø

NOTES;

1. THIS DETAIL SHALL BE USED AS A GUIDE. ALL SUPPORTS SHALL MEET THE REQUIREMENTS OF THE SPECIFICATIONS.

2. THE STEEL WELDLESS EYENUT SHALL BE INSTALLED TO PIVOT IN OPPOSITE DIRECTION OF ROLLER.

3. HANGERS THAT UTILIZE A TURNBUCKLE WILL REQUIRE THE INSTALLATION AND USE OF BOTH RIGHT AND LEFT HANDED

THREADS.

4. PIPE SIZE NOT INCLUDED IN THE LOAD SCHEDULE WILL NOT BE PERMISSIBLE.

5. THE THICKNESS OF THE INSERT SHALL BE AS REQUIRED TO FIT THE SUPPORT, BUT NOT LESS THAN THE PIPING SYSTEM

SUPPORTED.

THREADED STEEL ROD (REFER TO

LOAD SCHEDULE)

STEEL TURNBUCKLE MSS SP-69

TYPE 13 (REQUIRED ON PIPING

WITH INSULATION 2" THICK AND

GREATER)

HEX NUT, ASTM A194, GRADE 2H

(TYP.)

ADJUSTABLE ROLLER HANGER MSS

SP-69 TYPE 43

SERVICE PIPE (REFER TO PLANS

FOR SIZE)

METAL SHIELD MSS SP-69 TYPE 40

HIGH DENSITY THERMAL HANGER

INSERT, MIN 12" LONG (SEE NOTE 5)

NOTE:

HVAC EQUIPMENT, DUCTWORK AND PIPING

SHALL BE SUPPRTED FROM NEW UNISTRUT

FRAME SYSTEM. REFER TO STRUCTURAL

DWG S-207 "TYPICAL DETAIL MEP AND

PARTITION WALL HEAD UNISTRUT

FRAME SUPPORT" AND COORDINATION

NOTE "9" ON DWGS S-100 THROUGH S-107.

OVERFLOW

PUMP BUT ONLY ONE PUMP

SIMILAR FOR SIMPLEX

NOTE:

TO INDIRECT DRAIN

OF TAPPING

FULL SIZE

CONDENSATE

PUMPED

RETURN

CONDENSATE

FLOOR

FINISHED

VENT

NC

NC

4" THICK CONCRETE PAD

1"

NOTES;

1. THIS INFORMATION IS PROVIDED TO GIVE THE MINIMUM BEAM SIZE REQUIRED TO SUPPORT A LOAD FOR PIPE SUPPORTS.

2. MAXIMUM LOAD "P" SHALL BE THE HIGHEST OF THE HYDROSTATIC AND OPERATING LOADS.

MAXIMUM LOAD "P" (LBS)

SPAN RANGE W4x13 W6x9 W6x12 W8x10 W8x15

4' > L < 6'

0' > L < 4'

8' > L < 10'

6' > L < 8'

12' > L < 14'

10' > L < 12'

10,800 11,000 14,600 15,500 23,500

6,600 6,600 8,600 8,300 14,300

5,000 4,000 6,500 5,000 9,500

3,000 2,600 4,400 3,000 6,000

- 1,800 3,000 - 4,200

- - 2,200 - 3,100

SPAN

12"

12"

NEW BEAM

"P"

(MAX. LOAD AS SCHEDULED)

JL 3 1/2"x3 1/2"x 1/4"x5 1/2" FOR

8" BEAMS

12"x12"x 1/2" PLATE

INSIDE FACE OF

CONCRETE WALL

5/8" EXP. BOLT

(TYP. OF 4)

4" EMBEDMENT

JL 3 1/2"x3 1/2"x1/4"x4" FOR

OTHERS

INSULATION

INSULATED PIPE STAND, INSULATION

AND JACKETING ON PIPE STAND TO

MATCH INSULATED PIPE

WELDED CONN.,

(TYPICAL)

6"x6"x1/2" STEEL

PLATE

PIPE

2" DIA. SCH. 40

STEEL PIPE STAND

5/8" HILTI

ANCHORS,

4 REQUIRED

CONCRETE

SLAB

NOTE:

HVAC EQUIPMENT, DUCTWORK AND PIPING

SHALL BE SUPPRTED FROM NEW UNISTRUT

FRAME SYSTEM. REFER TO STRUCTURAL

DWG S-207 "TYPICAL DETAIL MEP AND

PARTITION WALL HEAD UNISTRUT

FRAME SUPPORT" AND COORDINATION

NOTE "9" ON DWGS S-100 THROUGH S-107.

NOTE:

TRAP TO HAVE NO MOVING PARTS AND CONTINUOUSLY PASS CONDENSATE THROUGH

A PRECISELY SIZED OPENING. PROVIDE 10 YEAR NON-PRORATED WARRANTY

CONNECTION

AND TEST ADAPTER

BLOWDOWN OPENINGBLOWDOWN VALVE

STRAINER

s" PIPE

316 S/S UNIT

SINGLE PIECE CAST

FOR EACH ORIFICE SIZE

PROVIDE (2) SPARE INSERTS

SIDE WITHOUT DOWN TIME.

THREADED INSERT FROM EITHER

180° HANDLE FOR REPLACING

INTO VALVE BALL

316 S/S INSERT THREADED

REMOVABLE "SHORT TUBE"

VALVE DISCHARGE.

SIZE LARGER THAN RELIEF

VENT PIPE SHALL BE (1)

VALVE

RELIEF

OUTLET

OUTDOORS THRU ROOF.

OVERHEAD, EXTEND

VENT PIPE SUPPORT

DRIP-PAN ASSEMBLY

DISCHARGE ELBOW &

2" 6"

DRAIN

TO FLOOR

3/4" EXTEND

INLET

STEAM MAIN LESS THAN

60 PSI (SEE DWGS FOR SIZE)

8'-0" FROM FLOOR MAX

INSULATION (AS REQUIRED) (REFER TO

TO SPECIFICATIONS FOR TYPE AND COVER)

SERVICE PIPE (REFER

TO PLANS FOR SIZE)

METAL SHIELD MSS SP-69 TYPE 40

CONTINUOUSLY WELD SADDLE

TO LEG SUPPORT

STEEL BASE PLATE, WELD TO LEG

SUPPORT (REFER TO SCHEDULE

FOR SIZE)

1" NON-SHRINK NON-

FERROUS GROUT

ANCHOR BOLT (4 REQ'D)

(REFER TO SCHEDULE

FOR SIZE AND EMBEDMENT)

1 1/4"Ø VENT HOLE (CENTER LINE 2"

ABOVE BOTTOM OF BASE PLATE)

SCHED. 40 BLACK STEEL SADDLE

LEG SUPPORT (REFER TO

SCHEDULE FOR SIZE)

SEGMENT OF SCHED. 40 BLACK

STEEL PIPE TO FORM SADDLE

HIGH DENSITY THERMAL HANGER

SUPPORT

NOTES;

1. FOR NON-INSULATED PIPES OUTSIDE PIPE WALL SHALL REST DIRECTLY ON

INNER WALL OF SADDLE.

2. THIS DETAIL SHALL BE USED AS A GUIDE. ALL SUPPORTS SHALL MEET THE

REQUIREMENTS OF THE SPECIFICATIONS.

BASE PLATE

18"x18"x1/2" 14"x14"x1/2"

14"x14"x1/2"

10"x10"x1/2"

10"x10"x1/2"

10"x10"x3/8" 10"x10"x3/8"

MIN. EMBEDMENT

5"

5" 4"

4"

4"

4"

4"

4"

4"

4"

3"

3"

3"

8"x8"x3/8"

8"x8"x3/8"

8"x8"x3/8"

6"x8"x3/8"

6"x8"x3/8"

6"x8"x3/8"

PIPE SIZE

30"Ø

24"Ø

20"Ø

18"Ø

16"Ø

14"Ø

12"Ø

10"Ø

8"Ø

6"Ø

5"Ø

4"Ø

3"Ø

SADDLE LEG SUPPORT

12"Ø

8"Ø

8"Ø

6"Ø

6"Ø

5"Ø

5"Ø

4"Ø

3"Ø

3"Ø

2"Ø

1 1/2"Ø

1 1/2"Ø

ANCHOR BOLTS

8"Øx8" LONG

8"Øx8" LONG

8"Øx8" LONG

8"Øx8" LONG

8"Øx8" LONG

8"Øx8" LONG

2"Øx8" LONG

2"Øx8" LONG

2"Øx8" LONG

2"Øx8" LONG

2"Øx6" LONG

2"Øx6" LONG

2"Øx6" LONG

PROVIDE 1-1/4 INCH MINIMUM WASH-DOWN DRAIN IN EACH PLENUM

AND TERMINATE EACH DRAIN AT BASE RAIL WITH CAP.

3.

MAX SPACING

11'

12'

14'

16'

17'

PIPE SIZE

2 1 2"Ø

3"Ø

4"Ø

5"Ø

6"Ø

ROD SIZE

4"Ø

4"Ø

8"Ø

NOTES;

1. THIS DETAIL SHALL BE USED AS A GUIDE. ALL COMPONENTS SHALL MEET THE REQUIREMENTS OF THE SPECIFICATIONS.

2. THE STEEL WELDLESS EYENUTS SHALL BE INSTALLED TO PIVOT IN OPPOSITE DIRECTIONS.

3. THE USE OF A TURNBUCKLE WILL REQUIRE THE INSTALLATION AND USE OF BOTH RIGHT AND LEFT HANDED THREADES.

4. PIPE SIZE NOT INCLUDED IN THE LOAD SCHEDULE WILL NOT BE PERMISSIBLE.

5. THE THICKNESS OF THE INSERT SHALL BE AS REQUIRED TO FIT THE SUPPORT, BUT NOT LESS THAN THE PIPING SYSTEM SUPPORTED.

THREADED STEEL ROD

(REFER TO LOAD SCHEDULE)

STEEL TURNBUCKLE

MSS SP-69 TYPE 13

HEX NUT, ASTM A194,

GRADE 2H (TYP.)

SERVICE PIPE (REFER

TO PLANS FOR SIZE)

HIGH DENSITY INSULATED STRUCTURAL

INSERT, MIN. 12" LONG (600 PSI MIN.

COMPRESSIVE STRENGTH (SEE NOTE 5)

STEEL WELDLESS EYENUT

MSS SP-69 TYPE 17

STEEL WELDLESS EYENUT

MSS SP-69 TYPE 17

THREE BOLT PIPE CLAMP

MSS SP-69 TYPE 3

19'8"Ø 7 8"Ø

8"Ø

8"Ø

SUPPORT STEEL

WELDED BEAM

ATTACHMENT W/BOLT

MSS SP-69 TYPE 22

NOTE:

HVAC EQUIPMENT, DUCTWORK AND PIPING

SHALL BE SUPPRTED FROM NEW UNISTRUT

FRAME SYSTEM. REFER TO STRUCTURAL

DWG S-207 "TYPICAL DETAIL MEP AND

PARTITION WALL HEAD UNISTRUT

FRAME SUPPORT" AND COORDINATION

NOTE "9" ON DWGS S-100 THROUGH S-107.

D

UN RCO

UT Y

HONOR

T Y

MD

CC

CII

PO INWEST T

USM A

DRAWN BY:

U. S. ARMY

GARRISON

PROJECT:

ARCHITECTURE, INTERIORS,

CIVIL, LANDSCAPE, MECHANICAL,

PLUMBING, FIRE PROTECTION

NORTH AMERICA INC

2318 MILL ROAD,

SUITE 1040,

ALEXANDRIA, VA 22314.

TELEPHONE: (703) 535-3008

FAX: (703) 535-1031

R.G.VANDERWEIL, LLP

1001 AVENUE OF THE

AMERICAS, 21st FLOOR

NEW YORK, NY 10018

ELECTRICAL,TELECOMMUNICATION,SECURITY

212.921.4142 TEL

212.921.4616 FAX

VANDERWEIL.com

CLIENT

Revision / Submission

XXX XXX XXX XXX XXX XXX

Date

00-00-00

Rev.#Rev. By

00-00-00

WEST POINT,N.Y.

USMA, WEST POINT, NY

100% DESIGN PACKAGE

FOR THE RENOVATION

AND MODERNIZATION

OF PERSHING

BARRACKS

REVIEWED BY:

PROJECT NUMBER:

SEAL: DRAWING NO.

SHEET TITLE:

HISTORIC CONSERVATION

40 WEST 27th

STREET,

SUITE 1201

NEW YORK, NY

10001

CONTACT:

MARY JABLONSKI

TEL: 212.532.7775

FAX: 212.532.2188

1 2 3 5 6

B

C

D

E

A

STRUCTURAL

ISSUE FOR BID DATE: 06/08/16

ATKINS #100040983

/8

/2

:5

:5

P

M

M-602

REP

DLH

HVAC DETAILS

NO SCALE

AIR SEPARATOR/ELIMIN. & EXPANSION TANK HW PIPING DIAGRAM

NO SCALE

ADJUSTABLE CLEVIS HANGER

NO SCALE

ADJUSTABLE ROLLER HANGER

NO SCALE

DUPLEX CONDENSATE RETURN PUMP (LESS THAN 200º F ONLY) PIPING

NO SCALE

MISCELLANEOUS STEEL FOR PIPE SUPPORT

NO SCALE

INSULATED VERTICAL PIPE SUPPORT

NO SCALE

REPLACEABLE INSERT ORIFICE STEAM TRAP

NO SCALE

STEAM SAFETY-VALVE & DRIP-PAN ASSEMBLY

NO SCALE

TYP. INSULATED PIPE SADDLE SUPPORT

12" = 1'-0"

ENERGY RECOVERY AIR HANDLING UNIT DETAIL

NO SCALE

PIPE CLAMP

MAV

DRAIN

INDIRECT

RELIEF TO

VB

TAV

AT 2/3 CAPACITY.

5. PROVIDE TWO SCV'S IN PARALLEL AS INDICATED, ONE AT 1/3 CAPACITY, OTHER

VB

SCV

SCV

PIPE TO NEAREST

F & T

VACUUM RETURN SYSTEMS.

INLET CONNECTION TO CONDENSATE RETURN REQUIRED ONLY ON

4. VACUUM BREAKERS ARE REQUIRED ON ALL SYSTEMS, VACUUM BREAKER

VALVE

INSPECTION

LINE-SIZE

6" DIRT POCKET

12" MIN

MAIN

RETURN

COND

MAIN

SUPPLY

STEAM

LARGER CONTROL VALVE

BYPASS SAME SIZE AS

INDIRECT DRAIN

HWR

HWS

3. PRESSURE RELIEF VALVE SET AT EQUIPMENT'S RATED PRESSURE.

TO PIPING.

FACILITATE TUBE BUNDLE REMOVAL WITH MINIMUM DISTURBANCE

2. PROVIDE PIPE UNIONS, FLANGES, AND ARRANGE WATER PIPING TO

1. BYPASS PIPING AROUND F&T TRAP LEG SHALL BE SAME SIZE AS TRAP.

NOTES:

N.C.

N.C.

DRAIN

VALVE

VACUUM BREAKER

DRAIN

INDIRECT

RELIEF TO

STEEL BASE PLATE, WELD TO LEG

SUPPORT (REFER TO SCHEDULE

FOR SIZE)

1" NON-SHRINK

NON-FERROUS

GROUT

ANCHOR BOLT (4 REQ'D)

(REFER TO SCHEDULE FOR

SIZE AND EMBEDMENT)

1 1/4"Ø VENT HOLE (CENTER LINE 2"

ABOVE BOTTOM OF BASE PLATE)

SCHED. 40 BLACK STEEL SADDLE

LEG SUPPORT (REFER TO

SCHEDULE FOR SIZE)

BASE PLATE

20"x20"x1/2"

18"x18"x1/2"

18"x18"x1/2"

14"x14"x1/2"

10"x10"x1/2"

10"x10"x1/2"

10"x10"x3/8"

MIN. EMBEDMENT

5"

5"

5"

4"

4"

4"

4" 4"

4"

4"

3"

3"

3"

10"x10"x3/8"

8"x8"x3/8"

8"x8"x3/8"

8"x8"x3/8"

8"x8"x3/8"

6"x6"x3/8"

NOTES;

1. THIS DETAIL SHALL BE USED AS A GUIDE. ALL SUPPORTS SHALL MEET THE

REQUIREMENTS OF THE SPECIFICATIONS.

SERVICE PIPE (REFER TO PLANS

FOR SIZE)

INSULATION (AS REQUIRED) (REFER

TO SPECIFICATIONS FOR TYPE AND

COVER)

CONTINUOUSLY WELD LEG

SUPPORT TO ELBOW

EXTEND INSULATION TO

COVER LEG SUPPORT

8' -0

" F R

O M

F

LO

O R

M A

X

12" MAX.

SADDLE LEG SUPPORT

14"Ø

10"Ø

10"Ø

8"Ø

6"Ø

6"Ø

6"Ø

6"Ø

4"Ø

3"Ø

4"Ø

4"Ø

2"Ø

PIPE SIZE

30"Ø

24"Ø

20"Ø

18"Ø

16"Ø

14"Ø

12"Ø

10"Ø

8"Ø

6"Ø

5"Ø

4"Ø

3"Ø

ANCHOR BOLTS

3/4"Øx8" LONG

3/4"Øx8" LONG

3/4"Øx8" LONG

5/8"Øx8" LONG

5/8"Øx8" LONG

5/8"Øx8" LONG

5/8"Øx8" LONG

5/8"Øx8" LONG

1/2"Øx8" LONG

1/2"Øx8" LONG

1/2"Øx6" LONG

1/2"Øx6" LONG

1/2"Øx6" LONG

COOLING COIL (TYP.)

FZ

FZ

REFER TO SPEC. FOR LENGTH

OF FREEZESTAT

FZ

FZ

x x x xx x x x x x x x

SPRING ISOLATOR (TYP.)

ANCHOR TO SLAB.

ELASTOMER PAD (TYP.)

FIRE PROOF CAULK (TOP

AND BOTTOM)

PIPE

SLEEVE

PIPE CLAMP WELDED TO

PIPE

INSULATION BUTTED TO CLAMP

WELD

VOID FILLED WITH

APPROVED FIRE STOPPING

BOLT TO CONC. SLAB

INSULATION BUTTED TO SLAB

PIPE CLAMP

INSULATION

RISER PIPE

PIPE CLAMP

NOTE:

1. REFER TO AND COMPLY WITH FIRESTOPPING SPECIFICATIONS.

4" M

IN

4" M

A X

1/2" NPT CONNECTION

BIMETAL

THERMOMETER

SERIES EL

NOTE:

PROVIDE AND INSTALL BIMETAL TYPE THERMOMETER. ASHCROFT MODEL

30-EL-60-E-040-XSG-0/200F, THREE INCH DIA. STAINLESS STEEL LIQUID

FILLED CASE, ½" NPT CONNECTION WITH EVERYANGLE CASE CONNECTION

TO ALLOW FOR 360 DEGREES ROTATION, BIMETAL STEM LENGTH OF 4",

SHATTERPROOF GLASS AND A TEMPERATURE RANGE OF 0 TO 200

DEGREES. THERMOMETER SHALL BE PROVIDED WITH STANDARD

CONFIGURATION 316 S.S THERMOWELL.

INSULATED PIPE

PRE-FAB BASE SUPPORT

EXTERIOR FLAT

NOTE:

PROVIDE SUPPORT SPACING PER

CODE AND/OR SPECIFICATIONS.

HEIGHT

MIN. PER

CODE

SURFACE

PIPE CLAMP (TYP.). PROVIDE

DOUBLE NUT FASTENING TO

AVOID CRUSHING INSULATION

GALV. CHANNEL

SUPPORT

14" MIN. CURB HEIGHT

STEAM MAIN

STEAM MAIN

FULL SIZE OF

STEAM MAIN

(M

IN

(M

IN

TO CONDENSATE

RETURN MAIN

CAP

NOTES:

1. ALL VALVES AND FITTINGS SHALL BE FULL LINE SIZE UNLESS NOTED OTHERWISE.

REDUCER (TYP.)

COMBINATION SHUTOFF/

CHECK/ MEASURING/

BALANCING VALVE

PRESSURE GAUGE W/

BALL VALVE & SNUBBER

ECCENTRIC REDUCER

PIPE TO NEAREST

FLOOR DRAIN

STEEL BASE RAIL

(OR INTERIA BASE)

PIPE SUPPORT

FOR SUCTION

DIFFUSER

SUCTION DIFFUSER W/INTEGRAL

STRAINER, 3/4" BLOWDOWN

VALVE & CAP. PIPE TO FLOOR

DRAIN

FLEXIBLE CONNECTION (TYP.)

PRESSURE/TEMPERATURE TEST

PORT W/ COCK (TYP.)

GATE VALVE.

2. GROUT PUMP BASE.

3. MECHANICAL COUPLINGS/JOINTS SHALL NOT BE USED IN SUBSTITUTION FOR FLEXIBLE

PIPE CONNECTIONS SHOWN.

4. SUCTION DIFFUSER INLET SHALL BE FULL PIPE SIZE.

FLOOR

4" THICK CONCRETE PAD

STEAM

SPEC

COND

SPEC

CONCENTRIC

REDUCER

STRAINER

UNION

(TYP.)

ISOLATION

VALVE (TYP.)

CHECK VALVE

LOCATE NEAR

TRAP

STEAM TRAP - REFER

TO PLANS AND SCHEMATICS

FOR STEAM TRAP DESIGNATION

GLOBE VALVE SIZE OF STEAM TRAPPROVIDE BY-PASS

FOR STEAM TRAPS

2-1/2" AND GREATER

SIZE OF STEAM TRAP

NOTE:

1. ALL STEAM TRAP PIPING AND VALVE COMPONENTS

SHALL BE ONE PIPE SIZE LARGER THAN STEAM TRAP.

3/4" TEST TEE WITH

VALVE & CAP

FLASH - TO MAIN

PRESSURE GAUGE W/BALL VALVE

CONCENTRIC REDUCER

PRESSURE RELIEF VALVE, W/DRIP

PAN ELBOW - REFER TO STEAM

SYSTEM SCHEMATIC ON DWG.

M-701 FOR RELIEF VALVE SETTINGS

DRIP PAN ELBOW

ASTM A106, GRADE B SCHED

80 FLASH TANK. ASME

BOILER AND PRESSURE

VESSEL CODE CONSTRUCTION

FULL SIZE DRIP LEG

MINIMUM 6" LONG

M

IN

CEMENT GROUT

FLOOR SLAB

CHROMED PIPE

ESCUTCHEON USED

IN EXPOSED AREAS

THROUGH PIPE SLEEVE.

INSULATION AS SPECIFIED PASSES

EXTEND PIPE SLEEVE 1" ABOVE

FLOOR. WHERE MORE THAN ONE

OCCURS, TOPS ARE LEVEL.

NOTE:

1. REFER TO AND COMPLY WITH FIRESTOPPING SPECIFICATIONS.

MAV

NOTE:

ALL VALVES AND FITTINGS SHOWN ABOVE MUST FIT

WITHIN THE FAN COIL ENCLOSURE. CONTROL

VALVES SHALL BE OVER EXTENDED DRAIN PAN.

RETURNSUPPLY

COIL

COIL MAV

RETURN SUPPLY

PIPE COOLING

COIL DRAIN PAN

TO DRAIN

CALIBRATED

BALANCING

VALVE (TYP)

AUTOMATIC

CONTROL

VALVE (TYP)

ECCENTRIC

REDUCER (TYP)

P/T PORT (TYP)

HED (TYP)

PIPE WALL SLEEVE.

SEAL W/FIRE STOPPING

REMOVABLE INSULATION

OVER MANUAL AIR VENT

MANUAL AIR VENT

WALL

CHWS/HWS MAIN

ABOVE CEILING

CEILING ACCESS

PANEL

CEILING

TO HVAC PIPE RISER

BALL VALVE

D

UN RCO

UT Y

HONOR

T Y

MD

CC

CII

PO INWEST T

USM A

DRAWN BY:

U. S. ARMY

GARRISON

PROJECT:

ARCHITECTURE, INTERIORS,

CIVIL, LANDSCAPE, MECHANICAL,

PLUMBING, FIRE PROTECTION

NORTH AMERICA INC

2318 MILL ROAD,

SUITE 1040,

ALEXANDRIA, VA 22314.

TELEPHONE: (703) 535-3008

FAX: (703) 535-1031

R.G.VANDERWEIL, LLP

1001 AVENUE OF THE

AMERICAS, 21st FLOOR

NEW YORK, NY 10018

ELECTRICAL,TELECOMMUNICATION,SECURITY

212.921.4142 TEL

212.921.4616 FAX

VANDERWEIL.com

CLIENT

Revision / Submission

XXX XXX XXX XXX XXX XXX

Date

00-00-00

Rev.#Rev. By

00-00-00

WEST POINT,N.Y.

USMA, WEST POINT, NY

100% DESIGN PACKAGE

FOR THE RENOVATION

AND MODERNIZATION

OF PERSHING

BARRACKS

REVIEWED BY:

PROJECT NUMBER:

SEAL: DRAWING NO.

SHEET TITLE:

HISTORIC CONSERVATION

40 WEST 27th

STREET,

SUITE 1201

NEW YORK, NY

10001

CONTACT:

MARY JABLONSKI

TEL: 212.532.7775

FAX: 212.532.2188

1 2 3 5 6

B

C

D

E

A

STRUCTURAL

ISSUE FOR BID DATE: 06/08/16

ATKINS #100040983

/8

/2

:5

:0

P

M

M-603

REP

DLH

HVAC DETAILS

NO SCALE

STEAM TO LIQUID HEAT EXCHANGER

NO SCALE

TYP. INSULATED PIPE RISER FLOOR SUPPORT

NO SCALE

TYPICAL COIL FREEZESTAT INSTALLATION

NO SCALE

TYPICAL PIPING RISER SUPPORT

NO SCALE

GAUGE CONNECTION

NO SCALE

PIPE SUPPORT DETAIL

NO SCALE

CONDENSATE DRIP LEG

NO SCALE

END SUCTION PUMP DETAIL

NO SCALE

STEAM TRAP PIPING

NO SCALE

FLASH TANK

NO SCALE

PIPE FLOOR SLAB PENETRATION DETAIL

NO SCALE

4-PIPE FAN COIL, 2-WAY CONTROL VALVES

8" X 8" STEEL BEARING PLATE

ANCHORED TO PAD (TYP OF 4)

4" THICK CONCRETE PAD

2-1/2" DIA STEEL PIPE LEG (TYP OF 4)

CONVERTOR CRADLE

FLOOR

NO SCALE

TYPICAL HVAC PIPE RISER BRANCH CONNECTION DETAIL

FLEXIBLE

CONNECTION

CONDENSATE DRAIN

WITH P-TRAP

CEILING.

HANGER ROD (TYP. OF 4)

SUPPLY DUCT

SECONDARY

DRAIN PAN

CONDENSATE

DRAIN PAN

COOLING AND

HEATING COIL

HINGED BOTTOM ACCESS W/SAFETY

CHAIN AND TAMPER-PROOF CAM

LOCK FASTENERS. LATCHES ARE

NOT ACCEPTABLE

SECTION VIEW

SUPPLY FAN

SUPPLY DUCT

FAN

MOTOR

HEATING AND

COOLING COIL

END POCKET

FOR VALVES

PLAN VIEW

END POCKET FOR

ELECTRICAL POWER

CONNECTION & CONTROLS

HWS, HWR, CHWS,

CHWR, COND. DRAIN

FLEXIBLE

CONNECTION

SUPPORT STEEL.

REFER TO

STRUCTURAL

DRAWINGS

HIGH LEVEL

CONDENSATE

SWITCH

NOTE:

HVAC EQUIPMENT, DUCTWORK AND PIPING

SHALL BE SUPPRTED FROM NEW UNISTRUT

FRAME SYSTEM. REFER TO STRUCTURAL

DWG S-207 "TYPICAL DETAIL MEP AND

PARTITION WALL HEAD UNISTRUT

FRAME SUPPORT" AND COORDINATION

NOTE "9" ON DWGS S-100 THROUGH S-107.

18" x 18"

8" x 8"

12" x 12"

NOTES:

4. VERTICAL POSITION SHOWN. HORIZONTAL INSTALLATION SIMILAR. DAMPER TO BE

SPRING LOADED WHEN HORIZONTAL.

3. ALL ATTACHMENTS PER MANUFACTURER'S APPROVED INSTALLATION INSTRUCTION.

2. 1-1/2"x1-1/2"x1/8" RETAINING ANGLES SHALL LAP STRUCTURAL OPENING 1" MIN. &

COVER CORNERS OF OPENINGS. ANGLES ATTACH TO SLEEVE ONLY AND MUST NOT

BE ATTACHED TO EACH OTHER AT CORNERS OR TO WALL.

1. PROVIDE ACCESS DOOR & LABEL ON SIDE OR BOTTOM OF DUCT AS FOLLOWS:

LINK

FUSIBLE

165°F

4" MIN.

1" MIN.

SLEEVE 16 GA. MIN.

FABRICATED STEEL

MANUF. OR FIELD

NOTE# 2

EACH SIDE

6" MAXIMUM

METAL STUD CONSTRUCTION

MATERIAL (TYP.)

FIRE RESISTIVE

NOTE # 1

FASTENER W/WASHER

DUCT

SHEET METAL

NOTE # 2)

MIN. ALL SIDES (SEE

1-1/2"x1-1/2"x1/8"

RETAINING ANGLES

CLOSURE TAPE (TYP.)

BARRIER (TYP.)

DUCT WRAP W/VAPOR

METAL DUCT

WRAPPED SHEET

PLAIN "S" SLIP

(555) SECURE TO SLEEVE

U.L. LABELED FIRE DAMPER,

DIMENSIONS.

LINEAR FOOT BOTH

CLEARANCE 1/8" PER

CONSTRUCTION

CONCRETE OR MASONRY

10" THRU 12"

14" THRU 20"

22" AND ABOVE

DOOR SIZEDUCT WIDTH

5. FIRE DAMPER BLADE SHALL BE OUTSIDE OF AIR STREAM WHEN OPEN.

FIRE DAMPER OPENING SHALL

BE FULL DUCT SIZE

ACCESS DOOR ON SIDE

OR BOTTOM OF DUCT.

FLOOR

STEEL SLEEVE OF

GAGE PER DAMPER

MANUFACTURER

INSTALL DAMPER IN

ACCORDANCE WITH

MANUFACTURER'S

RECOMMENDATIONS

ANCHOR ANGLE TO STEEL

SLEEVE, NOT TO WALL

"S" SLIP JOINT

RETAINING ANGLES SHALL BE

INDEPENDENT OF EACH OTHER (TYP)

F.D. ACCESS DOOR SIZE

DUCT WIDTH

6" THRU 18"

19" THRU 24"

25" THRU 36"

37" AND UP

DOOR SIZE

6" X 12"

12" X 18"

18" X 18"

12" X 18"

MIN. GAGE

55" - 84"

31" - 54"

13" - 30"

0" - 12"

DUCT DIMENSION

WALL SLEEVE

85" - UP 18

2" X 2" X 1/8"

1 1/2" X 1 1/2" X 1/8"

MINIMUM ANGLE SIZE

96" - UP

49" - 96"

0" - 48"

LENGTH

ANGLE IRON & FASTENER DIMENSIONS

FASTENERS

8" ON CENTER

6" ON CENTER

6" ON CENTER2 1/2" X 2 1/2" X 3/16"

1. INSTALL FIRE DAMPERS IN ACCORDANCE WITH DAMPER MANUFACTURER'S INSTALLATION

INSTRUCTIONS, AND REQUIREMENTS INDICATED ABOVE. WHERE REQUIREMENTS ARE IN

CONFLICT, THE MORE STRINGENT WILL GOVERN.

2. APPLY DUCT INSULATION OVER RETAINING ANGLES ONLY AFTER FINAL INSPECTION.

FUSIBLE

LINK

165° F

LABEL "FIRE DAMPER ACCESS"

3. FIRE DAMPER BLADE SHALL BE OUTSIDE OF AIR STREAM WHEN OPEN.

4. FIRE DAMPER OPENING/CONNECTION SHALL BE FULL SIZE OF DUCT.

9. S-JOINT, SLEEVE TO DUCT

6" MAXIMUM

10. CAULKING MATERIAL

1/2" MINIMUM

ITEM

WALL

FSD60 DAMPER (BY RUSKIN)

DUCT

1" MINIMUM

ON ALL SIDES

TYPICAL OVERLAP

OF DAMPER

3. AUXILIARY OPERATING JACK SHAFT

7. NEGATOR SPRING

8. MOUNTING ANGLES

2. FUSIBLE ROD

4. DAMPER FRAME

6. SLEEVE

5. FUSIBLE LINK WITH LOCK

1. OPERATOR/ACTUATOR

DESCRIPTION

APPLICATION:

COMBINATION FIRE AND LEAKAGE RATED DAMPERS ARE DESIGNED TO OPERATE WITH BLADES RUNNING

HORIZONTALLY AND MUST BE IN- STALLED WITHIN THE FIRE WALL DUCT OPENING. TO INSURE OPTIMUM

OPERATION AND PERFORMANCE, THE DAMPER MUST BE INSTALLED SO THAT IT IS SQUARE AND FREE FROM

RACKING. DO NOT COMPRESS OR STRETCH THE DAMPER FRAME INTO THE DUCT OR OPENING.

GENERAL INSTALLATION:

THE FIRE WALL OPENING SHALL BE A MINIMUM OF 1/4" PER INCH LARGER THAN THE OVERALL SIZE OF THE

DAMPER AND SLEEVE ASSEMBLY. THE MAXIMUM OPENING SIZE SHALL NOT EXCEED 1/4" PER INCH PLUS 1", NOR

SHALL THE OPENING BE LESS THAN 1/2" LARGER THAN ANY DAMPER AND SLEEVE ASSEMBLY.

AS DESCRIBED IN NFPA 90A AND AS DEFINED BY THE APPROPRIATE SMACNA DUCT CONSTRUCTION STANDARD, THE SLEEVE GAGE SHALL BE EQUAL TO OR HEAVIER THAN THE GAGE OF THE DUCT WHEN ONE OR MORE OF THE

FOLLOWING DUCT CONNECTIONS ARE USED: PLAN S-SLIP, HEMMED S-SLIP, STANDING S-SLIP, REINFORCED

STANDARD S-SLIP, INSIDE SLIP JOINT, AND DOUBLE S-SLIP. THE DAMPER IS FASTENED TO THE SLEEVE WITH 1/2"

WELDS SPACED 8" CENTER TO CENTER AND A MAXIMUM OF 2" FROM DAMPER CORNERS. IF OTHER DUCT SLEEVE

CONNECTIONS ARE USED, THE SLEEVE SHALL BE A MINIMUM OF 16 GAGE FOR DAMPERS UP TO 35" WIDE BY 25"

HIGH AND 14 GAGE FOR DAMPER WIDTHS EXCEEDING 35" OR HEIGHTS EXCEEDING 25".

MOUNTING ANGLES SHALL BE 1 1/2" X 1 1/2" X 14 GAGE MINIMUM AND FASTENED WITH NO. 10 BOLTS OR SCREWS

1/4" DIAMETER STEEL RIVETS OR 1/2" LONG TACK WELDS. SPACE FASTENING A ON CENTER FOR 1-1/2 HOUR

RATED DAMPERS.

WHEN JOINING MULTIPLE DAMPER ASSEMBLIES OR FASTENING THE DAMPER TO THE SLEEVE, DAMPERS SHALL

BE FASTENED WITH 1/4" 20 BOLTS, NO. 10 SCREWS, OR 1/2" LONG WELDS STAGGERED INTERMITTENTLY ON BOTH

SIDES. SPACE FASTENERS 6" ON CENTER AND A MAXIMUM 2" FROM THE ENDS OF THE JOINING SECTIONS OR

FROM EACH CORNER. WHEN JOINING MULTIPLE DAMPER ASSEMBLIES, A CONTINUOUS 1/4" BEAD OF

DOW-CORNING 100% SILICON RUBBER, DOW-CORNING SILASTIC 732, OR GE RTV 106 SEALANT SHALL BE APPLIED

ON THE MULLION JOINT. PRESS THE SURFACE OF THE SEALANT IN PLACE TO DISPEL ANY AIR.

ANOTHER BEAD OF THE SAME SEALANT SHALL BE APPLIED BETWEEN THE DAMPER AND SLEEVE IN THE SAME

MANNER. ONLY ONE SIDE OF THE DAMPER REQUIRES CAULKING. NOTE THAT SEALANT IS NOT REQUIRED WHEN

DAMPERS ARE SUPPLIED FOR FIRE DAMPER APPLICATIONS ONLY AND ARE NOT REQUIRED TO BE LEAKAGE

RATED.

DAMPER SLEEVE SHALL NOT EXTEND MORE THAN 6" BEYOND THE FIRE WALL OR PARTITION AND NOT MORE

THAN 9" ON THE OPERATOR/ACTUATOR SIDE.

THESE INSTRUCTIONS COMPLY WITH UNDERWRITERS LABORATORIES SAFETY STANDARDS 555 AND 555S.

INSTALLATION SHOWN AS AN EXAMPLE. SPECIFIC INSTALLATION SHALL CONFORM WITH MANUFACTURER'S, UL

APPROVED INSTRUCTIONS.

11. DUCT SMOKE DETECTOR

4 115-240

3 65-115

2&1/2 40-65 2 21-40 1&1/2 14-21

1&1/4 0-14

SEE NOTE 5

WATER COIL

TO

ADD'L

COILS

SEE NOTE 9

REDUCE AS

NEEDED (TYP) MAV

RETURN

SUPPLY

SEE NOTE 7 (TYP)

6" DIRT POCKET FULL SIZE

OF HEADER

SEE NOTE 6

(TYP)

DRAIN PAN(S) PIPING

(COOLING ONLY)

INDEPENDENT DRAIN

LINES EXTEND TO

NEAREST DRAIN (TYP)

CO

CO

PROVIDE DRAIN VALVES AT LOW POINTS OF ALL

COIL HEADERS SAME SIZE AS COIL-OUTLET SIZES

BUT NOT LESS THAN 3/8".TRAP SEAL REFER TO

DRAINPAN WATER SEAL

DETAIL (TYP)

FREEZE PROTECTION RETURN TEMPERATURE SENSOR. SEE CONTROLS DRAWINGS.9.

PROVIDE PRESSURE GAUGE ACROSS SUPPLY, RETURN AND STRAINER.8.

REFER TO SPECIFICATIONS FOR DRAIN PAN REQUIREMENTS.7.

FOR SUPPLY AND RETURN PIPES LARGER THEN 2" USE GATE VALVES WITH FLANGES FOR ISOLATION.6.

FOR SUPPLY AND RETURN PIPES 2" AND SMALLER, USE BALL VALVES WITH UNIONS FOR ISOLATION.5.

VALVE W/MEMORY STOP IN BYPASS LEG.

FOR ACTUAL JOB REQUIREMENTS. FOR 3-WAY VALVE PROVIDE ADDITIONAL THERMOMETER AND ISOLATION

TWO-WAY CONTROL VALVE SHOWN. SEE AUTOMATIC-TEMPERATURE-CONTROL DIAGRAM AND SPECIFICATIONS4.

PROVIDE SIMILAR PIPING ARRANGEMENTS ON EACH SIDE FOR TWO-SECTION-WIDE COIL ASSEMBLY.3.

REDUCERS AS REQUIRED.

LOCATE PIPE UNIONS (OR FLANGED BODY) AND ARRANGE PIPING TO FACILITATE COIL REMOVAL. PROVIDE2.

PROVIDE SIMILAR PIPING FOR 3 OR MORE COILS HIGH.1.

NOTES:

FLOW (GPM)SIZE (IN)

RUNOUT SIZING

FLOW

AIR

FZ

MAV

PTCO

PT

PT

HED (TYP)

NOTE 8

MAV

MAV

FZ

SEE NOTE 4

HORIZONTAL MAIN PIPING

CONNECTIONS SHALL BE SIMILAR.

2. TOP CONNECTIONS ARE SHOWN; BOTTOM

SYSTEM BALANCING.

STOP ON RETURN VALVE TO FACILITATE

ACCESSIBLE LOCATIONS. PROVIDE MEMORY

1. PROVIDE ISOLATION SERVICE VALVES AT

NOTES:

MINIMUM THREE-ELBOW

SWING JOINT AT BRANCH

MAIN TAKE-OFFS

BRANCH MAIN

COIL FREEZE PROTECTION PUMP -

REFER TO "INLINE PUMP ASSEMBLY"

DETAIL

TO COIL- REFER TO

"AHU/ERU COIL CONNECTION"

DETAIL

1. THIS DETAIL IS INTENDED TO DETAIL FREEZE PROTECTION PUMP PIPING

ARRANGEMENT. REFER TO "AHU/ERU COIL CONNECTION" DETAIL FOR

ADDITIONAL REQUIREMENTS.

NOTES:

CONTROL VALVE

MAV

MAV

REDUCE AS NEEDED

1. REFER TO AUTOMATIC CONTROL DRAWINGS AND SPECIFICATIONS

FOR CONTROL REQUIREMENTS.

NOTES:

UNIT HEATER

HWR

HWS

PT

PT

HED

SEE NOTE #1

AUTOMATIC AIR VENT

CONDENSING UNIT (TYP.)

FASTEN UNIT TO

SUPPORT STEEL

ROOF

SUPPORT STEEL. REFER TO

STRUCTURAL DRAWINGS

VIBRATOR

ISOLATOR

(TYP.)

PIPING SPECIFICATION:

UNDERGROUND STEAM AND CONDENSATE RETURN PIPING SHALL BE A

FACTORY FABRICATED AND PRE-INSULATED PIPING SYSTEM. THE SYSTEM

SHALL BE TESTABLE, DRAINABLE AND DRYABLE. THE SYSTEM SHALL CONSIST

OF THE FOLLOWING:

· 2 INCHES MINERAL WOOL INSULATION WITH STAINLESS STEEL BANDS

· SUPPORT ASSEMBLY

· 10 GAUGE STEEL CONDUIT, H-20 RATED

· 1 INCH POLYURETHANE FOAM INSULATION

· FRP OUTER PROTECTIVE JACKET

· PROVIDE GLAND SEAL AT INDOOR TERMINATION

· SEAL OFF UNDERGROUND JACKET TERMINATION IN ACCORDANCE WITH

MANUFACTURER AND MARK WITH UNDERGROUND MAGNETIC WARNING

TAPE.

· CONDENSATE RETURN SERVICE PIPE: SCHEDULE 80 STEEL

· STEAM SERVICE PIPE: SCHEDULE 40 STEEL

· PROVIDE ANCHOR BLOCK, VENT & DRAIN. END SEALS AND ANCHOR

BLOCKS IN ACCORDANCE WITH THE MANUFACTURER WRITTEN

INSTRUCTIONS.

· THE MANUFACTURER SHALL BE RESPONSIBLE FOR THE DESIGN OF

THERMAL EXPANSION COMPENSATION AND PROVIDE A PIPING SYSTEM IN

ACCORDANCE WITH ASME 31.1.