SYMBOL ITEM CAPACITY/SIZE MOTOR DATA BASIS OF DESIGN REMARKS

B‐1 OIL FIRED BOILER 646 MBH GROSS OUTPUT

562 MBH NET I.B.R. RATING

5.6 GPH FIRING RATE

1/3 HP 3450 RPM

120 VOLT/60 HZ

BURNHAM V905A BOILER

BECKET CF‐800 BURNER

PROVIDE COMPLETE TRIM INCLUDING TEMPERATURE/PRESSURE GUAGE,

HIGH LIMIT CONTROL, OPERATING CONTROL, LOW WATER CUT‐OFF,

PRESSURE RELIEF VALVE, DRAIN VALVE

AS‐1 AIR SEPARATOR 2‐1/2 INCH; Cv = 61 TACO 435 AIR SCOOP

ET‐1 EXPANSION TANK 37 GALLON TANK VOLUME

100% ACCEPTANCE VOLUME

TACO CA140‐125 12 PSIG PRECHARGE; 295 GALLON ESTIMATED SYSTEM VOLUME; 50%

PROPYLENE GLYCOL

MISCELLANEOUS EQUIPMENT SCHEDULE

SYMBOL MFGR / MODEL SERVICE FLUID GPM HEAD (FT) RPM HP VOLTS/PH REMARKS

CP‐1 GRUNDFOS MAGNA3 40‐120F UH LOOP 50% P.G. 32 28 VARIABLE 450W 115V/1

CP‐2 GRUNDFOS MAGNA3 40‐120F RADIANT & BASEBOARD 50% P.G. 30 32 VARIABLE 450W 115V/1

PUMP SCHEDULE

MOTOR DATA

NOTE: BASIS OF DESIGN PUMPS SELECTED WITH FOR EXCESS CAPACITY AND INTEGRAL VARIABLE SPEED CONTROL. SUBSTITUTION OF A CONSTANT SPEED PUMP IS NOT PERMITTED.

CAPACITY WPD

SYMBOL MFGR / MODEL (MBH) GPM FLUID EFT LFT (FT HD) CFM HP VOLTS/PH REMARKS

UH‐1 TRANE P‐202 95 8.0 50% P.G. 180F 150F <0.5 3200 1/4 115V/1

PROVIDE WITHOUT OPTIONAL OUTLET

DIFFUSER

UNIT HEATER SCHEDULE

MOTOR DATA

NOTE: LISTED CAPACITY DERATED FOR NON‐STANDARD CONDITIONS OF GLYCOL & 180F EFT