B3_Appendix_A-1_Hazmat.pdf

PDF 6 MB Posted

Attached to
WSMR HVAC Renovation B23640
Solicitation number
W9126G19B0006
Issued by

About this file

Appendix A

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Pre-Renovation Asbestos Survey and Hazardous Building Materials

Assessment

White Sands Missile Range

Building B23640 Repairs

Range Road 2 and Range Road 238

White Sands Missile Range, New Mexico 88002

November 12, 2018

Terracon Project No. 95187622

Prepared for:

ICE and Dannenbaum JV

Houston, Texas 77098

Prepared by:

Terracon Consultants, Inc.

Fort Worth, Texas 76118

Responsive ■ Resourceful ■ Reliable

TABLE OF CONTENTS

Page

1.0 INTRODUCTION

1.1 Project Objective

1.2 Reliance

2.0 BUILDING DESCRIPTIONS

3.0 ASBESTOS FIELD ACTIVITIES

3.1 Visual Assessment

3.2 Physical Assessment

3.3 Sample Collection

3.4 Sample Analysis

4.0 REGULATORY OVERVIEW

5.0 HAZARDOUS BUILDING MATERIALS

5.1 PCBs

5.2 Mercury

5.3 CFC

5.4 Batteries

5.5 Radioactive Sources

6.0 FINDINGS AND RECOMMENDATIONS………………………………………………………..6

7.0 GENERAL COMMENTS…………………………………………………………….…………

APPENDIX A – Asbestos Containing Materials

APPENDIX B – Identified Homogeneous Materials

APPENDIX C – Hazardous Building Materials Quantity Estimates

APPENDIX D – Analytical Laboratory Asbestos Summary

APPENDIX E – Licenses

Responsive ■ Resourceful ■ Reliable 1

Pre-Renovation Asbestos Survey and

Hazardous Building Materials Assessment

White Sands Missile Range - Building B23640 Repairs

Range Road 2 and Range Road 238

White Sands Missile Range, New Mexico 88002

November 12, 2018

1.0 INTRODUCTION

The purpose of the Pre-Renovation Asbestos Survey and Hazardous Building Materials

Assessment, conducted on the interior and exterior of the areas scheduled for renovation at

Building B23640 at White Sands Missile Range, New Mexico was to:

▪ locate, sample (if accessible), quantify and assess suspect building materials for the presence of asbestos; and

▪ locate and quantify equipment (i.e., fluorescent light ballasts, tube lamps, thermostat switches, refrigerators, air conditioners, emergency lighting, exit signs, alarm systems, and fire/smoke alarms) for the presence of polychlorinated biphenyls (PCBs), elemental mercury (Hg), chlorofluorocarbon (CFC), batteries, and radioactive sources.

The site services were conducted by an accredited/State of Texas licensed asbestos inspector on October 29 – 30, 2018.

Homogeneous areas with suspect asbestos-containing materials (ACM) were visually characterized and documented. Although reasonable effort was made to survey accessible suspect materials, additional suspect but unsampled materials could be located in walls, voids or in other concealed areas. Suspect ACM samples were collected in general accordance with the sampling protocols outlined in Environmental Protection Agency (EPA) regulation 40 CFR

763, the Asbestos Hazard Emergency Response Act (AHERA). ACM samples were submitted to a National Voluntary Laboratory Accreditation Program (NVLAP) laboratory for analysis by polarized light microscopy. It should be emphasized that aggressive procedures for collecting the samples (i.e. coring through multiple building material layers, making holes in walls/ceilings to access hidden materials, etc.) were limited due to the fact that the building is still occupied.

In conjunction with the asbestos survey, a visual assessment for Hg-containing, PCB-containing, CFC-containing equipment, batteries in emergency lighting and alarm equipment, and smoke alarms with radioactive sources was also conducted. Where observed, these items were documented and quantified.

Environmental Hazards Assessment White Sands Missile Range - Building B23640 Repairs Range Road 2 and Range Road 238 ■ White Sands Missile Range, New Mexico November 12, 2018 ■ Terracon Project No. 95187622

Responsive ■ Resourceful ■ Reliable 2

1.1 Project Objective

We understand the project services were requested due to planned HVAC renovation on the interior and exterior of building B23640 located at Range Road 2 and Range Road 238 at White

Sands Missile Range, New Mexico. EPA regulation 40 CFR 61, Subpart M, National Emission

Standards for Hazardous Air Pollutants (NESHAP), prohibits the release of asbestos fibers to the atmosphere during Renovation or renovation activities. The asbestos NESHAP requires that potentially regulated asbestos-containing building materials be identified, classified and quantified prior to planned disturbances.

The Resource Conservation and Recovery Act (RCRA) provides the EPA with the authority to regulate the waste status of Renovation or renovation debris, including Hg, CFC, radioactive, and PCB-containing materials. Specific regulatory requirements must be addressed prior to transporting, treating, storing, or disposing of hazardous wastes.

1.2 Reliance

This report was prepared for the exclusive use of ICE and Dannenbaum JV, its affiliates and subsidiaries and their successors, assigns and grantees for the project being discussed. No other individual or entity may rely on this report without written permission of Terracon, ICE, and

Dannenbaum JV. Reliance on this report by all authorized parties will be subject to the terms, conditions, and limitations stated in Task Order No. 6. The limitation of liability defined in

Terracon’s Master Services Agreement is the aggregate limit of Terracon’s liability to ICE and

Dannenbaum JV, and all relying parties.

2.0 BUILDING DESCRIPTION

Building B23640 is a single-story structure measuring approximately 5,300 square feet. The exterior walls consist of textured concrete masonry unit (CMU) block and the interior walls consist of textured CMU block, textured drywall, fibrous wall tile on drywall, and metal. The floors consist of ceramic floor tile, vinyl floor tile, and unfinished concrete. The ceilings consist a lay-in ceiling tile system suspended from the metal deck in areas not exposed to the metal deck. No fireproofing was observed on the metal deck on the day of the survey.

3.0 ASBESTOS FIELD ACTIVITIES

The survey was conducted by Mr. Chad Champagne, an Asbestos Hazard and Emergency

Response Act (AHERA) accredited asbestos inspector (License No. 60-3112), and Mr. Andrew

Cassidy, an AHERA accredited asbestos inspector. A copy of Mr. Champagne’s and Mr.

Cassidy’s licenses and certifications are provided in Appendix E.

White Sands Missile Range - Building B23640 Repairs

Responsive ■ Resourceful ■ Reliable 3

The survey was conducted in general accordance with the sample collection protocols established in EPA regulation 40 CFR 763, the AHERA. A summary of the survey activities is provided in the following subsections.

3.1 Visual Assessment

Our survey activities began with a visual assessment of the interior and exterior of the building scheduled for renovation to establish homogeneous areas with suspect ACMs. A homogeneous area consists of building materials that appear similar throughout in terms of color, texture and date of application. The interior assessments were limited to accessible areas. The exterior assessments included exterior walls, roofing materials and windows. It should be noted that additional suspect but unsampled materials could be located in walls, voids or other concealed areas. Building materials identified as concrete, glass, wood, masonry, metal or rubber are not considered suspect ACM and, therefore, were not sampled.

Also, if information was available to indicate a material did not contain asbestos (i.e. MSDS), the material was not sampled.

3.2 Physical Assessment

A physical assessment of each homogeneous area with suspect ACM was conducted to assess the friability and condition of the materials. A friable material is defined by the EPA as a material which can be crumbled, pulverized or reduced to powder by hand pressure when dry. Friability was assessed by physically touching suspect materials.

3.3 Sample Collection

Based on the findings of the visual assessment, bulk samples of suspect ACM were collected in general accordance with AHERA sampling protocols. Random samples were collected for each suspect homogeneous material identified. Samples were placed in sealable containers and labeled with unique sample numbers using an indelible marker.

Eighty-two (82) bulk samples representing twenty-six (26) homogeneous areas of suspect ACM were collected from the building. Due to safety concerns, electrical components were not sampled as part of this survey. The suspect building materials collected during the survey and submitted for analysis are included in the laboratory analytical report located in Appendix D.

3.4 Sample Analysis

Suspect ACM samples were delivered under proper chain of custody to Cates Laboratories, a

NVLAP accredited (Lab No. 200569-0) laboratory for analysis by Polarized Light Microscopy

White Sands Missile Range - Building B23640 Repairs

Responsive ■ Resourceful ■ Reliable 4

(PLM) with dispersion staining techniques per EPA Method 600/R-93/116. The percentage of asbestos where applicable, was determined by microscopic visual estimation.

4.0 REGULATORY OVERVIEW

The asbestos NESHAP (40 CFR Part 61 Subpart M) regulates asbestos fiber emission and asbestos waste disposal practices. It also requires the identification and classification of existing building materials prior to Renovation or renovation activity. Under NESHAP, asbestos containing building materials are classified as either friable, Category I nonfriable or

Category II nonfriable ACM. Friable materials are those that, when dry, may be crumbled, pulverized or reduced to powder by hand pressure. Category I nonfriable ACM includes packing, gaskets, resilient floor coverings and asphalt roofing products containing more than

1% asbestos. Category II nonfriable ACM are any materials other than Category I materials that contain more than 1% asbestos.

Friable ACM, Category I and II nonfriable ACM which is in poor condition and has become friable or which will be subject to drilling, sanding, grinding, cutting, or abrading and which could be crushed or pulverized during anticipated renovation or Renovation activities are considered regulated ACM (RACM). RACM must be removed prior to renovation or

Renovation activities. The owner or operator must provide the TDSHS with written notification of planned removal activities at least 10 working days prior to the commencement of asbestos abatement activities. Removal of RACM must be conducted by an accredited asbestos contractor. In addition, third party air monitoring may be performed during the abatement.

The OSHA Asbestos standard for the construction industry (29 CFR 1926.1101) regulates workplace exposure to asbestos. The OSHA standard requires employee exposure to airborne asbestos fibers be maintained below 0.1 asbestos fibers per cubic centimeter of air

(0.1 f/cc).

The OSHA standard classifies construction and maintenance activities which could disturb

ACM and specifies work practices and precautions which employers must follow when engaging in each class of regulated work. States that administer their own federally approved state OSHA programs may require other precautions.

5.0 HAZARDOUS BUILDING MATERIALS

Materials such as Hg, CFCs, radioactive sources, batteries, and PCBs can be found in building components. These materials are considered environmental hazards and require special precautions if they will be removed in association with the Renovation to prevent their entry into the environment. On occasion, manufacturers will label the equipment regarding the presence or absence of a hazardous material. To assess for these hazards, some building

White Sands Missile Range - Building B23640 Repairs

Responsive ■ Resourceful ■ Reliable 5 components were partially disassembled to locate a manufacturer’s label. Quantified PCB, CFC, and Hg-containing building components, batteries, and smoke alarms with radioactive sources are listed by inspected area in Appendix C.

5.1 PCBs

PCBs range from clear, oily liquids to white or yellowish waxy solids, depending on the degree of chlorination. They are stable, thermoplastic and non-flammable materials that found chief use in insulation for electric cables and wires in the production of electric condensers and additives for extreme pressure lubricants. Light ballasts can contain about one ounce of the toxic substance. The transportation, disposal and spill clean-up of PCB-containing ballasts is regulated by the Toxic Substances Control Act (TSCA), which is found in 40 Code of Federal

Regulations (CFR) Part 261.

Terracon conducted a representative visual assessment of light fixtures, interior electrical components, and pad-mounted electrical transformers to characterize PCB content. Typically, ballasts manufactured prior to 1979 are presumed to contain PCBs unless clearly marked as containing “No PCBs”. Ballasts that do not contain a “No PCBs” label are presumed to be

PCB-containing. PCB-containing ballasts were not observed in light fixtures on the day of the assessment Twenty-nine (29) wall mounted radio frequency interference filters located in the mechanical room closet are presumed to contain PCBs.

5.2 Mercury (Hg)

Metallic mercury (Hg) is a silver-white liquid at room temperature. Elemental and inorganic mercury compounds are used in manufacturing scientific instruments, electric equipment, mercury vapor lamps and high intensity discharge (HID) lights. Hg is considered a hazardous material due to its ability to bio accumulate within the environment. Recycling Hg-containing components reduces the load of mercury entering the environment.

Interior building areas were observed to have Hg-containing lights. Four-hundred and forty-two (442) fluorescent light tubes that contain mercury were observed throughout the building.

Five (5) thermostat switches that may contain mercury were observed in the mechanical room, computer room, and room 107 during the assessment. Prior to renovation, these items should be removed intact, packaged to prevent breakage and transferred to an approved recycling facility that recovers mercury.

5.3 CFC

A chlorofluorocarbon (CFC) is an organic compound that consists of carbon, hydrogen, chlorine, and fluorine. Many CFCs have been widely used as refrigerants, propellants, and

White Sands Missile Range - Building B23640 Repairs

Responsive ■ Resourceful ■ Reliable 6 solvents. Chlorofluorocarbons are believed to cause depletion of the atmospheric ozone layer.

Interior and exterior building areas were observed to potentially contain equipment which may contain CFCs. One (1) chiller/air handler unit in the mechanical room and three (3) HVAC units on the exterior of the building including one (1) abandoned chiller unit were observed to potentially contain CFCs. Prior to renovation, CFCs (refrigerants) should be removed by a qualified recycling firm that recovers CFCs.

5.4 Batteries

Batteries containing nickel-cadmium and lead-acid can be found in emergency lightning, exit signs, and alarm systems. The nickel-cadmium and lead-acid in these batteries are considered to be toxic.

Three (3) exit signs were observed at the entrances to the building that could potentially contain batteries.

5.5 Radioactive Sources

There are several types of smoke detectors and fire alarms. Ionization chamber and photoelectric smoke detectors are the two most common types available commercially.

Ionization chamber smoke detectors contain a small amount of radioactive material encapsulated in a metal chamber. Typically, the radioactive material is a composite of americium-241.

One (1) smoke detector was observed in the building. Prior to Renovation, this unit should be removed intact, packaged, and sent to the manufacturer of the unit or an approved recycling facility.

6.0 FINDINGS AND RECOMMENDATIONS

Based on the results of the PLM laboratory analyses laboratory analyses for samples collected by Terracon, asbestos was confirmed in the following materials:

▪ Tank insulation (black)

▪ Wall texture (beige, semi-smooth) with drywall and joint compound

▪ Valve insulation (black)

▪ Air handler unit mastic (black)

▪ 9” x 9” vinyl floor tile (brown with white streaks) with mastic (black)

White Sands Missile Range - Building B23640 Repairs

Responsive ■ Resourceful ■ Reliable 7

The identified asbestos containing materials were considered nonfriable and in good condition on the day of the survey.

Terracon understands the building is scheduled for renovation. Therefore, the identified asbestos containing materials that will be potentially impacted by the planned renovation must be abated prior to potential disturbance.

The asbestos abatement must be performed by a certified asbestos contractor in accordance with the NESHAP. Third party air monitoring should be performed during the abatement.

It is important to note that state and federal regulations require a ten-working day notification prior to any renovation activities in a building that affords public access or occupancy, regardless of whether asbestos is present or not. These activities must be performed in accordance with the current EPA and OSHA guidelines.

PCBs, Batteries, and Radioactive Sources were identified in the building but are not expected to be impacted by the planned renovation.

Identified Hg-containing lights and thermostats should be removed intact, segregated, packaged and recycled in accordance with applicable state and federal regulations prior to renovation of the building.

The CFCs should be removed from all equipment that contain CFCs prior to potential disturbance.

7.0 GENERAL COMMENTS

This pre-renovation asbestos survey and environmental hazards assessment was conducted in a manner consistent with the level of care and skill ordinarily exercised by members of the profession currently practicing under similar conditions in the same locale. The results, findings, conclusions and recommendations expressed in this report are based on conditions observed during the on-site services conducted at the buildings. The information contained in this report is relevant to the date on which this survey was conducted and should not be relied upon to represent conditions at a later date. This report has been prepared on behalf of and exclusively for use by ICE and Dannenbaum JV for specific application to their project as discussed. This report is not a bidding document. Contractors or consultants reviewing this report must draw their own conclusions regarding further investigation or remediation deemed necessary. Terracon does not warrant the work of regulatory agencies, laboratories or other third parties supplying information which may have been used in the preparation of this report. No warranty, expressed or implied, is made.

APPENDIX A

Asbestos Containing Materials Summary

White Sands Missile Range

Building B23640 Repairs

Range Road 2 and Range Road 238

White Sands Missile Range, New Mexico

Sample No. Material Location (Area) Friable/

Nonfriable

Assessed

Condition

Estimated

Quantity

36, 37, 38 Tank Insulation (Black) Mechanical Room Nonfriable Good 20 square feet

51, 52, 53

Wall Texture (beige, Semi-

Smooth) with Drywall and Joint

Compound

Room 102, Room 106, Room 107, Room 108, Room 113, and Storage

Room

Nonfriable Good 4,290 square feet

60, 61, 62 Valve Insulation (Black) Mechanical Room Nonfriable Good 15 square feet

63, 64, 65 Air handler Unit Mastic (Black) Mechanical Room Nonfriable Good 1,540 square feet

80, 81, 82

9” x 9” Vinyl Floor Tile (Brown with White Streaks) with Mastic

(Black)

Room 102, Room 103, Room 106, Room 107, Room 108, Room 113, Lobby, Computer Lab Area, Storage Room, and

Corridors

Nonfriable Good 6,330 square feet

APPENDIX B

Identified Homogeneous Materials

White Sands Missile Range

Building B23640 Repairs

Range Road 2 and Range Road 238

Material Asbestos Containing Sample Numbers

2’ x 4’ Ceiling Tile (Off-White, Heavy Fissure) No 1, 2, 3

2’ x 4’ Ceiling Tile (White, Pinhole and Fissure) No 4, 5, 6

Ceiling Texture (White, Semi-

Smooth) on Concrete No 7, 8, 9

12” x 12” Wall Tile (White, Fissures) with Mastic (Brown) No 10, 11, 12

CMU Wall Texture (Beige) No 13, 14, 15, 16, 17

CMU Wall Texture (White) No 18, 19, 20

Duct Insulation (Beige) No 21, 22, 23

Chiller Insulation Mastic (White, Interior) No 24, 25, 26

Boiler Insulation (White) No 27, 28, 29

Chiller Insulation (White) No 30, 31, 32

Boiler Flue Insulation (White) No 33, 34, 35

Tank Insulation (Black) Yes 36, 37, 38

Thermal System Pipe Insulation

(Gray) White) associated with Hot

Water Lines (Straight Runs)

No 39, 40, 41

Thermal System Pipe Insulation

(White) associated with Hot

Water Line Fittings

No 42, 43, 44

Thermal System Pipe Insulation

(White) associated with Chill

Water Lines (Straight Runs)

No 45, 46, 47

Thermal System Pipe Insulation

(White) associated with Chill

Water Lines Fittings

No 48, 49, 50

Wall Texture (beige, Semi-

Smooth) with Drywall and Joint

Compound

Yes 51, 52, 53

APPENDIX B

Identified Homogeneous Materials

White Sands Missile Range

Building B23640 Repairs

Range Road 2 and Range Road 238

Responsive ■ Resourceful ■ Reliable 2

Material Asbestos Containing Sample Numbers

Duct Mastic (White) No 54, 55, 56

Duct Mastic (Black) No 57, 58, 59

Valve Insulation (Black) Yes 60, 61, 62

Air Handler Unit Mastic (Black) Yes 63, 64, 65

Exterior CUM Texture (Beige) No 66, 67, 68, 69, 70

Exterior Thermal System Pipe

Insulation Mastic (White) No 71, 72, 73

Exterior Chiller System Material

(White) associated with

Abandoned Chiller

No 74, 75, 76

Exterior HVAC Duct Seam Caulk

(White) No 77, 78, 79

9” x 9” Vinyl Floor Tile (Brown with White Streaks) with Mastic

(Black)

Yes 80, 81, 82

APPENDIX C

Hazardous Building Materials Quantity Estimates

White Sands Missile Range

Building B23640 Repairs

Range Road 2 and Range Road 238

Fort Worth, Texas

Responsive ■ Resourceful ■ Reliable

Hazardous Building Materials

Location

PCB-

containing units

Hg-containing lights Hg-Switches

CFC

units Batteries

Radioactive

Sources*

Mechanical Room 29 40 2 1 1 0

Function Spaces 0 402 3 3 2 1

Hg = Mercury PCB = polychlorinated biphenyl CFC= chlorofluorocarbon *smoke alarm component

APPENDIX D

ANALYTICAL LABORATORY ASBESTOS SUMMARY

PLM REPORT SUMMARY

Cates Laboratories NVLAP Lab No. 200569-0

1339 Motor Circle TDSHS License No. 30-0287

Dallas, Texas 75207 (214) 920-5006

Client: Terracon Lab Job No.: PLM-18352

Project: WSMR - Bldg. B23640 Set No.: 27271

Project No: 95187622 Report Date: 11/6/2018

Identification: Asbestos, Bulk Sample Analysis Sample Date: 10/29-30/2018

Test Method: Polarized Light Microscopy/Dispersion Staining (PLM/DS)

EPA Method 600/R-93/116 Page 1 of 8

On 11/2/2018, eighty-two (82) bulk samples were submitted by Mr. Chad Champagne of Terracon for asbestos analysis by PLM/DS.

Copies of the lab data sheets are attached; additional information may be found therein. The results are summarized below:

Lab

Sample No.

Client

Field I.D.

Sample Description/Location Asbestos Content

These samples were analyzed by layers. The overall percent asbestos for the sample is reported when relevant. The EPA considers a material to be asbestos containing only if it contains greater than one percent asbestos by Calibrated Visual Area Estimation (CVAE). EPA regulations also indicate that Regulated Asbestos Containing

Materials (RACM) – materials that are friable or may become friable – be further analyzed by point counting when the results indicate less than ten percent asbestos by

CVAE. CatesLab utilizes CVAE on a routine basis and does not include point counting unless specifically requested by the client. The results may not be reproduced except in full.

CL670308

2' X 4' Ceiling Tile (off-white, heavy fissure) - Room 107, Southeast

None Detected

CL670309

2' X 4' Ceiling Tile (off-white, heavy fissure) - Room 107, Center

CL670310

2' X 4' Ceiling Tile (off-white, heavy fissure) - Office 102, Center

CL670311

2' X 4' Ceiling Tile (white, pinholes & fissures) - Corridor adjacent to

Break Room

CL670312

2' X 4' Ceiling Tile (white, pinholes & fissures) - Lobby, Center

CL670313

2' X 4' Ceiling Tile (white, pinholes & fissures) - Room 113, East

CL670314

Ceiling Texture (white, semi-smooth) on Concrete - Men's Restroom, Center

CL670315

East

CL670316

East

CL670317

12" X 12" Wall Tile (white, fissures) w/Mastic (brown) - Storage Area, South Wall

None Detected - Wall Tile

None Detected - Brown Mastic

CL670318

12" X 12" Wall Tile (white, fissures) w/Mastic (brown) - Storage Area, South Wall

CL670319

12" X 12" Wall Tile (white, fissures) w/Mastic (brown) - Room 102, adjacent to Entry

CL670320

CMU Wall Texture (beige) - South Corridor, East Wall

None Detected - Filler/Texture

None Detected - CMU Block

CL670321

CMU Wall Texture (beige) - South Corridor, South Wall

CL670322

CMU Wall Texture (beige) - Mechanical Room, North Wall

None Detected - Mortar

Project No: 95187622 Report Date: 11/6/2018

Identification: Asbestos, Bulk Sample Analysis Sample Date: 10/29-30/2018

Test Method: Polarized Light Microscopy/Dispersion Staining (PLM/DS)

EPA Method 600/R-93/116 Page 2 of 8

On 11/2/2018, eighty-two (82) bulk samples were submitted by Mr. Chad Champagne of Terracon for asbestos analysis by PLM/DS.

Copies of the lab data sheets are attached; additional information may be found therein. The results are summarized below:

Client

These samples were analyzed by layers. The overall percent asbestos for the sample is reported when relevant. The EPA considers a material to be asbestos containing only if it contains greater than one percent asbestos by Calibrated Visual Area Estimation (CVAE). EPA regulations also indicate that Regulated Asbestos Containing

Materials (RACM) – materials that are friable or may become friable – be further analyzed by point counting when the results indicate less than ten percent asbestos by

CVAE. CatesLab utilizes CVAE on a routine basis and does not include point counting unless specifically requested by the client. The results may not be reproduced

CL670323

CMU Wall Texture (beige) - Mechanical Room, West Wall

CL670324

CMU Wall Texture (beige) - Mechanical Room, Boiler Room

CL670325

CMU Wall Texture (white) - Men's Restroom, adjacent to Entry

CL670326

CMU Wall Texture (white) - System B Room, East Wall

CL670327

CMU Wall Texture (white) - System B Room, East Wall

CL670328

Duct Insulation (beige) - Room 107, Center

None Detected - Beige Mastic

None Detected - Cotton Wrap

None Detected - Insulation

CL670329

Duct Insulation (beige) - North Corridor, Center

CL670330

Duct Insulation (beige) - Room 113, Center

CL670331

Chiller Insulation Mastic (white, interior) - Mechanical Room, Chiller

Interior

None Detected - White Mastic

None Detected - Wrap

CL670332

CL670333

Project No: 95187622 Report Date: 11/6/2018

Identification: Asbestos, Bulk Sample Analysis Sample Date: 10/29-30/2018

Test Method: Polarized Light Microscopy/Dispersion Staining (PLM/DS)

EPA Method 600/R-93/116 Page 3 of 8

On 11/2/2018, eighty-two (82) bulk samples were submitted by Mr. Chad Champagne of Terracon for asbestos analysis by PLM/DS.

Copies of the lab data sheets are attached; additional information may be found therein. The results are summarized below:

Client

These samples were analyzed by layers. The overall percent asbestos for the sample is reported when relevant. The EPA considers a material to be asbestos containing only if it contains greater than one percent asbestos by Calibrated Visual Area Estimation (CVAE). EPA regulations also indicate that Regulated Asbestos Containing

Materials (RACM) – materials that are friable or may become friable – be further analyzed by point counting when the results indicate less than ten percent asbestos by

CVAE. CatesLab utilizes CVAE on a routine basis and does not include point counting unless specifically requested by the client. The results may not be reproduced

CL670334

Boiler Insulation (white) - Boiler Room, Boiler Unit

CL670335

CL670336

CL670337

Chiller Insulation (white) - Mechanical Room, Lower Chiller Wall

None Detected - White Sealant

CL670338

Chiller Insulation (white) - Mechanical Room, Lower Chiller Wall

CL670339

Chiller Insulation (white) - Mechanical Room, Upper Chiller Wall

CL670340

Boiler Flue Insulation (white) - Boiler Room, Flue Pipe

CL670341

CL670342

CL670343

Tank Insulation (black) - Mechanical Room, Tank adjacent to Boiler

Room

None Detected - Grey Sealant

Project No: 95187622 Report Date: 11/6/2018

Identification: Asbestos, Bulk Sample Analysis Sample Date: 10/29-30/2018

Test Method: Polarized Light Microscopy/Dispersion Staining (PLM/DS)

EPA Method 600/R-93/116 Page 4 of 8

On 11/2/2018, eighty-two (82) bulk samples were submitted by Mr. Chad Champagne of Terracon for asbestos analysis by PLM/DS.

Copies of the lab data sheets are attached; additional information may be found therein. The results are summarized below:

Client

These samples were analyzed by layers. The overall percent asbestos for the sample is reported when relevant. The EPA considers a material to be asbestos containing only if it contains greater than one percent asbestos by Calibrated Visual Area Estimation (CVAE). EPA regulations also indicate that Regulated Asbestos Containing

Materials (RACM) – materials that are friable or may become friable – be further analyzed by point counting when the results indicate less than ten percent asbestos by

CVAE. CatesLab utilizes CVAE on a routine basis and does not include point counting unless specifically requested by the client. The results may not be reproduced

CL670344

5% Chrysotile - Insulation Wrap

CL670345

5% Chrysotile - Insulation Wrap

CL670346

Thermal System Pipe Insulation (white) associated w/Hot Water Lines

(straight runs) - Mechanical Room, Upper 1" Lines North of Boiler

CL670347

CL670348

CL670349

Thermal System Pipe Insulation (grey) associated w/Hot Water Line

Fittings - Mechanical Room, Upper 1" Lines North of Boiler

None Detected - Beige Sealant

CL670350

CL670351

None Detected - Beige Sealant

CL670352

Thermal System Pipe Insulation (white) associated w/Chill Water Lines

(straight runs) - Mechanical Room, Chill Water Lines adjacent to Chiller

CL670353

(straight runs) - Mechanical Room, Chill Water Lines adjacent to Chiller

Project No: 95187622 Report Date: 11/6/2018

Identification: Asbestos, Bulk Sample Analysis Sample Date: 10/29-30/2018

Test Method: Polarized Light Microscopy/Dispersion Staining (PLM/DS)

EPA Method 600/R-93/116 Page 5 of 8

On 11/2/2018, eighty-two (82) bulk samples were submitted by Mr. Chad Champagne of Terracon for asbestos analysis by PLM/DS.

Copies of the lab data sheets are attached; additional information may be found therein. The results are summarized below:

Client

These samples were analyzed by layers. The overall percent asbestos for the sample is reported when relevant. The EPA considers a material to be asbestos containing only if it contains greater than one percent asbestos by Calibrated Visual Area Estimation (CVAE). EPA regulations also indicate that Regulated Asbestos Containing

Materials (RACM) – materials that are friable or may become friable – be further analyzed by point counting when the results indicate less than ten percent asbestos by

CVAE. CatesLab utilizes CVAE on a routine basis and does not include point counting unless specifically requested by the client. The results may not be reproduced

CL670354

(straight runs) - Mechanical Room, Central Pipe Run

CL670355

Thermal System Pipe Insulation (grey) associated w/Chill Water Line

Fittings - Mechanical Room, Chill Water Lines adjacent to Chiller

CL670356

Fittings - Mechanical Room, Chill Water Lines adjacent to Chiller

CL670357

Fittings - Mechanical Room, Central Pipe Run

CL670358

Wall Texture (beige, semi-smooth) w/Drywall & Joint Compound - Break

Room, Southeast Corner

3% Chrysotile - Paint Texture

None Detected - Joint Tape

3% Chrysotile - Joint Compound

None Detected - Paper

None Detected - Wallboard Material

CL670359

Wall Texture (beige, semi-smooth) w/Drywall & Joint Compound - Break

Room, Southwest Corner

2% Chrysotile - Paint Texture

2% Chrysotile - Joint Compound

CL670360

Wall Texture (beige, semi-smooth) w/Drywall & Joint Compound - North

Corridor, adjacent to Room 106

2% Chrysotile - Paint Texture

2% Chrysotile - Joint Compound

CL670361

Duct Mastic (white) - Room 113, East

CL670362

Duct Mastic (white) - North Corridor, East

Project No: 95187622 Report Date: 11/6/2018

Identification: Asbestos, Bulk Sample Analysis Sample Date: 10/29-30/2018

Test Method: Polarized Light Microscopy/Dispersion Staining (PLM/DS)

EPA Method 600/R-93/116 Page 6 of 8

On 11/2/2018, eighty-two (82) bulk samples were submitted by Mr. Chad Champagne of Terracon for asbestos analysis by PLM/DS.

Copies of the lab data sheets are attached; additional information may be found therein. The results are summarized below:

Client

These samples were analyzed by layers. The overall percent asbestos for the sample is reported when relevant. The EPA considers a material to be asbestos containing only if it contains greater than one percent asbestos by Calibrated Visual Area Estimation (CVAE). EPA regulations also indicate that Regulated Asbestos Containing

Materials (RACM) – materials that are friable or may become friable – be further analyzed by point counting when the results indicate less than ten percent asbestos by

CVAE. CatesLab utilizes CVAE on a routine basis and does not include point counting unless specifically requested by the client. The results may not be reproduced

CL670363

Duct Mastic (white) - Break Room, Center

CL670364

Duct Mastic (black) - North Corridor, Center

CL670365

Duct Mastic (black) - North Corridor, Center

CL670366

Duct Mastic (black) - Computer Lab, West

CL670367

Valve Insulation (black) - Mechanical Room, Center

5% Chrysotile

CL670368

CL670369

CL670370

Chiller Unit Mastic (black) - Mechanical Room, Lower Chiller Wall

CL670371

CL670372

7% Chrysotile

CL670373

Exterior CMU Texture (beige) - Exterior Wall, Southwest Corner

CL670374

Exterior CMU Texture (beige) - Exterior Wall, South Wall

CL670375

Exterior CMU Texture (beige) - Exterior Wall, South Wall

CL670376

Exterior CMU Texture (beige) - Exterior Wall, HVAC Pad Area

CL670377

Exterior CMU Texture (beige) - Exterior Wall, HVAC Pad Area

CL670378

Exterior Thermal System Pipe Insulation Mastic (white) - Exterior HVAC

Units

CL670379

CL670380

Project No: 95187622 Report Date: 11/6/2018

Identification: Asbestos, Bulk Sample Analysis Sample Date: 10/29-30/2018

Test Method: Polarized Light Microscopy/Dispersion Staining (PLM/DS)

EPA Method 600/R-93/116 Page 7 of 8

On 11/2/2018, eighty-two (82) bulk samples were submitted by Mr. Chad Champagne of Terracon for asbestos analysis by PLM/DS.

Copies of the lab data sheets are attached; additional information may be found therein. The results are summarized below:

Client

These samples were analyzed by layers. The overall percent asbestos for the sample is reported when relevant. The EPA considers a material to be asbestos containing only if it contains greater than one percent asbestos by Calibrated Visual Area Estimation (CVAE). EPA regulations also indicate that Regulated Asbestos Containing

Materials (RACM) – materials that are friable or may become friable – be further analyzed by point counting when the results indicate less than ten percent asbestos by

CVAE. CatesLab utilizes CVAE on a routine basis and does not include point counting unless specifically requested by the client. The results may not be reproduced

CL670381

Exterior Chiller System Material (white) associated w/Abandoned Chiller

- Exterior Abandoned Chiller Unit

None Detected - Chiller Material

CL670382

CL670383

CL670384

Exterior HVAC Duct Seam Caulk (white) - Southwest Exterior HVAC

Duct

CL670385

CL670386

CL670387

9" X 9" Vinyl Floor Tile (brown w/white streaks) w/Mastic (black) - East

Entryway

3% Chrysotile - Floor Tile

None Detected - Black Mastic

CL670388

9" X 9" Vinyl Floor Tile (brown w/white streaks) w/Mastic (black) -

Room 107, East

15% Chrysotile - Floor Tile

10% Chrysotile - Black Mastic

CL670389

9" X 9" Vinyl Floor Tile (brown w/white streaks) w/Mastic (black) - East

Corridor, Center

3% Chrysotile - Floor Tile

None Detected - Yellow Mastic

None Detected - Leveling Compound

None Detected - Black Mastic

Project No: 95187622 Report Date: 11/6/2018

Identification: Asbestos, Bulk Sample Analysis Sample Date: 10/29-30/2018

Test Method: Polarized Light Microscopy/Dispersion Staining (PLM/DS)

EPA Method 600/R-93/116 Page 8 of 8

On 11/2/2018, eighty-two (82) bulk samples were submitted by Mr. Chad Champagne of Terracon for asbestos analysis by PLM/DS.

Copies of the lab data sheets are attached; additional information may be found therein.

STATEMENT OF LABORATORY ACCREDITATION

The samples were analyzed in general accordance with the procedures outlined in the Method for the

Determination of Asbestos in Bulk Building Materials, EPA/600/R-93/116 or the U.S. Environmental

Protection Agency method, under AHERA (EPA 600/M4-82-020), for the analysis of asbestos in building materials by polarized light microscopy. The results of each bulk sample relate only to the material tested and the results shall not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government.

Specific questions concerning bulk sample results shall be directed to the Laboratory Director.

Analyst:

Benjamin Deans

Laboratory Director: John R. Cates, P.G.

Approved Signatory:

NVLAP LAB CODE 200569-0

Bulk Asbestos Analysis Sheet

Cates Laboratories EPA Method 600/R-93/116 NVLAP Lab No. 200569-0

Client: Terracon Lab Proj #: PLM-18352

Project: WSMR - Bldg. B23640 Set #: 27271

Project #: 95187622 Sample #: CL670308

Field ID #: 1 Page 1 of 1

Sample Description: 2' X 4' Ceiling Tile (off-white, heavy fissure) - Room 107, Southeast

Comments: Analyst: Benjamin Deans Date Analyzed: 11/5/2018

Lab Job #: PLM-18352 Sample #: CL670308 kkkx Layer 1 Ceiling Tile Covering Stereoscopic Examination 1 670308 Color Texture Homogeneous? % Fibrous % Asbestos % of Sample -1 White Tough Yes ND ND 10 PLM Examination:

Color/ Parallel Perpendicular Extinction Sign of Components % +/- Morphology Pleochroism Ref. Index Ref. Index Biref Angle Elongation Vinyl Binders 100 Non-fibrous 1 6

Prep/treatment: mechanical separation Asbestos Content: None Detected

Layer 2 Ceiling Tile Stereoscopic Examination 2 670308 Color Texture Homogeneous? % Fibrous % Asbestos % of Sample -1 Yellow Fibrous Yes 90 ND 90 PLM Examination:

Color/ Parallel Perpendicular Extinction Sign of Components % +/- Morphology Pleochroism Ref. Index Ref. Index Biref Angle Elongation Mineral Wool Fibers 90 Rods 0 2 6 Resin Binders 10 Non-fibrous 2 6

Prep/treatment: mechanical separation Asbestos Content: None Detected zzz

Project #: 95187622 Sample #: CL670309

Field ID #: 2 Page 1 of 1

Sample Description: 2' X 4' Ceiling Tile (off-white, heavy fissure) - Room 107, Center

Comments: Analyst: Benjamin Deans Date Analyzed: 11/5/2018

Lab Job #: PLM-18352 Sample #: CL670309 kx Layer 1 Ceiling Tile Covering Stereoscopic Examination 1 670309 Color Texture Homogeneous? % Fibrous % Asbestos % of Sample -1 White Tough Yes ND ND 10 PLM Examination:

Color/ Parallel Perpendicular Extinction Sign of Components % +/- Morphology Pleochroism Ref. Index Ref. Index Biref Angle Elongation Vinyl Binders 100 Non-fibrous 1 6

Prep/treatment: mechanical separation Asbestos Content: None Detected

Layer 2 Ceiling Tile Stereoscopic Examination 2 670309 Color Texture Homogeneous? % Fibrous % Asbestos % of Sample -1 Yellow Fibrous Yes 90 ND 90 PLM Examination:

Color/ Parallel Perpendicular Extinction Sign of Components % +/- Morphology Pleochroism Ref. Index Ref. Index Biref Angle Elongation Mineral Wool Fibers 90 Rods 0 2 6 Resin Binders 10 Non-fibrous 2 6

Prep/treatment: mechanical separation Asbestos Content: None Detected

Project #: 95187622 Sample #: CL670310

Field ID #: 3 Page 1 of 1

Sample Description: 2' X 4' Ceiling Tile (off-white, heavy fissure) - Office 102, Center

Comments: Analyst: Benjamin Deans Date Analyzed: 11/5/2018

Lab Job #: PLM-18352 Sample #: CL670310 kx Layer 1 Ceiling Tile Covering Stereoscopic Examination 1 670310 Color Texture Homogeneous? % Fibrous % Asbestos % of Sample -1 White Tough Yes ND ND 10 PLM Examination:

Color/ Parallel Perpendicular Extinction Sign of Components % +/- Morphology Pleochroism Ref. Index Ref. Index Biref Angle Elongation Vinyl Binders 100 Non-fibrous 1 6

Prep/treatment: mechanical separation Asbestos Content: None Detected

Layer 2 Ceiling Tile Stereoscopic Examination 2 670310 Color Texture Homogeneous? % Fibrous % Asbestos % of Sample -1 Yellow Fibrous Yes 90 ND 90 PLM Examination:

Color/ Parallel Perpendicular Extinction Sign of Components % +/- Morphology Pleochroism Ref. Index Ref. Index Biref Angle Elongation Mineral Wool Fibers 90 Rods 0 2 6 Resin Binders 10 Non-fibrous 2 6

Prep/treatment: mechanical separation Asbestos Content: None Detected

Project #: 95187622 Sample #: CL670311

Field ID #: 4 Page 1 of 1

Sample Description: 2' X 4' Ceiling Tile (white, pinholes & fissures) - Corridor adjacent to Break Room

Comments: Analyst: Benjamin Deans Date Analyzed: 11/5/2018

Lab Job #: PLM-18352 Sample #: CL670311 kx Layer 1 Ceiling Tile Stereoscopic Examination 1 670311 Color Texture Homogeneous? % Fibrous % Asbestos % of Sample -1 Beige w/wht pt Fibrous Yes 60 ND 100 PLM Examination:

Color/ Parallel Perpendicular Extinction Sign of Components % +/- Morphology Pleochroism Ref. Index Ref. Index Biref Angle Elongation Cellulose Fibers 30 ribbons high 1 6 Mineral Wool Fibers 30 Rods 0 1 6 Perlite 30 Glass Foam 0 1 6 Binders / Paint 10 Non-fibrous 1 6

Prep/treatment: mechanical separation Asbestos Content: None Detected

Project #: 95187622 Sample #: CL670312

Field ID #: 5 Page 1 of 1

Sample Description: 2' X 4' Ceiling Tile (white, pinholes & fissures) - Lobby, Center

Comments: Analyst: Benjamin Deans Date Analyzed: 11/5/2018

Lab Job #: PLM-18352 Sample #: CL670312 kx Layer 1 Ceiling Tile Stereoscopic Examination 1 670312 Color Texture Homogeneous? % Fibrous % Asbestos % of Sample -1 Beige w/wht pt Fibrous Yes 60 ND 100 PLM Examination:

Color/ Parallel Perpendicular Extinction Sign of Components % +/- Morphology Pleochroism Ref. Index Ref. Index Biref Angle Elongation Cellulose Fibers 30 ribbons high 1 6 Mineral Wool Fibers 30 Rods 0 1 6 Perlite 30 Glass Foam 0 1 6 Binders / Paint 10 Non-fibrous 1 6

Prep/treatment: mechanical separation Asbestos Content: None Detected

Project #: 95187622 Sample #: CL670313

Field ID #: 6 Page 1 of 1

Sample Description: 2' X 4' Ceiling Tile (white, pinholes & fissures) - Room 113, East

Comments: Analyst: Benjamin Deans Date Analyzed: 11/5/2018

Lab Job #: PLM-18352 Sample #: CL670313 kx Layer 1 Ceiling Tile Stereoscopic Examination 1 670313 Color Texture Homogeneous? % Fibrous % Asbestos % of Sample -1 Beige w/wht pt Fibrous Yes 60 ND 100 PLM Examination:

Color/ Parallel Perpendicular Extinction Sign of Components % +/- Morphology Pleochroism Ref. Index Ref. Index Biref Angle Elongation Cellulose Fibers 30 ribbons high 1 6 Mineral Wool Fibers 30 Rods 0 1 6 Perlite 30 Glass Foam 0 1 6 Binders / Paint 10 Non-fibrous 1 6

Prep/treatment: mechanical separation Asbestos Content: None Detected

Project #: 95187622 Sample #: CL670314

Field ID #: 7 Page 1 of 1

Sample Description: Ceiling Texture (white, semi-smooth) on Concrete - Men's Restroom, Center

Comments: Analyst: Benjamin Deans Date Analyzed: 11/5/2018

Lab Job #: PLM-18352 Sample #: CL670314 kx Layer 1 Paint Texture Stereoscopic Examination 1 670314 Color Texture Homogeneous? % Fibrous % Asbestos % of Sample -1 White Hard Yes ND ND 100 PLM Examination:

Color/ Parallel Perpendicular Extinction Sign of Components % +/- Morphology Pleochroism Ref. Index Ref. Index Biref Angle Elongation Paint 100 Non-fibrous 1 6

Prep/treatment: heat / melt Asbestos Content: None Detected

Project #: 95187622 Sample #: CL670315

Field ID #: 8 Page 1 of 1

Sample Description: Ceiling Texture (white, semi-smooth) on Concrete - Men's Restroom, East

Comments: Analyst: Benjamin Deans Date Analyzed: 11/5/2018

Lab Job #: PLM-18352 Sample #: CL670315 kx Layer 1 Paint Texture Stereoscopic Examination 1 670315 Color Texture Homogeneous? % Fibrous % Asbestos % of Sample -1 White Hard Yes ND ND 100 PLM Examination:

Color/ Parallel Perpendicular Extinction Sign of Components % +/- Morphology Pleochroism Ref. Index Ref. Index Biref Angle Elongation Paint 100 Non-fibrous 1 6

Prep/treatment: heat / melt Asbestos Content: None Detected

Project #: 95187622 Sample #: CL670316

Field ID #: 9 Page 1 of 1

Sample Description: Ceiling Texture (white, semi-smooth) on Concrete - Men's Restroom, East

Comments: Analyst: Benjamin Deans Date Analyzed: 11/5/2018

Lab Job #: PLM-18352 Sample #: CL670316 kx Layer 1 Paint Texture Stereoscopic Examination 1 670316 Color Texture Homogeneous? % Fibrous % Asbestos % of Sample -1 White Hard Yes ND ND 100 PLM Examination:

Color/ Parallel Perpendicular Extinction Sign of Components % +/- Morphology Pleochroism Ref. Index Ref. Index Biref Angle Elongation Paint 100 Non-fibrous 1 6

Prep/treatment: heat / melt Asbestos Content: None Detected

Project #: 95187622 Sample #: CL670317

Field ID #: 10 Page 1 of 1

Sample Description: 12" X 12" Wall Tile (white, fissures) w/Mastic (brown) - Storage Area, South Wall

Comments: Analyst: Benjamin Deans Date Analyzed: 11/5/2018

Lab Job #: PLM-18352 Sample #: CL670317 kx Layer 1 Wall Tile Stereoscopic Examination 1 670317 Color Texture Homogeneous? % Fibrous % Asbestos % of Sample -1 White w/wht pt Fibrous Yes 85 ND 90 PLM Examination:

Color/ Parallel Perpendicular Extinction Sign of Components % +/- Morphology Pleochroism Ref. Index Ref. Index Biref Angle Elongation Mineral Wool Fibers 85 Rods 0 1 6 Binders / Paint 15 Non-fibrous 1 6

Prep/treatment: mechanical separation Asbestos Content: None Detected

Layer 2 Brown Mastic Stereoscopic Examination 2 670317 Color Texture Homogeneous? % Fibrous % Asbestos % of Sample -1 Brown Hard Yes 10 PLM Examination:

Color/ Parallel Perpendicular Extinction Sign of Components % +/- Morphology Pleochroism Ref. Index Ref. Index Biref Angle Elongation Glue Binders 100 Non-fibrous 2 6

Prep/treatment: heat / melt Asbestos Content: None Detected

Project #: 95187622 Sample #: CL670318

Field ID #: 11 Page 1 of 1

Sample Description: 12" X 12" Wall Tile (white, fissures) w/Mastic (brown) - Storage Area, South Wall

Comments: Analyst: Benjamin Deans Date Analyzed: 11/5/2018

Lab Job #: PLM-18352 Sample #: CL670318 kx Layer 1 Wall Tile Stereoscopic Examination 1 670318 Color Texture Homogeneous? % Fibrous % Asbestos % of Sample -1 White w/wht pt Fibrous Yes 85 ND 90 PLM Examination:

Color/ Parallel Perpendicular Extinction Sign of Components % +/- Morphology Pleochroism Ref. Index Ref. Index Biref Angle Elongation Mineral Wool Fibers 85 Rods 0 1 6 Binders / Paint 15 Non-fibrous 1 6

Prep/treatment: mechanical separation Asbestos Content: None Detected

Layer 2 Brown Mastic Stereoscopic Examination 2 670318 Color Texture Homogeneous? % Fibrous % Asbestos % of Sample -1 Brown Hard Yes 10 PLM Examination:

Color/ Parallel Perpendicular Extinction Sign of Components % +/- Morphology Pleochroism Ref. Index Ref. Index Biref Angle Elongation Glue Binders 100 Non-fibrous 2 6

Prep/treatment: heat / melt Asbestos Content: None Detected

Project #: 95187622 Sample #: CL670319

Field ID #: 12 Page 1 of 1

Sample Description: 12" X 12" Wall Tile (white, fissures) w/Mastic (brown) - Room 102, adjacent to Entry

Comments: Analyst: Benjamin Deans Date Analyzed: 11/5/2018

Lab Job #: PLM-18352 Sample #: CL670319 kx Layer 1 Wall Tile Stereoscopic Examination 1 670319 Color Texture Homogeneous? % Fibrous % Asbestos % of Sample -1 White w/wht pt Fibrous Yes 85 ND 90 PLM Examination:

Color/ Parallel Perpendicular Extinction Sign of Components % +/- Morphology Pleochroism Ref. Index Ref. Index Biref Angle Elongation Mineral Wool Fibers 85 Rods 0 1 6 Binders / Paint 15 Non-fibrous 1 6

Prep/treatment: mechanical separation Asbestos Content: None Detected

Layer 2 Brown Mastic Stereoscopic Examination 2 670319 Color Texture Homogeneous? % Fibrous % Asbestos % of Sample -1 Brown Hard Yes 10 PLM Examination:

Color/ Parallel Perpendicular Extinction Sign of Components % +/- Morphology Pleochroism Ref. Index Ref. Index Biref Angle Elongation Glue Binders 100 Non-fibrous 2 6

Prep/treatment: heat / melt Asbestos Content: None Detected

Project #: 95187622 Sample #: CL670320

Field ID #: 13 Page 1 of 1

Sample Description: CMU Wall Texture (beige) - South Corridor, East Wall

Comments: Analyst: Benjamin Deans Date Analyzed: 11/5/2018

Lab Job #: PLM-18352 Sample #: CL670320 kx Layer 1 Filler/Texture Stereoscopic Examination 1 670320 Color Texture Homogeneous? % Fibrous % Asbestos % of Sample -1 Beige Blocky Yes ND ND 15 PLM Examination:

Color/ Parallel Perpendicular Extinction Sign of Components % +/- Morphology Pleochroism Ref. Index Ref. Index Biref Angle Elongation Aggregate/Binders/Paint 100 Non-fibrous 1 6

Prep/treatment: solvent dissolution Asbestos Content: None Detected

Layer 2 CMU Block Stereoscopic Examination 2 670320 Color Texture Homogeneous? % Fibrous % Asbestos % of Sample -1 Grey Blocky/Hard Yes ND ND 85 PLM Examination:

Color/ Parallel Perpendicular Extinction Sign of Components % +/- Morphology Pleochroism Ref. Index Ref. Index Biref Angle Elongation Aggregate/Binders 100 Non-fibrous 2 6

Prep/treatment: mechanical separation Asbestos Content: None Detected

Project #: 95187622 Sample #: CL670321

Field ID #: 14 Page 1 of 1

Sample Description: CMU Wall Texture (beige) - South Corridor, South Wall

Comments: Analyst: Benjamin Deans Date Analyzed: 11/5/2018

Lab Job #: PLM-18352 Sample #: CL670321 kx Layer 1 Filler/Texture Stereoscopic Examination 1 670321 Color Texture Homogeneous? % Fibrous % Asbestos % of Sample -1 Beige Blocky Yes ND ND 15 PLM Examination:

Color/ Parallel Perpendicular Extinction Sign of Components % +/- Morphology Pleochroism Ref. Index Ref. Index Biref Angle Elongation Aggregate/Binders/Paint 100 Non-fibrous 1 6

Prep/treatment: solvent dissolution Asbestos Content: None Detected

Layer 2 CMU Block Stereoscopic Examination 2 670321 Color Texture Homogeneous? % Fibrous % Asbestos % of Sample -1 Grey Blocky/Hard Yes ND ND 85 PLM Examination:

Color/ Parallel Perpendicular Extinction Sign of Components % +/- Morphology Pleochroism Ref. Index Ref. Index Biref Angle Elongation Aggregate/Binders 100 Non-fibrous 2 6

Prep/treatment: mechanical separation Asbestos Content: None Detected

Project #: 95187622 Sample #: CL670322

Field ID #: 15 Page 1 of 1

Sample Description: CMU Wall Texture (beige) - Mechanical Room, North Wall

Comments: Analyst: Benjamin Deans Date Analyzed: 11/5/2018

Lab Job #: PLM-18352 Sample #: CL670322 kx Layer 1 Filler/Texture Stereoscopic Examination 1 670322 Color Texture Homogeneous?