SYMBOL ITEM CAPACITY/SIZE MOTOR DATA BASIS OF DESIGN REMARKS
B‐1 OIL FIRED BOILER 646 MBH GROSS OUTPUT
562 MBH NET I.B.R. RATING
5.6 GPH FIRING RATE
1/3 HP 3450 RPM
120 VOLT/60 HZ
BURNHAM V905A BOILER
BECKET CF‐800 BURNER
PROVIDE COMPLETE TRIM INCLUDING TEMPERATURE/PRESSURE GUAGE,
HIGH LIMIT CONTROL, OPERATING CONTROL, LOW WATER CUT‐OFF,
PRESSURE RELIEF VALVE, DRAIN VALVE
AS‐1 AIR SEPARATOR 2‐1/2 INCH; Cv = 61 TACO 435 AIR SCOOP
ET‐1 EXPANSION TANK 37 GALLON TANK VOLUME
100% ACCEPTANCE VOLUME
TACO CA140‐125 12 PSIG PRECHARGE; 295 GALLON ESTIMATED SYSTEM VOLUME; 50%
PROPYLENE GLYCOL
MISCELLANEOUS EQUIPMENT SCHEDULE
SYMBOL MFGR / MODEL SERVICE FLUID GPM HEAD (FT) RPM HP VOLTS/PH REMARKS
CP‐1 GRUNDFOS MAGNA3 40‐120F UH LOOP 50% P.G. 32 28 VARIABLE 450W 115V/1
CP‐2 GRUNDFOS MAGNA3 40‐120F RADIANT & BASEBOARD 50% P.G. 30 32 VARIABLE 450W 115V/1
PUMP SCHEDULE
MOTOR DATA
NOTE: BASIS OF DESIGN PUMPS SELECTED WITH FOR EXCESS CAPACITY AND INTEGRAL VARIABLE SPEED CONTROL. SUBSTITUTION OF A CONSTANT SPEED PUMP IS NOT PERMITTED.
CAPACITY WPD
SYMBOL MFGR / MODEL (MBH) GPM FLUID EFT LFT (FT HD) CFM HP VOLTS/PH REMARKS
UH‐1 TRANE P‐202 95 8.0 50% P.G. 180F 150F <0.5 3200 1/4 115V/1
PROVIDE WITHOUT OPTIONAL OUTLET
DIFFUSER
UNIT HEATER SCHEDULE
MOTOR DATA
NOTE: LISTED CAPACITY DERATED FOR NON‐STANDARD CONDITIONS OF GLYCOL & 180F EFT