VOLUME 2- TEMF BUILDING
TACTICAL EQUIPMENT MAINTENANCE FACILITIES
PN: 088380
FORT HOOD, TEXAS
FORT WORTH DISTRICT
US ARMY CORPS
OF ENGINEERS
FO
R
T H O
O D
, TEXAS
VO
LU
M
E 2 - TEM
F BU
ILD
IN
G
TAC
TIC
AL EQ
U
IPM
EN
T M
AIN
TEN
AN
C
E FAC
ILITIES PN
: 088380
VO
LU
M E
TE
M F
BU
IL
D
IN
G
P
N : 0
FO
R T
H O
O D
, T
EX
AS
SOLICITATION NO. W9126G18R1986
DATED: JUNE 2018
THIS PROJECT WAS DESIGNED BY THE FORT WORT DISTRICT OF THE U.S. ARMY CORPS OF ENGINEERS.
THE INITIALS OR SIGNATURES AND REGISTRATION DESIGNATIONS OF INDIVIDUALS APPEAR ON THESE PROJECT DOCUMENTS WITHIN THE SCOPE OF THEIR EMPLOYMENT AS REQUIRED BY ER 1110-1-8152.
MARK L. BLACK, P.E.
CONTR. NO.
SHEET
NUMBER
1 2 3 4 5
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
U .S
. A R
M Y
EN
G
IN
EE
R D
IS
TR
IC
T, C
O R
PS
O
F
EN
G
IN
EE
R
S
FO
R T
W O
R
TH
, T
EX
AS
C
H
EC
KE
D
B Y:
US Army Corps of Engineers ®
D
C
B
A
PL
O
T
SC
AL
E:
PL
O
T D
AT
E:
SY
M
D
ES
C R
IP
TI
O N
D
AT
E
EN
G
IN
EE
R
IN
G
C O
N
ST
R U
C
TI
O N
D
IV
IS
IO
N
EN
G
IN
EE
R
IN
G
B
RA
NC
H
AP
R
R
6 7 8 9
E
F
7/
/2
3:
:1
PM
F O
RT
H O
O D, T
EX
A S
TA
CT
IC
AL
E
Q
UI
P M
EN
T M
AI
N T
EN
A N
CE
F
AC
IL
IT
IE
S
PN
: 0
3 8
TE
M
F
BU
IL
DI
NG
JU
N
E
W
G
R
Fort Worth District
P.
C
IS
N
ER
O
S- C
AM
AC
H O
P.
C
IS
N
ER
O
S- C
AM
AC
H O
G
IL
BE
R
T J.
V
AL
LA
, P
.E
C H
IE
F, M
EC
H
AN
IC
AL
S
EC
TI
O
N
G-002
IN
D E
X O
F
DR
A W
IN
G S
M . V
AV
R
A, P
.E
STRUCTURAL
1S-001 GENERAL STRUCTURAL NOTES AND DETAILS I
1S-002 GENERAL STRUCTURAL NOTES AND DETAILS II
1S-003 GENERAL STRUCTURAL NOTES AND DETAILS III
1S-004 GENERAL STRUCTURAL NOTES AND DETAILS IV
1S-005 GENERAL STRUCTURAL NOTES AND DETAILS V
1S-006 GENERAL STRUCTURAL NOTES AND DETAILS VI
1S-007 GENERAL STRUCTURAL NOTES AND DETAILS VII
1S-008 GENERAL STRUCTURAL NOTES AND DETAILS VIII
1S-100 OVERALL FOUNDATION PLAN
1S-101 DRILLED PIER PLAN
1S-102 FOUNDATION PLAN AREA A
1S-103 FOUNDATION PLAN AREA B
1S-104 FOUNDATION PLAN AREA C
1S-111 2ND FLOOR FRAMING PLAN
1S-201 MAINTENANCE BAY ELEVATION
1S-202 ADMIN AREA ELEVATION
1S-203 LOW ROOF AREA ELEVATION
1S-301 FOUNDATION SECTIONS I
1S-302 FOUNDATION SECTIONS II
1S-303 FOUNDATION SECTIONS III
1S-304 FOUNDATION SECTIONS IV
1S-311 FRAMING SECTIONS I
1S-312 FRAMING SECTIONS II
1S-401 ENLARGED PLANS I - ELEVATOR PIT
1S-402 ENLARGED PLANS II - MAINTENANCE PIT
1S-403 ENLARGED PLANS III - MAINTENANCE PIT
1S-501 FOUNDATION DETAILS I
1S-502 FOUNDATION DETAILS II
1S-600 WIND COMPONENTS AND CLADDING
1S-601 GRADE BEAM SCHEDULE
1S-700 OIL/WATER SEPARATOR I
1S-701 OIL/WATER SEPARATOR II
ARCHITECTURE
1A-001 GENERAL NOTES & ABBREVIATIONS
1A-002 LIFE SAFETY CRITERIA
1A-003 LIFE SAFETY PLAN FIRST FLOOR AREA A
1A-004 LIFE SAFETY PLAN FIRST FLOOR AREA B
1A-005 LIFE SAFETY PLAN FIRST FLOOR AREA C
1A-006 LIFE SAFETY PLAN SECOND FLOOR
1A-100 COMPOSITE FLOOR PLANS
1A-101 FIRST FLOOR PARTIAL PLAN AREA A
1A-102 FIRST FLOOR PARTIAL PLAN AREA B
1A-103 FIRST FLOOR PARTIAL PLAN AREA C
1A-104 SECOND FLOOR PATRIAL PLAN AREA A
1A-105 SECOND FLOOR PARTIAL PLAN AREA B
1A-106 ROOF PLAN
1A-107 FIRST FLOOR REFLECTED CEILING PARTIAL PLAN AREA A
1A-108 FIRST FLOOR REFLECTED CEILING PARTIAL PLAN AREA B
1A-109 FIRST FLOOR REFLECTED CEILING PARTIAL PLAN AREA C
1A-110 SECOND FLOOR REFLECTED CEILING PARTIAL PLAN AREA B
1A-111 ENLARGED PLANS
1A-201 BUILDING ELEVATIONS
1A-301 BUILDING CROSS SECTION
1A-302 BUILDING LONGITUDINAL SECTION
1A-310 WALL SECTIONS
1A-311 WALL SECTIONS II
1A-312 WALL SECTIONS III
1A-313 WALL SECTIONS IV
1A-401 RESTROOM ELEVATIONS
1A-402 RESTROOM ELEVATIONS II
1A-403 MILLWORK DETAILS
1A-404 ENLARGED STAIR PLANS AND SECTIONS
1A-405 STAIR SECTIONS AND DETAILS
1A-501 PLAN DETAILS
1A-502 PLAN DETAILS II
1A-503 PLAN DETAILS III
INTERIORS
1I101 FIRST FLR FURNITURE PLAN
1I102 FIRST FLR FURNITURE PARTIAL PLAN AREA B
1I103 FIRST FLR FURNITURE PARTIAL PLAN AREA C
1I104 SECOND FLR FURNITURE PLAN
1I105 SECOND FLR FURNITURE PARTIAL PLAN AREA B
1I106 FIRST FLR SIGNAGE FLOOR PLAN
1I107 FIRST FLR SIGNAGE PARTIAL PLAN AREA B
1I108 FIRST FLR SIGNAGE PARTIAL PLAN AREA C
1I109 SECOND FLR SIGNAGE PLAN
1I110 SECOND FLR SIGNAGE PARTIAL PLAN AREA B
1I501 SIGNAGE DETAILS
1I601 SIGNAGE SCHEDULE
1I602 FINISH SCHEDULE
PLUMBING
1P-001 PLUMBING LEGEND AND GENERAL NOTES
1P-101 FIRST FLOOR OVERALL PLUMBING FLOOR PLAN
1P-102 SECOND FLOOR OVERALL PLUMBING FLOOR PLAN
1P-901 RISER DIAGRAM - DOMESTIC HOT & COLD WATER
1P-902 DCW AND DHW ISOMETRIC ENLARGED RESTROOM
1P-903 RISER DIAGRAM - WASTE AND VENT
1P-904 WASTE AND VENT ISOMETRIC ENLARGED RESTROOM
1PL101 FIRST FLOOR WASTE AND VENT - A
1PL102 FIRST FLOOR WASTE AND VENT - B
1PL103 FIRST FLOOR WASTE AND VENT - C
1PL104 SECOND FLOOR WASTE AND VENT - B
1PL105 FIRST FLOOR DOMESTIC WATER - A
1PL106 FIRST FLOOR DOMESTIC WATER - B
1PL107 FIRST FLOOR DOMESTIC WATER - C
VOLUME 2 - TEMF BUILDING
GENERAL
G-001 COVER SHEET
G-002 INDEX OF DRAWINGS
FIRE ALARM
1FA001 FIRE ALARM LEGEND
1FA101 FIRST FLOOR - AREA A FIRE ALARM AND MASS NOTIFICATION PLAN
1FA102 FIRST FLOOR - AREA B FIRE ALARM AND MASS NOTIFICATION PLAN
1FA103 FIRST FLOOR - AREA C FIRE ALARM AND MASS NOTIFICATION PLAN
1FA104 SECOND FLOOR - FIRE ALARM AND MASS NOTIFICATION PLAN
1FA501 FIRE ALARM MATRIX
1FA502 LOC DETAILS
1FA503 FIRE ALARM REMOTE ANNUNCIATOR DETAIL
1FA601 FIRE ALARM RISER & ANTENNA DETAIL
MECHANICAL
1M-001 MECHANICAL GENERAL NOTES AND LEGENDS
1M-101 FIRST FLOOR OVERALL MECH FLOOR PLAN - A
1M-102 FIRST FLOOR OVERALL MECH FLOOR PLAN - B
1M-103 FIRST FLOOR OVERALL MECH FLOOR PLAN - C
1M-104 SECOND FLOOR OVERALL MECHANICAL PLAN - B
1M-201 MAINT. BAY ELEVATIONS
1M-202 MAINT. COOR. WEST ELEVATIONS
1M-203 MAINT. COOR. EAST ELEVATIONS
1M-901 OVERALL MECHANICAL ISOMETRIC
1MH101 FIRST FLOOR HVAC PLAN - A
1MH102 FIRST FLOOR HVAC PLAN - B
1MH103 FIRST FLOOR HVAC PLAN - C
1MH104 SECOND FLOOR HVAC PLAN - B
1MH401 ENLARGED MECHANICAL ROOM HVAC PLAN
1MH402 ENLARGED SECOND FLOOR DUCT CHASE PLAN
1MH901 HVAC ISOMETRIC VIEW
1MH902 ENLARGED MECHANICAL ROOM HVAC ISOMETRIC
1MP101 FIRST FLOOR MECHANICAL PLUMBING PLAN - A
1MP102 FIRST FLOOR MECHANICAL PLUMBING PLAN - B
1MP103 FIRST FLOOR MECHANICAL PLUMBING PLAN - C
1MP104 SECOND FLOOR MECHANICAL PLUMBING PLAN - B
1MP401 ENLARGED MECHANICAL ROOM MECHANICAL PLUMBING PLAN
1MP901 MECHANICAL PLUMBING ISOMETRIC VIEW
1MP902 ENLARGED MECHANICAL ROOM MECHANICAL PLUMBING ISOMETRIC
1M-501 CHILLED WATER SCHEMATIC
1M-502 HEATING WATER SCHEMATIC
1M-503 CHILLED WATER NODE DIAGRAM
1M-504 HEATING WATER NODE DIAGRAM
1M-505 MECHANICAL DETAILS
1M-506 MECHANICAL DETAILS
1M-507 MECHANICAL DETAILS
1M-508 MECHANICAL DETAILS
1M-509 MECHANICAL DETAILS
1M-601 MECHANICAL SCHEDULES
1M-602 MECHANICAL SCHEDULES
1MI001 CONTROLS LEGEND
1MI002 POINTS LIST INSTRUCTIONS
1MI801 AHU-1 - CONTROL SCHEMATIC
1MI802 AHU-1 - POINT SCHEDULE
1MI803 AHU-1 - SEQUENCE OF OPERATION
1MI804 DOAS-1 - CONTROL SCHEMATIC
1MI805 DOAS-1 - POINT SCHEDULE
1MI806 DOAS-1 - SEQUENCE OF OPERATION
1MI807 TYPICAL MAU - CONTROL SCHEMATIC
1MI808 TYPICAL MAU - POINT SCHEDULE
1MI809 TYPICAL MAU - SEQUENCE OF OPERATION
1MI813 VAV CONTROL SCHEMATIC
1MI814 VAV WITH REHEAT POINTS SCHEDULE
1MI815 VAV WITHOUT REHEAT POINTS SCHEDULE
1MI816 TYPICAL FAN COIL UNIT CONTROLS
1MI817 HYDRONIC UNIT HEATER CONTROLS
1MI818 OTHER SYSTEM CONTROLS
1MI819 CHILLED WATER SYSTEM CONTROLS
1MI820 CHILLED WATER SYSTEM POINT SCHEDULE
ELECTRICAL
1E-001 ELECTRICAL LEGEND
1E-002 ELECTRICAL HAZARDOUS PLAN
1EG101 FIRST FLOOR - AREA A LIGHTNING PROTECTION SYSTEM PLAN
1EG102 FIRST FLOOR - AREA B LIGHTNING PROTECTION SYSTEM PLAN
1EG103 FIRST FLOOR - AREA C LIGHTNING PROTECTION SYSTEM PLAN
1EG104 GROUNDNG PLAN - FIRST FLOOR
1EG105 GROUNDING PLAN - SECOND FLOOR
1EG501 GROUNDING DETAILS I
1EG502 GROUNDING DETAILS II
1EG503 GROUNDING DETAILS III
1EG504 GROUNDING DETAILS IV
1EG601 GROUNDING RISER DIAGRAM
1EL001 LIGHTING FIXTURE SCHEDULE & CONTROL SCHEDULE
1EL101 FIRST FLOOR - AREA A LIGHTING PLAN
1EL102 FIRST FLOOR - AREA B LIGHTING PLAN
1EL103 FIRST FLOOR - AREA C LIGHTING PLAN
1EL104 SECOND FLOOR - LIGHTING PLAN
1EL401 MAINTENANCE PIT ENLARGED LIGHTING PLAN
1EL501 LIGHTING DETAILS 1
1EL502 LIGHTING DETAILS 2
1EP101 FIRST FLOOR - AREA A POWER PLAN
1EP102 FIRST FLOOR - AREA B POWER PLAN
1EP103 FIRST FLOOR - AREA C POWER PLAN
1EP104 SECOND FLOOR - POWER PLAN
1EP111 FIRST FLOOR - AREA A EQUIPMENT POWER PLAN
1EP112 FIRST FLOOR - AREA B EQUIPMENT POWER PLAN
1EP113 FIRST FLOOR - AREA C EQUIPMENT POWER PLAN
1EP114 SECOND FLOOR - EQUIPMENT POWER PLAN
1EP401 ENLARGED POWER PLANS
1EP411 ENLARGED EQUIPMENT POWER PLAN
1EP412 MECHANICAL EQUIPMENT CONNECTION SCHEDULE
1EP501 POWER DETAILS 1
1EP601 POWER RISER DIAGRAM
1EP701 PANELBOARD SCHEDULE 1
1EP702 PANELBOARD SCHEDULE 2
1EP703 PANELBOARD SCHEDULE 3
1EP704 PANELBOARD SCHEDULE 4
1EP705 PANELBOARD SCHEDULE 5
1ET101 FIRST FLOOR - AREA A TELECOMMUNICATION PLAN
1ET102 FIRST FLOOR - AREA B TELECOMMUNICATION PLAN
1ET103 FIRST FLOOR - AREA C TELECOMMUNICATION PLAN
1ET104 SECOND FLOOR - TELECOMMUNICATION PLAN
1ET401 ENLARGED COMMUNICATION ROOMS
1ET501 TELECOMMUNICATIONS DETAILS 1
1ET502 TELECOMMUNICATION DETAILS 2
1ET503 TELECOMMUNICATION DETAILS 3
1ET601 TELECOMMUNICATIONS RISER DIAGRAM 1
1ET602 TELECOMMUNICATIONS RISER DIAGRAM 2
1ET603 TELECOMMUNICATIONS RISER DIAGRAM -
TELECOMMUNICATIONS CABINET
1EY101 FIRST FLOOR - AREA A SPECIAL SYSTEMS PLAN
1EY102 FIRST FLOOR - AREA B SPECIAL SYSTEMS PLAN
1EY103 FIRST FLOOR - AREA C SPECIAL SYSTEMS PLAN
1EY104 SECOND FLOOR - SPECIAL SYSTEMS PLAN
1EY401 ENLARGED ARMS AND COMSEC VAULTS
1EY501 SPECIAL SYSTEMS DETAIL
INDEX OF DRAWINGS
FIRE PROTECTION
1FX-101 FIRE PROTECTION FLOOR PLAN 1A
1FX-102 FIRE PROTECTION FLOOR PLAN 1B
1FX-103 FIRE PROTECTION FLOOR PLAN 1C
1FX-104 FIRE PROTECTION FLOOR PLAN 2
1FX-501 FIRE PROTECTION DETAILS
ARCHITECTURE (cont'd)
1A-510 WALL DETAILS
1A-511 WALL DETAIL II
1A-512 INTERIOR WALL PENETRATION DETAILS
1A-513 EXTERIOR WALL PENETRATION DETAILS
1A-520 ROOF DETAILS
1A-521 ROOF DETAILS II
1A-522 ROOF DETAILS III
1A-530 DOOR DETAILS
1A-531 DOOR DETAILS II
1A-540 WINDOW DETAILS
1A-541 WINDOW DETAILS II
1A-550 CEILING DETAILS
1A-570 MISC. DETAILS
1A-571 MISC. DETAILS II
1A-601 PARTITION TYPES
1A-602 DOOR SCHEDULE
1A-603 WINDOW SCHEDULE
1A-701 AIR BARRIER PLANS AND SECTIONS
1A-702 AIR BARRIER SECTIONS
PLUMBING (cont'd)
1PL108 SECOND FLOOR DOMESTIC WATER - B
1PL401 ENLARGED MECHANICAL WASTE AND VENT
1PL402 ENLARGED MECHANICAL DOMESTIC WATER
1PL403 ENLARGED REST ROOM WASTE AND VENT
1PL404 ENLARGED FIRST FLOOR REST ROOM DOMESTIC WATER
1PL405 ENLARGED SECOND FLOOR REST ROOM DOMESTIC WATER
1PP101 FIRST FLOOR NATURAL GAS, POL, AND COMPRESSED AIR - A
1PP102 FIRST FLOOR NATURAL GAS, POL , AND COMPRESSED AIR - B
1PP103 FIRST FLOOR NATURAL GAS, POL, AND COMPRESSED AIR - C
1PP104 SECOND FLOOR NATURAL GAS AND COMPRESSED AIR-B
1P-501 DOMESTIC COLD WATER SYSTEM SCHEMATIC
1P-502 DOMESTIC HOT WATER SYSTEM SCHEMATIC
1P-503 PLUMBING DETAILS
1P-504 PLUMBING DETAILS
1P-505 PLUMBING DETAILS
1P-601 PLUMBING SCHEDULES
MECHANICAL (cont'd)
1MI821 CHILLED WATER SYSTEM SEQUENCE OF OPERATION
1MI822 HEATING WATER SYSTEM CONTROLS
1MI823 HEATING WATER SYSTEM POINT SCHEDULE
1MI824 HEATING WATER SYSTEM SEQUENCE OF OPERATION
1MI825 DOMESTIC HOT WATER CONTROLS
1MI826 DOMESTIC HOT WATER POINT SCHEDULE
1MI827 DOMESTIC HOT WATER SEQUENCE OF OPERATION
1MI828 EF CONTROLS
1MI829 DEMAND RESPONSE CONTROLS
1MI830 HVAC CONTROLS MAU-4 UAV BLDG VENTILATION & HEATING
SYSTEM POINTS SCHEDULE -UAV
1 2 3 4 5
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
U .S
. A R
M Y
EN
G
IN
EE
R D
IS
TR
R
PS
O
F
EN
G
IN
EE
R
S
FO
R T
W O
R
TH
, T
EX
AS
C
H
EC
KE
D
B Y:
US Army Corps of Engineers ®
D
C
B
A
PL
O
T
SC
AL
E:
PL
O
T D
AT
E:
SY
M
D
ES
C R
IP
TI
O N
D
AT
E
EN
G
IN
EE
R
IN
G
C O
N
ST
R U
C
TI
O N
D
IV
IS
IO
N
EN
G
IN
EE
R
IN
G
B R
AN
C
H
AP
R R
6 7 8 9
E
F
7/
/2
1:
:1
PM
FO
RT
H O
O D, T X
TA
CT
IC
AL
E Q
UI
PM
EN
T
M
AI
NT
EN
AC
E
F A
CI
LI
TI
ES
PN
: 0
3 8
TE
M
F
BU
IL
DI
NG
JU
N
E
W
G
R
Fort Worth District
M . V
AV
R
A, P
.E
M . V
AV
R
A, P
.E
ZA
C
H G
ER
IC
H , P
.E
ST
R
U C
TU
R
AL
S
EC
TI
O N
C H
IE
F
1S-001
G
EN
ER
AL
S
TR
U C
TU
R A L
N O
TE
S
AN
D
DE
TA
IL
S I
Z.
G
ER
IC
H , P
.E
GENERAL REQUIREMENTS:
1. VERIFICATION: CONTRACTOR SHALL VERIFY ALL DIMENSIONS, ELEVATIONS AND SITE CONDITIONS BEFORE
STARTING WORK. NOTIFY THE CONTRACTING OFFICER IMMEDIATELY OF ANY DISCREPANCIES.
2. CONFLICTS: NOTES AND DETAILS ON THE DRAWINGS TAKE PRECEDENCE OVER THE GENERAL NOTES AND
TYPICAL DETAILS IN CASE OF CONFLICT.
3. CODES: ALL MATERIALS AND WORK SHALL CONFORM TO THE REQUIREMENTS OF UFC 3-301-01 STRUCTURAL
ENGINEERING, WITH CHANGE 3, (9-12-2016).
4. SUBSTITUTIONS: PROVIDE MANUFACTURER'S ICC REPORTS AND A LIST OF ALL PROPOSED SUBSTITUTIONS TO
THE CONTRACTING OFFICER FOR REVIEW AND APPROVAL BEFORE FABRICATION.
5. SIMILAR WORK: WHERE CONSTRUCTION DETAILS ARE NOT SHOWN OR NOTED FOR ANY PART OF THE WORK, SUCH DETAILS SHALL BE THE SAME AS FOR SIMILAR WORK SHOWN ON THE DRAWINGS.
6. PIPES, DUCTS, SLEEVES, CHASES, ETC.: SHALL NOT BE PLACED IN SLABS OR WALLS UNLESS SPECIFICALLY SHOWN OR NOTED NOR SHALL ANY STRUCTURAL MEMBER BE CUT FOR PIPES, DUCTS, ETC., UNLESS SPECIFICALLY SHOWN. THE CONTRACTOR SHALL OBTAIN WRITTEN CONSENT FROM THE CONTRACTING OFFICER
BEFORE INSTALLATION OF ANY ADDITIONAL PIPES, DUCTS, SLEEVES, CHASES, ETC.
7. EXCAVATIONS: LOCATE AND PROTECT UNDERGROUND OR CONCEALED CONDUIT, PLUMBING OR OTHER UTILITIES
WHERE NEW WORK IS BEING PERFORMED.
8. CONSTRUCTION LOADS: MATERIALS SHALL BE EVENLY DISTRIBUTED IF PLACED ON FRAMED FLOORS OR ROOFS.
LOADS SHALL NOT EXCEED THE ALLOWABLE LOADING FOR THE SUPPORTING MEMBERS AND THEIR
CONNECTIONS.
9. THE STRUCTURAL DRAWINGS ILLUSTRATE THE NEW STRUCTURAL MEMBERS; REFER TO ARCHITECTURAL, MECHANICAL AND ELECTRICAL DRAWINGS FOR NONSTRUCTURAL ITEMS WHICH REQUIRE SPECIAL PROVISIONS
DURING THE CONSTRUCTION OF STRUCTURAL MEMBERS.
10. REFER TO ARCHITECTURAL PLANS FOR FLOOR DEPRESSIONS, SLOPES, DRAINS, CURBS, PADS, EMBEDDED
ITEMS, NONBEARING PARTITIONS, ETC.
11. REFER TO MECHANICAL AND ELECTRICAL PLANS FOR SLEEVE AND HANGERS FOR PIPES, DUCTS AND
EQUIPMENT.
12. CONSTRUCTION METHODS AND PROJECT SAFETY: THE CONTRACT DRAWINGS AND SPECIFICATIONS REPRESENT THE FINISHED STRUCTURE AND DO NOT INDICATE METHODS, PROCEDURES OR SEQUENCE OF CONSTRUCTION.
THE CONTRACTOR SHALL TAKE THE NECESSARY PRECAUTIONS TO MAINTAIN AND INSURE THE INTEGRITY OF THE STRUCTURE DURING CONSTRUCTION. THE CONTRACTOR SHALL DESIGN, CONSTRUCT AND MAINTAIN ALL SAFETY DEVICES, INCLUDING SHORING AND BRACING, AND BE SOLELY RESPONSIBLE FOR CONFORMING TO ALL
LOCAL, STATE AND FEDERAL SAFETY AND HEALTH STANDARDS, LAWS AND REGULATIONS.
13. ANY DEVIATION FROM THE APPROVED SET OF STRUCTURAL DRAWINGS SHALL ONLY BE MADE AFTER WRITTEN
APPROVAL BY THE CONTRACTING OFFICER.
14. STRUCTURAL PLANS INDICATE ONLY THE APPROXIMATE LOCATION OF MECHANICAL, ELECTRICAL, AND OTHER EQUIPMENT, AS WELL AS THE RELATED AUXILIARY FRAMING NECESSARY TO SUPPORT SUCH EQUIPMENT. THE FINAL POSITIONING OF THESE ITEMS IS DEPENDENT UPON THE EQUIPMENT PROVIDED BY THE CONTRACTOR.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING WORK BETWEEN SUBCONTRACTORS AND CRAFTS IN THIS REGARD, AND PROVIDING NECESSARY DIMENSIONS IN A TIMELY MANNER TO ALL PARTIES
INVOLVED.
15. ROOF AND FLOOR MEMBERS: PROVIDE TEMPORARY BRACING AS REQUIRED DURING THE ERECTION OF THE STRUCTURAL FRAME. BRACING MUST BE FULLY EFFECTIVE UNTIL ROOF AND FLOOR DEAD LOADS ARE IN PLACE
AND PERMANENT LATERAL LOAD RESISTING SYSTEMS ARE IN PLACE.
16. DO NOT SCALE DRAWINGS.
17. IT IS THE CONTRACTORS RESPONSIBILITY TO COMPLY WITH ALL APPLICABLE LOCAL SAFETY REQUIREMENTS AND
REQUIREMENTS OF EM 385-1-1.
18. EXPANSION ANCHORS CAN ONLY BE USED FOR FIELD REPAIRS UNLESS NOTED OTHERWISE AND REQUIRE
APPROVAL OF THE CONTRACTING OFFICER.
TEMF DESIGN CRITERIA:
1. CODES AND CRITERIA:
UFC 3-301-01, STRUCTURAL ENGINEERING, WITH CHANGE 3 (SEPT. 12, 2016)
UFC 4-010-01, DoD MINIMUM ANTI TERRORISM STANDARDS FOR BUILDINGS, WITH CHANGE 1 (OCT. 1, 2013)
ASCE 7-10, MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES.
IBC 2015, INTERNATIONAL BUILDING CODE.
2. BUILDING OCCUPANCY CATEGORY: II
3. LIVE LOADS:
FIRST FLOOR:
ALL AREAS ..................................................................... 1000 psf (8,000 lbs CONCENTRATED)
SECOND FLOOR:
MECH./ELEC. ROOMS .................................................... 150 psf (2,000 lbs. CONCENTRATED) ALL OTHER AREAS ........................................................ 100 psf (2,000 lbs. CONCENTRATED)
ROOF ......................................................................................... 20 psf (300 lbs. CONCENTRATED)
OTHER LIVE LOADS NOT SHOWN SHALL BE IN ACCORDANCE WITH ASCE 7-10, MINIMUM.
4. SNOW LOADS:
GROUND SNOW, Pg ................................................................. 5 psf EXPOSURE FACTOR, Ce .......................................................... 0.9 THERMAL FACTOR, Ct ............................................................. 1.0 IMPORTANCE FACTOR, Is ....................................................... 1.0 SLOPE FACTOR, Cs ................................................................. 1.0 FLAT ROOF, Pf .......................................................................... 5 psf SLOPED ROOF, Ps .................................................................... 5 psf
TEMF DESIGN CRITERIA (CONTINUED):
5. WIND LOADS:
BASIC WIND SPEED, V .................................................................................... 115 mph RISK CATEGORY .............................................................................................. II EXPOSURE CATEGORY ................................................................................... C INTERNAL PRESSURE COEFFICIENT, GCpi ................................................... +/- 0.18
FOR COMPONENTS AND CLADDING PRESSURES, SEE SHEET 1S-600
6. SEISMIC LOADS:
RISK CATEGORY ............................................................................................... II SEISMIC IMPORTANCE FACTOR, Ie ................................................................ 1.0 SOIL SITE CLASSIFICATION ............................................................................. D SHORT PERIOD SPECTRAL ACCELERATION, Ss ........................................... 0.06 g ONE SECOND SPECTRAL ACCELERATION, S1 .............................................. 0.04 g DESIGN SHORT PERIOD SPECTRAL ACCELERATION, SDs .......................... 0.06 g DESIGN ONE SECOND SPECTRAL ACCELERATION, SD1 ............................. 0.06 g SEISMIC DESIGN CATEGORY .......................................................................... A
7. LATERAL FORCE RESISTING SYSTEM: PRE-ENGINEERED METAL BUILDING CONSISTING OF STEEL MOMENT FRAMES.
8. ANTI TERRORISM / FORCE PROTECTION: GLAZING AND DOORS, AND FRAMING AROUND GLAZING AND DOORS, SHALL MEET THE BLAST RESISTANCE REQUIREMENTS OF UFC 4-010-01, DoD MINIMUM ANTI TERRORISM STANDARDS FOR BUILDINGS, WITH
CHANGE 1 (OCT. 1, 2013) UNLESS NOTED OTHERWISE.
9. IN CASE OF DISCREPANCY BETWEEN CONTRACT DRAWINGS, CONTRACT SPECIFICATIONS, AND/OR APPLICABLE CODES AND
CRITERIA, THE MORE STRINGENT SHALL BE APPLIED.
CRANE DESIGN NOTES:
1. THE OVERHEAD CRANE SHALL BE TOP RUNNING WITH A CAPACITY OF 10 tons. REFER TO MECHANICAL AND SPECIFICATIONS
FOR MORE INFORMATION.
2. THE CRANE HOOK CLEARANCE SHALL BE 20 ft. MIN. ABOVE FINISH FLOOR.
3. THE STRUCTURE SUPPORTING THE BRIDGE CRANE SHALL BE DESIGNED FOR THE TOTAL VERTICAL LOAD FROM THE WEIGHT OF THE BRIDGE, TROLLEY HOIST, AND RATED CAPACITY OF THE CRANE. TOTAL VERTICAL LOAD SHALL BE ADJUSTED FOR THE FOLLOWING IMPACT LOAD FACTOR EXPRESSED AS A PERCENTAGE OF THE TOTAL VERTICAL LOAD. CRANE RUNWAY BEAMS AND RAILS SHALL ALSO BE DESIGNED FOR A LATERAL AND LONGITUDINAL FORCE EQUIVALENT TO A PERCENTAGE OF THE TOTAL VERTICAL LOAD AS SHOWN BELOW. REFER TO ASCE 7-10, SECTION 4.9 FOR MORE INFORMATION.
VERTICAL IMPACT FORCE ........................ 110%
LATERAL FORCE ........................................ 20%
LONGITUDINAL FORCE .............................. 10%
4. END STOPS SHALL BE PROVIDED AT THE END OF EACH CRANE RAIL. END STOPS SHALL BE DESIGNED FOR LOADS REQUIRED OF THE CRANE PROVIDED BY THE CONTRACTOR. THE CONTRACTOR SHALL COORDINATE LOCATIONS OF CRANE STOPS WITH
THE PRE-ENGINEERED METAL BUILDING SUPPLIER AND CRANE SUPPLIER.
PRE-ENGINEERD METAL BUILDING NOTES:
1. THE PRE-ENGINEERED BUILDING SHALL BE DESIGNED AND FABRICATED ACCORDING TO THE CONTRACT SPECIFICATIONS, AISC, MBMA, AND AISI, LATEST EDITIONS. MBMA CERTIFICATION IS REQUIRED OF THE METAL BUILDING SYSTEMS MANUFACTURER AND A CERTIFICATE TO VERIFY COMPLIANCE SHALL BE SUBMITTED WITH THE DESIGN ANALYSIS U.O.N. THE DIMENSIONAL TOLERANCES OUTLINED IN THE AWS CODE UNDER WORKMANSHIP AND THE TOLERANCES APPLICABLE TO HOT- ROLLED STEEL UNDER THE AISC "STANDARD MILL PRACTICE" SECTION SHALL BE REQUIRED IN THE FABRICATION OF THE
STEEL BUILDING FRAMES.
2. DESIGN LOADS: SHALL CONFORM WITH LIVE, WIND AND SEISMIC LOAD PARAMETERS NOTED IN "TEMF DESIGN CRITERIA" ON THIS SHEET (1S-001) PLUS COLLATERAL DEAD LOADS FROM MECH./ELEC., CEILINGS AND SPRINKLERS AS APPLICABLE. THE MINIMUM DESIGN COLLATERAL DEAD LOAD SHALL BE 12 psf. LOAD COMBINATIONS AND DESIGN STRESSES SHALL COMPLY
WITH AISC "SPECIFICATIONS FOR STRUCTURAL STEEL BUILDINGS".
3. THE FOLLOWING INFORMATION SHALL BE PROVIDED BY THE METAL BUILDING MANUFACTURER:
WIND DESIGN:
DESIGN BASE SHEAR
DESIGN UPLIFT
SEISMIC DESIGN:
SEISMIC FORCE RESISTING SYSTEM
RESPONSE MODIFICATION FACTOR, R
SEISMIC RESPONSE COEFFICIENT, Cs
SYSTEM OVER STRENGTH FACTOR, Ω
SEISMIC ANALYSIS PROCEDURE
DESIGN BASE SHEAR
4. CRANE SUPPORT DESIGN: THE METAL BUILDING MANUFACTURER SHALL DESIGN AND PROVIDE THE PRE-ENGINEERED METAL BUILDING AND CRANE SUPPORTS FOR ALL CODE REQUIRED LOADINGS AND SUPPORT OF A 10 TON BRIDGE CRANE. SEE
CONTRACT SPECIFICATIONS FOR CRANE REQUIREMENTS.
5. ANTI TERRORISM FORCE PROTECTION LOADS: ALL FRAMING ASSOCIATED WITH WINDOWS AND DOORS SHALL BE DESIGNED
BY THE METAL BUILDING MANUFACTURER TO MEET THE REQUIREMENTS OF UFC 4-010-01.
6. LATERAL DRIFT LIMITS: SHALL NOT EXCEED h/600 IN ANY DIRECTION FOR A 10 yr. WIND MRI.
7. EXTERIOR CLADDING, INCLUDING STANDING SEAM METAL ROOF, SHALL NOT BE PERMITTED TO ACT AS A DIAPHRAGM TO
TRANSFER LATERAL LOADS.
8. ALL COLUMNS SHALL BE ANALYZED AS HAVING PINNED BASES.
9. RIGID FRAME ANCHOR BOLTS SHALL BE DESIGNED AND FURNISHED BY THE CONTRACTOR. ANCHOR BOLTS SHALL BE DESIGNED BY A PROFESSIONAL ENGINEER, LICENSED IN THE PROJECT STATE, FOR THE FRAME REACTIONS PROVIDED BY THE METAL BUILDING MANUFACTURER. THE ANCHOR BOLT DESIGN ANALYSIS SHALL BE SUBMITTED FOR APPROVAL.
10. FOUNDATION: THE FOUNDATION SHOWN HEREIN SHALL BE THE MINIMUM PROVIDED. THE METAL BUILDING MANUFACTURER SHALL VERIFY THAT CONCRETE FOUNDATION DIMENSIONS AND REINFORCING SHOWN ARE ADEQUATE FOR FRAME REACTIONS AND EMBEDMENT OF COLUMN ANCHOR BOLTS. THE CONTRACTOR SHALL BE NOTIFIED IF DIMENSIONS
NEED TO BE INCREASED BEFORE CONSTRUCTION OF FOUNDATION BEGINS.
FOUNDATION NOTES:
1. SOILS INFORMATION BASED ON THE GEOTECHNICAL REPORT DATED FEBRUARY 2018, PROVIDED BY THE
GEOTECHNICAL BRANCH, US ARMY CORPS OF ENGINEERS, FORT WORTH DISTRICT.
2. DRILLED PIER FOUNDATIONS:
DESIGNED BASED ON THE FOLLOWING INFORMATION:
ALLOWABLE END BEARING ................................................................................ 25 ksf IN UNWEATHERED LIMESTONE ALLOWABLE SKIN FRICTION .............................................................................. 0.75 ksf
A. ALL DRILLED PIER EXCAVATIONS SHALL BE INSPECTED BY THE CONTRACTING OFFICER TO VERIFY DEPTH OF EXCAVATION AND PRESCRIBED PENETRATION INTO SPECIFIED FOUNDATION MATERIAL IS ACHIEVED.
THE CONTRACTOR SHALL EMPLOY A TESTING LAB TO VERIFY THAT THE ANTICIPATED STRATUM HAS
BEEN HIT AND TO RECORD INFORMATION INDEPENDENT OF THE FOUNDATION CONTRACTOR. THE
GOVERENMENT MAY ALSO PROVIDE INSPECTION; HOWEVER THIS DOES NOT RELIEVE THE CONTRACTOR
OF RESPONSIBILITY FOR INDEPENDENT INSPECTION.
B. ALL DRILLED PIERS SHALL NOT BE FOUNDED ANY SHALLOWER THAN 855.0 ft NGVD AND SHALL BE SOCKETED 3 ft OR 1 SHAFT DIAMETER, WHICHEVER IS GREATER, INTO DARK GRAY UNWEATHERED LIMESTONE PRIMARY UNLESS OTHERWISE NOTED. DRILLED PIERS 18 in DIAMETER OR LESS SHALL NOT BE FOUNDED GREATER THAN 40 ft.
C. PIER EXCAVATIONS SHALL BE FILLED WITH CONCRETE AS SOON AS POSSIBLE AFTER DRILLING AND INSPECTION. PIER EXCAVATIONS SHALL NOT BE LEFT OPEN OVERNIGHT. PRECAUTIONS SHALL BE TAKEN
DURING THE INSTALLATION OF PIERS TO THE POSSIBILITY OF CAVING.
D. CONCRETE SHALL BE PLACED IN THE DRY. GROUNDWATER SHALL BE ANTICIPATED DURING OPERATIONS, THEREFORE THE CONTRACTOR SHALL HAVE TEMPORARY STEEL CASINGS AT THE JOB SITE PRIOR TO
CONSTRUCTION OF DRILLING PIERS.
3. GRADE BEAMS AND PIER CAPS: A MINIMUM 6 in VOID SHALL BE PROVIDED BENEATH GRADE BEAMS AND PIER
CAPS, WHERE APPLICABLE. SEE TYPICAL GRADE BEAM VOID DETAIL ON 1S-004.
4. SLABS-ON-GRADE:
DESIGNED BASED ON THE FOLLOWING INFORMATION:
EFFECTIVE MODULUS OF SUBGRADE REACTION ............................................. 200 pci
A. THE CONTRACTOR SHALL OVEREXCAVATE 2 ft MIN., OR TO TOP OF LIMESTONE PRIMARY, WHICHEVER COMES FIRST, OF SOILS BELOW ALL SLABS-ON-GRADE. OVEREXCAVATION SHALL BE REPLACED WITH
COMPACTED NON-EXPANSIVE FILL IN ACCORDANCE WITH THE SPECIFICATIONS.
B. A 10 mil POLYETHYLENE VAPOR BARRIER AND 6 in MIN. CAPILLARY WATER BARRIER SHALL BE PROVIDED
BENEATH ALL SLABS-ON-GRADE.
C. SLAB-ON-GRADE ISOLATION JOINTS SHALL BE 1/2 in P.E.J. AND PROVIDED AT ALL CONTACT SURFACES
BETWEEN THE SLAB-ON-GRADE AND GRADE BEAMS/PIER CAPS UNLESS OTHERWISE NOTED.
1. TABLE DEVELOPED FOR f'c = 4,000 psi AND fy = 60,000 psi.
2. TABLE REPRESENTS TENSION DEVELOPMENT LENGTHS AND TENSION LAP SPLICE
LENGTHS BASED ON ACI 318.
3. TOP BARS ARE HORIZONTAL REINFORCEMENT PLACED SO THAT MORE THAN 12" OF
CONCRETE IS CAST BELOW THE REINFORCEMENT.
4. CASES:
A. CASE 1 APPLIES WHERE:
• CLEAR SPACING OF BARS BEING DEVELOPED OR SPLICED NOT LESS
THAN THE BAR DIAMETER, CLEAR COVER NOT LESS THAN BAR
DIAMETER, AND STIRRUPS OR TIES THROUGHOUT THE DEVELOPMENT
OR SPLICE LENGTH NOT LESS THAN THE ACI 318 MINIMUM
• CLEAR SPACING OF BARS BEING DEVELOPED OR SPLICED NOT LESS
THAN 2 BAR DIAMETERS AND CLEAR COVER NOT LESS THAN BAR
DIAMETER
B. CASE 2 APPLIES TO ALL OTHER CASES.
BAR
SIZE
BAR
DIAMETER
(in.)
DEVELOPMENT LENGTH (in.) LAP LENGTH (in.)
TOP BAR OTHER BARS TOP BAR OTHER BARS
CASE 1 CASE 2 CASE 1 CASE 2 CASE 1 CASE 2 CASE 1 CASE 2
0.375 0.500 0.625 0.750 0.875 1.000 1.125 1.250 1.375
1. TABLE DEVELOPED BASED ON f'm = 1,500 psi AND fy = 60,000 psi.
2. TABLE REPRESENTS TENSION DEVELOPMENT LENGTHS AND TENSION LAP SPLICE
LENGTHS BASED ON TMS 402
BAR DIAMETER (in.) DEVELOPMENT AND SPLICE LENGTH (in.)
BAR SIZE
0.375 0.500 0.625
SHEET
NUMBER
1 2 3 4 5
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
U .S
. A R
M Y
EN
G
IN
EE
R D
IS
TR
R
PS
O
F
EN
G
IN
EE
R
S
FO
R T
W O
R
TH
, T
EX
AS
C
H
EC
KE
D
B Y:
US Army Corps of Engineers ®
D
C
B
A
PL
O
T
SC
AL
E:
PL
O
T D
AT
E:
SY
M
D
ES
C R
IP
TI
O N
D
AT
E
EN
G
IN
EE
R
IN
G
C O
N
ST
R U
C
TI
O N
D
IV
IS
IO
N
EN
G
IN
EE
R
IN
G
B R
AN
C
H
AP
R R
6 7 8 9
E
F
As in di ca te d
7/
/2
1:
:3
PM
FO
RT
H O
O D, T X
TA
CT
IC
AL
E Q
UI
PM
EN
T
M
AI
NT
EN
AC
E
F A
CI
LI
TI
ES
PN
: 0
3 8
TE
M
F
BU
IL
DI
NG
JU
N
E
W
G
R
Fort Worth District
M . V
AV
R
A, P
.E
M . V
AV
R
A, P
.E
ZA
C
H G
ER
IC
H , P
.E
ST
R
U C
TU
R
AL
S
EC
TI
O N
C H
IE
F
1S-002
G
EN
ER
AL
S
TR
U C
TU
R A L
N O
TE
S
AN
D
DE
TA
IL
S
II
Z.
G
ER
IC
H , P
.E
CAST-IN-PLACE CONCRETE NOTES:
1. MATERIALS:
CEMENT ..................................................................................... ASTM C 150, TYPE II OR I AGGREGATE ............................................................................. ASTM C 33, CRUSHED ROCK REINFORCEMENT ..................................................................... ASTM A 615, GRADE 60
WELDED WIRE REINFORCEMENT (WWR) .............................. ASTM A 1064
2. CONCRETE STRENGTHS: THE CONCRETE STRENGTHS SHOWN IN THE FOLLOWING TABLE ARE THE MINIMUM COMPRESSIVE STRENGTHS AT 28 DAYS AND THE WATER CEMENT RATIO IS THE MAXIMUM. THE SPECIFIED SLUMP IS THE MAXIMUM PRIOR TO THE ADDITION OF ADMIXTURES. CONCRETE SHALL BE NORMAL WEIGHT CONCRETE (145 pcf).
ITEM: STRENGTH: AGGREGATE: SLUMP: WATER/CEMENT RATIO:
CONCRETE ON METAL DECK 4,000 psi 3/4 in 3 in 0.45 lb/lb SLABS-ON-GRADE 5,500 psi 1 in 3 in 0.45 lb/lb ALL OTHER CONCRETE 4,000 psi 1 in 3 in 0.45 lb/lb
SLAB-ON-GRADE CONCRETE FLEXURAL STRENGTH SHALL BE 650 psi MIN. AT 28 DAYS.
3. CONCRETE SHALL BE PROPORTIONED SUCH THAT 7 DAY STRENGTHS ARE A MINIMUM OF 70% OF THE SPECIFIED 28 DAY STRENGTH FOR ANY CONCRETE CONSTRUCTION REQUIRING SHORING, BRACING, OR TO RECEIVE
CONSTRUCTION LOADS.
4. A WATER-REDUCING ADMIXTURE CONFORMING TO ASTM C 494, USED IN STRICT ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS, MAY BE INCORPORATED IN THE CONCRETE DESIGN MIXES. A HIGH RANGE WATER REDUCING (HRWR) ADMIXTURE CONFORMING TO ASTM C 494, TYPE F OR G, MAY BE USED IN CONCRETE MIXES PROVIDING THAT SLUMP DOES NOT EXCEED 8 in. AN AIR-ENTRAINING AGENT CONFORMING TO ASTM C 260 SHALL BE USED IN CONCRETE MIXES FOR THE EXTERIOR HORIZONTAL SURFACES EXPOSED TO COLD
WEATHER.
5. REINFORCEMENT:
SHOP DRAWINGS, FABRICATION AND PLACING SHALL CONFORM TO ACI 315 AND ACI 318. SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTING OFFICER BEFORE FABRICATION. THE FOLLOWING MINIMUM CONCRETE
COVER SHALL BE PROVIDED FOR REINFORCEMENT:
CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH .................................................... 3 in
CONCRETE EXPOSED TO WEATHER:
NO. 6 THROUGH NO. 18 BARS ......................................................................................................................... 2 in NO. 5 BARS AND SMALLER .............................................................................................................................. 1-1/2 in
CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH GROUND:
NO. 14 AND NO. 18 BARS .................................................................................................................................. 1-1/2 in NO. 11 BARS AND SMALLER ............................................................................................................................. 3/4 in BEAMS, COLUMNS AND PLINTH STIRRUPS/SPIRALS .................................................................................... 1-1/2 in SLABS-ON-GRADE (TOP COVER) ..................................................................................................................... 1-1/2 in
6. REINFORCEMENT CHAIRS AND COVERS: PROVIDE AS REQUIRED TO MAINTAIN CONCRETE COVER.
7. VERTICAL REINFORCEMENT: SHALL BE DOWELLED TO SUPPORTING MEMBERS WITH THE SAME SIZE AND SPACING OF REINFORCEMENT AS SHOWN ON THE DRAWINGS AND GENERAL NOTES UNLESS OTHERWISE NOTED.
8. HORIZONTAL REINFORCEMENT: ALL BARS ENDING AT THE FACE OF A WALL, COLUMN OR BEAM SHALL EXTEND TO WITHIN 2 in OF THE FACE AND HAVE A 90 DEGREE HOOK UNLESS OTHERWISE NOTED.
9. TACK WELDING, WELDING, HEATING OR CUTTING OF BARS IS NOT PERMITTED UNLESS OTHERWISE NOTED.
10. REINFORCEMENT SPLICE AND DEVELOPMENT LENGTH:
A) THE FOLLOWING TABLE CONTAINS LAP SPLICE AND DEVELOPMENT LENGTHS.
CAST-IN-PLACE CONCRETE NOTES (CONTINUED):
12. FOR SPECIAL FINISHES, REFER TO ARCHITECTURAL DRAWINGS FOR MOLDS, GROOVES, ORNAMENTS, CLIPS, OR GROUNDS
REQUIRED TO BE ENCASED IN CONCRETE AND FOR LOCATION OF FLOOR FINISHES AND SLAB DEPRESSIONS.
13. PERMANENTLY EXPOSED CONCRETE CORNERS SHALL HAVE A 3/4 in CHAMFER.
14. CONSTRUCTION JOINTS: ALL CONSTRUCTION JOINTS SHALL BE CONSTRUCTED IN ACCORDANCE WITH ACI 318, SECTION 26.5.6, AND THE TYPICAL CONSTRUCTION JOINT DETAILS SHOWN ON THE STRUCTURAL DRAWINGS. ALL SURFACES OF CONSTRUCTION JOINTS SHALL BE CLEANED TO REMOVE DUST, CHIPS, OR OTHER FOREIGN DEBRIS PRIOR TO PLACING ADJACENT CONCRETE.
15. THE CONTRACTOR SHALL SUBMIT THE PROPOSED LOCATIONS OF CONSTRUCTION JOINTS TO THE CONTRACTING OFFICER FOR
APPROVAL BEFORE STARTING CONSTRUCTION.
B) ALL LAP SPLICES SHALL BE CLASS B (TENSION) UNLESS OTHERWISE NOTED ON PLANS.
C) IN NO CASE SHALL LAPS BE LESS THAN 24 in LONG.
D) INDIVIDUAL BARS IN A BUNDLE SHALL BE STAGGERED AT LEAST 87 EQUIVALENT BAR DIAMETERS FOR
BOTTOM BUNDLES AND 113 EQUIVALENT BAR DIAMETERS FOR TOP BUNDLES, WHERE THE EQUIVALENT DIAMETER IS BASED UPON THE COMBINED AREAS OF THE BARS BUNDLED. LAP LENGTHS FOR BARS IN
BUNDLES OF 4 OR MORE BARS SHALL BE INCREASED AN ADDITIONAL 11%.
11. ANCHOR BOLTS, DOWELS AND HOLD-DOWN ANCHORS SHALL BE SECURELY HELD IN PLACE PRIOR TO FOUNDATION INSPECTION BY THE SPECIAL INSPECTOR AND OBSERVATION BY THE CONTRACTING OFFICER.
REINFORCED HOLLOW CMU NOTES:
1. MATERIALS:
SPECIFIED COMPRESSIVE STRENGTH, f'm .............................................................................. 1,500 psi CONCRETE MASONRY BLOCK ................................................................................................... ASTM C 90 MORTAR ....................................................................................................................................... ASTM C 270, ASTM C 780, TYPE S GROUT .......................................................................................................................................... ASTM C 476, ASTM C 1019 REINFORCEMENT ........................................................................................................................ ASTM A 615, GRADE 60 WELDED REINFORCEMENT ........................................................................................................ ASTM A 706, GRADE 60 EXPANSION ANCHORS ............................................................................................................... ICC ES APPROVED FOR GROUT FILLED CMU
2. CMU BOND LAY UP SHALL BE RUNNING BOND, UNLESS OTHERWISE NOTED.
3. VERTICAL CELLS TO BE GROUTED SHALL HAVE VERTICAL ALIGNMENT SUFFICIENT TO MAINTAIN A CLEAR UNOBSTRUCTED CONTINUOUS VERTICAL CELL NOT LESS THAN 2 in X 3 in IN PLAN DIMENSIONS.
4. CMU CONTROL JOINTS: LOCATE WITHIN 24 in OF MASONRY VENEER CONTROL JOINTS SHOWN ON ARCHITECTURAL DRAWINGS.
CMU CONTROL JOINTS ARE NOT PERMITTED WITHIN 24 in OF EDGES OF OPENINGS, PILASTERS OR BEAM/JOIST BEARING.
5. ISOLATION JOINTS: PROVIDE ISOLATION JOINTS BETWEEN EXTERIOR AND INTERIOR CMU PARTITION WALLS.
6. FOUNDATION DOWELS: SHALL BE FULLY DEVELOPED INTO THE FOUNDATION AND 30 in MINIMUM INTO THE CMU WALL. PROVIDE A
FOUNDATION DOWEL FOR EACH VERTICAL REINFORCING BAR, UNLESS OTHERWISE NOTED.
7. VERTICAL REINFORCEMENT: USE (1) - #5 BAR AT 48 in ON CENTER, CENTERED IN THE WALL UNLESS OTHERWISE NOTED.
VERTICAL WALL REINFORCING SHALL EXTEND CONTINUOUSLY FROM THE FOUNDATION TO EMBED 5 in MINIMUM INTO THE BOND
BEAM AT TOP OF WALL AND TERMINATE WITH A 90 DEGREE HOOK, UNLESS OTHERWISE NOTED.
A. PLACE VERTICAL SUPPORT SPACERS AT 200 REINFORCEMENT DIAMETERS MAXIMUM.
B. DOWEL REINFORCEMENT TO SUPPORTING MEMBERS WITH SAME SIZE AND SPACING OF REINFORCEMENT AS NOTED
HEREIN.
C. PROVIDE (1) - #5 BAR MINIMUM AT CMU WALL ENDS AND AT EACH SIDE OF CONTROL JOINTS.
D. PROVIDE (2) - #5 BARS MINIMUM AT CMU WALL CORNERS.
8. HORIZONTAL/BOND BEAM REINFORCEMENT: PROVIDE A BOND BEAM AT TOP OF ALL CMU WALLS. PROVIDE BOTTOM AND INTERMEDIAT BOND BEAMS IN EXTERIOR CMU WALLS ONLY. BOND BEAMS SHALL BE PLACED AT 48 in ON CENTER MAXIMUM.
REINFORCE BOND BEAMS WITH (2) - #5 BARS. BOND BEAMS SHALL BE CONTINUOUS THROUGHOUT CMU WALLS, UNLESS
OTHERWISE NOTED.
A. AT CONTROL JOINTS INTERMEDIATE BOND BEAM REINFORCEMENT SHALL BE DISCONTINUOUS.
B. AT ISOLATION JOINTS ALL BOND BEAM REINFORCING STEEL SHALL BE DISCONTINUOUS.
C. EXTERIOR CMU WALLS SHALL HAVE INTERMEDIATE BOND BEAMS LOCATED AT THE SAME LEVELS.
9. REINFORCEMENT AT CMU WALL OPENINGS: EXTEND BARS A MINIMUM OF 40 BAR DIAMETERS OR 24 in, WHICHEVER IS GREATER, BEYOND CORNERS OF OPENINGS.
A. VERTICAL JAMB BARS: FOR EXTERIOR CMU WALLS, PROVIDE (2) -#5 VERTICAL BARS AT EACH SIDE OF THE OPENING. FOR INTERIOR CMU PARTITION WALLS, PROVIDE (1) - #5 BAR AT EACH SIDE OF THE OPENING. FOUNDATION DOWELS SHALL BE
PROVIDED FOR EACH VERTICAL JAMB BAR.
B. CMU LINTELS: PROVIDE (2) - #5 BARS BOTTOM FOR REINFORCEMENT. SEE TYPICAL DETAIL 5/1S-006. CMU LINTELS SHALL HAVE A MINIMUM 24 in BEARING AT BOTH ENDS. EXTEND BEARING AND REINFORCEMENT AROUND CORNERS AS REQUIRED TO MEET MINIMUM BEARING AND EXTENSION DISTANCES. REINFORCEMENT SHALL BE SUPPORTED BY WIRE CHAIRS. PLACE REINFORCEMENT 3 in ABOVE BOTTOM OF LINTEL UNLESS OTHERWISE NOTED. IN NO CASE SHALL BARS EXTEND ACROSS
CONTROL JOINTS.
10. CMU REINFORCEMENT DEVELOPMENT AND LAP SPLICE LENGTHS:
10. VERTICAL AND HORIZONTAL REINFORCING SHALL BE PROVIDED AS NOTED IN "REINFORCED HOLLOW CMU NOTES", THIS SHEET, AND THE SPECIFICATIONS. MINIMUM ADDITIONAL REINFORCING IS SHOWN ON "TYPICAL REINFORCED CMU WALL ELEVATION
DETAIL", 1S-006.
11. PROVIDE A MINIMUM 1/2 in CLEARANCE BETWEEN MAIN REINFORCING AND MASONRY UNITS.
12. REINFORCING CONGESTION: KNOCK OUT BLOCKS SHALL BE ALLOWED TO FACILITATE CONSTRUCTION.
13. GROUTING: ALL CELLS WITH REINFORCING AND/OR ANCHORS SHALL BE FILLED WITH GROUT, INCLUDING BOND BEAMS, LINTELS AND PILASTERS, AS INDICATED IN THE NOTES AND DRAWINGS. ALL BEAM/JOIST POCKETS SHALL BE FULLY GROUTED AFTER
BEAM JOIST PLACEMENT UNLESS OTHERWISE NOTED.
A. CONSOLIDATION: AT TIME OF PLACEMENT BY MECHANICAL VIBRATION AND THEN RECONSOLIDATE BEFORE PLASTICITY IS
LOST.
B. GROUT SHALL BE PLACED IN CONTINUOUS POUR IN GROUT LIFTS NOT EXCEEDING 5 ft UNLESS OTHERWISE NOTED.
C. HORIZONTAL CONSTRUCTION JOINTS: FORMED BY STOPPING THE GROUT POUR NOT LESS THAN 1/2 in
BELOW THE TOP OF THE UPPERMOST UNITS GROUTED. HORIZONTAL REINFORCING SHALL BE FULLY
EMBEDDED IN GROUT.
17. EXPANSION ANCHORS: SHALL BE PLACED IN GROUTED CMU CELLS ONLY. EMBEDMENT SHALL BE 5 in MINIMUM.
STRUCTURAL STEEL FRAMING NOTES:
1. MATERIALS:
W SHAPES ........................................................................... ASTM A 992, GRADE 50 (Fy = 50 ksi) M AND S SHAPES, CHANNELS, ANGLES .......................... ASTM A 36 (Fy = 36 ksi) RECTANGULAR HSS ........................................................... ASTM A 500, GRADE B (Fy = 36 ksi) ROUND HSS ......................................................................... ASTM A 500, GRADE B (Fy = 42 ksi) PIPE ...................................................................................... ASTM A 53, GRADE B (Fy = 35 ksi) PLATES AND BARS .............................................................. ASTM A 36 (Fy = 36 ksi) HIGH STRENGTH BOLTS ..................................................... ASTM F 3125, GRADE A 325 NUTS ..................................................................................... ASTM A 563, HEAVY HEX, GRADE C ANCHOR RODS .................................................................... ASTM F 1554, GRADE 36 (Fy = 36 ksi) NON-SHRINK GROUT ........................................................... ASTM C 1107, 5,000 psi (NON-METALLIC WELDING ELECTRODES ..................................................... E70XX, LOW HYDROGEN
2. WELDING: ALL WELDING SHALL BE PERFORMED BY CERTIFIED WELDERS IN ACCORDANCE WITH AWS D1.1
A. GROOVE AND BUTT WELDS SHALL BE COMPLETE JOINT PENETRATION WELDS, UNLESS OTHERWISE
NOTED.
B. FILLET WELD SIZES SPECIFIED ARE MINIMUMS, INCREASE AS REQUIRED PER AISC STEEL CONSTRUCTION
MANUAL TABLE J2.4.
C. WELD TERMINATIONS: WELDS TERMINATING AT ENDS OR SIDES, WHEREVER APPLICABLE, SHALL BE RETURNED CONTINUOUSLY AROUND CORNERS A DISTANCE OF 2 TIMES THE WELD SIZE PER AISC.
D. WELD LENGTHS: WHERE LENGTH IS NOT SPECIFIED, THE WELD SHALL BE FULL LENGTH OF THE JOINT.
3. THE CONTRACTOR SHALL SUBMIT A WELDING PROCEDURE SPECIFICATION (WPS), DEVELOPED BY THE FABRICATOR/ERECTOR, IN ACCORDANCE WITH AWS D1.1 FOR REVIEW BY THE CONTRACTING OFFICER. ALL WELDS SHALL BE PRE-QUALIFIED PER AWS D1.1. THE WPS SHALL INCLUDE THE WELDING PARAMETERS
RECOMMENDED BY THE ELECTRODE MANUFACTURER.
4. SHEAR/BEARING CONNECTIONS: SHALL BE DETAILED BASED ON THE DESIGN INFORMATION PROVIDED IN THE
STRUCTURAL DRAWINGS.
A. STANDARD SHEAR CONNECTIONS: DETAIL AS BOLTED OR WELDED DOUBLE-ANGLE, SINGLE PLATE, SINGLE ANGLE, OR TEE CONNECTIONS IN ACCORDANCE WITH THE CONNECTION TABLES IN THE AISC
MANUAL OF STEEL CONSTRUCTION.
B. ALL BEAM TO WIDE FLANGE COLUMN AND BEAM TO BEAM/GIRDER CONNECTIONS SHALL BE DETAILED AS
DOUBLE-ANGLE CONNECTIONS UNLESS OTHERWISE SHOWN.
C. FACTORED DESIGN FORCES/REACTIONS: AS SHOWN ON THE STRUCTURAL DRAWINGS OR, IF NOT SHOWN, THE FACTORED DESIGN REACTION SHALL BE HALF OF THE "MAXIMUM TOTAL UNIFORM LOAD"
(LRFD) TABULATED IN THE AISC MANUAL OF STEEL CONSTRUCTION.
D. SHEAR/BEARING CONNECTIONS SHALL BE DESIGNED BY A LICENSED PROFESSIONAL ENGINEER IN THE PROJECT STATE. THIS DESIGN SERVICE SHALL BE INCLUDED IN THE CONTRACTOR'S SCOPE OF SERVICES. SHOP DRAWINGS OF CONNECTIONS SHALL BE SEALED BY A LICENSED PROFESSIONAL
ENGINEER IN THE PROJECT STATE.
5. ANCHORS: SUBSTITUTION OF EXPANSION, DRILLED OR ADHESIVE ANCHORS FOR EMBEDDED ANCHORS SHOWN
ON THE DRAWINGS SHALL NOT BE PERMITTED.
6. THE STRUCTURE SHALL NOT BE CONSIDERED STABLE DURING CONSTRUCTION UNTIL ALL ELEMENTS (INCLUDING METAL DECKING, CONCRETE FLOOR SLABS, JOISTS, ETC.) ARE IN PLACE, CONNECTED, AND ACHIEVED THEIR FULL DESIGN STRENGTH. TEMPORARY SUPPORTS AND BRACING SHALL NOT BE REMOVED OR MODIFIED UNTIL ALL ELEMENTS ARE IN PLACE, CONNECTED, AND HAVE ACHIEVED THEIR FULL DESIGN STRENGTH. THE CONTRACTOR IS RESPONSIBLE FOR ALL TEMPORARY CONSTRUCTION BRACING THAT IS
REQUIRED.
7. STRUCTURAL STEEL THAT IS EXPOSED TO WEATHER SHALL BE HOT-DIP GALVANIZED (G-90) AFTER
FABRICATION.
ARMS/COMSEC VAULT NOTES:
1. ARMS/COMSEC VAULT WALLS SHALL BE 8 in. THICK (MIN.) CAST-IN-PLACE CONCRETE REINFORCED WITH #4
BARS AT 9 in. ON-CENTER-EACH-WAY, EACH FACE, WITH THE TWO LAYERS STAGGERED TO PROVIDE A 4-1/2 in.
GRID. SEE DETAIL 1/1S-008. VAULT LID/CEILING SHALL BE 10 in. THICK (MIN.) CAST-IN-PLACE CONCRETE WITH #5 BARS AT 9 in. ON-CENTER-EACH-WAY, TOP AND BOTTOM, STAGGERED TO PROVIDE A 4-1/2 in. GRID. SEE DETAIL 1/1S-008.
2. ARMS/COMSEC VAULT SLAB-ON-GRADE SHALL BE 8 in. THICK (MIN.) WITH #4 BARS AT 12 in. ON-CENTER-EACH- WAY TOP AND #5 BARS AT 12 in. ON-CENTER-EACH-WAY BOTTOM, UNLESS OTHERWISE NOTED.
3. REFER TO AR 190-11 "PHYSICAL SECURITY OF ARMS, AMMUNITION, AND EXPLOSIVES" AND "CAST-IN-PLACE
CONCRETE NOTES" FOR ADDITIONAL VAULT CONSTRUCTION REQUIREMENTS.
4. CONCRETE PLACEMENT FOR ARMS/COMSEC VAULT WALLS AND ROOF MAY NOT PROCEED UNTIL WRITTEN SECURITY CERTIFICATION AND CONTRACTING OFFICER APPROVAL IS RECIEVED. CERTIFICATION CAN ONLY PROCEED AFTER REINFORCING STEEL IS IN PLACE. BE AWARE THAT SEPERATE CONCRETE PLACEMENTS FOR
VARIOUS PORTIONS OF THE VAULT MUST HAVE SEPERATE INSPECTIONS.
MASONRY VENEER NOTES:
1. REFER TO THE SPECIFICATIONS FOR ANCHOR TIE PRODUCTS, SPACING AND OTHER REQUIREMENTS. SPACE
ANCHORS AROUND THE PERIMETER OF OPENINGS WITHIN 8 in OF OPENING EDGE UNLESS OTHERWISE NOTED.
PROVIDE ANCHORS AT TOP COURSE UNLESS NOTED OTHERWISE.
2. STEEL LOOSE LINTEL SCHEDULE FOR OPENINGS.
OPENING SIZE LINTEL SIZE MINIMUM END BEARING
UP TO 5'-0" L4x4x1/4 6 in 5'-0" TO 7'-0" L6x4x5/16 (LLV) 8 in 7'-0" TO 8'-0" L6x4x3/8 (LLV) 8 in
A. SEE ARCHITECTURAL FOR WINDOW AND DOOR SCHEDULE.
B. LINTEL ANGLES SHALL BE HOT DIP GALVANIZED AFTER FABRICATION.
C. PROVIDE 3/8 in GAP IN MORTAR AT ENDS OF ANGLES AND FILL GAP WITH BACKER ROD.
4. FOR WINDOW SILL CAP STONE SUPPORT, SEE DETAIL 1/1S-007.
1 2 3 4 5
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
U .S
. A R
M Y
EN
G
IN
EE
R D
IS
TR
R
PS
O
F
EN
G
IN
EE
R
S
FO
R T
W O
R
TH
, T
EX
AS
C
H
EC
KE
D
B Y:
US Army Corps of Engineers ®
D
C
B
A
PL
O
T
SC
AL
E:
PL
O
T D
AT
E:
SY
M
D
ES
C R
IP
TI
O N
D
AT
E
EN
G
IN
EE
R
IN
G
C O
N
ST
R U
C
TI
O N
D
IV
IS
IO
N
EN
G
IN
EE
R
IN
G
B R
AN
C
H
AP
R R
6 7 8 9
E
F
7/
/2
1:
:4
PM
FO
RT
H O
O D, T X
TA
CT
IC
AL
E Q
UI
PM
EN
T
M
AI
NT
EN
AC
E
F A
CI
LI
TI
ES
PN
: 0
3 8
TE
M
F
BU
IL
DI
NG
JU
N
E
W
G
R
Fort Worth District
M . V
AV
R
A, P
.E
M . V
AV
R
A, P
.E
ZA
C
H G
ER
IC
H , P
.E
ST
R
U C
TU
R
AL
S
EC
TI
O N
C H
IE
F
1S-003
G
EN
ER
AL
S
TR
U C
TU
R A L
NO
TE
S
AN
D D E
TA
I L
S
III
Z.
G
ER
IC
H , P
.E
STEEL JOIST NOTES:
1. DESIGN, FABRICATION AND ERECTION OF JOISTS, JOIST EXTENTIONS, JOIST SUBSTITUTES, AND JOIST GIRDERS
SHALL CONFORM TO THE CURRENT SJI STANDARD SPECIFICATIONS.
2. JOISTS, JOIST EXTENSIONS, JOIST SUBSTITUTES, AND JOIST GIRDERS SHALL BE AS SHOWN ON THE PLANS FOR
THE INDICATED SLOPES AND THE FOLLOWING CRITERIA:
A. DEAD LOAD: ACTUAL WEIGHT OF ROOF/FLOOR SYSTEM WITH MECHANICAL, ELECTRICAL AND
ARCHITECTURAL ITEMS. DEAD LOAD SHALL NOT BE LESS THAN 20 psf.
B. LIVE LOAD: AS INDICATED IN THE "TEMF DESIGN CRITERIA" WITH A LIVE LOAD DEFLECTION OF LESS THAN L/360.
C. GROSS WIND COMPONENT AND CLADDING UPLIFTS ARE SHOWN IN "WIND COMPONENTS AND CLADDING TABLE". FOR ASD DESIGN METHOD, NET UPLIFT IS DETERMINED USING 60% OF THE ACTUAL DEAD LOAD.
UPLIFTS NOT SPECIFIED SHALL BE 10 psf MINIMUM.
D. ANY CONCENTRATED LOADS OVER 50 lbs INCLUDING BUT NOT LIMITED TO MECHANICAL AND ELECTRICAL ITEMS. REFER TO STRUCTURAL, MECHANICAL AND ELECTRICAL PLANS FOR EQUIPMENT LOCATION AND
APPROXIMATE EQUIPMENT WEIGHT.
3. THE CONTRACTOR SHALL COORDINATE LOCATIONS AND WEIGHTS OF MECHANICAL AND ELECTRICAL EQUIPMENT
WITH THE JOIST MANUFACTURER BEFORE JOISTS ARE FABRICATED.
4. JOISTS, JOIST SUBSTITUTES, AND JOIST GIRDERS AT COLUMN GRID LINES SHALL BE DESIGNED FOR AN AXIAL LOAD OF 4,000 lbs.
5. JOIST BRIDGING SHALL BE PROVIDED BY THE JOIST MANUFACTURER AS REQUIRED.
6. SEE STRUCTURAL DRAWINGS FOR ADDITIONAL REQUIREMENTS.
METAL DECKING NOTES:
1. MATERIALS:
THE FOLLOWING ARE MINIMUMS
FLOOR DECK ........................................................................... ASTM A 653, SS, GRADE 50 (Fy = 50 ksi), G90 GALVANIZED ROOF DECK ............................................................................. ASTM A 653, SS, GRADE 33 (Fy = 33 ksi), G90 GALVANIZED CLOSURE PLATES/ANGLES ................................................... ASTM A 653, SS, GRADE 33 (Fy = 33 ksi), G90 GALVANIZED
2. MECHANICAL PROPERTIES:
THE FOLLOWING ARE MINIMUMS
FLOOR DECK:
TYPE ........................................................................................ 1.0 WR FORM DECK THICKNESS ............................................................................. 20 GAGE FASTENER PATTERN ............................................................. 36/3, 5/8" PUDDLE WELD OR EQUAL NO. OF SIDE LAP FASTENERS .............................................. 4, #10 TEK SCREWS OR EQUAL
ROOF DECK:
TYPE ........................................................................................ 1.5 WR ROOF DECK THICKNESS ............................................................................. 20 GAGE FASTENER PATTERN ............................................................. 36/5, #12 TEK SCREWS OR EQUAL NO. OF SIDE LAP FASTENERS .............................................. 5, #10 TEK SCREWS OR EQUAL
3. PROVIDE METAL DECKING AND CLOSURE PLATES/ANGLES IN COMPLIANCE WITH SDI "DESIGN MANUAL FOR COMPOSITE DECKS, FORM DECKS, ROOF DECKS AND CELLULAR METAL FLOOR DECK WITH ELECTRICAL
DISTRIBUTION", LATEST EDITION AND SDI "DIAPHRAGM DESIGN MANUAL" LATEST EDITION.
4. BEAR DECKING 2 in MINIMUM AT SUPPORTS. LAP DECKING AT ENDS 2 in MINIMUM AND CENTER LAPS OVER
SUPPORTS.
5. WELD METAL DECKING IN COMPLIANCE WITH ANSI/AWS D1.3 USING E60XX ELECTRODES MINIMUM. WELDERS
SHALL BE CERTIFIED AS REQUIRED BY AWS.
6. SUBMIT COMPLETE METAL DECKING SHOP DRAWINGS TO THE CONTRACTING OFFICER FOR REVIEW. SHOP
DRAWINGS SHALL INDICATE ICC REPORT NUMBER, IF APPLICABLE.
7. ALL DECKING SHALL BE CONTINUOUS OVER AT LEAST 2 SPANS UNLESS OTHERWISE NOTED.
8. WHERE NO SPECIFIC SUPPORT IS INDICATED, PROVIDE CONTINUOUS L3X3X1/4 OR EQUIVALENT BENT PLATE AS
REQUIRED TO SUPPORT DECK EDGES.
9. FLOOR DECK: PROVIDE FLASHING AND CLOSURE PLATES AT ENDS OF DECK UNITS AROUND COLUMN OPENINGS
AND PERIMETER LOCATIONS REQUIRING CONCRETE UNLESS OTHERWISE NOTED OR SHOWN.
10. ROOF DECKS: DO NOT SUSPEND PIPING, DUCT WORK, UTILITIES, SUSPENDED CEILINGS, LIGHT FIXTURES OR
OTHER LOADS FROM ROOF DECKING.
ABBREVIATIONS:
ALT ALTERNATE
ACI AMERICAN CONCRETE INSTITUTE
AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION
AISI AMERICAN IRON AND STEEL INSTITUTE
ASCE AMERICAN SOCIETY OF CIVIL ENGINEERS
ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS
AB ANCHOR BOLT
ARCH ARCHITECT, ARCHITECTURAL
@ AT (MEASUREMENT)
B PL BASE PLATE
BM BEAM
BRG BEARING
BF BOTH FACES
BOT BOTTOM
BLDG BUILDING
CL CENTER LINE
CLR CLEAR
COL COLUMN
CONC CONCRETE
CMU CONCRETE MASONRY UNIT
CONN CONNECTION
CONT CONTINUOUS
CJ CONTROL OR CONSTRUCTION JOINT
COORD COORDINATE
DL DEAD LOAD
DET DETAIL
DIA DIAMETER
DWG(S) DRAWING(S)
EA EACH
EF EACH FACE
ES EACH SIDE
EW EACH WAY
EL ELEVATION
EQ EQUAL
EQUIP EQUIPMENT
EXIST EXISTING
EXP BT EXPANSION BOLT
EJ EXPANSION JOINT
EXT EXTERIOR
FS FAR SIDE
FIN FLR FINISHED FLOOR
FF EL FINISHED FLOOR ELEVATION
FDTN FOUNDATION
ft FEET
GA GAGE
GALV GALVANIZED
HORIZ HORIZONTAL
IBC INTERNATIONAL BUILDING CODE
IJ ISOLATION JOINT
in INCH(ES) k KIP(S)
LL LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
MFR('S) MANUFACTURER('S)
MCJ MASONRY CONTROL JOINT
MAX MAXIMUM
MECH MECHANICAL
MIN MINIMUM
I MOMENT OF INERTIA
NS NEAR SIDE
NTS NOT TO SCALE
OC ON CENTER
OCEW ON CENTER EACH WAY
OPP OPPOSITE
lb(s) POUND(S) plf POUNDS PER LINEAR FOOT psf POUNDS PER SQUARE FOOT pcf POUNDS PER CUBIC FOOT
PEMB PRE-ENGINEERED METAL BUILDING
QTY QUANTITY
R RADIUS
RC REINFORCED CONCRETE
REINF REINFORCEMENT
REBAR REINFORCING STEEL BARS
REQ(D) REQUIRE(D)
ROT ROTATED
SJ SAW JOINT
SCHED SCHEDULE
SIM SIMILAR
SQ SQUARE
sf SQUARE FEET sq in SQUARE INCH(ES) sq yd SQUARE YARD
SSMR STANDING SEAM METAL ROOF
SDI STEEL DECK INSTITUTE
SJI STEEL JOIST INSTITUTE
STRCT STRUCTURAL
THRU THROUGH
T&B TOP AND BOTTOM
TO TOP OF
TOB TOP OF BEAM
TOC TOP OF CONCRETE
TOM TOP OF MASONRY
TOS TOP OF STEEL
TOW TOP OF WALL
TL TOTAL LOAD
TYP TYPICAL
UFC UNIFORM FACILITIES CRITERIA
UON UNLESS OTHERWISE NOTED
UNO UNLESS NOTED OTHERWISE
VERT VERTICAL
yd YARD
SPECIAL INSPECTION NOTES:
1. SPECIAL INSPECTOR: EMPLOYED BY THE CONTRACTOR ACTING AS THE GOVERNMENTS AGENT (IBC SECTION
1704.1).
2. REPORTS: PREPARED BY THE INSPECTOR, SIGNED BY AN ENGINEER AND SUBMITTED TO THE CONTRACTING OFFICER. ALL DISCREPANCIES SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE CONTRACTOR FOR
CORRECTION; THEN, IF NOT CORRECTED, TO THE CONTRACTING OFFICER.
3. THE SPECIAL INSPECTION IS TO BE CONTINUOUS DURING THE PERFORMANCE OF THE WORK UNLESS
OTHERWISE NOTED.
4. CERTIFICATION: THE INSPECTOR SHALL BE CERTIFIED BY THE CONTRACTING OFFICER TO PERFORM THE TYPES OF SPECIAL INSPECTIONS SPECIFIED. A CERTIFICATE OF SATISFACTORY COMPLETION OF WORK REQUIRING
SPECIAL INSPECTION SHALL BE COMPLETED AND SUBMITTED TO THE CONTRACTING OFFICER.
5. OFF-SITE FABRICATION:
A. SUBMIT APPLICATION TO THE CONTRACTING OFFICER FOR APPROVAL PRIOR TO FABRICATION.
B. SUBMIT A CERTIFICATE OF COMPLIANCE FOR OFF-SITE FABRICATION TO THE CONTRACTING OFFICER
PRIOR TO ERECTION OF PRE-FABRICATED COMPONENTS.
ITEM CONTINUOUS
(REF. NOTE 3)
PERIODIC
(REF. NOTE 3)
SOILS:
GRADING, EXCAVATION & FILL
FINAL FOUNDATION PREPARATION
CONCRETE:
REINFORCING PLACEMENT
REINFORCING WELDING
REINFORCING COUPLING
ANCHOR BOLTS & INSERTS
MATERIAL VERIFICATION
PREPARATION OF TEST SPECIMENS
CONCRETE PLACEMENT
EPOXY & EXPANSION ANCHOR PLACEMENT
CURING
STRUCTURAL STEEL:
HIGH STRENGTH BOLTING
WELDING OF ANCHORS & STUDS
WELDING OF STAIRS & RAILING SYSTEMS
STEEL DECK WELDING
EMBEDED PLATES
DETAIL CONFORMANCE
SHOP WELDING (REF. NOTE 2):
SINGLE PASS FILLET WELDS < 5/16 in.
FILLET WELDS > 5/16 in.
PARTIAL & COMPLETE PENETRATION WELDS
FIELD WELDING:
SINGLE PASS FILLET WELDS < 5/16 in.
FILLET WELDS > 5/16 in.
PARTIAL & COMPLETE PENETRATION WELDS
COLD-FORMED STEEL FRAMING WELDS
FLOOR…