Revised_Sheet_E203.pdf
PDF 327 KB Posted
- Attached to
- Construct Aircraft Apron- MTANG Federal contract opportunity
- Solicitation number
- W9124V19B0002
About this file
This document includes an electrical site plan sheet and details for a federal contract opportunity to construct an aircraft apron at Montana Army National Guard. Key requirements include replacing existing lighting with new LED luminaires and floodlights, installing new lighting controls and a panelboard, upgrading power distribution infrastructure to support the new lighting layout, and providing interior and exterior lighting controls at on-site buildings. The solicitation is identified as number W9124V19B0002 and is being issued by the Department of the Army Montana Army National Guard to construct the aircraft apron. No pricing or response deadline details are provided in the opportunity description.
Revised Sheet E203
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Abstract_OF_1419_certified.pdf | ||
| MTANG_Apron_S100,S200,S201.pdf | ||
| FAA.P-153.pdf | ||
| W9124V19B0002_Amendment_0002_SF_30.pdf | ||
| Questions_as_of_22_Aug.pdf | ||
| W9124V19B0002_Amendment_0001.pdf | ||
| 52.204-24.pdf | ||
| W9124V19B0002_0001_SF30.pdf | ||
| CQCP_C-100.pdf | ||
| Revised_Sheet_E415.pdf | ||
| 52.204-25.pdf | ||
| Questions_as_of_16_Aug.pdf | ||
| Questions_as_of_8_Aug.pdf | ||
| W9124V19B0002_Site_Visit_notes.pdf | ||
| SiteVisitSignInSheet.pdf | ||
| Pre-Bid_Conference_Slides.pdf | ||
| W9124V19B0002_MTANG_Construct_Aircraft_Apron.pdf |
Show all 17
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1 3 5 7
W A R N
IN
G
W A R N
IN
G
W A R N
IN
G
W A R N
IN
G
T T
(12) NEW LED APRON LIGHTS AND (2) NEW
FLOOD LIGHTS MOUNTED ON BUILDING 80.
NEW LOCATION FOR EXISTING POLE
REMOVED DURING DEMOLITION.
J
59' SETBACK LINE. ALL SITE POLES AND
EQUIPMENT LOCATED ABOVE GRADE TO BE
LOCATED OUTSIDE OF THIS LINE.
1 2
6 7
13 14
EXISTING TRANSFORMER
WITH FEED-THROUGH,
PRIMARY LUGS.
NEW LIGHT CONTROLS
MOUNTED ON BUILDING 80
NEW METER/CT'S AND
PANELBOARD LDP
LDP-13
FLAG NOTES THIS SHEET:
1. REPLACE THE (12) EXISTING 1000W HPS
LUMINAIRES REMOVED DURING DEMOLITION WITH
(12) TYPE A LED LUMINARIES. CONNECT TO NEW
LIGHTING DISTRIBUTION PANEL LDP. DRIVERS FOR
THE NEW LUMINAIRES TO BE REMOTELY LOCATED
IN A MUSCO NEMA 3R ENCLOSURE LOCATED ON
THE LIGHT POLE.
2. REPLACE THE (2) EXISTING 400W SECURITY FLOOD
LIGHTS REMOVED DURING DEMOLITION WITH (2)
TYPE B LED LUMINAIRES. DRIVERS FOR THE NEW
LUMINAIRES TO BE REMOTELY LOCATED IN A
MUSCO NEMA 3R ENCLOSURE LOCATED ON THE
LIGHT POLE.
3. PROVIDE NEW LIGHTING CONTROLS IN NEMA 3R
ENCLOSURE MOUNTED ON CONCRETE PEDESTAL.
COORDINATE WITH MUSCO LIGHTING CONTROLS
BEING INSTALLED ON LIGHT POLES.
4. DRIVERS FOR THE NEW LUMINAIRES TO BE
REMOTELY LOCATED IN A MUSCO NEMA 3R
ENCLOSURE LOCATED ON THE LIGHT POLE.
5. PROVIDE NEW CONCRETE BASE TO MATCH
EXISTING AND INSTALL EXISTING POLE REMOVED
AND SAVED DURING DEMOLITION.
6. PROVIDE BARE COPPER 2/0 AWG DOWN LEAD
FROM LIGHTNING PROTECTION AIR TERMINAL
DOWN INSIDE POLE AND OUT TO A BURIED 3/4" DIA
OR LARGER COPPER GROUND ROD, 10'-0" MIN
EMBEDMENT.
7. PROVIDE NEW 277V POWER CONNECTION TO
EXISTING FAA OBSTRUCTION LIGHTS TO NEW
PANEL LDP.
8. PROVIDE PRIMARY FEEDER FROM EXISTING
TRANSFORMER FOR RECONNECTION OF EXISTING
RELOCATED 500KVA TRANSFORMER. PROVIDE
NEW TRANSFORMER PAD WITH CUT OUTS IN PAD
FOR INCOMING AND OUT GOING CONDUITS FOR
TRANSFORMER CONNECTIONS AND ALSO THE
CONDUITS BEING PROVIDED FOR FUTURE USE.
SEE FLAG NOTES 9 AND 10 BELOW.
9. PROVIDE (1) 4" PVC CONDUIT FROM EXISTING
RELOCATED 500KVA AROUND NEW APRON
LOCATION TO EXISTING FENCE LINE TO THE WEST
OF FORMER BUILDINGS 45,46,47, 48, (THESE
BUILDINGS HAVE BEEN REMOVED, USE PAD FOR
LOCATION REFERENCE) AND OUT TO ROAD
CROSSING TO THE SOUTHWEST OF THESE
BUILDINGS. IN -GRADE PULL BOXES TO BE
INSTALLED EVERY 400'-0" ALONG CONDUIT
ROUTING. EXACT LOCATIONS OF BOXES TO BE
FIELD VERIFIED WITH OWNER PRIOR TO START OF
WORK.
10. PROVIDE (3) 3" CONDUITS FROM TRANSFORMER
SECONDARY STUB OUT INTO IN GRADE BOX FOR
FUTURE USE.
11. PROVIDE (1) 4" PVC FOR 480V FUTURE POWER
(SEE FLAG NOTE 9.) AND FEEDER FOR NEW
SERVICE ENTRANCE RATED PANELBOARD LDP.
SEE ONE LINE DIAGRAM ADDITIONAL ELECTRICAL
REQUIREMENTS AND INFORMATION.
12. FEEDER FOR NEW SERVICE ENTRANCE RATED
PANELBOARD LDP AND A FEEDER FOR LIGHT POLE
CIRCUIT IN A 3"PVC, SEE ONE LINE DIAGRAM AND
PANELBOARD SCHEDULE FOR ADDITIONAL
ELECTRICAL REQUIREMENTS AND INFORMATION.
13. PROVIDE (12) TYPE A LED LUMINAIRES MOUNTED
ON BUILDING 80. CONNECT TO NEW LIGHTING
DISTRIBUTION PANEL LDP. DRIVERS FOR THE NEW
LUMINAIRES TO BE REMOTELY LOCATED IN A
MUSCO NEMA 3R ENCLOSURE LOCATED ON THE
BUILDING. COORDINATE WITH MUSCO SUPPLIER.
SEE STRUCTURAL SHEETS FOR ADDITIONAL
MOUNTING INFORMATION.
14. PROVIDE (2) TYPE B LED LUMINAIRES MOUNTED
ON BUILDING 80 AT +30'-0'' AFG. CONNECT TO NEW
LIGHTING DISTRIBUTION PANELBOARD
LDP.DRIVERS FOR THE NEW LUMINAIRES TO BE
REMOTELY LOCATED IN A MUSCO NEMA 3R
ENCLOSURE LOCATED ON THE BUILDING.
COORDINATE WITH MUSCO SUPPLIER. SEE
STRUCTURAL SHEETS FOR ADDITIONAL
MOUNTING INFORMATION.
15. PROVIDE NEW LIGHTING CONTROLS IN NEMA 3R
ENCLOSURE SURFACE MOUNTED TO BUILDING.
16. NEW SERVICE ENTRANCE RATED PANELBOARD
'LDP' FED FROM THE EXISTING RELOCATED
500KVA TRANSFORMER FOR POWER
DISTRIBUTION TO ALL SITE POLES. PROVIDE IN
NEMA 3R ENCLOSURE SURFACE MOUNTED TO
BUILDING.
17. FEEDER FOR NEW SERVICE ENTRANCE RATED
PANELBOARD LDP AND (2) FEEDERS FOR LIGHT
POLE CIRCUITS EACH IN A 2"PVC. SEE ONE LINE
DIAGRAM AND PANELBOARD LDP SCHEDULE ON
E4.0 FOR ADDITIONAL ELECTRICAL
REQUIREMENTS AND INFORMATION.
18. INTERCEPT EXISTING 2"PVC AND PROVIDE A PULL
BOX. EXTEND TO PANELBOARD 'LDP'.
19. PROVIDE NEW POWER WIRING FOR NEW POLE
LIGHTING IN EXISTING 2"PVC.
20. PROVIDE NEW POLE LIGHT POWER FEED IN 2" PVC.
21. PROVIDE TYPE 'BP' FIXTURE ON BACKSIDE OF
BUILDING 80 AT 30' AFG. SEE STRUCTURAL PLANS
FOR ADDITIONAL MOUNTING INFORMATION AND
EXACT LOCATION. FIXTURE CONTROLLED VIA
INTEGRAL PHOTOCELL.
22. PROVIDE NEW EXTRA HEAVY DUTY AIR PORT
RATED COVER ON EXISTING IN GROUND PULL
BOX. COORDINATE EXACT LOCATION WITH
MONTANA AIR NATIONAL GUARD. SEE DETAILS ON
SHEET E415 FOR ADDITIONAL INFORMATION.
23. EXISTING 18" RCP CULVERT.
24. EXISTING FIRE HYDRANT.
25. EC SHALL PROVIDE INTERIOR LIGHTING CONTROL
STATIONS AT MOCC AND BDOC ON CAMPUS.
PROVIDE EXTERIOR ANTENNA ON BUILDING(S)
WITHIN 50' OF CONTROL LOCATION. SEE INTERIOR
LIGHTING CONTROL SCHEMATIC AND LIGHTING
CONTROL SEQUENCE OF OPERATIONS FOR MORE
INFORMATION. COORDINATE EXACT LOCATIONS
OF INTERIOR CONTROLS WITH OWNER ON SITE.
NOTE: NOT ALL FLAG NOTES MAY BE USED ON THIS SHEET.
BIM FILE PATH:
SHEET NO.:
TITLE:
copyright 2019 SMA, P.C.
KEYMAP:
BILLINGS
175 North 27th Street | Suite 1312 Billings | MT | 59101 P| 406/545.46420 www.mkkeng.com
ENGINEER SEAL:
PROJECT:
PROJECT LOCATION:
PREPARED FOR:
LOGO:
PROJECT NUMBER:
DRAWN BY:
CHECKED BY:
TEAM:
PHASE:
DATE:
PROJECT NUMBER:
Pl ot
D at e:
HELENA
920 Front Street | Suite 104 Helena | MT | 59601 P| 406/438.1467 www.mkkeng.com
BID SET
REVISIONS:
No. Date Revision Description
F:\sitedev\17209 - MANG Apron\Apron-CADD
JKSE 169101
16 MAY 2019
W. VORDERBERG
C. LAFERRIERE
MTANG C-130 APRON
GREAT FALLS, MT
TYPE B-3 SUBMITTAL
Robert Peccia & Associates, Inc.
1-800-667-8160 ã 2019
5/16/19
5/ 1/
F ile fil es
\C or po ra te \O ffi ce s\ De nv er
\M
KK
\0 3-
Bi lli ng s\
.0 3.
M
TA
NG
A pr on
L ig ht in g\
DW
GS
\E
1.
EL
EC
TR
IC
AL
S
IT
E
PL
AN
PA
RT
IA
L_ 1.
dw g
E203
APRON ELECTRICAL SITE PLAN
- PARTIAL AREA B
SCALE:
NORTH
APRON ELECTRICAL SITE PLAN - PARTIAL AREA B
1" = 100'1
N
1 13 AUG 2019 ADDENDUM #1
AutoCAD SHX Text
SM
AutoCAD SHX Text
ELECT
AutoCAD SHX Text
MW
AutoCAD SHX Text
MW
AutoCAD SHX Text
MW
AutoCAD SHX Text
MW
AutoCAD SHX Text
MW
AutoCAD SHX Text
MW
AutoCAD SHX Text
MW
AutoCAD SHX Text
MW
AutoCAD SHX Text
CO
AutoCAD SHX Text
SM
AutoCAD SHX Text
MW
AutoCAD SHX Text
MW
AutoCAD SHX Text
MW
AutoCAD SHX Text D
AutoCAD SHX Text D
AutoCAD SHX Text
MW
AutoCAD SHX Text W
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text
PV
AutoCAD SHX Text
ELECT
AutoCAD SHX Text
MW
AutoCAD SHX Text
MW
AutoCAD SHX Text
PV
AutoCAD SHX Text
MW
AutoCAD SHX Text
MW
AutoCAD SHX Text
PV
AutoCAD SHX Text
ELECT
AutoCAD SHX Text D
AutoCAD SHX Text
PV
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text D
AutoCAD SHX Text
PV
AutoCAD SHX Text
CO
AutoCAD SHX Text
MW
AutoCAD SHX Text T
AutoCAD SHX Text D
AutoCAD SHX Text
MW
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
REFERENCE
AutoCAD SHX Text
TRUE
| Sheets and Views |
| E1.2 ELECTRICAL SITE PLAN - PARTIAL AREA B |
File details come from the government source that posted it. Updated .