TABLE OF CONTENTS

VOLUME 2

Table of Contents

Project Contact List

1-Year Labor Warranty

O&M Instructions .................................................................................................. 28 31 74.10 28

Data Sheets

Installation Sheets

FA Program Reports

Technical Manuals

Shop Drawings

Product Data

• Item No. 3

• Item No. 4

• Item No. 5

• Item No. 6

• Item No. 7

• Item No. 8

• Item No. 9

Preliminary Testing

FIO

Job No: 12-02

(By Spec Section) 7/8/2013Date:

Contract Addresses

The Dalles Dam Elevator Refurb

Title

Fax

Phone

NameAddressRole Section

SpecCompany

OWN US Army Corps of Engineers 00001 - Owner

333 SW First Ave Portland, OR 97204-3495

Phone:

Fax:

503-808-4614 503-808-4605

Albert Wright Project Engineer

1060 NW Corporate Drive Troutdale, OR 97060

Phone: 503-492-3570 Fax:

Cellular: 541-968-1254 albert.w.wright@usace.army.mil

Brian Schmidtke Phone: 503-808-4708 Fax: 503-808-4605 brian.p.schmidtke@usace.army.mil

Carl Brenneise201 3rd Avenue Walla Walla, WA 99362

Phone: 509-527-7540 Fax:

Carl.B.Brenneise@usace.army.mil

Control Room - EmergencyPO Box 564 The Dalles, OR 97058

Phone: 541-298-7505 Fax:

Daniel Mansur

GQAR

PO Box 564 The Dalles, OR 97058

Phone: 541-374-2146 Fax:

Cellular: 503-804-1187

Daniel.G.Mansur@usace.army.mil

Daniel Pullen201 3rd Avenue Walla Walla, WA 99362

Phone: 509-527-7561 Fax:

Daniel.F.Pullen@usace.army.mil

Deitra Greene Security Badging

P.O. Box 564 The Dalles, OR 97058-998

Phone: 541-506-7828 Fax:

deitra.greene@usace.army.mil

Heather Keizur Pagers

PO Box 564 The Dalles, OR 97058

Phone: 541-298-7512 Fax:

Heather.B.Keizur@usace.army.mil

Jeffrey Renner Contract Specialist

Phone: 503-808-4630 Fax: 503-808-4605

Jeff.S.Renner@usace.army.mil

Jim Dennis

Phone: 541-298-7415 Fax:

Jon Lomeland201 3rd Avenue Walla Walla, WA 99362

Phone: 509-527-7652 Fax:

Jon.A.Lomeland@usace.army.mil

Kaleka Ross Procurement Tech

Phone: 503-808-4611 Fax: 503-808-4605

Kaleka.I.Ross@usace.army.mil

Karen Rutherford QCS Contact

P.O. Box 70 Cascade Locks, OR 97014-0070

Phone: 541-374-5456 Fax: 541-374-2245

Karen.K.Rutherford@usace.army.mil

Kelli Zak201 3rd Avenue Walla Walla, WA 99326

Phone: 509-527-7554 Fax:

Kelli.S.Zak@usace.army.mil

Kenneth Samsel Phone: 541-374-8250 Fax:

Kenneth.G.Samsel@usace.army.mil

Mark Heiller Contracting Officer

Phone: 503-808-4612 Fax:

Page 1 of 7Todd Construction, Inc.

Contract Addresses

The Dalles Dam Elevator Refurb

Title

Fax

Phone

NameAddressRole Section

SpecCompany

Matt Stewart Security Clearance

PO Box 564 The Dalles, OR 97058

Phone: 541-296-1181 Fax:

Matthew.L.Stewart@usace.army.mil

Naameh Nomie Admin Cntrcting Off.

1060 NW Corporate Drive Troutdale, OR 97060

Phone: 503-492-3570 Fax:

Cellular: 503-880-9462

Naameh.A.Nomie@usace.army.mil

Resident EngineerP.O. Box 70 Cascade Locks, OR 97014-0070

Phone: 503-808-4614 Fax: 503-808-4605

Richard Reiner Onsite POC

PO Box 564 The Dalles, OR 97058

Phone: 541-506-7805 Fax:

Cellular: 541-980-4911

Richard.L.Reiner@usace.army.mil

Robert van der Borg Phone: 503-808-4614 Fax: 503-808-4605

Robert.D.Vanderborg@usace.army.mil

Russell Thornton Phone: 509-527-7558 Fax:

Russell.M.Thornton@usace.army.mil

Scott Apple Resident Engineer

P.O. Box 70 Cascade Locks, OR 97014-0070

Phone: 541-374-5457 Fax:

Scott.A.Apple@usace.army.mil

Scott WilcoxP.O. Box 70 Cascade Locks, OR 97014-0070

Phone: 541-374-8250 Fax:

Cellular: 503-709-8777

Scott.W.Wilcox@usace.army.mil

Steven Sipe Phone: 503-808-4957 Fax: 503-808-4605 steven.c.sipe@usace.army.mil

Tierney CampbellPO Box 546 The Dalles, OR 97058

Phone: 503-808-4422 Fax:

Tierney.A.Campbell@usace.army.mil

Travis CromwellP.O. Box 70 Cascade Locks, OR 97014-0070

Phone: 541-374-8250 Fax: 541-374-2245

Cellular: 360-713-7279

Travis.L.Cromwell@usace.army.mil

Page 2 of 7Todd Construction, Inc.

Contract Addresses

The Dalles Dam Elevator Refurb

Title

Fax

Phone

NameAddressRole Section

SpecCompany

GC Todd Construction, Inc. 00190 - General Contractor

PO Box 949 Tualatin, OR 97062

Phone:

Fax:

503-620-7652 503-620-6825

Brent Schafer President

Phone: 503-620-7652 Fax: 503-620-6825

Cellular: 503-789-4588 bschafer@toddconstruction.com

Charlene Sattler Project Assistant

Phone: 503-620-7652 Fax: 503-620-6825 csattler@toddconstruction.com

Claudia Vidal Admin. Assistant

Phone: 503-620-7652 Fax: 503-620-6825 cvidal@toddconstruction.com

Harv Wingerd Gen Superintendent

Phone: 503-620-7652 Fax: 503-620-6825

Cellular: 503-351-2875 hwingerd@toddconstruction.com

Janica Stewart Accounting Manager

Phone: 503-620-7652 Fax: 503-620-6825 jstewart@toddconstruction.com

Jason Crone Superintendent

Phone: 503-620-7652 Fax: 503-620-6825

Cellular: 971-235-2261 jcrone@toddconstruction.com

Kayla Evans-Roders Project Assistant

Phone: 503-620-7652 Fax: 503-620-6825 kevans@toddconstruction.com

Ken Dixon VP/Controller

Phone: 503-620-7652 Fax: 503-620-6825

Cellular: 503-310-7099 kdixon@toddconstruction.com

Larry Kennebeck Project Manager

Phone: 503-620-7652 Fax: 503-620-6825

Cellular: 503-351-4006 lkennebeck@toddconstruction.com

Laura Pfeifer Office Assistant

Phone: 503-620-7652 Fax: 503-620-6825 lpfeifer@toddconstruction.com

Matthew Boydston Equipment Manager

Phone: 503-620-7652 Fax: 503-620-6825

Cellular: 971-404-8815 mboydston@toddconstruction.com

Tim Moore Lead Carpenter

Phone: 503-620-7652 Fax: 503-620-6825 tmoore@toddconstruction.com

Page 3 of 7Todd Construction, Inc.

Contract Addresses

The Dalles Dam Elevator Refurb

Title

Fax

Phone

NameAddressRole Section

SpecCompany

SUB B&B Masonry - 1069 04000 - Masonry

PO Box 758 Brush Prairie, WA 98606

Phone:

Fax:

360-944-9873 360-944-7350

Kevin Storey Primary

Phone: 360-944-9873 Fax: 360-944-7350

Cellular: 360-798-7013

KevinS@brickandblock.net

Sue Sutton Prevailing Wage Coor

Phone: 360-944-9873 Fax: 360-944-7350 ssuttonbnb@hotmail.com

Heather Detchman Billing

Phone: 360-944-9873 Fax: 360-944-7350 mailto:Heather.Detchman@gmail.com

SUB The Dalles Iron Works LLC - 1828 05500 - Miscellaneous Metal

720 E 2ND Street The Dalles, OR 97058

Phone:

Fax:

541-296-3876 541-296-3733

Loyal Quackenbush Primary Contact

Phone: 541-296-3876 Fax: 541-296-3733 loyalq@gmail.com

Linda Quackenbush Billing/PW

Phone: 541-296-3876 Fax: 541-296-3733 loyalq@gmail.com

SUP Bell Hardware of Portland Inc - 1078 08005 - Door, Frame & Hardware Supplier

26300 SW 95th Ave, Ste 102 Wilsonville, OR 97070

Phone:

Fax:

503-570-9610 503-570-9412

Josh Crane Primary Contact

Phone: 503-570-9610 Fax: 503-570-9412 joshc@bellhardware.com

Brooks Riese Jobsite

Phone: 503-570-9610 Fax: 503-570-9412 joshc@bellhardware.com

SUB Stintzi Drywall - 5610 09250 - Gypsum Board

2149 Cascade Ave.

Suite 106-A, #213 Hood River, OR 97031

Phone:

Fax:

541-387-2832

Gerald Stintzi Primary Contact

Phone: 541-387-2832 Fax:

gstintzi111@aol.com

SUP Architectural Specialties Inc - 1051 10210 - Wall Louvers

PO Box 22325 Milwaukie, OR 97269

Phone:

Fax:

503-232-2966 503-232-4028

Jo Meyer RFQ/Billing

Phone: 503-232-2966 Fax: 503-232-4028 sales@archsp.com

Connie Ness Sub/CO

Phone: 503-232-2966 Fax: 503-232-4028 connie@archsp.com

Page 4 of 7Todd Construction, Inc.

Contract Addresses

The Dalles Dam Elevator Refurb

Title

Fax

Phone

NameAddressRole Section

SpecCompany

SUP Soha Sign Co Inc - 5606 10410 - Directories

1601 G Street Vancouver, WA 98663

Phone:

Fax:

360-693-8531 360-750-1075

Mike Stark Primary Contact

Phone: 360-693-8531 Fax: 360-750-1075

Cellular: 360-600-9654 mike@sohasign.com

SUB NCM Contracting Group LP - 1436 13280 - Hazardous Material Remediation

10367 SE Helena St Milwaukie, OR 97222

Phone:

Fax:

503-255-5999 503-254-8180

Bill Wing Jobste - Abatement

Phone: 503-255-5999 Fax: 503-254-8180

Cellular: 503-209-0999 bwing@ncmgroup.com

Ed Woodward District Manager

Phone: 503-255-5999 Fax: 503-254-8180 ewoodward@ncmgroup.com

Eric Lehman RFQ/Sub-Abatement

Phone: 503-255-5999 Fax: 503-254-8180

Cellular: 503-449-4737

ELehman@ncmgroup.com

Jeff Wunderlich Phone: 503-255-5999 Fax: 503-254-8180

Cellular: 206-423-0538

JWunderlich@ncmgroup.com

Josh McGlohn Jobsite

Phone: 503-255-5999 Fax: 503-254-8180

Karmen Fierro

PW

Phone: 503-255-5999 Fax: 503-254-8180

Cellular: 425-952-2947 kfierro@ncmgroup.com

Katrina Braaten Billing

Phone: 503-255-5999 Fax: 503-254-8180

Cellular: 503-808-1987 kbraaten@ncmgroup.com

Lidia Beaumont CO - Abatement

Phone: 503-255-5999 Fax: 503-254-8180

Cellular: 503-808-1989 lbeaumont@ncmgroup.com

Michelle Griffin PW - Abatement

Phone: 425-881-0623 Fax: 503-254-8180 mgriffing@ncmgroup.com

Zac Lloid Jobsite - Demo

Phone: 503-255-5999 Fax: 503-254-8180

Cellular: 503-764-6526

Page 5 of 7Todd Construction, Inc.

Contract Addresses

The Dalles Dam Elevator Refurb

Title

Fax

Phone

NameAddressRole Section

SpecCompany

SUB GB Manchester Corp - 3731 13850 - Fire Alarm Systems

6000 NE 88th St Vancouver, WA 98665

Phone:

Fax:

503-287-1112 360-816-0482

Nathan Butz Sub/CO

Phone: 503-287-1112 Fax: 503-287-1863

Cellular: (360) 772-2244 nathan.b@gbmanchester.com

Tim Tormanen Jobsite

Phone: 503-287-1112 Fax: 360-816-0482 tim.t@gbmanchester.com

Cindy Lindberg Billing

Phone: 503-287-1112 Fax: 360-816-0482 cindy.l@gbmancester.com

SUB ThyssenKrupp Elevator - 1606 14210 - Electric Traction Elevators

14626 NE Airport Way Portland, OR 97230

Phone:

Fax:

503-255-0079 866-720-5824

Eric DeShazer621 S. Royal Lane, Suite 500 Coppell, TX 75019

Phone: 972-471-8421 Fax: 866-523-2365

Cellular: 214-636-1624 eric.deshazer@thyssenkrupp.com

Greg Van Dyke Phone: 503-255-0079 Fax: 866-720-5824

Cellular: 503-449-7431 greg.vandyke@thyssenkrupp.com

Kevin Mason Submittals/RFQ

Phone: 503-255-0079 Fax: 866-720-5824

Cellular: 503-209-3069 kevin.mason@thyssenkrupp.com

Shawn Finlinson Billing

Phone: 503-255-0079 Fax: 866-720-5824

Cellular: 801-481-3707 shawn.finlonson@thyssenkrupp.com

Steve King Phone: 503-255-0079 Fax: 866-720-5824

Cellular: 503-849-7738

Steve Liablin Jobsite

Phone: 503-255-0079 Fax: 866-720-5824

Cellular: 503-209-2728 steve.laiblin@thyssenkrupp.com

Claudia Ringler

CO/PW

Phone: 503-255-0079 Fax: 866-720-5824

Cellular: 503-209-2728 claudia.ringler@thyssenkrupp.com

Page 6 of 7Todd Construction, Inc.

Contract Addresses

The Dalles Dam Elevator Refurb

Title

Fax

Phone

NameAddressRole Section

SpecCompany

SUB Access Electric & Heating Inc - 5594 15700 - Heating, Ventilating, and Air Conditioning Sub

106904 E 297 Pr SE Kennewick, WA 99338

Phone:

Fax:

509-545-8755 509-374-4671

Joellen Haynes Billing/PW

Phone: 509-545-8755 Fax: 509-374-4671

Cellular: 509-851-8036 accesselectric@yahoo.com

Clay Haynes Jobsite/Sub/RFQ

Phone: 509-545-8755 Fax: 509-374-4671

Cellular: 509-250-3830 accessrhino@yahoo.com

SUB Hage Electric & Const Serv Inc - 1933 16000 - Electrical

3701 Klindt Drive The Dalles, OR 97058

Phone:

Fax:

541-296-1962 541-296-2191

Brian Zuercher Phone: 541-296-1962 Fax: 541-296-2191

Garry Hage Sub/CO/RFQ

Phone: 541-296-1962 Fax: 541-296-2191 garryhage@hageelectric.com

James Shaver Phone: 541-296-1962 Fax: 541-296-2191

Jason Hage Jobsite

Phone: 541-296-1962 Fax: 541-296-2191

Cellular: 541-993-9145 jasonhage@hageelectric.com

Joshua Adams Phone: 541-296-1962 Fax: 541-296-2191

Kyle Ruder Phone: 541-296-1962 Fax: 541-296-2191

Michael Hammel Phone: 541-296-1962 Fax: 541-296-2191

Nicole Hage Billing/PW

Phone: 541-296-1962 Fax: 541-296-2191 nicolehage@hageelectric.com

Noe Zaragoza Phone: 541-296-1962 Fax: 541-296-2191

Ryan Johnson Phone: 541-296-1962 Fax: 541-296-2191

Page 7 of 7Todd Construction, Inc.

Warranty FA System

SUBMITTALS FOR GOVERNMENT APPROVAL

The Dalles Lock & Dam Elevator Refurbishment

Contract No. W9127N-12-C-0004 NA

INTERIOR FIRE DETECTION AND ALARM SYSTEM

proposed by G.B. Manchester Corp.

CCB 60178

SUBMITTAL PARAGRAPH DESCRIPTION

28 31 74-23 -- Warranty: 1 year Parts & Labor

GUARANTY & WARRANTY

On premises repair is to be provided during normal working hours (8:00 am - 5:00 p.m.) at no cost to US Army Corps of Engineers on the The Dalles Lock and

Dam East Elevator Replacement - Fire Alarm System for a period of twelve (12) months from the date of completion of installation (11/16/12). Damage by misuse, abuse or accident - i.e. fires, floods, etc. is not covered by this warranty. Qualified personnel, skilled in the repair of electronic equipment shall be dispatched to service or repair the equipment within 24 to 48 hours, excluding weekends and holidays, after receipt of repair request.

G.B. MANCHESTER CORPORATION

6000 NE 88

th Street

Vancouver, WA 98665

(360) 816-0484 fax (360 816-0482

CCB 60178

Authorized by:

NATHaN BUTZ Nathan Butz Project Manager

EAST ELEVATOR - SUBMITTAL SD-10: O&M DATA

SUBMITTALS FOR GOVERNMENT APPROVAL

The Dalles Lock & Dam Elevator Refurbishment

Contract No. W9127N-12-C-0004 NA

INTERIOR FIRE DETECTION AND ALARM SYSTEM

proposed by G.B. Manchester Corp.

CCB 60178

SUBMITTAL PARAGRAPH DESCRIPTION

28 31 74-18 1.8(G)

Data Sheets

Installation Sheets

O&M Instructions

FA Program Reports

FIO

CSattler Text Box

CSattler Typewritten Text

CSattler Typewritten Text

CSattler Typewritten Text

(THIS PAGE LEFT INTENTIONALLY BLANK)

EAST ELEVATOR - OPERATION AND MAINTENANCE INSTRUCTIONS

for

The Dalles Lock & Dam Elevator Refurbishent

Solicitation No. W9127N-12-R-0001

Sec. 28 31 74.10 28 Interior Fire Detection and Alarm System proposed by G.B. Manchester Corp.

CCB 60178

MFG MODEL # DESCRIPTION

EST 3X-SFS1R Fire Alarm Control Panel USER'S GUIDE

EST 4X-LCD FACP Annnunciator USER INTERFACE CONTROLS

EST 3X-SFS1R Fire Alarm Control Panel Operating Instructions

EST SIGA Detectors SIGA Detectors APPLICATION GUIDE

FIO

CSattler Text Box

(THIS PAGE LEFT INTENTIONALLY BLANK)

EST3X User Guide

P/N 3101799-EN • REV 1.0 • ISS 10MAY11

Copyright © 2011 UTC Fire & Security. All rights reserved.

Trademarks and patents

The EST3X name and EST logo are trademarks of UTC Fire & Security.

Other trade names used in this document may be trademarks or registered trademarks of the manufacturers or vendors of the respective products.

Manufacturer Edwards, A Division of UTC Fire & Security Americas Corporation, Inc.

8985 Town Center Parkway, Bradenton, FL 34202, USA

Version This document applies to EST3X control panels with firmware version 1.0.

FCC compliance This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules.

These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.

Contact information For contact information, see www.utcfireandsecurity.com.

EST3X User Guide i

Content

Important information iii Fire alarm system limitations vi Intended audience vii

Chapter 1 Introduction 1

System overview 2 System hardware capabilities 2 Overview of operator controls and indicators 4 System operation 8 Event messages 9 User access levels 10 Using the rotary controller 11 Using the paging microphone 13

Chapter 2 Basic operating instructions 15

Checking for active points 16 Finding detectors that may need servicing 17 Viewing history reports 18 Finding firmware and database version numbers 18 Viewing the alarm count 19 Determining panel TCP/IP settings 19 Determining if your 3-MODCOM is NFPA 72 compliant 20 Silencing the panel buzzer 20 Silencing alarm signals 21 Acknowledging events 22 Resetting the fire alarm system 22 Performing a lamp test 22 Activating alarm signals manually 23 Changing the LCD screen language 23

Chapter 3 Advanced operating instructions 25

Changing detector alarm sensitivity 26 Changing event message routes 26 Disabling and enabling devices 27 Disabling and enabling zone groups 28 Setting the system time and date 29 Using a TCP/IP connection to write to the panel 29 Using a TCP/IP connection to read from the panel 30 Guard patrol routes 32 ii EST3X User Guide

Bypassing the photo element on SIGA2-PHS smoke detectors 33

Testing a carbon monoxide (CO) detector 34

Chapter 4 Preventive maintenance and testing 37

Introduction 38 Service provider information 38 Visual inspection schedule 38 Troubleshooting 41

Appendix A System addressing 43

Address formats 44 Card address 44 Hardware layer device addresses 46 Operator layer device address 47 Remote annunciator device addresses 49

Glossary 57

Index 59

EST3X User Guide iii

Important information

Limitation of liability

To the maximum extent permitted by applicable law, in no event will UTCFS be liable for any lost profits or business opportunities, loss of use, business interruption, loss of data, or any other indirect, special, incidental, or consequential damages under any theory of liability, whether based in contract, tort, negligence, product liability, or otherwise. Because some jurisdictions do not allow the exclusion or limitation of liability for consequential or incidental damages the preceding limitation may not apply to you. In any event the total liability of UTCFS shall not exceed the purchase price of the product. The forgoing limitation will apply to the maximum extent permitted by applicable law, regardless of whether UTCFS has been advised of the possibility of such damages and regardless of whether any remedy fails of its essential purpose.

Installation in accordance with this manual, applicable codes, and the instructions of the authority having jurisdiction is mandatory.

While every precaution has been taken during the preparation of this manual to ensure the accuracy of its contents, UTCFS assumes no responsibility for errors or omissions.

EST3X FCC compliance

This equipment can generate and radiate radio frequency energy. If the equipment is not installed in accordance with this manual, it may cause interference to radio communications. This equipment has been tested and found to comply with the limits for Class A computing devices pursuant to Subpart B of Part 15 of the FCC Rules. These rules are designed to provide reasonable protection against such interference when this equipment is operated in a commercial environment. Operation of this equipment is likely to cause interference, in which case the user, at his own expense, will be required to take whatever measures may be required to correct the interference.

3-MODCOM FCC compliance

Cautions

• To ensure proper operation, this dialer must be installed according to the enclosed installation instructions. To verify that the dialer is operating properly and can successfully report an alarm, it must be tested immediately after iv EST3X User Guide installation, and periodically thereafter, according to the enclosed test instructions.

• In order for the dialer to be able to seize the phone line to report an alarm or other event when other customer equipment (telephone, answering system, computer modem, etc.) connected to the same line is in use, the dialer must be connected to a properly installed RJ-31X jack. The RJ-31X jack must be connected in series with, and ahead of, all other equipment attached to the same phone line. Series installation of an RJ-31X jack is depicted in the wiring diagram. If you have any questions concerning these instructions, you should consult your telephone company or a qualified installer.

Testing

When programming emergency numbers or making test calls to emergency numbers, remain on the line and briefly explain to the dispatcher the reason for the call. Perform programming and testing activities in the off-peak hours, such as early morning or late evenings.

Compliance

• For equipment approved before July 23, 2001: This dialer complies with Part 68 of the FCC rules. A label attached to the dialer contains, among other information, the FCC registration number and ringer equivalence number (REN) for this equipment. If requested, this information must be provided to the telephone company.

For equipment approved after July 23, 2001: This dialer complies with Part 68 of the FCC rules and the requirements adopted by the Administrative Council for Terminal Attachments (ACTA). A label attached to the dialer contains, among other information, a product identifier in the format US:AAAEQ##TXXXX. If requested, this information must be provided to the telephone company.

• The plug and jack used to connect the dialer to the premises wiring and telephone network must comply with the applicable FCC Part 68 rules and requirements adopted by ACTA. The dialer must be connected to a compliant RJ-31X or RJ-38X jack using a compliant cord. If a modular telephone cord is supplied with the dialer, it is designed to meet these requirements. See installation instructions for details.

• A ringer equivalence number (REN) is used to determine how many devices you can connect to a telephone line. If the total REN value for all devices connected on a telephone line exceeds that allowed by the telephone company, the devices may not ring on an incoming call. In most (but not all) areas the total REN value should not exceed 5.0. To be certain of the total REN value allowed on a telephone line, contact the local telephone company.

EST3X User Guide v

For products approved after July 23, 2001, the REN is part of the product identifier in the format US:AAAEQ##TXXXX. The digits ## represent the REN without a decimal point. Example: 03 is an REN of 0.3. For earlier products the REN is listed separately.

• If the dialer is harming the telephone network, the telephone company will notify you in advance that temporary discontinuance of service may be required. If advance notice isn’t practical, the telephone company will notify you as soon as possible. You will also be advised of your right to file a complaint with the FCC, if you believe it is necessary.

• The telephone company may make changes to its facilities, equipment, operations, or procedures that could affect the operation of the dialer. If this happens, the telephone company will provide advance notice in order for you to make necessary modifications to maintain uninterrupted service.

• If you are experiencing problems with the dialer, contact the manufacturer for repair or warranty information. If the dialer is harming the telephone network, the telephone company may request that you disconnect the dialer until the problem is resolved.

• The dialer contains no user serviceable parts. In case of defects, return the dialer for repair.

• You may not connect the dialer to a public coin phone or a party line service provided by the telephone company.

3-MODCOM Industry Canada information

Note: The Industry Canada label identifies certified equipment. This certification means that the equipment meets certain telecommunications network protective, operational, and safety requirements. Industry Canada does not guarantee the equipment will operate to the user’s satisfaction.

Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications company. The equipment must also be installed using an acceptable method of connection. The customer should be aware that compliance with the above conditions may not prevent degradation of service in some situations.

Repairs to certified equipment should be made by an authorized Canadian maintenance facility designated by the supplier. Any repairs or alterations made by the user to this equipment, or equipment malfunctions, may give the telecommunications company cause to request the user disconnect the equipment.

vi EST3X User Guide

Caution: Users should not attempt to make connections themselves, but should contact the appropriate electric inspection authority, or electrician, as appropriate.

Users should ensure for their own protection that the electrical ground connections of the power utility, telephone lines, and internal metallic water pipe system, if present, are connected together. This precaution may be particularly important in rural areas.

Note: The Load Number (LN) assigned to each terminal device denotes the percentage of the total load to be connected to a telephone loop which is used by the device, to prevent overloading. The termination on a loop may consist of any combination of devices subject only to the requirements that the sum of the Load Numbers of all the devices does not exceed 100.

Advisory messages

Advisory messages alert you to conditions or practices that can cause unwanted results. The advisory messages used in this document are shown and described below.

WARNING: Warning messages advise you of hazards that could result in injury or loss of life. They tell you which actions to take or to avoid in order to prevent the injury or loss of life.

Caution: Caution messages advise you of possible equipment damage. They tell you which actions to take or to avoid in order to prevent the damage.

Note: Note messages advise you of the possible loss of time or effort. They describe how to avoid the loss. Notes are also used to point out important information that you should read.

Fire alarm system limitations

The purpose of an automatic fire alarm system is to provide early detection and warning of a developing fire. There are a number of uncontrollable factors that can prevent or severely limit the ability of an automatic fire alarm system to provide adequate protection. As such, an automatic fire alarm system cannot guarantee against loss of life or loss of property.

EST3X User Guide vii

Two main causes of system failures are improper installation and poor maintenance. The best way to minimize these types of system failures is to have only trained fire alarm system professionals design, install, test, and maintain your fire alarm system in accordance with national and local fire codes.

Fire alarm systems will not operate without electrical power. As fires frequently cause power interruption, we suggest that you discuss ways to safeguard the electrical system with your local fire protection specialist.

In the event your EST3X control panel needs servicing, please contact your system service provider as soon as possible. Refer to “Service provider information” on page 38 for their name and contact information.

Intended audience

The intent of this document is to provide the EST3X life safety system owner with control panel operating instructions. You may assume that your site-specific software has been installed and that the final overall system testing has been completed prior to you using this guide. The extent of your use with panel buttons, indicators, and menus is dependant upon your access privileges.

viii EST3X User Guide

EST3X User Guide 1

Chapter 1 Introduction

Summary

This chapter provides information about your EST3X control panel to give you a basic understanding of its operation.

Content

System overview 2 System hardware capabilities 2 Overview of operator controls and indicators 4 System operation 8 Event messages 9 User access levels 9 Using the rotary controller 11 Using the paging microphone 13

Chapter 1: Introduction

2 EST3X User Guide

System overview

The EST3X control panel can operate as a stand-alone panel, as part of a 64-node EST3X life safety network, or as part of a 64-node EST3 life safety network. The EST3X control panel is listed for the following types of service:

• Commercial protected premises fire alarm control unit

• Smoke control system

• Releasing device control unit

• Emergency communication and relocation

The EST3X control panel is also listed for use as a burglary annunciator when connected to an EST3 life safety system that includes security features.

The EST3X user interface includes indicators and operator controls that allow you to respond quickly in emergency situations. The EST3X user interface gives you the ability to view message details and system reports, and to enable and disable devices and groups. With the correct access level passwords, you can activate and restore sensitivity settings and message routing, test system devices, and other tasks.

System hardware capabilities

The EST3X control panel, in its basic configuration, supports up to:

• 250 addressable devices

• Four Class B notification appliance or auxiliary power output circuits

• 30 remote or graphic annunciators for a total of 30 sets of common controls, 3,840 LED indicators, and 1,920 switches

• Two RS-232 ports (one RJ-11 modular jack for panel programming and diagnostics and one terminal block connection for connecting accessory devices)

With the proper hardware options, you can expand the EST3X control panel to support:

• 1,250 additional addressable devices (1,500 total)

• 24 Class B initiating device circuits

• 12 additional Class B notification appliance circuits (16 total)

• Four Class A notification appliance or auxiliary power output circuits

EST3X User Guide 3

• Three reverse polarity outputs

• Three control-display modules for a total of 72 local LED indicators and 36 local switches

• Two dialer outputs

• One Ethernet connection for panel programming and diagnostics

• Live voice and prerecorded audio messaging

• Connection to an EST3X or EST3 life safety network using copper, fiber optics, or both (maximum network size may not exceed 64 nodes)

4 EST3X User Guide

Overview of controls and indicators

Figure 1: 4X-LCD User Interface

1. Alarm LED

2. Disable LED

3. SUP (Supervisory) LED

4. GND Fault LED

5. CPU Fail LED

6. Trouble LED

7. Power LED

8. Panel Silence button and LED

9. Reset button and LED

10. Acknowledge button and LED

11. Alarm Silence button and LED

12. Rotary controller

13. Display

14. Normal display screen (see Figure 2)

15. Off -normal display screen (see Figure 3)

EST3X User Guide 5

Figure 2: Normal screen

1. Time

2. Date

3. Custom banner message

4. Number of times the panel has gone into alarm

Figure 3: Off-normal screen

1. Time

2. Date

3. Number of active points

4. Number of disabled points

5. Selected event message

6. Contents of selected event message queue. In this example, the Alarm message queue.

7. Most recent highest priority event message

8. Monitor queue with the number of active monitor event messages

9. Trouble queue with the number of active trouble event messages

10. Supervisory queue with the number of active supervisory event messages

11. Alarm queue with the number of active alarm event messages

6 EST3X User Guide

Figure 4: 3X-PMI Paging Microphone Interface

1. Push-to-talk button

2. Paging Microphone

3. Paging volume indicator (indicates the sound level of the person speaking into the microphone)

4. Ready to page LED

5. All Call button and LED

6. Page to Evac button and LED

7. All Call Minus button and LED

8. Page to Alert button and LED

EST3X User Guide 7

Figure 5: RLCD-C and RLCD Remote Annunciator

Controls Enabled

Ack/Silence

Reset

Signal Silence

Drill

Lamp Test

Power Fire Alarm Supervisory Ground Fault Trouble

3 4 5 6 7 8 9

15 14 13 12 11RLCD-C

Controls Enabled

Ack/Silence

Lamp Test

Power Fire Alarm Supervisory Ground Fault Trouble

3 4 5 9

15 14 13 12 11RLCD

1. Display

2. Up button

3. Down button

4. Enter button

5. Lamp Test button and LED

6. Drill button and LED

7. Signal Silence button and LED

8. Reset button and LED

9. Ack/Silence button and LED

10. Controls Enabled LED

11. Trouble LED

12. Ground Fault LED

13. Supervisory LED

14. Fire Alarm LED

15. Power LED

8 EST3X User Guide

Figure 6: RLED-C Remote Annunciator

Controls Enabled

Ack/Silence

Reset

Signal Silence

Drill

Lamp Test

Power Fire Alarm Supervisory Ground Fault Trouble

1 2 3 4

11 10 9 8 7

1. Power LED

2. Fire Alarm LED

3. Supervisory LED

4. Ground Fault LED

5. Trouble LED

6. Controls Enabled LED

7. Ack/Silence button and LED

8. Reset button and LED

9. Signal Silence button and LED

10. Drill button and LED

11. Lamp Test button and LED

12. Programmable LEDs

System operation

The basic function of the EST3X control panel is to monitor status changes in the life safety system and to activate outputs according to the site-specific software.

Status change signals, also called events, are classified as follows:

• Alarm (highest priority): Events that signal fire alarms or other life-threatening emergencies

• Supervisory: Events that signal off-normal conditions with sprinkler and extinguishing systems and other equipment related to property safety

• Trouble: Events that signal faults within the system

• Monitor (lowest priority): Events that signal the operation of ancillary equipment

EST3X User Guide 9

During normal operation (no events), the EST3X control panel displays the Normal screen (see Figure 2). When the automatic fire detection system signals a status change, the EST3X control panel:

• Posts the event message for the point that activated the event into the appropriate event message queue and displays the off-normal screen (see Figure 3)

• Turns on the corresponding system status LED

• Turns on the panel buzzer to the pattern for the highest priority active event

• Displays the most recent, highest priority event message (see Figure 3)

• Activates common relays and programmed outputs

Event messages

The EST3X control panel uses event messages to identify points that signal a status change. The first line of the event message displays the event number and the event name. The second line displays the message text. The message text is either the address of the point that activated the event or, if programmed, a location description.

Event messages are stored in queues. There is one queue for each type of event message (see Figure 3).

The EST3X control panel automatically displays the content of the highest priority event message queue, except when you are viewing event messages in another queue. If you are viewing event messages in one queue when a higher priority event message is placed in another queue, the EST3X control panel continues to display the content of the current queue until the user timeout period expires or until you select the other queue.

To view an event message in the current queue:

1. Turn the rotary controller to select the event message. The selected event message appears in the highlighted area at the top of the display.

To view an event message in another queue:

1. Click the rotary controller to display the Queue Menu.

2. Click the event message queue from the list of options.

3. Turn the rotary controller to select the event message.

10 EST3X User Guide

To get details about an event message:

1. Select the event message.

2. Click the rotary controller to display the Queue Menu.

3. Click Details.

User access levels

The EST3X control panel uses access levels to prevent unauthorized users from operating certain controls and menu commands. Access levels 1 to 4 require a password. Access level 0 does not. Table 1 lists the operator controls and menu commands available for each access level.

Once you have entered an access level password you do not have to enter it again for any operator control or menu command with the same access level or lower unless the user timeout period expires. After that, you are required to enter the access level password again. The user timeout period is typically set for 5 minutes.

See your project documentation for the access level passwords programmed for your system.

Table 1: User access level privileges

User access level Privileges

Level 0 (No password required)

• Acknowledge function (button)

• Alarm silence function (button) [1]

• Panel silence function (button) [1]

• Reset function (button) [1]

• Event details

• Statuses

• Reports

• Drill function (activate/restore)

• Output selection

• Display/printer selection

• Printer selection

• Toggle language

Level 1 All level 0 privileges, plus:

• Guard patrol routes (activate/restore)

EST3X User Guide 11

User access level Privileges

Level 2 All level 0 and level 1 privileges, plus:

• Devices (enable/disable)

• Zone groups (enable/disable)

• Remote read lock (activate/restore)

• Remote write unlock (activate/restore)

• Sensor bypass (activate/restore)

• Gas accel response (activate/restore)

• Alternate sensitivity (activate)

• Alternate message route (activate)

• Primary sensitivity (restore)

• Primary message route (restore)

• Change time (program)

• Change date (program)

• Security devices (bypass/remove bypass)

• Security partitions (arm/disarm)

• Change password for level 1 (program)

[1] May be programmed to require an access level password. See your project documentation for details.

Using the rotary controller

The EST3X rotary controller performs the functions of a computer keyboard and the Enter key. Turning the rotary controller allows you to scroll through event messages on the LCD screen, menus and lists, and numbers for panel, card, and device addressing. Pressing (clicking) the rotary controller allows you to access event message details, menus, and selection screens and to enter address numbers and backspaces.

Selecting menus and commands

Press the rotary controller to access the first menu, from which you will access other menus. For all menus, turn the dial to scroll to a desired selection. Press the dial to click the selection.

12 EST3X User Guide

Returning to the event message screen or previous screen

Pressing the rotary controller while in certain screens returns you to the event message screen or to the previous screen.

Note: Pressing the Acknowledge button also returns you to the event message screen or to the previous screen.

Returning to the previous screen from an address field

In an address field, you can return to the previous screen from the first number in the field by turning the rotary controller to the “<” character and then pressing the dial.

For example, in the address field below you are positioned at the first number. If you click the “<” character you will return to the previous screen.

ENTER DEVICE

<PCCDDDD

Entering a panel, card, or device address

To enter a panel, card, or device address, turn the rotary controller clockwise or counterclockwise to scroll to the desired number (0-9), and then press it to enter the number. Pressing the rotary controller automatically moves the cursor to the next number position.

Note: You do not have to enter a panel number except when you want to enter the panel, card, or device address for a remote EST3X control panel. See your project documentation for a list of panel numbers.

Backspacing

In an address field, you can backspace to a previous number by turning the rotary controller to scroll to the “<” character and then pressing the dial. You can then enter the number.

In the address example below, you will be able to change the number 3.

ENTER DEVICE

0103<DDDD

EST3X User Guide 13

Using the paging microphone

The 3X-PMI Paging Microphone Interface (see Figure 4) gives emergency responders the ability to broadcast instructions to occupants throughout the protected premises. There are four types of page you can make:

• All Call: Broadcasts live voice messages throughout the facility

• Page to Evac: Broadcasts live voice messages only to areas receiving evacuation signals

• Page to Alert: Broadcasts live voice messages only to areas receiving alert signals

• All Call Minus: Broadcasts live voice messages only to areas that are not receiving evacuation signals or alert signals

To make an announcement using the paging microphone:

1. Select the area to receive the page by pressing the appropriate page function button. The button’s LED indicates when the system is ready for you to speak.

2. Press the PTT button on the microphone. The Ready to Page LED flashes while the preannouncement tone is sounding.

3. Begin speaking once the Ready to Page LED is on steady. Adjust your voice level so that the Paging Volume indicator only flickers occasionally in the middle. Avoid speaking so loud that the Paging Volume indicator lights all the way to the right.

4. When you are finished speaking, release the PTT button, and then press the page function button again to cancel the page and return the system to its previous condition.

Note: The system automatically cancels the page and returns to its previous condition after a short delay if you do not cancel the page manually.

14 EST3X User Guide

EST3X User Guide 15

Chapter 2 Basic operating instructions

Summary

This chapter provides instructions for operating the basic features of your EST3X life safety system. Basic features are those that anyone can operate. Typically, basic features do not require passwords.

Content

Checking for active points 16 Finding detectors that may need servicing 17 Viewing an event history report 18 Finding firmware and database version numbers 18 Viewing the alarm history 19 Determining the panel TCP/IP settings 19 Determining if your 3-MODCOM is NFPA 72 compliant 20 Silencing the panel buzzer 20 Silencing alarm signals 21 Acknowledging events 22 Resetting the fire alarm system 22 Performing a lamp test 22 Activating alarm signals manually 23 Changing the display screen language 23

Chapter 2: Basic operating instructions

16 EST3X User Guide

Checking for active points

The EST3X control panel provides the following status reports to help you find out if any points in the system are in an active or other off-normal state:

• All Active Points: Lists all points that are in an active or other off-normal state (trouble, disable, etc.)

• Alarm: Lists all alarm points that are in the active state

• Supervisory: Lists all supervisory points that are in the active state

• Trouble: Lists all points that are in the trouble state

• Monitor: Lists all monitor points that are in the active state

• Test: Lists all points in an active service group that are in the active or trouble state

• Disabled Points: Lists all points that are in the disabled state

• Outputs: Lists all output points that are in the active state (audibles, visibles, panel LEDs)

To check for active points:

1. Access the Main menu, and then click Status.

2. Click one of the reports described above.

3. Enter the panel address (PP).

4. Click Display and scroll through the report.

— or —

Click Print Locally.

5. When finished, click the rotary controller or press the Acknowledge button to exit the report.

EST3X User Guide 17

Finding detectors that may need servicing

The EST3X control panel provides the following maintenance reports to help you find out if any addressable smoke detectors need servicing:

• Dirty Devices > 80%: Lists all addressable smoke detectors that have a %Dirty value of greater than 80%. Smoke detectors that are more than 80% dirty should be cleaned or replaced as soon as possible.

Note: The %Dirty value is an indication of a smoke detector’s ability to compensate for dust and dirt buildup inside the chamber. Smoke detectors with higher %Dirty values are less able to compensate.

• Dirty Devices > 20%: Lists all addressable smoke detectors that have a %Dirty value greater than 20%. A smoke detector that is more than 20% dirty should be noted for possible cleaning or replacing.

• Single Device: Lists the %Dirty value for a single smoke detector. The report also includes the smoke detector’s model type, primary and alternate alarm sensitivity values, and, if programmed, a location description. To view this report you must know the device address of the smoke detector.

• Devices on a Card: Lists the %Dirty value for all of the smoke detectors on a signaling line circuit. The report also includes each smoke detector’s model type, primary and alternate alarm sensitivity values, and, if programmed, a location description. To view this report you must know the panel number, card number, and loop number of the signaling line circuit.

To find detectors that may need servicing:

1. Access the Main Menu, click Reports, and then click Device Maintenance.

2. Click one of the reports described above.

3. Enter the device address (PPCCDDDD), or the loop address (PPCCL).

4. Click Display and scroll through the report.

— or —

Click Print Locally.

5. When finished, click the rotary controller or press the Acknowledge button to exit the report.

18 EST3X User Guide

Viewing history reports

The EST3X control panel provides the following history reports for determining when the last 1,100 events and operator commands were activated or restored:

• History with Text: Provides a history of events and operator commands logged by the panel. For each point that activated or restored, the detail includes the point’s message text.

• History without Text: Provides a history of events and operator commands logged by the system. For each point that activated or restored, the detail includes the point’s device address.

To view a history report:

1. Access the Main Menu, click Reports, and then click History.

2. Click one of the reports described above.

3. Enter the panel address (PP).

4. Click Display and scroll through the report.

— or —

Click Print Locally.

5. When finished, click the rotary controller or press the Acknowledge button to exit the report.

Finding firmware and database version numbers

By viewing a Revisions report, you can find the version numbers for the following:

• The CPU firmware

• The project database and the SDU used to compile and download the project database

• The audio database, if equipped with a paging microphone

• The application code (firmware), bootloader code, and database for each card installed in the panel

To view the Revisions report:

1. Access the Main Menu, click Reports, and then click Revisions.

2. Enter the panel address (PP).

EST3X User Guide 19

3. Click Display and scroll through the report.

— or —

Click Print Locally.

4. When finished, click the rotary controller or press the Acknowledge button to exit the report.

Viewing the alarm count

The EST3X control panel records how many times it went into the alarm condition. During normal operation, the alarm count is displayed on the LCD.

When the EST3X user interface displays the off-normal screen, you must run a Revisions report to see the alarm count.

To view the alarm count:

1. Access the Main Menu, click Reports, and then click Revisions.

2. Enter the panel address (PP).

3. Click Display and scroll through the report. The alarm count is on the second line of the report.

— or —

Click Print Locally.

4. When finished, click the rotary controller or press the Acknowledge button to exit the report.

Determining panel TCP/IP settings

If your panel is equipped with an Ethernet (TCP/IP) connection, you may be asked to provide the IP address, subnet mask, and gateway settings.

To determine the panel TCP/IP settings:

1. Access the Main Menu, click Reports, and then click Revisions.

2. Enter the panel address (PP).

3. Click Display and scroll through the report. The settings are at the bottom of the report.

— or —

Click Print Locally.

20 EST3X User Guide

4. When finished, click the rotary controller or press the Acknowledge button to exit the report.

Determining if your 3-MODCOM is NFPA 72 compliant

A MODCOM compliance report tells you if the 3-MODCOM installed in the panel meets NFPA 72 configuration requirements. The report does not indicate why the 3-MODCOM may be noncompliant.

To view the MODCOM Compliance report:

1. Access the Main Menu, click Reports, and then click Modcom Compliance.

2. Enter the panel address (PP).

3. Click Display and scroll through the report.

— or —

Click Print Locally.

4. When finished, click the rotary controller or press the Acknowledge button to exit the report.

Silencing the panel buzzer

The EST3X control panel sounds the panel buzzer when an event message is posted into one of the event message queues. Pressing the Panel Silence button or acknowledging the event message silences the buzzer. The panel buzzer automatically re-sounds when a new event message is posted or when the panel trouble re-sound timer expires (typically after 24 hours).

Notes

• The panel buzzer may be configured to sound periodically to remind you that the panel has been silenced.

• For nonlatching events, the panel buzzer automatically silences when the event is restored.

• Pressing the Panel Silence button also silences the buzzer on remote annunciators, provided that the remote annunciators are communicating.

EST3X User Guide 21

To silence the panel buzzer:

1. Press the Panel Silence button or acknowledge the event message.

2. If prompted, enter the access level password.

Silencing alarm signals

WARNING: Death or serious injury. The protected premises may be occupied.

Do not silence alarm signals or reset the control panel unless you are authorized to do so and only after all occupants have been evacuated.

Pressing the Alarm Silence button silences all audible alarm signals and, if configured, all visible alarm signals. Pressing the Alarm Silence button does not silence alarm signals under the following conditions:

• When a waterflow alarm switch is active and the system is configured to prevent silencing alarm signals activated by a waterflow alarm switch

• When the system is configured to delay the silencing of alarm signals, in which case the Alarm Silence button may be inoperable for up to three minutes following an alarm event

Silenced alarm signals automatically turn back on when:

• The Alarm Silence button is pressed a second time

• Another alarm input activates

• Another alarm input in the same zone activates, unless the system is configured to prevent it

To silence alarm signals:

1. Press the Alarm Silence button.

2. If prompted, enter the access level password.

Acknowledging events

Acknowledging an event confirms that you have seen the event message. When you acknowledge an event, the EST3X control panel places a check mark and the word “Acknowledged” next to the event. On proprietary systems, you cannot silence the panel until all events have been acknowledged.

22 EST3X User Guide

To acknowledge an event:

1. Press the Acknowledge button.

Resetting the fire alarm system

WARNING: Death or serious injury. The protected premises may be occupied.

Do not reset the fire alarm system until the proper authorities have determined that the threat of fire is no longer present.

Pressing the Reset button restores the fire alarm system to its normal state — provided that all latched inputs have been restored. If alarm signal initiating devices have not been restored, active alarm signals remain active and silenced alarm signals remain silenced.

Notes

• System programming may render the Reset button inoperable for up to three minutes following an alarm event.

• Resetting the system does not enable disabled points or restore outputs activated by a switch.

To reset the fire alarm system:

1. Press the Reset button.

2. If prompted, enter the access level password.

Performing a lamp test

Use the Lamp Test command on the Test Menu to verify the operation of the LCD and LED indicators. The lamp test command temporarily turns on the panel buzzer, all LED indicators, and every pixel on the LCD.