AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print)
30-105-04 EXCEPTION TO SF 30
APPROVED BY OIRM 11-84
STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA
FAR (48 CFR) 53.243
The Solicitation for Building 23640 HVAC Renovation White Sands Missile Range, New Mexico is amended as follows.
See SF30 Continuation Sheet(s)
NOTE: Proposal Receipt date is 08 August 2019; at 10:00am.,CST, as previously announced.
1. CONTRACT ID CODE PAGE OF PAGES
J 1 2
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
16C. DATE SIGNED
BY
16B. UNITED STATES OF AMERICA 15C. DATE SIGNED 15B. CONTRACTOR/OFFEROR
(Signature of Contracting Officer) (Signature of person authorized to sign)
8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X 9A. AMENDMENT OF SOLICITATION NO.
W9126G19B0006
X 9B. DATED (SEE ITEM 11)
10 July 2019
10B. DATED (SEE ITEM 13)
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer is extended, X is not extended.
Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:
(a) By completing Items 8 and 15, and returning copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE
CONTRACT ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
10A. MOD. OF CONTRACT/ORDER NO.
2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)
6. ISSUED BY
3. EFFECTIVE DATE
16-July-2019
CODE
US ARMY ENGINEER DISTRICT, FORT WORTH
ATTN: CESWF-CT
819 TAYLOR ST, ROOM 2A19
P.O. BOX 17300
FORT WORTH TX 76102-0300
W9126G 7. ADMINISTERED BY (If other than item 6)
4. REQUISITION/PURCHASE REQ. NO.
CODE
See Item 6
FACILITY CODE CODE
EMAIL: TEL:
W9126G19B0006
SECTION SF 30 BLOCK 14 CONTINUATION PAGE
SUMMARY OF CHANGES
CHANGES TO SOLICITATION W9126G19B0006
CHANGES TO DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS
11. Replacement Sections: Replace the following section with the accompanying new section of the same number and title bearing the notation W9126G19B0006 0001
00 11 00.01 - SOLICITATION, OFFER AND AWARD, SF-1442
00 21 00 - INSTRUCTIONS, CONDITIONS, AND NOTICES TO OFFERORS
00 21 30 - SITE VISITS
CHANGES TO THE DRAWINGS
14. New Drawings.- The new drawings listed below which are included in this amendment, bearing the notation W9126G19B0006 0001 shall be added to and become a part of the contract documents:
G0-0-01 COVER SHEET
G0-1-01 GENERAL PROJECT INFO
A1-0-01 FIRST FLOOR PLAN - ARCH DEMO
A1-0-02 REFLECTED CEILING PLAN - ARCH DEMO
A1-1-01 FIRST FLOOR PLAN
A1-1-02 REFLECTED CEILING PLAN
M0-1-01 MECHANICAL LEGEND, SYMBOLS AND ABBREVIATIONS
M2-0-01 FIRST FLOOR PLAN - HVAC DEMO
M2-1-01 FIRST FLOOR PLAN - HVAC DUCTWORK
M2-2-01 FIRST FLOOR PLAN - HVAC PIPING
M5-1-01 MECHANICAL SYSTEM DIAGRAMS
M6-1-01 MECHANICAL DETAILS
M7-1-01 MECHANICAL SCHEDULES
M7-1-02 MECHANICAL SCHEDULES
M8-1-01 MECHANICAL CONTROLS
M8-1-02 MECHANICAL CONTROLS
M8-1-03 MECHANICAL CONTROLS
M8-1-04 MECHANICAL CONTROLS
M9-1-01 MECHANICAL PIPING ISOMETRICS
E0-1-01 ELECTRICAL LEGEND, SYMBOLS AND ABBREVIATIONS
E2-0-01 FIRST FLOOR PLAN - POWER DEMOLITION
E2-1-01 FIRST FLOOR PLAN - POWER
E4-1-01 ELECTRICAL POWER PARTIAL ONE-LINES
E4-1-02 ELECTRICAL POWER SCHEDULES
End of Summary of Changes
Project Title: HVAC Renovation of Bldg B23640.
Location: White Sands Missile Range, New Mexico.
This is a Small Business Design Bid Build construction Invitation for Bid.
Magnitude of Construction is betw een $1,000,000 and $5,000,000.
NOTE: Bid Bond is required IAW FAR 52.228-1. Additionally, the w inning contractor w ill be required to provide Insurance and Perfomance & Payment Bonds IAW FAR 52.228-5 & 52.228-15, respectively.
X
AMANDA N LANE (817) 886-1077
NOTE: In sealed bid solicitations "offer" and "offeror" mean "bid" and "bidder".
10. THE GOVERNMENT REQUIRES PERFORMANCE OF THE WORK DESCRIBED IN THESE DOCUMENTS
NEGOTIATED
16-Jul-2019
(RFP)
(IFB)
CALL:
B. TELEPHONE NO. (Include area code) (NO COLLECT CALLS)
See Item 7
2. TYPE OF SOLICITATION
SEALED BID
3. DATE ISSUED
9. FOR INFORMATION A. NAME
SOLICITATION
NSN 7540-01-155-3212 1442-101 STANDARD FORM 1442 (REV. 4-85)
Prescribed by GSA
FAR (48 CFR) 53.236-1(e)
11. The Contractor shall begin performance w ithin _______1 calendar days and complete it w ithin ________365 calendar days after receiving aw ard, X notice to proceed. This performance period is X mandatory, negotiable. (See _________________________01 00 00.00 44
12 A. THE CONTRACTOR MUST FURNISH ANY REQUIRED PERFORMANCE AND PAYMENT BONDS?
(If "YES," indicate within how many calendar days after award in Item 12B.)
X YES NO
13. ADDITIONAL SOLICITATION REQUIREMENTS:
A. Sealed offers in original and __________1 copies to perform the w ork required are due at the place specif ied in Item 8 by ___________ local time ______________08 Aug 2019 (date). If this is a sealed bid solicitation, offers must be publicly opened at that time.
shall be marked to show the offeror's name and address, the solicitation number, and the date and time of fers are due.
B. An offer guarantee X is, is not required.
C. All offers are subject to the (1) w ork requirements, and (2) other provisions and clauses incorporated in the solicitation in full text or by reference.
D. Offers providing less than _______120 calendar days for Government acceptance after the date offers are due w ill not be considered and w ill be rejected.
SOLICITATION, OFFER,
AND AWARD
(Construction, Alteration, or Repair)
1. SOLICITATION NO.
IMPORTANT - The "offer" section on the reverse must be fully completed by offeror.
4. CONTRACT NO.
7. ISSUED BY CODE
US ARMY ENGINEER DISTRICT, FORT WORTH
ATTN: CESWF-CT
819 TAYLOR ST, ROOM 2A17
FORT WORTH TX 76102-0300
W9126G
PAGE OF PAGES
1 OF
CODE
(Title, identifying no., date):
12B. CALENDAR DAYS
10:00 AM (hour)
Sealed envelopes containing offers
5. REQUISITION/PURCHASE REQUEST NO. 6. PROJECT NO.
8. ADDRESS OFFER TO (If Other Than Item 7)
817-886-6403FAX:TEL: 817-886-1043 TEL: FAX:
W9126G19B0006 45
<am#0001> Block 13A Date changed from 13Aug2019 to 08Aug2019 </am#0001>
W9126G19B0006 0001
20B. SIGNATURE
(REV. 4-85)STANDARD FORM 1442 BACK
TO SIGN
NSN 7540-01-155-3212
SOLICITATION, OFFER, AND AWARD (Continued) (Construction, Alteration, or Repair)
CODE FACILITY CODE
17. The offeror agrees to perform the w ork required at the prices specif ied below in strict accordance w ith the terms of this solicitation, if this offer is accepted by the Government in w riting w ithin ________ calendar days after the date offers are due.
the minimum requirements stated in Item 13D. Failure to insert any number means the offeror accepts the minimum in Item 13D.)
AMOUNTS SEE SCHEDULE OF PRICES
18. The offeror agrees to furnish any required performance and payment bonds.
19. ACKNOWLEDGMENT OF AMENDMENTS
(The offeror acknowledges receipt of amendments to the solicitation -- give number and date of each)
AMENDMENT NO.
DATE
20A. NAME AND TITLE OF PERSON AUTHORIZED TO SIGN
OFFER (Type or print)
AWARD (To be completed by Government)
21. ITEMS ACCEPTED:
22. AMOUNT 23. ACCOUNTING AND APPROPRIATION DATA
24. SUBMIT INVOICES TO ADDRESS SHOWN IN ITEM
(4 copies unless otherwise specified)
CODE
(Insert any number equal to or greater than
20C. OFFER DATE
25. OTHER THAN FULL AND OPEN COMPETITION PURSUANT TO
10 U.S.C. 2304(c) 41 U.S.C. 253(c)
CODE27. PAYMENT WILL BE MADE BY:26. ADMINISTERED BY
(Include ZIP Code)14. NAME AND ADDRESS OF OFFEROR 15. TELEPHONE NO. (Include area code)
See Item 14
(Include only if different than Item 14)16. REMITTANCE ADDRESS
30B. SIGNATURE
29. AWARD (Contractor is not required to sign this document.)
document and return _______ copies to issuing office.) Contractor agrees Your of f er on this solicitation, is hereby accepted as to the items listed. This award con-to f urnish and deliv er all items or perf orm all work, requisitions identif ied summates the contract, which consists of (a) the Gov ernment solicitation and on this f orm and any continuation sheets f or the consideration stated in this y our of f er, and (b) this contract award. No f urther contractual document is contract. The rights and obligations of the parties to this contract shall be necessary .
gov erned by (a) this contract award, (b) the solicitation, and (c) the clauses, representations, certif ications, and specif ications or incorporated by ref er-ence in or attached to this contract.
30A. NAME AND TITLE OF CONTRACTOR OR PERSON AUTHORIZED 31A. NAME OF CONTRACTING OFFICER (Type or print)
30C. DATE
(Type or print)
TEL: EMAIL:
31B. UNITED STATES OF AMERICA 31C. AWARD DATE
BY
CONTRACTING OFFICER WILL COMPLETE ITEM 28 OR 29 AS APPLICABLE
(Contractor is required to sign this28. NEGOTIATED AGREEMENT
(M ust be fully completed by offeror)OFFER
Section 00 21 00 - Instructions, Conditions and Notices to Offerors
SEALED BIDDING INSTRUCTIONS
SEALED BIDDING
INSTRUCTIONS
1. INQUIRIES
OFFEROR'S QUESTIONS AND COMMENTS
All questions and/or comments are to be submitted via ProjNet.
Bidder Inquiry in ProjNet at http://www.projnet.org/projnet
To submit and review bid inquiry items, bidders will need to be a current registered user or self-register into system. To self-register go to web page, click BID tab select Bidder Inquiry, select agency USACE, enter Key for this solicitation listed below, and your e-mail address, click login.
Fill in all required information and click create user. Verify that information on next screen is correct and click continue.
From this page you may view all bidder inquiries or add inquiry.
Bidders will receive an acknowledgement of their question via email, followed by an answer to their question after it has been processed.
The Solicitation Number is: W9126G19B0006 The Bidder Inquiry Key is: 6Q2YAY-2Y2C6P
Last day to submit ProjNet questions is 5 calendar days prior to bid closure date in order to ensure adequate time is allotted to form an appropriate response and amend the solicitation, if necessary.
Offerors are requested to review the specification in its entirety, review the Bidder Inquiry System for answers to questions prior to submission of a new inquiry.
The call center operates weekdays from 8AM to 5PM U.S. Central Standard Time Zone (Chicago). The telephone number for the Call Center is 800-428-HELP.
2. INSTRUCTIONS TO OFFERORS
SPECIAL INSTRUCTIONS PERTAINING TO ELECTRONIC BIDS SUBMISSION (FAR
14.302 & 14.304)
a. All bids and a copy of the SF24 Bid Bond MUST be received electronically via the FEDBIZOPPS (FBO.GOV) “Electronic Response” feature no later than <am#001> 22 July 2019 08 August 2019 </am#001> at 10:00 AM (CDT). No bids, or amendments to bids, in Original will be accepted.
b. Electronically submitted offers must include the completed SF 1442 (in accordance with FAR 52.214-18), Acknowledgment of all amendments, completed CLIN schedule, and original Bid Bond.
c. Offers received will be publicly opened at the following location:
US Army Engineer District, Fort Worth 819 Taylor St, Room TBD Fort Worth, TX 76102
02:00 PM (CDT)
d. Teleconference Dial-in Information for the public 1-888-675-2535 Access Code 2998176# Security code: 1234 on <am#001> 22 July 2019 08 August 2019 </am#0001> at 02:00 PM CDT.
e. Please note, oral explanations or instructions are not binding. Any information given to an Offeror which impacts the solicitation and/or offer will be given in the form of a written amendment to the solicitation.
f. SENDING FILES. In an effort to reduce paperwork and reduce cost, all proposals shall be submitted electronically. All submissions should be in Adobe PDF format. The Price Proposal and Technical Proposal shall be submitted as “separate” single files. Offerors may use compressions utility software such as WinZip or PKZip to reduce file size and facilitate transmission.
Title the file(s) in the following format:
W9126G19B0006_COMPANY NAME_DESCRIPTION
ELECTRONIC PROPOSAL SUBMISSION IS REQUIRED THROUGH THE FEDBIZOPPS
(FBO.GOV) “ELECTRONIC RESPONSE” FEATURE. The FBO vendor user guide has information & instructions on how to utilize this feature. The FBO vendor user guide is accessible via the following web URL:
https://www.fbo.gov/downloads/FBO_Vendor_Guide.pdf.
File Size Limitations. Offerors are advised to follow the FBO instructions for uploading files larger than 10MB (java upload). FBO has not posted official file size limitations for its electronic response module, however it has been observed that uploads to FBO tend to be problematic when the files are sized 100MB or greater. If needed, Offerors are advised to break the files down into smaller sections in order to upload it to the system. In such cases, please divide the sections as logically as possible and be sure to clearly name the files as specified above.
Upload Completion & Deadline. Interested parties shall submit responses no later than the date specified on solicitation document. The time & date of proposal receipt will be the upload completion / delivery time & date recorded within FBO. Do not assume that electronic submission will occur instantaneously. Large files (e.g. 10MB or more) will take some time to upload. Offerors should time their upload effort with prudence by not waiting until the last few
W9126G19B0006 0001 m2pmjjf9 Cross-Out m2pmjjf9 Cross-Out minutes—this will allow for unexpected delays in the transmittal process and troubleshooting.
Proposal submission difficulties should be coordinated with the Federal Service Desk at https://fsd.gov and/or +1-866-606-8220 (Mon-Fri 8am-8pm Eastern Time UTC -5:00). Experience shows that if an upload doesn’t complete until after the deadline, the FBO system WILL NOT COMPLETE. The FBO system will automatically shut off the “Electronic Submission” feature at the specified deadline--once that occurs, the feature will disappear from the announcement.
Offerors are encouraged to keep a copy of the upload confirmation for their record. Proposals received after the date and time will be handled in accordance with FAR 15.208-Submission, Modification, Revision and Withdrawal of Proposals.
g. Original copies of the Bid Bond shall be submitted to the following point of contact two (2) calendar days after the bid due date.
US Army Engineer District, Fort Worth ATTN: Amanda Lane 819 Taylor St, Room 2A17 Fort Worth, TX 76102-0300
h. OFFERS BY TELEGRAPH. Offers received by telegraph, modifications thereto, or cancellations of offers will NOT BE ACCEPTED.
i. FACSIMILE OFFERS. Facsimile offers, modifications thereto, or cancellations of offers will
NOT BE ACCEPTED.
j. EMAIL. Modifications and cancellations of offers WILL NOT be accepted. Only the original electronically submitted bid will be accepted by the Government.
k. RESPONSIBILITY. Award will be made to the lowest, responsible bidder whose bid, conforming to the invitation for bids, will be the most advantageous to the Government. To be determined responsible, the apparent low bidder shall:
(1) Have adequate financial resources to perform the contract, or the ability to obtain them. The contractor will be required to provide the Name of the Financial Institution, POC, and phone number.
(2) Have a satisfactory performance record. The contractor shall have no performance annotated with an individual rating of less than SATISFACTORYon any Final Evaluation within the last six (6) years from the bid opening date.
(3) Have a satisfactory record of integrity and business ethics. Awardee will be required to provide at least three (3) references for like work, to include Business Name, Point of Contact, and telephone number.
(4) Have the necessary organization, experience, accounting and operational controls, and technical skills, or the ability to obtain them (including, as appropriate, such elements as production control procedures, property control systems, quality assurance measures, and safety programs applicable to materials to be produced or services to be performed by the prospective contractor and subcontractors). Per FAR 9.104-3, acceptable evidence normally consists of a commitment or explicit arrangement that will be in existence at the time of the contract to acquire the needed facilities, equipment, other resources or personnel.
(5) Have the necessary production, construction, and technical equipment and facilities, or the ability to obtain them; and
(6) Be otherwise qualified and eligible to receive an award under applicable laws and regulations
3. NOTIFICATION OF UNSUCCESSFUL BIDDERS. All contract award information for this solicitation will be published electronically on FedBizOpps (FBO) at www.fbo.gov/ Solicitation Number W9126G19B0006. Written unsuccessful bidder letters will not be issued.
4. PREPROPOSAL CONFERENCE / SITE VISIT
SITE VISIT. See FAR clause 52.236-27 SITE VISIT (CONSTRUCTION) (FEB 1995) –
ALTERNATE I (FEB 1995)
IMPORTANT NOTES. (1) Remarks and explanations addressed during the conference shall not qualify or alter the terms and conditions of the solicitation. (2) The terms and conditions of the solicitation remain unchanged unless the solicitation is formally amended in writing.
CLAUSES INCORPORATED BY REFERENCE
52.204-7 System for Award Management OCT 2018 52.204-22 Alternative Line Item Proposal JAN 2017 52.214-3 Amendments To Invitations For Bids DEC 2016 52.214-4 False Statements In Bids APR 1984 52.214-5 Submission Of Bids DEC 2016 52.214-6 Explanation To Prospective Bidders APR 1984 52.214-7 Late Submissions, Modifications, and Withdrawals of Bids NOV 1999 52.214-18 Preparation of Bids-Construction APR 1984 52.214-19 Contract Award-Sealed Bidding-Construction AUG 1996 52.214-34 Submission Of Offers In The English Language APR 1991 52.214-35 Submission Of Offers In U.S. Currency APR 1991 52.217-5 Evaluation Of Options JUL 1990 52.225-10 Notice of Buy American Requirement--Construction
Materials
MAY 2014
52.225-25 Prohibition on Contracting with Entities Engaging in Certain Activities or Transactions Relating to Iran-- Representation and Certifications.
AUG 2018
CLAUSES INCORPORATED BY FULL TEXT
52.216-1 TYPE OF CONTRACT (APR 1984)
The Government contemplates award of a Firm Fixed Price (FFP) contract resulting from this solicitation.
(End of provision)
52.228-1 BID GUARANTEE (SEP 1996)
(a) Failure to furnish a bid guarantee in the proper form and amount, by the time set for opening of bids, may be cause for rejection of the bid.
(b) The bidder shall furnish a bid guarantee in the form of a firm commitment, e.g., bid bond supported by good and sufficient surety or sureties acceptable to the Government, postal money order, certified check, cashier's check, irrevocable letter of credit, or, under Treasury Department regulations, certain bonds or notes of the United States.
The Contracting Officer will return bid guarantees, other than bid bonds, (1) to unsuccessful bidders as soon as practicable after the opening of bids, and (2) to the successful bidder upon execution of contractual documents and bonds (including any necessary coinsurance or reinsurance agreements), as required by the bid as accepted.-
(c) The amount of the bid guarantee shall be Twenty (20%) percent of the bid price or $3,000,000.00, whichever is less.-
(d) If the successful bidder, upon acceptance of its bid by the Government within the period specified for acceptance, fails to execute all contractual documents or furnish executed bond(s) within 10 days after receipt of the forms by the bidder, the Contracting Officer may terminate the contract for default.-
(e) In the event the contract is terminated for default, the bidder is liable for any cost of acquiring the work that exceeds the amount of its bid, and the bid guarantee is available to offset the difference.
(End of provision)
52.233-2 SERVICE OF PROTEST (SEP 2006)
(a) Protests, as defined in section 33.101 of the Federal Acquisition Regulation, that are filed directly with an agency, and copies of any protests that are filed with the Government Accountability Office (GAO), shall be served on the Contracting Officer (addressed as follows) by obtaining written and dated acknowledgment of receipt from
USACE Fort Worth Attention: John H. Rodgers 819 Taylor St.
Fort Worth, TX 76102 SWF-Protest@usace.army.mil
(b) The copy of any protest shall be received in the office designated above within one day of filing a protest with the GAO.
(End of provision)
52.236-27 SITE VISIT (CONSTRUCTION) (FEB 1995)
(a) The clauses at 52.236-2, Differing Site Conditions, and 52.236-3, Site Investigations and Conditions Affecting the Work, will be included in any contract awarded as a result of this solicitation. Accordingly, offerors or quoters are urged and expected to inspect the site where the work will be performed.
(b) Site visits may be arranged during normal duty hours by contacting:
Refer to Section 00 21 30 for Site Visit information.
(End of provision)
52.252-1 SOLICITATION PROVISIONS INCORPORATED BY REFERENCE (FEB 1998)
This solicitation incorporates one or more solicitation provisions by reference, with the same force and effect as if they were given in full text. Upon request, the Contracting Officer will make their full text available. The offeror is cautioned that the listed provisions may include blocks that must be completed by the offeror and submitted with its quotation or offer. In lieu of submitting the full text of those provisions, the offeror may identify the provision by paragraph identifier and provide the appropriate information with its quotation or offer. Also, the full text of a solicitation provision may be accessed electronically at this/these address(es):
http://farsite.hill.af.mil/vffara.htm http://farsite.hill.af.mil/vmdfara.htm http://www.usace.army.mil/Portals/2/docs/Contracting/UAI_Version%203__1%20NOV%202014.pdf
(End of provision)
52.252-5 AUTHORIZED DEVIATIONS IN PROVISIONS (APR 1984)
(a) The use in this solicitation of any Federal Acquisition Regulation (48 CFR Chapter 1) provision with an authorized deviation is indicated by the addition of"(DEVIATION)" after the date of the provision.
(b) The use in this solicitation of any DFARS (48 CFR Chapter 2) provision with an authorized deviation is indicated by the addition of "(DEVIATION)" after the name of the regulation.
(End of provision)
B23640 HVAC Renovation WSMR19B23640
SECTION 00 21 30
SITE VISITS
PART 1 GENERAL
1.1 SITE VISITS
(a) Pursuant to Contract Clause "FAR 52.236-3, Site Investigation and Conditions Affecting the Work," and the Site Visit Clause in Section 00 21 00 INSTRUCTIONS, CONDITIONS, AND NOTICES TO BIDDERS, prospective bidders will be permitted to inspect the site where services are to be performed and to satisfy themselves as to all general and local conditions that may affect the cost of performance of the Contract to the extent such information is reasonably obtainable. Bidders are urged and expected to inspect the site where the work will be performed. Site visits will be arranged during normal duty hours.
(b) Site visit information: See for site visit dates, time, location, and point of contact information.The site visit will be:
Date: [ TBD ] Time: [ TBD ] Location: [ TBD ]
POC:
Name: Thomas G Smiley, P.E. (Primary) Address:Bldg 102 Headquarters Ave, White Sands Missile Range, NM 88002-5008
Telephone: (575) 678-2591 Email: Thomas.G.Smiley@usace.army.mil
Name: Daniel Hartell (Secondary) Address:Bldg 102 Headquarters Ave, White Sands Missile Range, NM 88002-5008
Telephone: (575) 678-3288 Email: Daniel.H.Hartell@usace.army.mil
PART 2 PRODUCTS (NOT USED)
PART 3 EXECUTION (NOT USED)
-- End of Section --
DOCUMENT 00 21 30 Page 1
</am#0001>
<am#0001> 22 July 2019
0900 - 1200 MST
Building 23640, White Sands Missile Range, NM
W9126G19B0006 0001 m2pmjjf9 Cross-Out m2pmjjf9 Cross-Out m2pmjjf9 Cross-Out
US Army Corps of Engineers ®
SHEET ID
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
X
IS
S
U E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
File Path:
Plot Date:
M A
R K
D E
S C
R
IP
T
IO
N
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
P L O
T S
C A
L E
US Army Corps of Engineers ®
F
IL
E N
A M
E
SEAL
N O T F
O R
C O N S
TR
U C
TIO
N
IN
A
S S
O C
IA
T
IO
N
W
IT
H
IC
E
D A
N N
E N
B A
U M
J V
BIM 360://60588760-WSMR B23640/60588760_R18_MECH.rvt
5/7/2019 2:20:50 PM
BIM 360://60588760-WSMR B23640/60588760_R18_MECH.rvt
G0-0-01
C
IM
P
A R
A T
O
C
IM
P
A R
A T
O
IC
E
D
B J
V
R
M E
A D
O R
M A
Y
W
G -1
-D
-0
:1
B
B A
T T
E R
Y C
O N
T R
O L
B U
IL
D
IN
G
C O
VE
R
SH
EE
T
F O
R T
W O
R T
H D
IS
T
R
IC
T
FORT WORTH DISTRICT
MAY 08, 2019 ISSUE DATE.:
VO LUME: 1
B23640
R
M
E C
H .r v t
B23640 BATTERY CONTROL BUILDING
M A
Y
F
IN
A L D
E S
IG
N
D
100% FINAL DESIGN
WHITE SANDS MISSILE RANGE
BUILDING 23640 REPAIRS
WHITE SANDS MISSILE RANGE, NM
W H
IT
E
S A
N D
S M
IS
S
IL
E
R A
N G
E
B U
IL
D
IN
G
R
E P
A
IR
S
ENVIRONMENTAL NOTES
A.
B.
C.
D.
E.
F.
HAZMAT MATERIAL WAS FOUND IN THE BUILDING THROUGH FIELD
SAMPLES COLLECTED BY TERRACON WHICH ARE INCLUDED IN
APPENDIX A OF DESIGN ANALYSIS REPORT (DAR). HAZMAT MATERIAL
SHALL BE HANDLED, STORED, AND DISPOSED OF IN ACCORDANCE
WITH CURRENT FEDERAL AND STATE LAWS AND REGULATIONS, AND
MUST ALSO ADHERE TO WSMR DPW'S ENVIRONMENTAL
REQUIREMENTS.
A SATELLITE ACCUMULATION POINT (SAP) MUST BE ESTABLISHED BY
THE CONTRACTOR FOR ACCUMULATION OF LEAD-BASED-PAINT AND
ASBESTOS WASTE GENERATED DURING REMOVAL AND ABATEMENT
ON WSMR. CONTACT THE HAZARDOUS WASTE MANAGEMENT CENTER
(HWMC, 575-678-4641, FOR FURTHER GUIDANCE. A SAP MAY ALSO BE
REQUIRED FOR PROPER MANAGEMENT AND DISPOSAL OF PAINT
RELATED WASTE WHEN MATERIALS OTHER THAN LATEX OR ARCYLIC
PAINT IS USED. AN INVENTORY OF PRODUCTS TO BE USED ON WSMR,
ALONG WITH MANUFACTURER'S SDS/MSDS, SHALL BE PROVIDED TO
THE HWMC PRIOR TO START OF WORK.
COMPLY WITH ALL APPLICABLE OSHA AND THE SAFETY AND HEALTH
REQUIREMENTS MANUAL (EM385-1-1) REQUIREMENTS, INLCUDING (BUT
NOT LIMITED TO): ASBESTOS, LEAD, CONFINED SPACE ENTRY,
HEARING PROTECTION, LOCKOUT-TAGOUT, HOT WORK, RESPIRATORY
PROTECTION, TRENCHING AND SHORING, LIFTING, HAZCOM, ETC.
WHILE NOT ANTICIPATED FOR THIS PROJECT, PROJECTS MUST
PROTECT STORM SEWER DRAINS (INCLUDING AREA DRAINS),
MANHOLES, INLETS, TRENCHES AND SURFACE RUN-OFF DRAINAGES,
ROOF DRAINS, ETC. FROM DISCHARGES OF PROCESS WATER,
SEDIMENT, PETROLEUM RESIDUES, AND ALL OTHER CONTAMINANTS,
DISCHARGES OF CONTAMINATED OR PROCESS WATER MAY ONLY BE
PERMITTED INTO THE SANITARY SEWER IF AUTHORIZED BY THE
CONTRACTING OFFICER AND ENVIRONMENTAL HEALTH & SAFETY (EH
& S) OFFICE AT WHITE SANDS MISSILE RANGE (WSMR).
SHOULD, DURING THE COURSE OF EXCAVATION, DEMOLITION, OR
CONSTRUCTION, POSSIBLE ENVIRONMENTAL CONTAMINATION ISSUES
ARISE CONTACT EH&S OFFICE AT WSMR IMMEDIATELY. IT IS THE
RESPONSIBILITY OF THE CONTRACTOR TO PROPERLY MANAGE AND
DISPOSE OF HAZARDOUS MATERIALS AND WASTE GENERATED
DURING THE COURSE OF THE PROJECT. COPIES OF ALL PAPERWORK
FOR HAZARDOUS MATERIAL AND WASTE DISPOSAL MUST BE
SUBMITTED TO THE HAZARDOUS MATERIALS PROGRAM MANAGER,
AND WHERE APPROPRIATE, THE PROJECT MUST USE THE PROPER
EPA ID NUMBERS ON ALL WASTE DISPOSAL DOCUMENTS.
PAINTING: INCREASE VENTILATION DURING AND AFTER PAINTING TO
REDUCE ODOR MIGRATION. DO NOT USE OIL-BASED PAINTS.
CONTRACTOR'S
LAYDOWN AREA
R A
N G
E R
O A
D
BATTERY CONTROL
BUILDING B23640
PROJECT SITE
PROJECT NOTES
A.
B.
C.
D.
E.
F.
PROJECT SHALL COMPLY WITH THE 2015 INTERNATIONAL
CODE COUNCIL (ICC) CODES AND LATEST UNITED FACILITIES
CRITERIA (UFC) STANDARDS. THE US ARMY CORPS OF
ENGINEERS, FORT WORTH DISTRICT IS THE AUTHORITY
HAVING JURISDICTION (AHJ).
CONTRACTOR SHALL NOT SHUT DOWN OR TAKE OUT OF
SERVICE ANY SYSTEM(S) WITHOUT FIRST COORDINATING
WITH AND RECEIVING APPROVAL FROM THE FROM THE
CONTRACTING OFFICER. A DETAILED SCHEDULE OF ACTIVITY
AND METHOD OF PROCEDURE (MOP) IS REQUIRED WHEN A
CONSTRUCTION ACTIVITY AFFECTS THE SAFETY OF
OCCUPANTS, OR WHEN EVENTS ARE TO BE HELD IN THE
BUILDING DURING CONSTRUCTION.
WHERE DIMENSIONS ARE NOT SHOWN, THE DRAWINGS SHALL
NOT BE SCALED FOR ROUGH-IN MEASUREMENTS OR USED AS
SHOP DRAWINGS. WHERE DRAWINGS ARE REQUIRED FOR
THESE PURPOSES OR HAVE TO BE MADE FROM FIELD
MEASUREMENTS, THE CONTRACTOR SHALL OBTAIN
MEASUREMENTS AND PREPARE THE DRAWINGS.
TEMPORARY HEATING AND COOLING IS NOT REQUIRED
DURING CONSTRUCTION.
ENSURE THAT THE PROJECT STAGING AREA(S) AND
CONSTRUCTION ACTIVITIES DO NOT CAUSE THE
OBSTRUCTION OF PATHS OF EGRESS INSIDE THE BUILDING,
BLOCK EXIT DISCHARGE FROM THE BUILDING OR IMPEDED
EMERGENCY VEHICLE ACCESS TO THE AREA.
NECESSARY MEASURES TO PREVENT THE ACCIDENTAL
ACTIVATION OF NEARBY SMOKE DETECTORS ARE REQUIRED
FOR ACTIVITIES WHICH GENERATE DUST OR FUMES WITHIN
THE BUILDING.
IN THE EVENT THAT FIRE ALARM IS NOT ACTIVE DURING
CONSTRUCITON ACTIVITIES, CONTRACTOR TO PROVIDE
PROVISION FOR FIRE WATCH DURING ANY CUTTING,
GRINDING, WELDING AND OTHER RELATED ACTIVITES. NOTIFY
WSMR AND SITE FIRE OF CONSTRUCTION ACTIVITY PLAN
PRIOR TO COMMENCING WORK.
US Army Corps of Engineers ®
SHEET ID
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
X
IS
S
U E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
File Path:
Plot Date:
M A
R K
D E
S C
R
IP
T
IO
N
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
P L O
T S
C A
L E
SHEET OF
F
IL
E N
A M
E
SEAL
N O T F
O R
C O N S
TR
U C
TIO
N
IN
A
S S
O C
IA
T
IO
N
W
IT
H
IC
E
D A
N N
E N
B A
U M
J V
BIM 360://60588760-WSMR B23640/60588760_R18_MECH.rvt
5/7/2019 2:20:55 PM
BIM 360://60588760-WSMR B23640/60588760_R18_MECH.rvt
G0-1-01
C
IM
P
A R
A T
O
C
IM
P
A R
A T
O
IC
E
D
B J
V
R
M E
A D
O R
M A
Y
W
G -1
-D
-0
:1
B
B A
T T
E R
Y C
O N
T R
O L
B U
IL
D
IN
G
G
EN
ER
AL
P
RO
JE
C
T
IN
FO
F O
R T
W O
R T
H D
IS
T
R
IC
T
B23640
R
M
E C
H .r v t
M A
Y
F
IN
A L D
E S
IG
N
D
100% FINAL DESIGN
W H
IT
E
S A
N D
S M
IS
S
IL
E
R A
N G
E
B U
IL
D
IN
G
R
E P
A
IR
S
SHEET INDEX
SHEET
No.
SHEET
ID SHEET TITLE
1 G0-0-01 COVER SHEET
2 G0-1-01 GENERAL PROJECT INFO
3 A1-0-01 FIRST FLOOR PLAN - ARCH DEMO
4 A1-0-02 REFLECTED CEILING PLAN - ARCH DEMO
5 A1-1-01 FIRST FLOOR PLAN
6 A1-1-02 REFLECTED CEILING PLAN
7 M0-1-01 MECHANICAL LEGEND, SYMBOLS AND ABBREVIATIONS
8 M2-0-01 FIRST FLOOR PLAN - HVAC DEMO
9 M2-1-01 FIRST FLOOR PLAN - HVAC DUCTWORK
10 M2-2-01 FIRST FLOOR PLAN - HVAC PIPING
11 M5-1-01 MECHANICAL SYSTEM DIAGRAMS
12 M6-1-01 MECHANICAL DETAILS
13 M7-1-01 MECHANICAL SCHEDULES
14 M7-1-02 MECHANICAL SCHEDULES
15 M8-1-01 MECHANICAL CONTROLS
16 M8-1-02 MECHANICAL CONTROLS
17 M8-1-03 MECHANICAL CONTROLS
18 M8-1-04 MECHANICAL CONTROLS
19 M9-1-01 MECHANICAL PIPING ISOMETRICS
20 E0-1-01 ELECTRICAL LEGEND, SYMBOLS AND ABBREVIATIONS
21 E2-0-01 FIRST FLOOR PLAN - POWER DEMOLITION
22 E2-1-01 FIRST FLOOR PLAN - POWER
23 E4-1-01 ELECTRICAL POWER PARTIAL ONE-LINES
24 E4-1-02 ELECTRICAL POWER SCHEDULES
Scale: 6" = 1'-0"
1 PROJECT SITE LOCATION
Scale: NTS
C
E
MTR ANTENNA #1
VESTIBULE
SHIELDED VESTIBULE MTR ANTENNA #2
MTR ANTENNA #3
COMPUTER LAB
3-6 AMDTD BATTLE
LAB
BATTERY CONTROL
ROOM
BREAK ROOM
SHIELDED VESTIBULE
BOILER ROOM
MECHANICAL AND
ELECTRICAL
EQUIPMENT ROOM
CORRIDOR
SHIELDED VESTIBULE
PIPE SPACE
NO WORK IN SECURE
AREA
SHIELDED VESTIBULE
VESTIBULE
COMPUTER LAB /
STORAGE
CORRIDOR
FILTER ACCESS
ENTRY
OFFICE 101
OFFICE 102
OFFICE 103
STAIR
MENS RR
WOMENS RR
OFFICE 113
OBSERVATION
3 3
3A 1A
G G
DD
H H
FF
2A
2A A
2B
2B
25' - 0" 34' - 6"
14' - 5"
18' - 0"
17' - 11"
17' - 11"
18' - 1"
18' - 1" 18' -
0"
34' - 6"
94' - 0"
24x24
20x20
36x36
48x42
GENERAL DEMOLITION NOTES
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
M.
N.
THE INTENT OF THESE DRAWINGS AND NOTES IS TO INDICATE
THE GENERAL SCOPE OF WORK RELATED TO DEMOLITION.
SPECIFIC ITEMS NOT INDICATED, BUT REQUIRED IN ORDER TO
FACILITATE NEW WORK, SHALL BE INCLUDED AS PART OF THE
CONTRACTOR'S SCOPE OF WORK. THE WORK INDICATED IN
THESE NOTES AND ON THE DRAWINGS SHALL INCLUDE, BUT NOT
BE LIMITED TO: STRUCTURAL DEMOLITION, UTILITIES AND CIVIL
DEMOLITION, AND ARCHITECTURAL DEMOLITION.
IF UNANTICIPATED ARCHITECTURAL, MECHANICAL, ELECTRICAL,
PLUMBING, CIVIL, STRUCTURAL OR OTHER ELEMENTS CONFLICT
WITH DEMOLITION DWGS, REPORT THE NATURE AND EXTENT OF
THE CONFLICT TO THE CONTRACTING OFFICER IN WRITTEN
ACCURATE DETAIL PRIOR TO PROCEEDING. PENDING RECEIPT
OF INSTRUCTIONS, CONTRACTOR SHALL REARRANGE
DEMOLITION SCHEDULE TO MAINTAIN PROGRESS.
CONTRACTOR TO COORDINATE DEMOLITION WITH ALL TRADES.
CONSTRUCTION WORK SHALL BE CONFINED TO THE AREAS
DESIGNATED.
CONSTRUCTION WORK AREA SHALL BE ACCESSED VIA
DEDICATED PASSAGE AND ENTRY. CONTRACTOR SHALL
PROTECT ALL AREAS OF THE EXISTING BUILDING UTILIZED FOR
ACCESS TO AND FROM THE CONSTRUCTION AREA.
ALL EXISTING MEANS OF EGRESS FOR THE OCCUPANTS AND
USERS OF THE BUILDING SHALL BE MAINTAINED CLEAR AND FREE
OF ALL OBSTRUCTIONS AT ALL TIMES. MAINTAIN EMERGENCY
EGRESS DURING DEMOLITION.
THE CONTRACTOR SHALL MAINTAIN COMPLETE AND UP-TO-DATE
DRAWINGS AT THE JOB SITE.
GOVERNMENT ASSUMES NO RESPONSIBILITY FOR ACTUAL
CONDITION OF ITEMS OR STRUCTURES TO BE DEMOLISHED.
THE CONTRACTOR SHALL PROTECT ALL AREAS OUTSIDE THE
CONTRACT LIMITS AND RESTORE ALL SUCH PROPERTY TO ITS
CONDITION PRIOR TO THE START OF THE WORK.
ALL EXISTING CONSTRUCTION, SURFACES AND EQUIPMENT TO
REMAIN SHALL BE FULLY PROTECTED FROM DAMAGE. IF THE
EXISTING CONSTRUCTION TO REMAIN IS IN ANY WAY DISTURBED,
WEAKENED OR DAMAGED DUE TO CONTRACTOR'S NEGLIGENCE
OR PROGRESS OF WORK, IT SHALL BE RESTORED TO ITS
ORIGINAL CONDITION BY THE CONTRACTOR AT NO EXTRA COST
TO THE GOVERNMENT.
MAINTAIN EXISTING UTILITIES. DO NOT INTERRUPT EXISTING
BUILDING UTILITIES EXCEPT WHEN AUTHORIZED IN WRITING BY
THE CONTRACTING OFFICER. SEE GENERAL CONDITIONS IN THE
PROJECT SPECIFICATION MANUAL.
KEEP PASSAGEWAYS AND EXTERIOR SPACES CLEAN
CONTINUOUSLY. NO DEBRIS SHALL BE ALLOWED TO
ACCUMULATE ON THE SITE. DEBRIS SHALL BE REMOVED BY THE
CONTRACTOR AS THE JOB PROCEEDS. LEGALLY DISPOSE OF
MATERIALS OFF-SITE, THE SITE SHALL BE LEFT BROOM CLEAN AT
THE COMPLETION OF DEMOLITION.
FIRE ALARM DEVICES: REMOVE AND STORE FIRE ALARM
DEVICES. FIRE ALARM CONDUIT AND WIRE SHALL REMAIN IN
PLACE.
UNDER THE RECONSTRUCTION SCOPE, RE-INSTALL THE FIRE
ALARM DEVICES IN THEIR ORIGINAL LOCATIONS. REPAIR TO THE
FIRE ALRM SYSTEM AND RE-COMMISSIONING SHAL BE BY
OTHERS.
0 8' 16' 24'2' 4'
SCALE: 1/8" = 1'-0"
US Army Corps of Engineers ®
SHEET ID
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
X
IS
S
U E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
File Path:
Plot Date:
M A
R K
D E
S C
R
IP
T
IO
N
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
P L O
T S
C A
L E
SHEET OF
F
IL
E N
A M
E
GRAPHIC SCALE
SEAL
N O T F
O R
C O N S
TR
U C
TIO
N
IN
A
S S
O C
IA
T
IO
N
W
IT
H
IC
E
D A
N N
E N
B A
U M
J V
BIM 360://60588760-WSMR B23640/60588760_R18_MECH.rvt
5/7/2019 2:20:41 PM
BIM 360://60588760-WSMR B23640/60588760_R18_MECH.rvt
A1-0-01
C
IM
P
A R
A T
O
C
IM
P
A R
A T
O
IC
E
D
B J
V
R
M E
A D
O R
M A
Y
W
G -1
-D
-0
:1
B
B A
T T
E R
Y C
O N
T R
O L
B U
IL
D
IN
G
FI
R
ST
F
LO
O
R
PL
AN
AR
C
H D
EM
O
F O
R T
W O
R T
H D
IS
T
R
IC
T
B23640
R
M
E C
H .r v t
M A
Y
F
IN
A L D
E S
IG
N
D
100% FINAL DESIGN
W H
IT
E
S A
N D
S M
IS
S
IL
E
R A
N G
E
B U
IL
D
IN
G
R
E P
A
IR
S
Scale: 1/8" = 1'-0"
1 ARCHITECTURAL DEMOLITION - FIRST FLOOR PLAN
KEYNOTES
1 REMOVE EXISTING CONCRETE HOUSEKEEPING PAD. REPAIR
CONCRETE FLUSH WITH SURROUNDING MECHANICAL ROOM
FLOOR.
2 REMOVE EXISTING 6-INCH THICK CONCRETE CONTAINMENT CURB.
REPAIR CONCRETE FLUSH WITH SURROUNDING MECHANICAL
ROOM FLOOR.
3 EXISTING CONCRETE PAD/CURB IS INTEGRAL TO EXISTING FLOOR
SLAB. SAW CUT AROUND PERIMETER OF EXISTING PAD.
4 EXISTING BOILER ROOM WALL SHALL BE MINIMUM 1-HOUR
FIRE-RATED CONSTRUCITON.
5 ENLARGE EXISTING 48-INCH WIDE BY 24-INCH HIGH OPENING IN
CMU WALL FOR NEW 120-INCH WIDE BY W BY 60-INCH HIGH LOUVER
AS INDICATED ON MECHANICAL DRAWINGS. ALL OPENINGS SHALL
BE PROTECTED IN ACCORDANCE WITH MILITARY HANDBOOK
1013/1A.
6 FILL EXISTING OPENING IN CMU BLOCK WALL AFTER DEMOLITION
OF MECHANICAL EQUIPMENT.
7 EXISTING MECHANICAL ROOM WALLS ARE NOT REQUIRED TO BE
FIRE-RATED UNDER THE INTERNATIONAL BUILDING CODE, SECTION
509. MECHANICAL ROOM DOES NOT CONTAIN FUEL-BURNING
APPLIANCES, BOILERS OF 10 HP OR MORE, BATTERY STORAGE,
COMBUSTIBLE STORAGE, ETC. THE BOILER IS SEPERATED FROM
THE MECHANICAL ROOM BY A RATED WALL, AS INDICATED ON THE
DRAWING.
3A1A
C
D
E
F
1 2
2A A
2B
MTR ANTENNA #1
VESTIBULE
SHIELDED VESTIBULE
MTR ANTENNA #2
MTR ANTENNA #3
COMPUTER LAB
3-6 AMDTD BATTLE
LAB
BATTERY CONTROL
ROOM
BREAK ROOM
SHIELDED VESTIBULE
BOILER ROOM
MECHANICAL AND
ELECTRICAL
EQUIPMENT ROOM
CORRIDOR
SHIELDED VESTIBULE
PIPE SPACE
NO WORK IN SECURE
AREA
SHIELDED VESTIBULE
VESTIBULE
COMPUTER LAB /
STORAGE
CORRIDOR
FILTER ACCESS
ENTRY
OFFICE 101
OFFICE 102
OFFICE 103
STAIR
MENS RR
WOMENS RR
OFFICE 113
OBSERVATION
TYP1
TYP1
TYP1
TYP1
G
D
H
F
2A A
2B
GENERAL DEMOLITION NOTES
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L
M..
N.
THE INTENT OF THESE DRAWINGS AND NOTES IS TO INDICATE
THE GENERAL SCOPE OF WORK RELATED TO DEMOLITION.
SPECIFIC ITEMS NOT INDICATED, BUT REQUIRED IN ORDER TO
FACILITATE NEW WORK, SHALL BE INCLUDED AS PART OF THE
CONTRACTOR'S SCOPE OF WORK. THE WORK INDICATED IN
THESE NOTES AND ON THE DRAWINGS SHALL INCLUDE, BUT NOT
BE LIMITED TO: STRUCTURAL DEMOLITION, UTILITIES AND CIVIL
DEMOLITION, AND ARCHITECTURAL DEMOLITION.
IF UNANTICIPATED ARCHITECTURAL, MECHANICAL, ELECTRICAL,
PLUMBING, CIVIL, STRUCTURAL OR OTHER ELEMENTS CONFLICT
WITH DEMOLITION DWGS, REPORT THE NATURE AND EXTENT OF
THE CONFLICT TO THE CONTRACTING OFFICER IN WRITTEN
ACCURATE DETAIL PRIOR TO PROCEEDING. PENDING RECEIPT OF
INSTRUCTIONS, CONTRACTOR SHALL REARRANGE DEMOLITION
SCHEDULE TO MAINTAIN PROGRESS.
CONTRACTOR TO COORDINATE DEMOLITION WITH ALL TRADES.
CONSTRUCTION WORK SHALL BE CONFINED TO THE AREAS
DESIGNATED.
CONSTRUCTION WORK AREA SHALL BE ACCESSED VIA
DEDICATED PASSAGE AND ENTRY. CONTRACTOR SHALL
PROTECT ALL AREAS OF THE EXISTING BUILDING UTILIZED FOR
ACCESS TO AND FROM THE CONSTRUCTION AREA.
ALL EXISTING MEANS OF EGRESS FOR THE OCCUPANTS AND
USERS OF THE BUILDING SHALL BE MAINTAINED CLEAR AND FREE
OF ALL OBSTRUCTIONS AT ALL TIMES. MAINTAIN EMERGENCY
EGRESS DURING DEMOLITION.
THE CONTRACTOR SHALL MAINTAIN COMPLETE AND UP-TO-DATE
DRAWINGS AT THE JOB SITE.
GOVERNMENT ASSUMES NO RESPONSIBILITY FOR ACTUAL
CONDITION OF ITEMS OR STRUCTURES TO BE DEMOLISHED.
THE CONTRACTOR SHALL PROTECT ALL AREAS OUTSIDE THE
CONTRACT LIMITS AND RESTORE ALL SUCH PROPERTY TO ITS
CONDITION PRIOR TO THE START IF THE WORK.
ALL EXISTING CONSTRUCTION, SURFACES AND EQUIPMENT TO
REMAIN SHALL BE FULLY PROTECTED FROM DAMAGE. IF THE
EXISTING CONSTRUCTION TO REMAIN IS IN ANY WAY DISTURBED,
WEAKENED OR DAMAGED DUE TO CONTRACTOR'S NEGLIGENCE
OR PROGRESS OF WORK, IT SHALL BE RESTORED TO ITS
ORIGINAL CONDITION BY THE CONTRACTOR AT NO EXTRA COST
TO THE GOVERNMENT.
MAINTAIN EXISTING UTILITIES. DO NOT INTERRUPT EXISTING
BUILDING UTILITIES EXCEPT WHEN AUTHORIZED IN WRITING BY
THE CONTRACTING OFFICER. SEE GENERAL CONDITIONS IN THE
PROJECT SPECIFICATION MANUAL.
KEEP PASSAGEWAYS AND EXTERIOR SPACES CLEAN
CONTINUOUSLY. NO DEBRIS SHALL BE ALLOWED TO
ACCUMULATE ON THE SITE. DEBRIS SHALL BE REMOVED BY THE
CONTRACTOR AS THE JOB PROCEEDS. LEGALLY DISPOSE OF
MATERIALS OFF-SITE, THE SITE SHALL BE LEFT BROOM CLEAN AT
THE COMPLETION OF DEMOLITION.
FIRE ALARM DEVICES: REMOVE AND STORE FIRE ALARM DEVICES.
FIRE ALARM CONDUIT AND WIRE SHALL REMAIN IN PLACE.
UNDER THE RECONSTRUCTION SCOPE, RE-INSTALL THE FIRE
ALARM DEVICES IN THEIR ORIGINAL LOCATIONS. REPAIR TO THE
FIRE ALRM SYSTEM AND RE-COMMISSIONING SHAL BE BY
OTHERS.
0 8' 16' 24'2' 4'
SCALE: 1/8" = 1'-0"
US Army Corps of Engineers ®
SHEET ID
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
X
IS
S
U E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
File Path:
Plot Date:
M A
R K
D E
S C
R
IP
T
IO
N
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
P L O
T S
C A
L E
SHEET OF
F
IL
E N
A M
E
GRAPHIC SCALE
SEAL
N O T F
O R
C O N S
TR
U C
TIO
N
IN
A
S S
O C
IA
T
IO
N
W
IT
H
IC
E
D A
N N
E N
B A
U M
J V
BIM 360://60588760-WSMR B23640/60588760_R18_MECH.rvt
5/7/2019 2:20:43 PM
BIM 360://60588760-WSMR B23640/60588760_R18_MECH.rvt
A1-0-02
C
IM
P
A R
A T
O
C
IM
P
A R
A T
O
IC
E
D
B J
V
R
M E
A D
O R
M A
Y
W
G -1
-D
-0
:1
B
B A
T T
E R
Y C
O N
T R
O L
B U
IL
D
IN
G
R
EF
LE
C
TE
D
C
EI
LI
NG
P
LA
N
AR
C
H D
EM
O
F O
R T
W O
R T
H D
IS
T
R
IC
T
B23640
R
M
E C
H .r v t
M A
Y
F
IN
A L D
E S
IG
N
D
100% FINAL DESIGN
W H
IT
E
S A
N D
S M
IS
S
IL
E
R A
N G
E
B U
IL
D
IN
G
R
E P
A
IR
S
Scale: 1/8" = 1'-0"
ARCHITECTURAL DEMOLITION - REFLECTED
CEILING PLAN
KEYNOTES
1 REMOVE EXISTING CEILING GRID AND STRUCTURAL SUPPORT
TEES AS REQUIRED TO ACCOMMODATE HVAC DEMOLITION AND
ABATEMENT ACTIVITIES. STORE TILES AND TEES FOR
RE-INSTALLATION. CONTRACTOR TO INSPECT AND REPLACE
DAMAGED CEILING TILES AND STRUCTURAL SUPPORT TEES AND
WIRES AS NECESSARY. ASSUME A MINIMUM 25% TILE AND GRID
REPLACEMENT IN BID ESTIMATE.
GENERAL NOTES
A. THE INTENT OF THESE DRAWINGS IS TO INDICATE THE WORK TO
BE PROVIDED BY THE GENERAL CONTRACTOR AS A RESULT OF
THE MECHANCIAL AND ELECTRICAL SYSTEMS REPLACEMENTS.
THERE ARE NO CHANGES TO OCCUPANCY, SPACE USE TYPE,
EGRESS (LIFE SAFETY) OR FIRE RATINGS OF EXISTING
ASSEMBLIES.
C
E
3A1A
C
D
E
F
1 2
2A A
2B
MTR ANTENNA #1
VESTIBULE
SHIELDED VESTIBULE
MTR ANTENNA #2
MTR ANTENNA #3
COMPUTER LAB
3-6 AMDTD BATTLE
LAB
BATTERY CONTROL
ROOM
BREAK ROOM
SHIELDED VESTIBULE
BOILER ROOM
MECHANICAL AND
ELECTRICAL
EQUIPMENT ROOM
CORRIDOR
SHIELDED VESTIBULE
PIPE SPACE
NO WORK IN SECURE
AREA
SHIELDED VESTIBULE
VESTIBULE
COMPUTER LAB /
STORAGE
CORRIDOR
FILTER ACCESS
ENTRY
OFFICE 101
OFFICE 102
OFFICE 103
STAIR
MENS RR
WOMENS RR
OFFICE 113
OBSERVATION
G
D
H
F
2A A
2B
6' - 0"
3' - 6"
5' - 6"
0 8' 16' 24'2' 4'
SCALE: 1/8" = 1'-0"
US Army Corps of Engineers ®
SHEET ID
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
X
IS
S
U E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
File Path:
Plot Date:
M A
R K
D E
S C
R
IP
T
IO
N
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
P L O
T S
C A
L E
SHEET OF
F
IL
E N
A M
E
GRAPHIC SCALE
SEAL
N O T F
O R
C O N S
TR
U C
TIO
N
IN
A
S S
O C
IA
T
IO
N
W
IT
H
IC
E
D A
N N
E N
B A
U M
J V
BIM 360://60588760-WSMR B23640/60588760_R18_MECH.rvt
5/7/2019 2:20:46 PM
BIM 360://60588760-WSMR B23640/60588760_R18_MECH.rvt
A1-1-01
C
IM
P
A R
A T
O
C
IM
P
A R
A T
O
IC
E
D
B J
V
R
M E
A D
O R
M A
Y
W
G -1
-D
-0
:1
B
B A
T T
E R
Y C
O N
T R
O L
B U
IL
D
IN
G
FI
RS
T
FL
O O
R
PL
AN
F O
R T
W O
R T
H D
IS
T
R
IC
T
B23640
R
M
E C
H .r v t
M A
Y
F
IN
A L D
E S
IG
N
D
100% FINAL DESIGN
W H
IT
E
S A
N D
S M
IS
S
IL
E
R A
N G
E
B U
IL
D
IN
G
R
E P
A
IR
S
KEYNOTES
1 REPAIR CONCRETE FLUSH WITH SURROUNDING MECHANICAL
ROOM FLOOR.
Scale: 1/8" = 1'-0"
1 ARCHITECTURAL - FIRST FLOOR PLAN
3A1A
C
D
E
F
1 2
2A A
2B
MTR ANTENNA #1
VESTIBULE
SHIELDED VESTIBULE
MTR ANTENNA #2
MTR ANTENNA #3
COMPUTER LAB
3-6 AMDTD BATTLE
LAB
BATTERY CONTROL
ROOM
BREAK ROOM
SHIELDED VESTIBULE
BOILER ROOM
MECHANICAL AND
ELECTRICAL
EQUIPMENT ROOM CORRIDOR
SHIELDED VESTIBULE
PIPE SPACE
NO WORK IN SECURE
AREA
SHIELDED VESTIBULE
VESTIBULE
COMPUTER LAB /
STORAGE
CORRIDOR
FILTER ACCESS
ENTRY
OFFICE 101
OFFICE 102
OFFICE 103
STAIR
MENS RR
WOMENS RR
OFFICE 113
OBSERVATION
TYP1
TYP 1
TYP1
TYP1
G
D
H
F
2A A
2B
GENERAL NOTES
A. THE INTENT OF THESE DRAWINGS IS TO INDICATE THE WORK TO
BE PROVIDED BY THE GENERAL CONTRACTOR AS A RESULT OF
THE MECHANCIAL AND ELECTRICAL SYSTEMS REPLACEMENTS.
THERE ARE NO CHANGES TO OCCUPANCY, SPACE USE TYPE,
EGRESS (LIFE SAFETY) OR FIRE RATINGS OF EXISTING
ASSEMBLIES.
0 8' 16' 24'2' 4'
SCALE: 1/8" = 1'-0"
US Army Corps of Engineers ®
SHEET ID
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
X
IS
S
U E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
File Path:
Plot Date:
M A
R K
D E
S C
R
IP
T
IO
N
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
P L O
T S
C A
L E
SHEET OF
F
IL
E N
A M
E
GRAPHIC SCALE
SEAL
N O T F
O R
C O N S
TR
U C
TIO
N
IN
A
S S
O C
IA
T
IO
N
W
IT
H
IC
E
D A
N N
E N
B A
U M
J V
BIM 360://60588760-WSMR B23640/60588760_R18_MECH.rvt
5/7/2019 2:20:49 PM
BIM 360://60588760-WSMR B23640/60588760_R18_MECH.rvt
A1-1-02
C
IM
P
A R
A T
O
C
IM
P
A R
A T
O
IC
E
D
B J
V
R
M E
A D
O R
M A
Y
W
G -1
-D
-0
:1
B
B A
T T
E R
Y C
O N
T R
O L
B U
IL
D
IN
G
R
EF
LE
C
TE
D
C
EI
LI
NG
P
LA
N
F O
R T
W O
R T
H D
IS
T
R
IC
T
B23640
R
M
E C
H .r v t
M A
Y
F
IN
A L D
E S
IG
N
D
100% FINAL DESIGN
W H
IT
E
S A
N D
S M
IS
S
IL
E
R A
N G
E
B U
IL
D
IN
G
R
E P
A
IR
S
Scale: 1/8" = 1'-0"
1 ARCHITECTURAL - REFLECTED CEILING PLAN
KEYNOTES
1 RE-INSTALL CEILING GRID IN EXISTING LOCATION. CONTRACTOR
TO INSPECT AND REPLACE DAMAGED CEILING TILES AND
STRUCTURAL SUPPORT TEES AND WIRES AS NECESSARY.
RE-INSTALL ACRYLIC LENSES IN LOCATIONS TO ALLOW EXISTING
LIGHTING FIXTURES TO SHOW THORUGH CEILING.
SUPPLY
DIFFUSER, TYP.
RETURN
DIFFUSER, TYP.
FLOW ARROW
CONNECT TO EXISTING
PIPE CAPPED
END OF DEMOLITION
AIRFLOW ARROW
DESCRIPTIONSYMBOL
MECHANICAL SYMBOLS LIST
NOTE: NOT ALL SYMBOLS MAY BE USED.
TEMPERATURE SENSOR
HUMIDITY SENSOR
PIPE UNION
REDUCED PRESSURE BACKFLOW PREVENTER
THREE-WAY CONTROL VALVE
TWO-WAY CONTROL VALVE
GENERAL SERVICE VALVE (SEE SPECIFICATIONS
FOR VALVE TYPE PER APPLICATION)
CHECK VALVE (ARROW INDICATES
DIRECTION OF FLOW)
AUTOMATIC BALANCING VALVE
AUTOMATIC AIR VENT
TEMPERATURE/PRESSURE TEST PLUG
(PETE'S PLUG)
DRAIN VALVE WITH THREADED
HOSE CONNECTION
THERMOMETER
STRAINER WITH BLOW DOWN VALVE
PRESSURE GAUGE WITH STOPCOCK
PITCH DOWN IN DIRECTION OF ARROW
FLEXIBLE PIPE CONNECTION
PIPE ANCHOR
MANUAL AIR VENT
PIPE GUIDES OR SLEEVES
FLOW METER
RELIEF VALVE
PRESSURE REDUCING VALVE
MANUAL BALANCING VALVEM
A
AV
MAV
TWO-WAY PRESSURE INDEPENDENT
CONTROL AND BALANCE VALVE
COCO CLEAN OUT
PICBV
THERMOSTAT WITH ADJUSTABLE CONTROLT
HUMIDISTAT WITH ADJUSTABLE CONTROLH
CARBON DIOXIDE SENSOR
CARBON MONOXIDE SENSOR
NITROGEN DIOXIDE SENSOR
CO2
CO
NO2
H
T
STEAM TRAP
STEAM PRESSURE REGULATING VALVE
OCCUPANCY SENSOR OS
PIPE DROP
PIPE RISE
PIPE TEE DOWN
PIPE REDUCER
HEAT TRACE CONTROL PANELHT
DESCRIPTIONSYMBOL
MECHANICAL SYMBOLS LIST CONT.
NOTE: NOT ALL SYMBOLS MAY BE USED.
SUPPLY DIFFUSER WITH FLEXIBLE DUCT
SUPPLY DIFFUSER
RETURN/EXHAUST GRILLE
SIDEWALL SUPPLY DIFFUSER
SIDEWALL RETURN/EXHAUST GRILLE
DAMPERS
BDD: BACKDRAFT DAMPER
FSD: FIRE/SMOKE DAMPER
FD: FIRE DAMPER
MD: MOTORIZED DAMPER
SD: SMOKE DAMPER
VD: VOLUME DAMPER
BDD
TAG - NECK SIZE
AIRFLOW (CFM)
TAG - NECK SIZE
AIRFLOW (CFM)
TAG - NECK SIZE
AIRFLOW (CFM)
TAG - NECK SIZE
AIRFLOW (CFM)
TAG - NECK SIZE
AIRFLOW (CFM)
S1-6ø
TAG EXAMPLE:
S1-6ø
TAG EXAMPLE:
R1-22x10
TAG EXAMPLE:
S2-12x8
TAG EXAMPLE:
R2-12x8
TAG EXAMPLE:
E1-22x10
E2-12x8
NEW WORK DUCTWORK
EXISTING DUCTWORK
DEMOLITION DUCTWORK
NEW WORK PIPING
EXISTING PIPING
DEMOLISHED PIPING
NEW WORK MECHANICAL EQUIPMENT
(WITH CLEARANCE SHOWN)
EXISTING MECHANICAL EQUIPMENT
DEMOLISHED MECHANICAL EQUIPMENT
VAV TERMINAL BOX (WITH REHEAT)
GENERIC FAN
GENERIC PUMP
RECTANGULAR DUCT ELBOW DOWN
SUPPLY AND OUTDOOR AIR
OVAL DUCT ELBOW DOWN
ROUND DUCT ELBOW DOWN
RECTANGULAR DUCT ELBOW DOWN
RETURN, RELIEF, AND EXHAUST AIR
OVAL DUCT ELBOW DOWN
ROUND DUCT ELBOW DOWN
1. IF MIN COOLING CFM IS NOT SHOWN ON
PLANS, THEN MIN COOLING CFM IS EQUAL
TO 30% OF MAX COOLING CFM.
2. HEATING CFM IS EQUAL TO MIN COOLING
CFM.
TAG EXAMPLES:
DUCTWORK PLANS
TAG
MAX COOLING CFM / MIN COOLING CFM
PIPING PLANS
TAG
GPM
TERMINAL BOXES
TB1
0.5
TB1
500/200
TB1
DUCTWORK
PLANS
PIPING
PLANS
TERMINAL BOX NOTES
ACCESS DOOR
DESCRIPTIONSYMBOL
CONTROLS SYMBOLS GUIDE
NOTE: NOT ALL SYMBOLS MAY BE USED.
AIR FLOW MEASURING DEVICEAF
AIR SWITCHAS
CT CONDUCTIVITY TRANSMITTER
CURRENT SENSORCS
DIFFERENTIAL PRESSURE TRANSMITTERDP
DL DATA LINK
END SWITCHES
FLOW METERFM
HAND-OFF-AUTO SWITCHHOA
LEVEL TRANSMITTERLT
METERM
PHT PH TRANSMITTER
PRESSURE SWITCHPS
PRESSURE TRANSMITTERPT
DUCT SMOKE DETECTORDSD
STARTER
TEMPERATURE SWITCHTS
VARIABLE FREQUENCY DRIVEVFD
VT
WATER FLOW SWITCHFS
VIBRATION TRANSMITTER
ELECTRONIC ACTUATOREA
US Army Corps of Engineers ®
SHEET ID
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
X
IS
S
U E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
File Path:
Plot Date:
M A
R K
D E
S C
R
IP
T
IO
N
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
P L O
T S
C A
L E
SHEET OF
F
IL
E N
A M
E
SEAL
N O
T F O
R
C O
N S
TR
U
C
TIO
N
IN
A
S S
O C
IA
T
IO
N
W
IT
H
IC
E
D A
N N
E N
B A
U M
J V
BIM 360://60588760-WSMR B23640/60588760_R18_MECH.rvt
5/7/2019 2:22:17 PM
BIM 360://60588760-WSMR B23640/60588760_R18_MECH.rvt
M0-1-01
C
IM
P
A R
A T
O
C
IM
P
A R
A T
O
IC
E
D
B J
V
R
M E
A D
O R
M A
Y
W
G -1
-D
-0
:1
B
B A
T T
E R
Y C
O N
T R
O L
B U
IL
D
IN
G
M
EC
H
AN
IC
AL
L
EG
EN
D
, S
YM
BO
LS
A N
D A
BB
R
EV
IA
TI
O
NS
F O
R T
W O
R T
H D
IS
T
R
IC
T
B23640
R
M
E C
H .r v t
M A
Y
F
IN
A L D
E S
IG
N
D
100% FINAL DESIGN
W H
IT
E
S A
N D
S M
IS
S
IL
E
R A
N G
E
B U
IL
D
IN
G
R
E P
A
IR
S
MECHANICAL ABBREVIATIONS
NOTE: NOT ALL ABBREVIATIONS MAY BE USED.
ABBREVIATION DESCRIPTION
(D) EXISTING TO BE DEMOLISHED
(E) EXISTING TO REMAIN
AFF ABOVE FINISHED FLOOR
APD AIR PRESSURE DROP
BAS BUILDING AUTOMATION SYSTEM
BFP BACKFLOW PREVENTOR
BHP BRAKE HORSEPOWER
BLDG BUILDING
BOB BOTTOM OF BEAM
BOD BOTTOM OF DUCT
BOP BOTTOM OF PIPE
BOS BOTTOM OF STRUCTURE
BTUH BRITISH TEHRMAL UNITS PER HOUR
CFM CUBIC FEET PER MINUTE
CL CENTER LINE
CO CLEAN OUT
COP COEFFICIENT OF PERFORMANCE
CV CONSTANT VOLUME
DB DRY BULB
DIA DIAMETER
DN DOWN
EAT ENTERING AIR TEMPERATURE
EER ENERGY EFFICIENCY RATIO
EFF EFFICIENCY
ESP EXTERNAL STATIC PRESSURE
EWT ENTERING WATER TEMPERATURE
FLA FULL LOAD AMPS
FPI FINS PER INCH
FPM FEET PER MINUTE
FPS FEET PER SECOND
FT FEET
GAL GALLONS
GPM GALLONS PER MINUTE
HD HEAD
HP HORSEPOWER
ID INNER DIAMETER
IPLV INTEGRATED PART LOAD VALUE
KW KILOWATTS
LAT LEAVING AIR TEMPERATURE
LWT LEAVING WATER TEMPERATURE
MBH THOUSAND BTUH
MCA MAXIMUM CURRENT AMPACITY
MOCP MAXIMUM OVERCURRENT PROTECTION
N/A NOT APPLICABLE
NC NORMALLY CLOSED
NO NORMALLY OPEN
NPLV NON-STANDARD PART LOAD VALUE
NPSH NET POSITIVE SUCTION HEAD
NTS NOT TO SCALE
OD OUTSIDE DIAMETER
PD PRESSURE DROP
PPH POUNDS PER HOUR
PPM PARTS PER MILLION
PRV PRESSURE REDUCING VALVE
PSI PUNDS PER SQUARE INCH
REFRIG REFRIGERANT
RH RELATIVE HUMIDITY
RPM REVOLUTIONS PER MINUTE
SEER SEASONAL ENERGY EFFICIENCY RATIO
SP STATIC PRESSURE
TSP TOTAL STATIC PRESSURE
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VAV VARIABLE AIR VOLUME
VFD VARIABLE FREQUENCY DRIVE
W WATTS
WB WET BULB
WG WATER GAUGE
WPD WATER PRESSURE DROP
MECHANICAL SYSTEM TYPES
NOTE: NOT ALL ABBREVIATIONS MAY BE USED.
ABBREVIATION DESCRIPTION
CHR CHILLED WATER RETURN
CHS CHILLED WATER SUPPLY
CWR CONDENSER WATER RETURN
CWS CONDENSER WATER SUPPLY
D DRAIN
EA EXHAUST AIR
GR GEOTHERMAL RETURN
GS GEOTHERMAL SUPPLY
HR HEAT PUMP RETURN
HS HEAT PUMP SUPPLY
HWR HEATIN HOT WATER RETURN
HWS HEATING HOT WATER SUPPLY
MW MAKEUP WATER - GENERIC
OA OUTDOOR AIR
PC PUMPED CONDENSATE
R REFRIGERANT
RA RETURN AIR
REL RELIEF AIR
SA SUPPLY AIR
MECHANICAL GENERAL NOTES
24. PROVIDE THERMOSTATS FOR ALL EQUIPMENT THAT MAINTAINS…