W911SA19B2009_Attachment_2_CLIN_0001_Drawings.pdf

PDF 7 MB Posted

Attached to
Construct 5 Buildings at Fort McCoy, WI Federal contract opportunity
Solicitation number
W911SA19B2009
Issued by
Department of the Army Materiel Command Mission and Installation Contracting Command Fort McCoy

About this file

Attachment 2 CLIN 0001 Drawings

View the file

Other files for this federal contract opportunity

Other files attached to Construct 5 Buildings at Fort McCoy, WI, newest first.
File Type Posted
W911SA19B2009_Abstract_of_Offers.pdf PDF
W911SA19B20090002_Solicitation_Amendment_0002.docx DOCX document
W911SA19B2009_Attachment_2_CLIN_0001_Drawings_Amended_7-12-19.pdf PDF
W911SA19B2009_Attachment_7_CLINs_0006_and_0007_Drawings_Amended_7-12-19.pdf PDF
W911SA19B2009_Attachment_6_CLIN_0005_Drawings_Amended_7-12-19.pdf PDF
W911SA19B2009_Attachment_11_Drawing_Groundwater.pdf PDF
W911SA19B2009_Attachment_5_CLIN_0004_Drawings_Amended_7-12-19.pdf PDF
W911SA19B2009_Attachment_3_CLIN_0002_Drawings_Amended_7-12-19.pdf PDF
W911SA19B2009_Attachment_4_CLIN_0003_Drawings_Amended_7-12-19.pdf PDF
W911SA19B20090001_Solicitation_Amendment_0001.docx DOCX document
W911SA19B2009_site_visit_sign_in_sheet.pdf PDF
W911SA19B2009_Attachment_8_Specifications.pdf PDF
W911SA19B2009_Attachment_9_Wage_Determination.docx DOCX document
W911SA19B2009_Solicitation.docx DOCX document
W911SA19B2009_Attachment_5_CLIN_0004_Drawings.pdf PDF
W911SA19B2009_Attachment_3_CLIN_0002_Drawings.pdf PDF
W911SA19B2009_Attachment_6_CLIN_0005_Drawings.pdf PDF
W911SA19B2009_Attachment_10_SF24.pdf PDF
W911SA19B2009_Attachment_1_AT_OPSEC.pdf PDF
W911SA19B2009_Attachment_4_CLIN_0003_Drawings.pdf PDF
W911SA19B2009_Attachment_7_CLINS_0006_and_0007_Drawings.pdf PDF
Show all 21

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Fort McCoy, Wisconsin

SHEET INDEX:

2012 IBC CODE SUMMARY

PROJECT SQUARE FOOTAGE

EXITING INFORMATION

SYMBOLS

CODE INFORMATION

CALCULATION:

1.

LIFE SAFETY:

APPLICABLE CODES:

3.

2. UNIFIED FACILITIES CRITERIA (UFC) 1-200-01

GENERAL BUILDING REQUIREMENTS

NFPA 101 - LIFE SAFETY

CODE 2009 EDITION

CAPACITY OF BUILDING AT ONE TIME WILL BE 80. EXIT WIDTH IS BASED ON .15" PER

PERSONS. (IBC TABLE 1005.1)

EXIT TRAVEL DISTANCE : 300'

WITH SPRINKLER - MIN. 2 EXITS 3

PROVIDED

DIRECTION OF

EGRESS

TOTAL EXIT WIDTH

AT DOOR

BUILDING INFORMATION:

MINIMUM NUMBER OF

SANITARY FIXTURES

TABLE 2902.1

SANITARY FIXTURE COUNT:

TABLE 2902.1

40 MALE / 40 FEMALE (SEE TABLE THIS SHEET)

1 PER 50 WATER CLOSET, 1 PER 50 LAVATORIES

TYPE OF CONSTRUCTION:

MAX. HEIGHT & NO. OF STORIES:

BASEMENT:

MEZZANINE:

OCCUPANCY SEPARATION REQUIRED:

ROOF ACCESS:

OCCUPANT LOAD FOR EXITING:

TYPE V-B

55'-0", 4 STORY

NO

NO

NOT REQUIRED

NO

SEE TABLE THIS SHEET

SPRINKLER SYSTEM:

TYPE OF SYSTEM:

YES (ALLOWS INCREASES IN HEIGHT & FLOOR AREA)

DRY

MEN - TOILETS

MEN - URINALS

REQ'D PROVIDED TOTAL

ELECTRIC WATER COOLERS (1 ACCESSIBLE)

SINKS W/ FAUCET SPIGOTS OR CUP DISPENSERS

BOTTLED WATER COOLER BY OWNER (1 ACCESSIBLE)

DRINKING WATER SOURCE:

PROVIDED TOTALREQ'D0

4 1

OCCUPANCY GROUP A-3 = 80

TOTAL = 80

= 40 MALE / 40 FEMALE

CALCULATION:

OCCUPANCY GROUP A-3 = 80 X 0.2 = 16"

TOTAL REQUIRED = 16"

TOTAL PROVIDED = 204.0"

OCCUPANCY GROUP A-3 = 6,673

TOTAL = 6,673 SQUARE FEET

68'

68'

GENERAL

G1.0 COVER SHEET AND CODE ANALYSIS

STRUCTURAL

S0.0 GENERAL NOTES & SCHEDULES

S0.1 FOUNDATION PLAN

S3.1 ROOF FRAMING PLAN

S7.1 STRUCTURAL DETAILS

S7.2 MASONRY DETAILS

ARCHITECTURAL

A0.0 GENERAL NOTES & SYMBOLS

A1.1 NOTED FLOOR PLAN

A1.2 DIMENSIONED FLOOR PLAN AND DETAILS

A2.1 REFLECTED CEILING PLAN

A2.2 TYPICAL WALL/CEILING DETAILS

A3.1 ROOF PLAN

A3.2 TYPICAL ROOF DETAILS

A4.1 EXTERIOR ELEVATIONS

A4.2 EXTERIOR ELEVATIONS

A5.1 BUILDING SECTIONS

A5.2 WALL SECTIONS

A5.3 SECTION DETAILS

A5.4 WALL TYPES AND DETAILS

A6.1 INTERIOR ELEVATIONS AND MOUNTING HEIGHTS

A7.1 DOOR DETAILS

A8.1 SCHEDULES

FIRE PROTECTION

F0.0 FIRE ALARM GENERAL NOTES AND SYMBOLS LEGEND

F1.1 FIRE ALARM PLAN

F1.2 FIRE PROTECTION PLAN

PLUMBING

P0.0 GENERAL NOTES AND SYMBOL LEGEND

P1.1 BELOW GRADE PLAN AND DWV ISOMETRIC

P1.2 ABOVE GRADE PLAN AND WATER ISOMETRIC

MECHANICAL

M0.0 ABBREVIATIONS AND SYMBOLS

M1.1 HVAC PLAN

M1.2 ENLARGED MECHANICAL ROOM PLAN

M5.1 MECHANICAL ROOM SECTIONS

M8.1 HVAC SCHEDULES

ELECTRICAL

E0.0 ELECTRICAL SYMBOLS

E1.1 ELECTRICAL COMMUNICATION PLAN

E1.2 ELECTRICAL POWER PLAN

E1.3 ELECTRICAL LIGHTING PLAN

E2.1 ELECTRICAL DETAILS & SCHEDULES

UNISEX - URINALS

WOMEN - TOILETS

UNISEX - TOILETS

MEN - LAVATORIES

WOMEN - LAVATORIES

UNISEX - LAVATORIES

DRINKING FACILITIES REQ'D

REQ'D

REQ'D

REQ'D

PROVIDED TOTAL

PROVIDED TOTAL

PROVIDED TOTAL

PROVIDED TOTAL

PROVIDED TOTAL

PROVIDED TOTAL

PROVIDED TOTAL

REQ'D

REQ'D

REQ'D--

68'

CBA

B224-G1.0

A nt ho ny

L an e M in ne ap ol is , M

N

P:

-4

-3

2, F : 6

-4

-3

EXIT DIAGRAM

1/6 CLIN0001

CONSTRUCT TACTICAL ANALYSIS

FEEDBACK FACILITY (TAFF)

BUILDING 224

ALLOWABLE AREA:

ALLOWABLE AREA W/AUTOMATIC SPRINKLER:

6,000 S.F.

18,000 S.F.

ACTUAL AREA: 6,673S.F.

FIRE SEPARATION BETWEEN BLDGS: > 30 FT.

ACTUAL HGT. : APPROX 25 FT.

ACTUAL STORIES: ONE

OCCUPANCY GROUP: A3

FIRE SEPARATION

BETWEEN BLDGS GREATER THAN 30'

2985 SOUTH RIDGE ROAD, SUITE B

GREEN BAY, WI 54304

T 920-468-1978 AECOM Project Number: 60344155

LINTEL SCHEDULE

L-1 W8x18 W/ 3/8" BOTT. PLATE & 3/8" x 4" STUDS @ 16" O.C. TOP

7 1/2" MIN. NOTES #1,2,3

NOTES:

1. CMU CORES W/HEADED STUDS SHALL BE GROUTED

2. GROUT & REINFORCE JAMB W/ (1) #5.

3. PROVIDE 7"x10"x 3/8" BEARING PLATE IN MASONRY WALL W/ (2)

1/2" Ø x 6" HEADED STUDS WELD BEAM TO PLATE

LINTEL DESCRIPTION BEARING

EA. END REMARKS

MASONRY REINFORCING SCHEDULE

NOTES:

1. IN ADDITION TO THE SCHEDULED VERTICAL REINFORCING, ALL CONCRETE BLOCK

WALLS, INCLUDING THOSE WITH NO SCHEDULED REINFORCING, SHALL HAVE ALL

CORES AT CORNERS AND ADJACENT TO OPENINGS GROUTED AND REINFORCED

WITH (1) #5 BAR.

2. SEE FOR REINFORCING ADJACENT TO EXTERIOR OPENINGS IN CMU WALLS.

3. ALL MASONRY COURSING SHALL BE RUNNING BOND UNLESS NOTED OTHERWISE.

4. MASONRY REINFORCING SHALL BE GRADE 60.

5. f'm = 1500 PSI, MORTAR TYPE S COMPRESSIVE STRENGTH = 1800 PSI, ASTM-C-270

6. MATERIALS:

A. CMU UNITS SHALL COMPLY WITH ASTM C-90, GRADE N.

CMU UNITS SHALL HAVE MIN. 28 DAY COMPRESSIVE STRENGTHS:

NET AREA = 2150 PSI

GROSS AREA = 1000 PSI

B. MORTAR TYPE S (1800 PSI).

C. MASONRY GROUT ASTM C476 (2500 PSI MIN.)

7. REINFORCING SPLICE LAP LENGTHS (MINIMUM):

#4 BARS: 25"

#5 BARS: 31"

#6 BARS: 52"

#7 BARS: 61"

#8 BARS: 75"

8. HORIZONTAL JOINT REINFORCING REQUIRED AT EVERY COURSE BELOW GRADE &

EVERY OTHER COURSE ABOVE GRADE UNLESS NOTED OTHERWISE.

9. MASONRY MARK INDICATES SIZE & REINFORCING OF CMU'S ABOVE GRADE.

10. CONTROL JOINTS:

-PROVIDE MCJ'S AT 24'-0" O.C. MAX. SPACING.

-ONE CORE SHALL BE GROUTED & REINFORCED EACH SIDE OF CONTROL

JOINTS.

-HORIZONTAL JOINT REINFORCING SHALL NOT CONTINUE THROUGH JOINT.

-BOND BEAM REINF SHALL EXTEND THROUGH JOINT

-SEE ARCHITECTURAL ELEVATIONS FOR CONTROL JOINT LOCATIONS.

11. MASONRY UNITS BELOW GRADE SHALL BE GROUTED SOLID.

12. PROVIDE BOND BM. W/ (2) #5 BOTT. @ JOIST BEARING.

13. MASONRY SHALL COMPLY WITH BUILDING CODE REQUIREMENTS FOR MASONRY

STRUCTURES (ACI 530-11/ASCE 5-11/TMS 402-11), SPECIFICATION FOR

MASONRY STRUCTURES (ACI 530.1-11/ASCE 6-11/TMS 602-11) AND THEIR

RESPECTIVE COMMENTARIES. THIS INCLUDES PROVISIONS FOR COLD AND HOT

WEATHER CONSTRUCTION REQUIREMENTS.

14. NON-SCHEDULED LINTELS IN NON-BEARING INTERIOR WALLS SHALL BE:

OPENING WIDTH LINTEL

X ≤ 4'-0" 8"D BOND BM W/ (2) #4 BOTT.

4'-0" < X ≤ 6'-0" 16"D BOND BM W/ (2) #4 BOTT.

15. SEE SHEET S7.2 FOR TYPICAL MASONRY REINFORCING DETAILS

16. MASON SHALL MARK GROUTED & REINFORCED CORES WITH A PENCIL "X" FOR EASY

IDENTIFICATION DURING CONSTRUCTION.

17. BRACE MASONRY WALLS UNTIL ROOF SYSTEM IS IN PLACE.

MARK

M-1

BLOCK WIDTH

8"

VERTICAL REINFORCING

#5 @ 48" O.C.

DOWELS (CMU TO FOOTING)

#5 x 3'-6" @ 48" O.C.

TYPICAL LINTEL CONFIGURATION

7 1/2"@ 8" WALL

11 1/2"@ 12" WALL

1/8 4@12

L-X @ MASONRY WALL

STRIP FOOTING SCHEDULE

MARK WIDTH REINFORCINGDEPTH

SF-1 (4) #5 CON'T

SEE PLAN & GENERAL NOTES FOR ADDITIONAL INFORMATION.

3'-0" 12"

CONCRETE SCHEDULE

CLASS OF CONSTRUCTION

CLASS A

STRENGTH

@ 28 DAYS

MAXIMUM

AGGREGATE

MINIMUM CEMENT

(BAGS/CY)

AIR CONTENT

BY VOLUME

MAXIMUM

WATER/CEMENT

5% TO 7%

CLASS B CLASS C CLASS D CLASS E CLASS F

4000 PSI 4000 PSI 4000 PSI 4000 PSI 4000 PSI 3000 PSI

3 1/2" 3 1/2" 3 1/2"4" 4" 8"

3/4" 3/4" 1 1/2" 5/8" 3/8"

6 6 5 3/45 1/4 5 5 1/4

1% TO 3% 5% TO 7% 1% TO 3% 1% TO 3% 1% TO 3%

.45 .45 .45 .65.50 .50

SPECIFIC USE CLASS

FOUNDATION & RETAINING WALL FOOTINGS

COLUMN FOOTINGS

EXTERIOR WALLS & PIERS

EXTERIOR SLABS, STOOPS, WALKS, CURBS

MEZZANINE FLOOR SLABS

CMU BOND BEAMS, COREFILL (MASONRY GROUT)

A OR B

A OR B

C A

B

E F

3/4"

NOTES:

1. CLEAR CONCRETE COVER FOR REINFORCING STEEL:

A. MASONRY: LOCATE IN CENTER OF WALL (U.N.O.)

B. WALLS: 2" EXTERIOR FACES

1 1/2" INTERIOR FACES

C. FOOTINGS: 2" FORMED EDGES

3" CAST AGAINST GROUND

2. REINFORCING STEEL SHALL COMPLY WITH ASTM A615 GRADE 60

3. STANDARD BAR HOOKS:

#4: 6" #5: 7.5" #6: 9" #7: 10.5" #8: 12"

4. DO NOT WELD OR FIELD BEND REINFORCING BARS. EXCEPT AS APPROVED BY

ENGINEER.

5. LIMIT SIZE OF CONCRETE POURS. MAXIMUM LENGTH OF WALL AND SLAB POURS

SHALL NOT EXCEED 60 FT.

6. BEFORE CONCRETE IS PLACED, CONSTRUCTION JOINTS SHALL BE CLEANED AND

LAITANCE REMOVED AND SURFACE WETTED. STANDING WATER SHALL BE REMOVED.

7. CONSTRUCTION JOINTS SHALL HAVE ROUGHENED SURFACES. THE SURFACE SHALL

HAVE AN AMPLITUDE OF 1/4" MIN.

8. CHAMFER EXPOSED EDGES OF CONCRETE 3/4" UNLESS OTHERWISE NOTED.

9. EQUIPMENT PAD AND SLAB LOCATIONS, DIMENSIONS AND HEIGHTS TO BE

COORDINATED BY CONTRACTOR. VERIFY WITH EQUIPMENT MANUFACTURER'S

REQUIREMENTS.

DEVELOPMENT & LAP SPLICE LENGTH IN CONCRETE

BAR SIZE

#3

DEVELOPMENT LENGTH

15" #4 #5 #6

20" 25" 30"

#7 44"

CLASS B SPLICE

20" 26" 33" 40" 58"

DEVELOPMENT LENGTH CLASS B SPLICE

#8 #9

#10 #11

33" 40" 58" 75"

51" 66" 66" 86" 57" 74" 74" 96" 63" 82" 82" 107" 70" 91" 91" 118"

Fy = 60,000 psi Fc = 3500 psi MIN.

51" 43" 34" 26"

26" 20"

HORIZONTAL REINFORCING WITH 12" OR LESS

CONCRETE BELOW AND VERTICAL

REINFORCING

HORIZONTAL REINFORCING WITH GREATER

THAN 12" CONCRETE BELOW

MAXIMUM SLUMP

(BEFORE HRWR)

INTERIOR FLOOR SLABS: FLY ASH PERCENTAGE OF CEMENT

CONTENT LIMITED TO 10%. UTILIZE MID TO HIGH RANGE WATER

REDUCER TO ACHIEVE 6" SLUMP FOR CONCRETE THAT IS NOT

PUMPED. IF CONCRETE IS PUMPED, A PLASTICIZER MAY BE UTILIZED

TO ACHIEVE 8" MAX SLUMP PRIOR TO PUMPING. 1/2 % MAX

ACCELERATOR PERMITTED IN SLAB CONCRETE.

STRUCTURAL DESIGN LOADS

ABBREVIATIONS

TO TOP OF

TOF TOP OF FOOTING

TOW TOP OF WALL

TOL TOP OF LEDGE

TOC TOP OF CONCRETE

TOS TOP OF STEEL

TSL TOP OF SLAB

FDN FOUNDATION

SFX STRIP FOOTING TYPE

PX PIER TYPE

WWF WELDED WIRE FABRIC

JBE JOIST BEARING ELEVATION

TBE TRUSS BEARING ELEVATION

CJ CONTROL JOINTS

E.W. EACH WAY

E.F. EACH FACE

I.F.A. INNER FACE

O.F. OUTER FACE

A.G. ABOVE GRADE

S.O.G. SLAB ON GRADE

NLBW NON-LOAD BEARING

WALL

- S - FOOTING STEP

LGT LIGHT GAUGE TRUSS

DESIGN CODE: IBC 2012

LIVE LOADS:

GROUND FLOOR: 150 PSF

TRUSS DESIGN LOADS:

TOP CHORD LIVE (TCLL): 20 PSF OR 300 LB POINT LOAD

BOTTOM CHORD LIVE (BCLL): 10 PSF (NON CONCURRENT W/ TCLL)

COLLATERAL LOAD (BOTTOM CHORD) 5 PSF

SNOW LOADS:

GROUND SNOW LOAD, (Pg): 40 PSF SNOW LOAD EXPOSURE FACTOR, (Ce): 1.0 SNOW LOAD IMPORTANCE FACTOR, (Is): 1.0 THERMAL FACTOR, (Ct): 1.0 FLAT ROOF SNOW LOAD, (Pf ): 26.5 PSF

WIND LOAD:

ULTIMATE WIND SPEED, VULT: 115 MPH

NOMINAL DESIGN SPEED, VASD: 89 MPH

RISK CATEGORY II

WIND EXPOSURE CATEGORY C

ENCLOSURE CLASSIFICATION ENCLOSED

INTERNAL PRESSURE COEFFICIENT +/-0.18

MWFRS= WW+LW+INT: 27.4 psf NET UPLIFT: 15 psf

SEISMIC DATA

RISK CATEGORY II

SEISMIC IMPORTANCE FACTOR (Ie): 1.0

MAPPED SPECTRAL RESPONSE ACCELERATION PARAMETERS

Ss: 5.0 % g S1: 4.0 % g

SITE CLASS: D

DESIGN SPECTRAL RESPONSE ACCELERATION PARAMETERS

SDS: 5.3%g SD1: 6.4%g

SEISMIC DESIGN CATEGORY: A

BASIC SEISMIC FORCE-RESTRAINING SYSTEM:

ORDINARY REINFORCED MASONRY SHEAR WALLS

DESIGN BASE SHEAR 45 PLF

SEISMIC RESPONSE COEFFICIENT (CS): .01

RESPONSE MODIFICATION FACTOR (R): 2

1. STRUCTURAL STEEL GRADE

WF SHAPES ASTM A992 (50 KSI)

MISC. SHAPES/PLATES ASTM A36 (36 KSI)

STRUCTURAL TUBES ASTM A500 GRADE B (46 KSI)

PIPE COLUMNS ASTM A53 TYPE E-GRADE B (35 KSI)

2. STEEL BEAMS WITH RESIDUAL CAMBER RESULTING FROM MILL FABRICATION

OR ROLLING SHALL BE SHOP FABRICATED AND ERECTED SUCH THAT RESIDUAL

CAMBER COUNTERACTS DEFLECTION.

3. ALL STRUCTURAL STEEL SHALL BE FABRICATED AND ERECTED ACCORDING TO

THE LATEST AISC SPECIFICATIONS.

4. SHOP AND FIELD WELDING SHALL BE DONE BY AWS CERTIFIED WELDERS WITH

E70XX ELECTRODES.

5. ALL STEEL SHALL BE PRIMED WITH SSPC PRIME PAINT UNLESS STEEL IS TO BE

FIREPROOFED, WELDED OR EMBEDDED IN CONCRETE.

6. CONNECTIONS SHALL BE AISC TYPE 2 (SIMPLE) WITH 3/4" BOLTS U.N.O:

FIELD BOLTING TO COLUMNS A325-X

FIELD BOLTING TO BRACED FRAMES A325-SC

ALL OTHER FIELD BOLTING A325-X

ALL OTHER SHOP BOLTING A325

ANCHOR BOLTS ASTM F1544 THREADED

W/ END NUT

7. MINIMUM CONNECTION PLATE THICKNESS = 5/16"

MINIMUM WELD = 3/16"

MINIMUM DESIGN LOAD = 10 KIPS

8. ANY LOADS SHOWN ON THE PLANS ARE SERVICE LOADS, ASD DESIGN.

STRUCTURAL STEEL NOTES

SPREAD FOOTING SCHEDULE

MARK SIZE REINFORCING

F-1 3'-0"x3'-0"x12"

SEE PLAN & GENERAL NOTES FOR ADDITIONAL INFORMATION.

(4) #5 E.W. BOTT.

S7.2

L-2 BOND BEAM W/(2) #5 BOTT. 7 1/2" MIN. -

L-3 BOND BEAM W/(2) #5 BOTT.

AND C8x11.5 INSIDE FACE AND

W/5/8" EXP. ANCHORS AT 12" O.C.

7 1/2" MIN. -

CBA

B224-S0.0

A nt ho ny

L an e M in ne ap ol is , M

N

P:

-4

-3

2, F : 6

-4

-3

2985 SOUTH RIDGE ROAD, SUITE B

GREEN BAY, WI 54304

'-8

4'-11" 8'-0"

'-1

0" 8'

-0

'-1

0"

5' -0

5'-0"

TOW = 99'-4"

SF-1

{TOF 96'-0"}

SF-1

{TOF 96'-0"}

SF-1

{TOF 96'-0"}

TOW = 99'-4"

SF-1

{TOF 96'-0"}

F-1

{TOF 96'-0"}

F-1

{TOF 96'-0"}

S7.1

TYP.

TOW = 100'-0"

S7.1

'-1

0"

'-0

'-1

0"

2' -0

'-0

2' -0

S7.1

4" S.O.G. W/ 6x6 W1.4xW1.4 WWF SEE

6/S7.1 T.S.L. 100'-0"

M-1

M-1

M-1

M-1

5' -0

S7.1

S7.1

S7.1 2 8'-0" 34'-10"

5' -0

S7.1

34'-10"8'-0"67'-2"

TOW = 99'-4"

TOW = 100'-0"

M-1

M-1

TOW = 99'-4"

15'-1"10'-0"9'-10"10'-2"

S7.1

S7.1

54'-3"

ELECTRICAL BOX.

SEE ELECTRICAL SHEETS

℄ THICKENED

SLAB

℄ THICKENED

SLAB

℄ THICKENED

SLAB

℄ THICKENED

SLAB

S7.1

CONTROL JT TYP,

SEE

S7.1

S7.1

WALL CONTROL JOINT

SEE TYP.

SF-2

{TOF 96'-0"}

TYP.

FOUNDATION NOTES

1) DEPRESS TOP OF FOUNDATION WALL 8" AT ALL EXTERIOR DOOR OPENINGS UNLESS OTHERWISE DETAILED, AND PROVIDE #4 L-SHAPED DOWELS @ 1'-4" O.C. W/ 1'-6" LEGS BETWEEN FOUNDATION WALL AND STOOP SLAB.

2) WALL FOOTINGS ARE CONTINUOUS POURED CONCRETE W/ CONTINUOUS REINFORCEMENT PLACED 3" CLEAR OF THE BOTTOM AND SIDES.

3) WHERE FILL IS REQUIRED ON TWO SIDES OF WALL IT SHALL BE PLACED SIMULTANEOUSLY.

4) MINIMUM REINFORCEMENT COVER:

A. CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH............................................................................................................................. 3"

B. FORMED SURFACES EXPOSED TO EARTH OR WEATHER

#6 THROUGH #18 BARS.............................................................................................................................................................................. 2" #5 AND SMALLER BARS.............................................................................................................................................................................. 1 1/2"

C. STRUCTURAL SLABS AND WALLS NOT EXPOSED TO

WEATHER OR EARTH.................................................................................................................................................................................. 3/4"

D. BEAMS & COLUMNS:

PRIMARY REINFORCEMENT, TIES, STIRRUPS, NOT EXPOSED

TO WEATHER OR EARTH............................................................................................................................................................................ 1 1/2"

S0.1

SCALE - 3/16" = 1'-0"

FOUNDATION PLAN

A nt ho ny

L an e M in ne ap ol is , M

N

P:

-4

-3

2, F : 6

-4

-3

CBA

B224-S0.12985 SOUTH RIDGE ROAD, SUITE B

GREEN BAY, WI 54304

110'-0"

'-8

3' -0

3'

-0

3'-0"

G

IR

D

ER

T R

U

SS

G

IR

D

ER

T R

U

SS

NOTE 1

NOTE 1

3'-0"

8'-0"

SHADED AREA:

BLOCKED DIAPHRAGM

DETAIL 12/S7.1

8'-0"

'-0

13'-0"

3' -0

3'

-0

3'-0"

NOTE 1

S7.1

S7.1

W x1

TO

S=

9'

-4

S7.1

S7.1

W 8x13

TOS=109'-4"

W 8x13

TOS=109'-4"

S7.1

'-1

0"

'-1 0"

2X8 STRUCTURAL FASCIA REQUIRED

2X8 STRUCTURAL

FASCIA REQUIRED

L-1

L-1

N O

TE

L-

SHADED AREA:

BLOCKED DIAPHRAGM

DETAIL 12/S7.1

S7.1

N O

TE

S7.2

SEE

DETAIL

SEE DETAIL TYP

ALL BEAM EMBEDS

IN CMU WALL

LINTEL L-2 AT LOUVERS

L-2 AND L-3

LINTEL L-1 AT LOUVER L-1

LINTEL L-3 AT LOUVER L-4

LINTEL L-2 AT AT

PASS-THRU

LINTEL L-3 AT DOOR 103

1. DENOTES 5/8" APA RATED

SHEATHING WITH 8d NAILS @ 6" O.C.@ SUPPORTED

EDGES AND @ 12" O.C. AT INTERMEDIATE SUPPORTS.

2. ACTUAL TRUSS LAYOUT TO BE DETERMINED BY TRUSS

SUPPLIER. GIRDER TRUSS LOCATIONS SHALL BE AS

SHOWN UNLESS APPROVED BY ENGINEER. MAXIMUM

TRUSS SPACING = 2'-0" O.C.

3. TRUSS BEARING = 112'-8" @ EXTERIOR MASONRY WALL.

4. FOR LINTELS ABOVE HVAC OPENINGS, SEE ARCH.

ELEVATIONS.

5. TRUSS DESIGN ENGINEER TO PROVIDE BLOCK

MEMBER/BRAKE BLOCKING, AND ALL CONNECTIONS TO

WALL TO TRANSFER THE FOLLOWING DIAPHRAGM

LOADS:

WIND 0.26 KLF

SEISMIC 0.03 KLF

6. MINIMUM SHEATHING FASTENING SHALL BE: 5/8" APA

RATED SHEATHING WITH 8d NAILS AT 6" OC @

SUPPORTED EDGES AND @12" OC AT INTERMEDIATE

SUPPORTS. PROVIDE DIAPHRAGM BLOCKING IN AREAS

SHOWN IN PLAN.

7. TRUSS MANUFACTURER TO DESIGN TIE DOWNS TO

WALL AS REQUIRED.

8. TRUSS DESIGN ENGINEER TO CALCULATE SNOW

LOADING (UNIFORM, UNBALANCED, DRIFT, SLIDING)

IN ACCORDANCE WITH IBC 2012. WISCONSIN CODE

AMENDMENTS DO NOT APPLY.

9. CONTRACTOR TO COORDINATE CABLE TRAY

LOCATIONS AND LOADS WITH TRUSS MANUFACTURER.

ROOF FRAMING PLAN NOTES

1. ROOF SAFETY TIE-DOWN HOOKS. SEE SPEC 07610.

TRUSS MFR TO DESIGN TRUSSES AND ADDITIONAL

BLOCKING/FRAMING REQUIRED TO SUPPORT 5000 LB

TENSILE LOAD (LIVE LOAD) IN ALL DIRECTIONS

PARALLEL TO PLANE OF ROOF. BLOCKING SHALL BE

CAPABLE OF TRANSFERRING 5000 LB LOAD THROUGH

ROOF DIAGRAM IN ANY DIRECTION TO WALLS BELOW.

2. LINTELS SHOWN IN ROOF PLAN ARE FOR EXTERIOR

DOORS, PASS-THRUS, AND LOUVERS. SEE SHEET

B224-S50.0 FOR LINTEL SCHEDULE.

KEY NOTES:

S3.1

SCALE - 3/16" = 1'-0"

ROOF FRAMING PLAN

CBA

B224-S3.1

A nt ho ny

L an e M in ne ap ol is , M

N

P:

-4

-3

2, F : 6

-4

-3

2985 SOUTH RIDGE ROAD, SUITE B

GREEN BAY, WI 54304

2"

CONCRETE SLAB

COMPACTED

ENGINEERED

GRANULAR BACKFILL

VAPOR BARRIER

REINFORCING: SEE PLAN FOR REINFORCING

NATURAL SOIL BASE

SE

E

PL

AN

6"

S7.1

SCALE - 1" = 1'-0"

TYP. SLAB ON GRADE

LAP 30 BAR DIA.

CONT. STRIP

FOOTING

BENT BAR @

CORNERS,

MATCH SIZE OF

CONT.

CONT. STRIP FOOTING

REINFORCING, SEE FOOTING

SCHEDULE

LAP 30 BAR

DIAMETERS

CONT. STRIP FOOTING

REINFORCING, SEE FOOTING

SCHEDULE

BENT BAR @ CORNERS,

MATCH SIZE OF CONT.

CONT. STRIP FOOTING

S7.1

SCALE - 1" = 1'-0"

STRIP FOOTING INTERSECTION

30 X DIA.

BAR

MATCH HORIZ.

REINF.

TYPICAL HORIZONTAL

WALL REINFORCEMENT

TYPICAL HORIZONTAL

WALL REINFORCEMENT

#4 X 2'-0" X 2'-0" CORNER BARS

AT 12" O.C.

S7.1

SCALE - 1" = 1'-0"

FDN. WALL INTERSECTION

AT CONSTRUCTION

JOINT PROVIDE

WATERSTOP

1"

1"

4"

NOTES:

1) OVER LONG FOUNDATION SPANS,

EQUALLY SPACE CONTROL JOINTS

2) COORDINATE CONCRETE FINISH WITH

ARCHITECTURAL DRAWINGS.

3) LIMIT SPACING TO 30' O.C.

4) CONTROL JOINTS SHOULD COINCIDE

WITH MASONRY CMU CONTROL JOINTS.

5) TAPE HORIZONTAL REINFORCING BARS

THAT RUN THRU JOINT 12" ON EA. SIDE

OF JOINT TO BREAK BOND W/ CONCRETE.

S7.1

SCALE - 1" = 1'-0"

WALL CONTROL & CONST. JOINT

#6 X 4'-0", EA. FACE,

TYP.

#6, EACH FACE,

TYP.

NOTE: APPLIES TO ALL HOLES WHERE DIAMETER

OR DIMENSION "A" OR "B" IS GREATER

OR EQUAL TO FOUNDATION THICKNESS.

A

B

DIA.

24" TYP.

3" MAX.

S7.1

SCALE - 1" = 1'-0"

TYP. HOLE IN CONCRETE WALL

DISCONTINUE WWF AT

CONSTRUCTION JOINTS

SMOOTH 1"Ø X 2'-0" LONG BARS SPACED 3-0" O.C.

(GREASE ONE END)

NOTE: SAWCUTS SHALL BE

COMPLETED WITHIN 6HRS. OF

PLACING CONCRETE

SAW CUT JOINT TO 1/3

SLAB THICKNESS

PROVIDE CONTROL JOINTS AT A

MAXIMUM SPACING OF 15'-0" O.C.

EACH WAY. KEEP AREAS RELATIVELY

SQUARE. AVOID ANGLES LESS THAN

90 DEGREES

CONSTRUCTION JOINT

CONTROL JOINT

S7.1

SCALE - 3/4" = 1'-0"

SLAB JOINT DETAILS

4"

8"4" 4"

#4 x 24" x24" BENT BAR @ 24" O.C.

#4 @ 1"-4" EACH WAY

1/4"/FT SLOPE FROM BLDG.

8" C.I.P. WALL

#4 VERT. BARS @ 32" O.C.

#4 BARS TOP & BOTTOM (2'-0"

LAP AT CORNERS)

2 - #4'S CONT.

NOTE:

STOOP SLAB AND WALLS TO

BE DOWELED TO BUILDING

FOUNDATION

T.O.F.

SEE PLAN

T.O.W.

SEE PLAN

T.S.L.

100'-0"

S7.1

SCALE - 3/4" = 1'-0"

CONCRETE STOOP DETAIL

#4 @ 1'-4"

A7.1

FOUNDATION WALL, SEE

EQ

EQ

1'-6"

THICKENED SLAB

AT DOORWAY

#4 x 1'-4" DOWELS

@ 12" O.C. TYP EA DOOR

5" MIN

1'-0" MIN STRUCTURAL FILL

BELOW FOOTING

T.O.F.

SEE PLAN

T.S.L.

SEE PLAN

#5 @ 1'-0" O.C. ALT HOOKS

FOOTING, SEE SCHEDULE

INSULATION, SEE SHEET

A5.2

THERMAL BREAK, SEE

SHEET A5.2

REINFORCE WALL PER

SCHEDULE

(2) #4 T & B

S7.1

SCALE - 3/4" = 1'-0"

FOUNDATION DETAIL

#5@12"

8"

1'-0" MIN STRUCTURAL FILL

BELOW FOOTING

T.O.F.

SEE PLAN

2" CLR.

COVER

S/

S

T.O. PIER

99'-4"

#3 TIES @ 10" O.C.

SPREAD FOOTING,

SEE FOUND. PLAN

& SCHEDULE FOR

SIZE AND REINF.

HOOK BARS INTO

FOOTING

T.S.L.

SEE PLAN

GROUT ALL

CORES SOLID

SECTION A

(8) #6 BARS

S7.1

SCALE - 3/4" = 1'-0"

TYP. COLUMN PIER

B

#3@8 TIES

8" CMU FULLY GROUTED TYP.

ALTERNATE COURSES

2'-0"

2' -0

A

SECTION B

8-#6

#3@10" TIES

2'-0"

2' -0

4-#6 FULL HEIGHT

OF MASONRY

COLUMN.

LAP W/MATCHING

DOWELS INTO

FOUNDATION

N O

M

IN

AL

NOMINAL NOMINAL

2" CLR TO TIES,

TYP. TIES TO

OCCUR AT

MORTAR JOINTS

1'-0" MIN STRUCTURAL FILL

BELOW FOOTING

DISCONTINUE WWF AT

CONSTRUCTION JOINTS

SMOOTH 1"Ø X 2'-0" LONG BARS SPACED 3-0" O.C.

(GREASE ONE END)

NOTE: SAWCUTS SHALL BE

COMPLETED WITHIN 6HRS. OF

PLACING CONCRETE

SAW CUT JOINT TO 1/3

SLAB THICKNESS

PROVIDE CONTROL JOINTS AT A

MAXIMUM SPACING OF 15'-0" O.C.

EACH WAY. KEEP AREAS RELATIVELY

SQUARE. AVOID ANGLES LESS THAN

90 DEGREES

CONSTRUCTION JOINT

S7.1

SCALE - 3/4" = 1'-0"

SLAB JOINT DETAILS

8"

ROOF SHEATHING, SEE PLAN

TRUSS ANCHOR EACH

TRUSS, AS REQD BY

TRUSS MFR

TREATED 2X8 TOP PL

BOND BM W/ (2) #5 BOTT.

SEE ARCH.

3'-0"

5/8" DIA. ANCHOR

BOLT @ 2'-0" O.C.

MIN 5" EMBEDMENT

1/

4"

S7.1

SCALE - 3/4" = 1'-0"

TRUSS BEARING DETAIL

2X4 WOOD BLOCKING

@ PANEL EDGES W/

8d NAILS @ 6"O.C.

MAIN SUPPORT

MEMBERS @ 24" O.C.

S7.1

SCALE - 1/4" = 1'-0"

DIAPHRAGM DETAIL

ROOF SHEATHING,

SEE PLAN

TRUSS ANCHOR

EACH TRUSS AS

REQD BY TRUSS MFR

TREATED 2X6 TOP PL W/

(1) 1

2" DIA. BOLT @ 2'-0"

O.C. STAGGERED

2.5

3'-0"

1/

4"

S7.1

SCALE - 3/4" = 1'-0"

TYP. TRUSS BEARING ON STEEL BEAM

SLAB t

S7.1

SCALE - 3/4" = 1'-0"

THICKENED SLAB DETAIL

2'-0"

WWF

#4@12"

3-#4 CONT

6" MIN

T.S.L.

100'-0"

ELECTRICAL BOX

A nt ho ny

L an e M in ne ap ol is , M

N

P:

-4

-3

2, F : 6

-4

-3

CBA

B224-S7.12985 SOUTH RIDGE ROAD, SUITE B

GREEN BAY, WI 54304

GROUT FILL CELLS AT VERT. REINF., MORTAR

CROSS WEBS ADJ. TO FILLED CELLS. LOW LIFT

GROUTING SHALL BE USED.

VERT. REINF. SPACING,

SEE SCHEDULE

VERT. REINF. SEE ELEVATIONS & GENERAL

NOTES. WHERE REINF. TERMINATES AT

HIGHEST BOND BEAM. PROVIDE STD. 90°

HOOK. REINF. SIZE SHALL MATCH FDN.

DOWELS & RUN CONT. THROUGH

INTERMEDIATE BOND BEAM LEVELS. PROVIDE

VERT. REINF. POSITIONER HARDWARE.

SPECIFIED WALL WIDTH,

SEE PLAN

FIRST COURSE SHALL BE

SET IN FULL MORTAR BED.

CONC. STEM WALL

CONC. FDN. SEE PLAN

CMU BOND BEAM, REINF.

CONT. ACROSS VERTICAL

CONTROL JOINTS

VERT. CONTROL JOINT, SEE

MASONRY ELEVATIONS

WIRE LATHE OVER NON

GROUTED CELLS, SHEET

METAL OR FELT ARE NOT

PERMITTED

MIN. SPLICE LAP (48)

BAR DIAMETER

HORIZ. JT. REINF. "LADDER TYPE"

PROVIDE PREFABRICATED L's AND T's AT

WALL INTERSECTIONS. SEE SPECS

NOTES:

SEE MASONRY ELEVATIONS FOR REINF. OF

SHEAR WALLS. SEE SCHEDULE FOR REINF.

OF WALLS NOT SHOWN ON MASONRY

ELEVATIONS. FOR BOND BEAM LOCATIONS

REFER TO MASONRY ELEVATIONS.

TYP. MASONRY CONSTRUCTION DETAIL

S7.2

BOND BEAM AT

TOP OF WALL

W

L

W

L

W

L

SEE DEVELOPMENT

LENGTH SCHED.

(1) J.B.

EA. SIDE

(1) J.B.

EA. SIDE

(2) J.B.

EA. SIDE

(1 ) H

.B

EA

. S

ID

E

(2 ) H

.B

EA

. S

ID

E

(2 ) H

.B

EA

. S

ID

E

TOP OF SLAB

CASE 1 CASE 2 CASE 3

CASE 1. WALLS: W AND L<2'-0" AND WL>100 SQ.IN.

CASE 2. WALLS: W OR L>2'-0" BUT <4'-0"

CASE 3. WALLS: W OR L>4'-0"

NOTES:

1. J.B. (JAMB BARS): (1) #5 VERTICAL WITH LENGTH AND SPLICE SAME AS

VERTICAL WALL REINFORCEMENT.

2. H.B. (HORIZONTAL BARS): (1) #5 HORIZONTAL WITHIN 8" OF OPENING.

3. J.B.'s AND H.B.'s MAY BE REPLACED BY REINFORCEMENT JAMB SECTIONS, LINTELS, BOND BEAMS, OR COMPARABLE HORIZONTAL WALL REINFORCEMENT

IMMEDIATELY ADJACENT TO OPENING.

4. VERTICAL BARS EXTEND 6" INTO BOND BEAM AND HOOK END.

TYP. REINFORCEMENT AT INTERIOR MASONRY OPENINGS

S7.2

(NOT USED)

S7.2

NOTES:

1. SEE MASONRY ELEVATIONS FOR CMU CONTROL JOINT LOCATIONS, U.N.O.

2. BOND BEAM REINFORCING SHALL BE CONT. THROUGH CONTROL JOINT.

3. INTERIOR MASONRY WALLS NOT SHOWN ON ELEVATION VIEWS SHALL NOT

EXCEED 24'-0" CONTROL JOINT SPACING, U.N.O.

PROVIDE VERT REINF. IN

GROUT FILLED CELL EA.

SIDE OF JOINT, TYP.

GALVANIZED LADDER TYPE

JOINT REINF. @ 1'-4" O.C.

STOP AT ALL CJ's

PREFORMED GASKET

CENTERLINE CONTROL

JOINT

SEALANT W/ BACKER ROD

(TYP.), SEE ARCH

TYP. CMU CONTROL JOINT

S7.2

3/8" JOINT KEEP

CLEAN OF MORTAR

(1) BAR AT GROUTED CELL,

SEE MASONRY SCHEDULE

TYP. CMU WALL END

S7.2

5 TYP. MASONRY WALL CORNER

STD

HOOK

FULLY BONDED

INTERSECTION

MIN. REINF. IN

WALLS (3)#5 AT

CORNER CELLS (1

EA. CELL)

NOTE:

GROUT ALL REINF.

CELLS SOLID

HORIZ. OR BOND BEAM

REINF. ALTERNATE

DIRECTION OF HOOKS.

S7.2

SEE LAP

SPLICE SCHED.

HORIZ. OR BOND BEAM

REINF. ALTERNATE

DIRECTION OF HOOKS.

FULLY BONDED

INTERSECTION

NOTE:

GROUT ALL REINF.

CELLS SOLID

MIN. REINF. IN WALLS (4)

#5 AT CORNER CELLS (1

EA. CELL) NOTE:

NON-LOAD BEARING

WALLS SHALL CONFORM

TO MINS. NOTED.

TYP. MASONRY WALL INTERSECTION

S7.2

GROUT

BEAM AS NOTED

2" TYP

REINF FULL HEIGHT

BLOCK SOLID

1" MIN NONSHRINK

ANCHOR BOLTS

GROUT

2-5/8" DIA X 1'-4"

2-#4 X 4'-0" GROUT

GROUT SOLID

GROUT FULL HEIGHT

BEARING WITH MASONRY

FILL CORES BENEATH

AFTER PLACING BEAM

REINF FULL HEIGHT

2-5/8" DIA X 1'-4"

GROUT FULL HEIGHT

BEARING WITH MASONRY

ANCHOR BOLTS

BEAM AS NOTED

1" MIN NONSHRINK GROUT

FILL CORES BENEATH

S7.2

NTS

BEAM SEAT DETAIL

ELEVATION

SECTION

6"

A nt ho ny

L an e M in ne ap ol is , M

N

P:

-4

-3

2, F : 6

-4

-3

CBA

B224-S7.22985 SOUTH RIDGE ROAD, SUITE B

GREEN BAY, WI 54304

ELEVATION REFERENCE

SECTION REFERENCE

DETAIL NUMBER

DETAIL REFERENCE

SHEET NUMBER

WALL TYPE,

SEE SHEET A5.4

FOR WALL TYPES.

REVISION TAG.

DETAIL TITLE

DRAWING TITLE

SCALE

SHEET NUMBER

- FIRE EXTINGUISHER CABINET.FEC

- FLOOR DRAIN, SEE PLUMBING, TYP.

- FURNISHED BY CONTRACTOR, INSTALLED BY CONTRACTORFCIC

KEY NOTES.

101 DOOR TYPES, SEE SHEET

A8.1 FOR DOOR SCHEDULE.

FLOOR PLAN SYMBOL LEGEND

REF - REFRIGERATOR *FCIC

MW - MICROWAVE

A1.1

SCALE - 1/8" = 1'-0"

TITLE

A1.1 1 10

A1.1

A1.1

EXIT SIGN

EMERGENCY EXTERIOR LIGHT

2'-0" x 4'-0" FLUORESCENT

EMERGENCY LIGHTING

4'-0" 2 LAMP

FLUORESCENT G

2'-0" x 2'-0" LED

GENERAL NOTES

A. SCALES SHOWN ONLY APPLY WHEN THESE DRAWINGS ARE

PRINTED ON 22" x 34" PAPER. SCALES ARE HALF SIZED WHEN PRINTED ON 11" x 17" PAPER.

B. SEE SITE PLANS FOR ACTUAL FLOOR ELEVATION.

CBA

B224-A0.0

A nt ho ny

L an e M in ne ap ol is , M

N

P:

-4

-3

2, F : 6

-4

-3

2985 SOUTH RIDGE ROAD, SUITE B

GREEN BAY, WI 54304

67'-10" 35'-8"

'-8

35'-8"55'-8"5'-8"

16'-4 9/16"

'-5

/1

6" 110'-0"

'-7

'-7

'-8

18'-11 5/8"

7'-10 3/16"

'-7

/4

7' -6

9' -7

8'

-2

'-4

/1

6"

'-6

/1

6"

4' -8

5'-4" 3'

-8

/1 6"

'-1

5/

15'-6"

15'-0"

16'-4 9/16"

6'-6"

15'-0" 3'

-8

/1 6"

'-6

/2

'-6

1/

'-6

/8

6'-6"6'-6"

6' -6

7'-10 3/16" 3'-10 13/16" 3'-9 3/16"

14'-0"

8'-0"

5' -0

A5.1

A5.1

100A 100B

107A

107B

107C

PASS-THRU

'-0

PASS-THRU

5'-11"

2'-0"

4' -2

/4

VINYL BASE

WALL PROTECTION

PANEL

COAT HOOK

WALL GUARD

4' -0

0.0194 S.S. ENCLOSURE

PROVIDE 1" TABS ON ENDS.

PROVIDE 60 MIL EPDM

THERMAL SEPERATION

BETWEEN ENCLOSURE &

ACCESS PANEL. SECURE

BOX TO CMU & MTL STUD

CONSTRUCTION W/EXP.

ANCHORS. FILL ENCLOSURE

W/4" UNFACED BATT INSUL.

12"x12" ACCESS PANEL

SECURE TO WALL

FRAME OPENING

W/RUNNER CHANNELS

A1.2

SCALE - 3/16" = 1'-0"

DIMENSIONED FLOOR PLAN

A1.2

SCALE - 1/4" = 1'-0"

WALLPROTECTION ELEVATION

CBA

B224-A1.2

A nt ho ny

L an e M in ne ap ol is , M

N

P:

-4

-3

2, F : 6

-4

-3

A1.2

SCALE - 1 1/2" = 1'-0"

PASS-THRU

2985 SOUTH RIDGE ROAD, SUITE B

GREEN BAY, WI 54304

1. REFER TO PLUMBING, MECHANICAL, ELECTRICAL FOR LOCATIONS OF RELATED ITEMS.

2. COORDINATE WITH HVAC AND ELECTRICAL PLANS FOR LOCATIONS/QUANITIES/TYPES OF

DIFFUSERS AND LIGHTS.

3. REFER TO ROOM FINISH SCHEDULES FOR CEILING MATERIALS AND HEIGHTS.

4. GYPSUM CEILING CONTROL JOINTS TO BE 50'-0" MAX. EITHER DIRECTION OR TO LIMIT

AREAS TO 2500 S.F.

5. REFER TO TYPICAL WALL/CEILING DETAILS ON SHEET A2.2.

6. REFER TO A0.0 FOR ALL NOTES AND LEGENDS.

REFLECTED CEILING PLAN GENERAL NOTES

1. 24"W X 36"L ACCESS PANEL IN 6 MIL. VAPOR BARRIER AT UNDERSIDE

OF TRUSSES. CENTER BETWEEN TRUSSES. SEE DETAIL

KEY NOTES:

A1.2

A2.1

SCALE - 3/16" = 1'-0"

REFLECTED CEILING PLAN

CBA

B224-A2.1

A nt ho ny

L an e M in ne ap ol is , M

N

P:

-4

-3

2, F : 6

-4

-3

2985 SOUTH RIDGE ROAD, SUITE B

GREEN BAY, WI 54304

6"

6"

6"

6"

6"

6"

6"

6"

6"

6"

6"

6"

6"

A2.1

SCALE - 3/4" = 1'-0"

CEILING DETAIL - A

A2.1

SCALE - 3/4" = 1'-0"

CEILING DETAIL - E

A2.1

SCALE - 3/4" = 1'-0"

CEILING DETAIL - D NOT USED

A2.1

SCALE - 3/4" = 1'-0"

CEILING DETAIL - F

A2.1

SCALE - 3/4" = 1'-0"

CEILING DETAIL - B

A2.1

SCALE - 3/4" = 1'-0"

CEILING DETAIL - C

A2.1

SCALE - 3/4" = 1'-0"

CEILING DETAIL - G

A2.1

SCALE - 3/4" = 1'-0"

CEILING DETAIL - H NOT USED

A2.1

SCALE - 3/4" = 1'-0"

CEILING DETAIL - D

A2.1

SCALE - 3/4" = 1'-0"

CEILING DETAIL - I

ACOUSTICAL CEILING TILES.

CEILING SUSPENSION WIRE.

WOOD TRUSSES

SOUND BATT. INSULATION.

BATT INSULATION (R-49 W/6 MIL. VAPOR BARRIER)

2X4 WOOD BLOCKING

KEY NOTES - CEILING DETAILS

3 5/8" MTL. STUD.

6" MTL. STUD.

CBA

B224-A2.2

A nt ho ny

L an e M in ne ap ol is , M

N

P:

-4

-3

2, F : 6

-4

-3

2985 SOUTH RIDGE ROAD, SUITE B

GREEN BAY, WI 54304

PRE-FINISHED 3"x4"

ALUMINUM DOWNSPOUT

WITH CONCRETE SPLASH

BLOCK

PRE-FINISHED 8"

ALUMINUM GUTTER

PRE-FINISHED 3"x4"

ALUMINUM DOWNSPOUT WITH

CONCRETE SPLASH BLOCK

PRE-FINISHED 3"x4"

ALUMINUM DOWNSPOUT WITH

CONCRETE SPLASH BLOCK

SNOW BARS - SNOW GUARDS.

SEE SHEET A-3.2 FOR DETAILS

LINE OF EXTERIOR

WALL BELOW.

PRE-FINISHED STANDING

SEAM METAL ROOF

PRE-FINISHED 3"x4" ALUMINUM

DOWNSPOUT WITH CONCRETE

SPLASH BLOCK

PRE-FINISHED 8"

ALUMINUM GUTTER

PRE-FINISHED 3"x4" ALUMINUM

DOWNSPOUT WITH CONCRETE

SPLASH BLOCK

PRE-FINISHED 3"x4" ALUMINUM

DOWNSPOUT WITH CONCRETE

SPLASH BLOCK

SNOW BARS - SNOW GUARDS

SEE SHEET A3.2 FOR DETAILS

LINE OF EXTERIOR

WALL BELOW.

PRE-FINISHED VENTED

RIDGE CAP - SEE SHEET

A3.2 FOR DETAILS

SNOW BARS - SNOW

GUARDS. SEE SHEET

A3.2 FOR DETAILS

SNOW BARS - SNOW

GUARDS - SEE SHEET

A3.2 FOR DETAILS

PRE-FINISHED 3"x4"

ALUMINUM DOWNSPOUT

WITH CONCRETE SPLASH

BLOCK

PRE-FINISHED 5"

ALUMINUM GUTTER

PRE-FINISHED 3"x4" ALUMINUM

DOWNSPOUT WITH CONCRETE

SPLASH BLOCK

PRE-FINISHED 5"

ALUMINUM GUTTER

PRE-FINISHED

HIP CAP - SEE

SHEET A3.2

FOR DETAILS

PRE-FINISHED

HIP CAP - SEE

SHEET A3.2

FOR DETAILS

SLOPE

4:12

PRE-FINISHED HIP

CAP - SEE SHEET A3.2

FOR DETAILS

PRE-FINISHED HIP

CAP - SEE SHEET A3.2

FOR DETAILS

SLOPE

4:12

SLOPE

2.5:12

SL

O

PE 4:

SL

O

PE

4:

SL

O

PE

2.

5:

SL

O

PE

2.

5:

PRE-FINISHED VENTED

RIDGE CAP - SEE SHEET A3.2

FOR DETAILS

PRE-FINISHED

HIP CAP - SEE SHEET

A3.2 FOR DETAILS

3" VENT

PRE-FINISHED STANDING

SEAM METAL ROOF

ROOF TIE-DOWN

- SEE SPECS

ROOF TIE-DOWN

- SEE SPECS

FLUE PIPES - SEE SHEET M-1.2

FOR DETAILS (TYP.)

A3.1

SCALE - 3/16" = 1'-0"

ROOF PLAN

CBA

B224-A3.1

A nt ho ny

L an e M in ne ap ol is , M

N

P:

-4

-3

2, F : 6

-4

-3

2985 SOUTH RIDGE ROAD, SUITE B

GREEN BAY, WI 54304

A3.2

1 1/2" = 1'-0"

DOWNSLOPE EDGE WITH GUTTER

UNDERLAYMENT

ICE-DAM PROTECTION MEMBRANE

(EXTEND MIN. 36" BEYOND INTERIOR WALL)

PLYWOOD DECK

METAL PANEL

ALUM GUTTER. THE FRONT

OF THE GUTTER SHOULD BE

A MINIMUM 1" LOWER THAN

THE BACK TO ALLOW

OVERFLOW

GUTTER BRACKET SUPPORT

(SECURE WITH 2 FASTENERS)

GUTTER

SPACER

GUTTER CLEAT

PRE-FINISHED ALUMINUM FASCIA

PLYWOOD DECK

WOOD FASCIA BOARD

WOOD TRUSSES

ICE DAM

CONTINUOUS

GUTTER CLEAT

GUTTER

CONTINUOUS ZEE SET

IN SEALANT

HEAVY GAGE

PERFORATED METAL

SHEET METAL RIDGE

CAP

SLOPE

TURN PANEL UP

ALONG RIDGE

UNDERLAYMENT

ICE-DAM PROTECTION

MEMBRANE

PLYWOOD DECK

METAL ROOF PANEL

A3.2

1 1/2" = 1'-0"

RIDGE CAP (VENTING)

A3.2

1 1/2" - 1'-0"

HIP CAP FLASHING

WOOD TRUSSES.

SLOPE

SLOPE

UNDERLAYMENT

ICE-DAM MEMBRANE

PROTECTION

ROOF DECK

METAL ROOF PANEL

SHEET METAL HIP CAP

TURN PANEL PAN UP

ZEE CLOSURE

TAPE SEALANT

UNDERLAYMENT

METAL ROOF PANEL

GASKETED FASTENERS

SECURE FLASHING

COLLAR FLANGE TO

ROOF PANEL AND NOT

TO DECK SO AS NOT TO

FIX PANEL AT

PENETRATION

PREFORMED

PENETRATION

FLASHINGS

SEALANT BEAD

BETWEEN PIPE AND

FLASHING TOOLED TO

FACILITATE RUNOFF

EQUIPMENT SUPPORT

STAND/VENT STACK

ICE-DAM PROTECTION

MEMBRANE (CENTERED

ON PENETRATION)

ROOF DECK (SEE

SPECS FOR TYPE)

SLOPE

SET SECUREMENT RING IN

CONTINUOUS BEAD OF

SEALANT

STAINLESS STEEL

DRAWBAND

A3.2

1 1/2' = 1'-0"

STACK VENT FLASHING

WOOD TRUSS

COUNTERFLASHING OR SIDING

METAL ROOF PANEL

ROOF DECK (SEE

SPECS FOR TYPE)

ICE-DAM PROTECTION

MEMBRANE

UNDERLAYMENT CLOSURE IF REQUIRED

BY MANUFACTURER

SLOPE

RAKE FLASHING

A3.2

1 1/2" = 1'-0"

ROOF TO WALL TRANSITION (RAKE)

SLOPE

UTILITY CLAMP

CROSS MEMBER

PREFINISHED COLOR

STRIP

STAINLESS STEEL BOLT

AND WASHER

STANDING SEAM

METAL ROOF

UTILITY CLAMP

STAINLESS STEEL SET

SCREW

CROSS MEMBER

CROSS MEMBER

A3.2

1 1/2" = 1'-0"

SNOW GUARD DETAIL

CBA

B224-A3.2

A nt ho ny

L an e M in ne ap ol is , M

N

P:

-4

-3

2, F : 6

-4

-3

2985 SOUTH RIDGE ROAD, SUITE B

GREEN BAY, WI 54304

FINISH FLOOR

100'-0"

DOOR HEAD

107'-4"

T.O. CMU

112'-8"

8" SPLIT-FACE

CMU

8" SMOOTH-FACE

CMU

PRE-FINISHED

ALUMINUM STORE

FRONT SYSTEM

PRE-FINSIHED

ALUMINUM

DOWN SPOUT

PRE-FINSIHED STANDING

SEAM METAL ROOF

PRE-FINISHED

ALUMINUM GUTTER

2.5

PRE-FINSIHED STANDING

SEAM METAL ROOF

PRE-FINISHED

ALUMINUM GUTTER

PRE-FINISHED

ALUMINUM FASCIA

PRE-FINISHED

ALUMINUM GUTTER

FOOTING AND

FOUNDATION WALLS,

SEE STRUCTURAL

CONCRETE

SPLASH BLOCK

CONCRETE

SPLASH BLOCK

PRE-FINSIHED

ALUMINUM

DOWN SPOUT

SNOW BARS - SNOW GUARD,

SEE 7/A-3.2 FOR DETAILS

SNOW BARS - SNOW UARD,

SEE 7/A-3.2 FOR DETAILS

PRE-FINISHED

ALUMINUM FASCIA

PRE-FINISHED

ALUMINUM FASCIA

A5.1

CONCRETE

SPLASH BLOCK

2' -8

8"

4' -8

8"

2' -8

'-8

8" 8"

CJ CJ

FINISH FLOOR

100'-0"

DOOR HEAD

107'-4"

8" SPLIT-FACE CMU8" SMOOTH-FACE

CMU

PRE-FINISHED

ALUMINUM GUTTER

CONCRETE

SPLASH BLOCK

SNOW BARS - SNOW GUARD,

SEE DETAIL 7/A3.2 (TYP)

PRE-FINISHED

ALUMINUM FASCIA

INSULATED HOLLOW

METAL DOOR

INSULATED HOLLOW

METAL DOOR

A5.1

PRE-FINISHED

ALUMINUM GUTTER

PRE-FINISHED

ALUMINUM FASCIA

SNOW BARS - SNOW GUARD,

SEE DETAIL 7/A3.2 (TYP)

PRE-FINISHED

ALUMINUM GUTTER

SNOW BARS - SNOW GUARD,

SEE DETAIL 7/A3.2 (TYP)

PRE-FINSIHED STANDING

SEAM METAL ROOF

CONCRETE

SPLASH BLOCK

PRE-FINSIHED

ALUMINUM

DOWN SPOUT

8" SPLIT-FACE

CMU

PRE-FINSIHED

ALUMINUM

DOWN SPOUT

FOOTING AND

FOUNDATION WALLS,

SEE STRUCTURAL

2.5

PRE-FINSIHED

ALUMINUM

DOWN SPOUT

CONCRETE

SPLASH BLOCK

FINISH FLOOR

100'-0"

CANOPY

TRUSS BEARING

109'-6"

T.O. CMU

112'-8"

PRE-FINSIHED

ALUMINUM

DOWN SPOUT

107'-4"

CONCRETE

SPLASH BLOCK

DOOR HEAD

CJ

8" SMOOTH-FACE CMU

2' -8

8"

4' -8

8"

2' -8

'-8

8" 8"

T.O. CMU

112'-8"

CJ CJ CJ CJ CJ

PASS-THRU -

CONFIRM LOCATION

W/GOVERNMENT

A4.1

SCALE - 3/16" = 1'-0"

SOUTH ELEVATION

A4.1

SCALE - 3/16" = 1'-0"

WEST ELEVATION

CBA

B224-A4.1

A nt ho ny

L an e M in ne ap ol is , M

N

P:

-4

-3

2, F : 6

-4

-3

2985 SOUTH RIDGE ROAD, SUITE B

GREEN BAY, WI 54304

FINISH FLOOR

100'-0"

T.O. CMU

112'-8"

8" SPLIT-FACE CMU

8" SMOOTH-FACE CMU

PRE-FINSIHED STANDING

SEAM METAL ROOF

PRE-FINISHED

ALUMINUM GUTTER

PRE-FINISHED

ALUMINUM GUTTER

PRE-FINISHED

ALUMINUM FASCIA

PRE-FINISHED

ALUMINUM GUTTER

FOOTING AND

FOUNDATION WALLS,

SEE STRUCTURAL

CONCRETE

SPLASH BLOCK

CONCRETE

SPLASH BLOCK

PRE-FINSIHED

ALUMINUM

DOWN SPOUT

SNOW BARS - SNOW GUARD,

SEE 7/A-3.2 FOR DETAILS

SNOW BARS - SNOW GUARD,

SEE 7/A-3.2 FOR DETAILS

PRE-FINISHED

ALUMINUM FASCIA

A5.1

2' -8

8"

4' -8

8"

2' -8

'-8

8"

8"

CJ CJ

PASS-THRU -

CONFIRM LOCATION

W/GOVERNMENT

FINISH FLOOR

100'-0"

DOOR HEAD

107'-4"

T.O. CMU

112'-8"

8" SPLIT-FACE

CMU 8" SMOOTH-FACE CMU

PRE-FINISHED

ALUMINUM GUTTER

CONCRETE

SPLASH BLOCK

SNOW BARS - SNOW GUARD,

SEE DETAIL 7/A3.2 (TYP)

PRE-FINISHED

ALUMINUM FASCIA

INSULATED HOLLOW

METAL DOOR

SNOW BARS - SNOW GUARD,

SEE DETAIL 7/A3.2 (TYP)

INSULATED HOLLOW

METAL DOOR

A5.1

PRE-FINSIHED

ALUMINUM

DOWN SPOUT

PRE-FINISHED

ALUMINUM GUTTER

FOOTING AND

FOUNDATION WALLS,

SEE STRUCTURAL

PRE-FINISHED

ALUMINUM FASCIA

PRE-FINISHED

ALUMINUM GUTTER

SNOW BARS - SNOW GUARD,

SEE DETAIL 7/A3.2 (TYP)

PRE-FINSIHED STANDING

SEAM METAL ROOF

109'-6"

CONCRETE

SPLASH BLOCK

PRE-FINSIHED

ALUMINUM

DOWN SPOUT

2.5

PRE-FINSIHED

ALUMINUM

DOWN SPOUT

CONCRETE

SPLASH BLOCK

FINISH FLOOR

100'-0"

CANOPY

TRUSS BEARING

PRE-FINSIHED

ALUMINUM

DOWN SPOUT

CONCRETE

SPLASH BLOCK

DOOR HEAD

CJ

107'-4"

CJCJ

8" SPLIT-FACE CMU

8" SMOOTH-FACE

CMU

2' -8

8"

4' -8

8"

2' -8

'-8

8" 8"

CJCJCJ

A4.2

SCALE - 3/16" = 1'-0"

NORTH ELEVATION

A4.2

SCALE - 3/16" = 1'-0"

EAST ELEVATION

CBA

B224-A4.2

A nt ho ny

L an e M in ne ap ol is , M

N

P:

-4

-3

2, F : 6

-4

-3

2985 SOUTH RIDGE ROAD, SUITE B

GREEN BAY, WI 54304

A5.3

A5.3

A7.1

A7.1

A7.1

3'-0"

2.5

8' -8

FL. LINE

41 41

A5.3

2' -8

SP

LI

T-

FA

C

E

2' -8

SP

LI

T-

FA

C

E

8"

SM

0O

TH

FA

C

E

8"

SM

O O

TH

FA

C E

8"

SM

O O

TH

FA

C E

3'-0"

'-8

4' -8

SP

LI

T-

FA

C

E 8"

SM

O

O

TH

-F

AC

E

FL. LINE

KEYNOTES

POURED CONCRETE FOOTING - REFER TO STRUCTURAL

POURED CONCRETE FOUNDATION WALL - REFER TO STRUCTURAL

POURED CONCRETE STOOP - REFER TO STRUCTURAL

CONCRETE SLAB ON GRADE

8" SPLIT-FACE CMU WITH HORIZONTAL REINFORCING @ 8" O.C. -

REFER TO STRUCTURAL DRAWINGS FOR VERTICAL REINFORCING.

8" SMOOTH-FACE BOND BEAM

8" SMOOTH FACE CMU, ALSO PROVIDE BEHIND CANOPY ROOF.

8" CMU GROUTED SOLID

NOT USED

WEEP VENTILATORS @ 32" O.C. TYP.

STEEL BEAM - REFER TO STRUCTURAL

STEEL LINTEL- REFER TO STRUCTURAL

COMPACTED FILL

2" RIGID PERIMETER INSULATION (R-VALUE PER INCH = 5 MIN.).

UNDERSLAB INSULATION 48" WIDE.

1" RIGID SLAB EDGE INSULATION (R-VALUE PER INCH = 5 MIN.)

4" BATT INSULATION R-11

4" BATT INSULATION R-11 - FULL HEIGHT IN ALL INTERIOR WALLS

BATT INSULATION MINIMUM R-49 W/6 MIL. VAPOR BARRIER

3 5/8" METAL STUDS AT 16" O.C. TYP.

2" RIGID WALL INSULATION

6 MIL. VAPOR BARRIER

ACOUSTICAL CEILING TILES

5/8" EXT. GRADE PLYWOOD SHEATHING

NOT USED

ALUMINUM ENTRY DOOR - REFER TO A7.1

BLOK-FLASH THRU-WALL FLASHING

BY MORTAR NET LTD

PRE-FINISHED METAL CAP FLASHING

NOT USED

SLAB EDGE EXPANSION JOINT - NO R-VALUE REQUIRED

WALL OPENING FLASHING - PROVIDE END DAMS AT EACH END -

PROVIDE SPLICE COVERS AT ALL FLASHING JOINTS

2X10 PRESSURE TREATED WOOD BLOCKING

1X10 FASCIA BOARD

PRE-ENGINEERED WOOD TRUSSES WITH ENERGY HEAL

PROPER VENTS - LOCATED EVERY TRUSS CAVITY

ICE AND WATER SHIELD - TO EXTEND MINIMUM OF 36" BEYOND

EXTERIOR WALL

PRE-FINISHED STANDING SEAM METAL ROOF

PRE-FINISHED VENTED RIDGE CAP

PRE-FINISHED HIP CAP

PRE-FINISHED METAL DRIP EDGE

PRE-FINISHED ALUM. FASCIA/CLADDING

PRE-FINISHED VENTED ALUM. SOFFIT

PRE-FINISHED 8 IN ALUM BOX GUTTER

TWO PIECE COUNTER FLASHING - SURFACE MOUNT

VINYL BASE

1 5/8" METAL STUDS @ 16" O.C.

PRE-FINISHED METAL TRIM

6" GRAVEL BASE

VAPOR BARRIER

5/8" GYPSUM BOARD - EXTEND TO TRUSSES AT EXTERIOR WALLS

- REFER TO WALL TYPES ON SHEET A5.4 FOR GYPSUM BOARD TYPES

A5.2

SCALE - 3/4" = 1'-0"

WALL SECTION

A5.2

SCALE - 3/4" = 1'-0"

WALL SECTION

CBA

B224-A5.2

A nt ho ny

L an e M in ne ap ol is , M

N

P:

-4

-3

2, F : 6

-4

-3

2985 SOUTH RIDGE ROAD, SUITE B

GREEN BAY, WI 54304

2.5

CANOPY TRUSS BEARING

KEYNOTES

POURED CONCRETE FOOTING - REFER TO STRUCTURAL

POURED CONCRETE FOUNDATION WALL - REFER TO STRUCTURAL

POURED CONCRETE STOOP - REFER TO STRUCTURAL

CONCRETE SLAB ON GRADE - REFER TO STRUCTURAL

8" SPLIT-FACE CMU WITH HORIZONTAL REINFORCING @ 8" O.C. -

REFER TO STRUCTURAL DRAWINGS FOR VERTICAL REINFORCING.

8" SMOOTH-FACE BOND BEAM

8" SMOOTH FACE CMU, ALSO PROVIDE BEHIND CANOPY ROOF.

8" CMU GROUTED SOLID

NOT USED

WEEP VENTILATORS @ 32" O.C. TYP.

STEEL BEAM - REFER TO STRUCTURAL

STEEL LINTEL- REFER TO STRUCTURAL

COMPACTED FILL

2" RIGID PERIMETER INSULATION (R-VALUE PER INCH = 5 MIN.).

UNDERSLAB INSULATION 48" WIDE.

1" RIGID SLAB EDGE INSULATION (R-VALUE PER INCH = 5 MIN.)

4" BATT INSULATION R-11

4" BATT INSULATION R-11 - FULL HEIGHT IN ALL INTERIOR WALLS

BATT INSULATION MINIMUM R-49 W/6 MIL. VAPOR BARRIER

3 5/8" METAL STUDS AT 16" O.C. TYP.

2" RIGID WALL INSULATION

5/8" GYPSUM BOARD - EXTEND TO TRUSSES AT EXTERIOR WALLS

- REFER TO WALL TYPES ON SHEET A-5.4 FOR GYPSUM TYPES

6 MIL. VAPOR BARRIER

ACOUSTICAL CEILING TILES

5/8" EXT. GRADE PLYWOOD SHEATHING

NOT USED.

ALUMINUM ENTRY DOOR - REFER TO A7.1

BLOK-FLASH THRU-WALL FLASHING BY MORTAR NET LTD

PRE-FINISHED METAL CAP FLASHING

NOT USED

SLAB EDGE EXPANSION JOINT - NO R-VALUE REQUIRED

WALL OPENING FLASHING - PROVIDE END DAMS AT EACH END -

PROVIDE SPLICE COVERS AT ALL FLASHING JOINTS

2X10 PRESSURE TREATED WOOD BLOCKING

1X10 FASCIA BOARD

PRE-ENGINEERED WOOD TRUSSES WITH ENERGY HEAL

PROPER VENTS - LOCATED EVERY TRUSS CAVITY

ICE AND WATER SHIELD - TO EXTEND MINIMUM OF 36" BEYOND

EXTERIOR WALL

PRE-FINISHED STANDING SEAM METAL ROOF

PRE-FINISHED VENTED RIDGE CAP

PRE-FINISHED HIP CAP

PRE-FINISHED METAL DRIP EDGE

PRE-FINISHED ALUM. FASCIA/CLADDING

PRE-FINISHED VENTED ALUM. SOFFIT

PRE-FINISHED 8 IN ALUM BOX GUTTER

TWO PIECE COUNTER FLASHING-SURFACE MOUNT

VINYL BASE

1 5/8" METAL STUDS @ 16" O.C.

PRE-FINISHED METAL TRIM

6" GRANULAR FILL (TO MATCH SPEC TERMINOLOGY)

VAPOR BARRIER

A5.3

SCALE - 1 1/2" = 1'-0"

DETAIL

A5.3

SCALE - 1 1/2" = 1'-0"

DETAIL

A5.3

SCALE - 1 1/2" = 1'-0"

DETAIL

CBA

B224-A5.3

A nt ho ny

L an e M in ne ap ol is , M

N

P:

-4

-3

2, F : 6

-4

-3

2985 SOUTH RIDGE ROAD, SUITE B

GREEN BAY, WI 54304

4' -0

" M

AX

. T O

TO

P

O F

H

AN

D

LE

O R

E

XI

TI

N

G

2' -1

1"

30" MIN.

17"-19"30" MIN.

48" MIN. CLR.

FL. SPACE

" M

IN

" M

AX

1'-3"

36"

MIN.

1'-0"

MAX42"

" T

O

12"6"

ND

M

IN

. TOILET

6"

1'-6"

" M

IN

" M

IN

" M

AX

LAV.

6" MAX.

8" MAX.

17" MIN.

9" M

IN

LAV.

" M

AX

" M

AX

PTD/DISP

5' -0

2'

-8

VE

R

IF

Y

M O

U N

TI

N

G

FIRE

EXTINGUISHER

CABINET

FIRE

EXTINGUISHER

H

EI

G H

T W

IT

H

T H

E

FI

R E

M

AR

SH

AL

24"W X 36"H

MIRROR TYP.DRINKING

FOUNTAIN

CLEAR FLOOR SPACE PER

DRINKING FOUNTAIN

1' -5

40"

R

B

G G G

GG

B

R

N

P

M

P

M E

P F

NM

R

B

G

N

R

N

R

B

G

Q

E

F

N M

R

N

M R

QQJ

2'-0" 1'-6" K

J

2'-0" 20'-0"

K

2'-6" 2'-6" 2'-6" 3'-0" 5'-0" 2'-6" 2'-6" 2'-6"2'-6" 2'-6" 2'-6"2'-6" 2'-6" 2'-6"

5'-0" 3'-0" 3'-0"

MARK ITEM MOUNTING HT.

MOP AND BROOM HOLDER

WALL MOUNTED SINK WITH PIPING PROTECTIVE COVER

DRINKING FOUNTAIN

18" METAL SHELVES.

36" GRAB BAR

42" GRAB BAR

24" X 36" MIRROR

48" A.F.F. TO C

SEE PLBG

CENTER @ 34" A.F.F.

CENTER @ 34" A.F.F.

72" TO TOP

ACCESSORY SCHEDULE

34" A.F.F. MAX

SOAP DISPENSER

DOOR MOUNTED COAT HOOK

MULTI-ROLL TOILET PAPER DISPENSER

FLOOR MOUNTED WATER CLOSET

5'-6" A.F.F.

28" A.F.F. TO TOP

19" A.F.F.

NAPKIN DISPENSER/DISPOSAL 19" A.F.F. TO CENTER

MARK ITEM MOUNTING HT.

MOP BASIN SEE PLBG

PAPER TOWEL DISPENSER AND WASTE 40" A.F.F. TO BOT.

URINAL

PLASTIC PARTITIONS

17" A.F.F.

60" A.F.F.

40" A.F.F.

H

A

E

M

F

D

G

L

N

Q

R

N

N

N

M

R

Q R

Q R

Q B

K

G

B

K

G

B

J

G

B

K

G

B

K

J

L

M

L

M

E

M

F

P

L R

P

P

P

N L

M

R

2' -6

2'

-6

1' -3

2' -6

2'

-6

2' -6

2'

-9

5' -0

1'

-6

2' -6

3'

-6

3' -0

5'

-0

1' -6

A6.1

SCALE - 1/4" = 1'-0"

MENS ROOM

A6.1

SCALE - 1/4" = 1'-0"

MENS ROOM

A6.1

SCALE - 1/4" = 1'-0"

MENS ROOM

A6.1

SCALE - 1/4" = 1'-0"

MENS ROOM

A6.1

SCALE - 1/4" = 1'-0"

WOMENS RESTROOM

A6.1

SCALE - 1/4" = 1'-0"

STANDARD MOUNTING HEIGHTS

A6.1

SCALE - 1/4" = 1'-0"

WOMENS RESTROOM

A6.1

SCALE - 1/4" = 1'-0"

WOMENS RESTROOM

A6.1

SCALE - 1/4" = 1'-0"

WOMENS RESTROOM

A6.1

SCALE - 3/8" = 1'-0"

ENLARGED RESTROOM PLAN

CBA

B224-A6.1

A nt ho ny

L an e M in ne ap ol is , M

N

P:

-4

-3

2, F : 6

-4

-3

2985 SOUTH RIDGE ROAD, SUITE B

GREEN BAY, WI 54304

VAPOR BARRIER

R-11 BATT

INSULATION

3 5/8" METAL

STUDS 16" O.C.

5/8" GYPSUM

BOARD

CONTINUOUS

SEALANT

LINE OF WALL

BEYOND

8" CMU

WEEP BAFFLE

THRU WALL FLSHING

STEEL LINTEL, SEE

STRUCTURAL DRAWINGS

EXPOSED STEEL

TO BE PAINTED

CONTINUOUS SEALANT

HOLLOW METAL FRAME,

GROUT SOLID WITH MORTAR

SMOOTH CMU FACE ON

RETURN OF OPENING

HOLLOW METAL DOOR

2" RIGID INSULATION

BLK. AT RIGID INSUL.

8" CMU

WEEP BAFFLE

THRU WALL FLSHING

STEEL LINTEL, SEE

STRUCTURAL DRAWINGS

EXPOSED STEEL

TO BE PAINTED

CONTINUOUS SEALANT

THERMALLY BROKEN

ALUMINUM DOOR

SMOOTH CMU FACE ON

RETURN OF OPENING

VAPOR BARRIER

R-11 BATT

INSULATION

3 5/8" METAL

STUDS 16" O.C.

5/8" GYPSUM

BOARD

CONTINUOUS

SEALANT

LINE OF WALL

BEYOND

2" RIGID INSULATION

2" WD. BLK.

BLK. AT RIGID INSUL.

VAPOR BARRIER

R-11 BATT

INSULATION

3 5/8" METAL

STUDS 16" O.C.

5/8" GYPSUM

BOARD

CONTINUOUS

SEALANT

8" CMU

MASONRY REINFORCING,

SEE STRUCTURAL

DRAWINGS

CONTINUOUS SEALANT

SMOOTH CMU FACE ON

RETURN OF OPENING

HOLLOW METAL FRAME,

GROUT SOLID WITH MORTAR

HOLLOW METAL DOOR

2" RIGID INSULATION

BLK. AT RIGID INSUL.

VAPOR BARRIER

5/8" GYPSUM

BOARD

CONTINUOUS

SEALANT

8" CMU

MASONRY REINFORCING,

SEE STRUCTURAL

DRAWINGS

CONTINUOUS SEALANT

SMOOTH CMU FACE ON

RETURN OF OPENING

THERMALLY BROKEN

ALUMINUM DOOR

3 5/8" METAL

STUDS 16" O.C.

R-11 BATT

INSULATION

2" RIGID INSULATION

2" WD. BLK.

BLK. AT RIGID INSUL.

FOUNDATION WALL, SEE

STRUCTURAL DRAWINGS

SMOOTH CMU FACE ON

RETURN OF OPENING

THERMALLY BROKEN

ALUMINUM DOOR

CONCRETE STOOP, SEE

STRUCTURAL DRAWINGS

SLAB EDGE

INSULATION

CONCRETE SLAB

ON GRADE, SEE

STRUCTURAL

DRAWINGS

VAPOR BARRIER

RIGID INSULATION

GRAVEL BASE

COMPACTED EARTH

LINE OF WALL

BEYOND

FOUNDATION WALL, SEE

STRUCTURAL DRAWINGS

SMOOTH CMU FACE ON

RETURN OF OPENING

HOLLOW CORE METAL DOOR

CONCRETE STOOP, SEE

STRUCTURAL DRAWINGS

SLAB EDGE

INSULATION

CONCRETE SLAB

ON GRADE, SEE

STRUCTURAL

DRAWINGS

LINE OF WALL

BEYOND

SEALANT

VAPOR BARRIER

RIGID INSULATION

GRAVEL BASE

COMPACTED EARTH

METAL STUDS @ 16" O.C.

CONTINUOUS SEALANT

(TYP. EACH SIDE)

HOLLOW METAL FRAME

5/8" GYPSUM BOARD

4 7/8"

2"

5 7/8"

BATT INSUL. WHERE REQ'D.

SEE WALL TYPES ON

FLOOR PLAN

METAL STUDS @ 16" O.C.

CONTINUOUS SEALANT

(TYP. EACH SIDE)

HOLLOW METAL FRAME

5/8" GYPSUM BOARD

4 7/8"

2"

5 7/8"

BATT INSUL. WHERE REQ'D.

SEE WALL TYPES ON

FLOOR PLAN

A7.1

SCALE: 1 1/2" = 1'-0"

DOOR HEAD DETAIL - HOLLOW METAL

A7.1

SCALE: 1 1/2" = 1'-0"

DOOR HEAD DETAIL - ALUMINUM

A7.1

SCALE: 1 1/2" = 1'-0"

DOOR JAMB DETAIL - HOLLOW METAL

A7.1

SCALE: 1 1/2" = 1'-0"

DOOR SILL DETAIL - HOLLOW METAL

A7.1

SCALE: 1 1/2" = 1'-0"

DOOR SILL DETAIL - ALUMINUM

A7.1

SCALE: 1 1/2" = 1'-0"

DOOR JAMB DETAIL - ALUMINUM

A7.1

SCALE: 1 1/2" = 1'-0"

DOOR JAMB DETAIL - HOLLOW METAL

A7.1

SCALE: 1 1/2" = 1'-0"

DOOR HEAD DETAIL - HOLLOW METAL

CBA

B224-A7.1

A nt ho ny

L an e M in ne ap ol is , M

N

P:

-4

-3

2, F : 6

-4

-3

2985 SOUTH RIDGE ROAD, SUITE B

GREEN BAY, WI 54304

7' -2

2" 7'

-0

H.M.

SEE

SCHEDULE

2"

7' -2

2" 7'

-0

H.M.

SEE

SCHEDULE

2"

7' -4

4" 7'

-0

SEE SCHEDULE

H.M.

REMOVABLE

MULLION

2"

SE

E

SC

H

ED

U

LE

SEE

SCHED.

A

8"

6"

1' -0

SE

E

SC

H

ED

U

LE

SEE

SCHED.

B

6"

8"

2' -6

SEE SCHEDULE

7' -4

2" 7'

-2

ALUM.

REMOVABLE

MULLION

EXTERIOR

ONLY

2"

DOOR AND FRAME SCHEDULE

DOOR FRAME

NUMBER WD HGT TYPE FINISH TYPE

100A (2) 3'-0" 7'-2" DK BRONZE ---

NOTES

MAT'LTHK

1-3/4"

MATERIAL

SIZE & QUANTITY

GLAZING FINISH

FIRE

RATING

LABEL

HARDWARE

GROUP NUMBER

ALUM A FULL LITE 4 DK BRONZE

---100B 7'-2" 1-3/4" ALUM A FULL LITE 4

103 7'-0" ---1-3/4" INS HM --- 3 P-A

104 3'-0" 7'-0" ---1-3/4" WOOD --- 1 P-A

107B 7'-0" P-A ---1-3/4"

WOOD

3 P-A

106 3-0" 7'-0" SSP ---1-3/4" WOOD --- 1 P-A

107C

SSP

WOOD 1 P-A

C

C

B

C

109 3-0" 7'-0" ---1-3/4" ---

P-A

C

ALUM

ALUM

HM

HM

HM

HM

HM

DK BRONZE DK BRONZE

100A

100B

107B

107C

SSP

P-A

110 3'-0" 7'-0" ---1-3/4" WOOD 1 P-A

111 3'-0" 7'-0" SSP ---1-3/4" WOOD --- 1 P-A

112 3'-0" 7'-0" ---1-3/4" --- 1 P-A

C

C

C

HM

HM

HM

SSP

------ 1 P-AHM 102SSP102 3'-0" 7'-0" 1-3/4" WOOD C

---SSP 1 P-AHM 1053'-0" 7'-0" 1-3/4" ---C

INS HM

108 3'-0" 7'-0" SSP ---1-3/4" WOOD --- 1 P-AC HM 108

7'-0" P-A ---1-3/4" INS HM 3 P-AB HM

WOOD SSP

--- 107A107A 7'-0" 1-3/4" 2

SSPWOOD P-AB HM

REMOVABLE MULLION

REMOVABLE MULLION

REMOVABLE MULLION

REMOVABLE MULLION

(2) 3'-0"

(2) 3'-0"

(2) 3'-0"

(2) 3'-0"

(2) 3'-0"

HALF LITE

HALF LITE

HALF LITE

SE

E

SC

H

ED

U

LE

SEE

SCHED.

C

ALUM - ALUMINUM

HM - HOLLOW METAL

INS HM - INSULATED METAL

SW- SOLID CORE WOOD

P-A- PAINT ALKYD

PT- PAINT LATEX

SSP- STAIN, SEAL AND POLYURETHANE

ROOM FINISH SCHEDULE

NUMBER NAME FLOOR SOUTH WESTBASE

WALLS

EAST

CEILING

NUMBERMATERIAL NOTESHEIGHT

100 VESTIBULE CONC PT/GYP. BD 24X48 ACT

101 HALLWAY

MECHANICAL ROOM103

SUPERVISOR OFFICE

104 BREAK ROOM VB

NORTH

VB

VB

VB

PT/GYP. BD PT/GYP. BD PT/GYP. BD

24X48 ACT

24X48 ACT

8'-0"

PT/GYP. BD PT/GYP. BD PT/GYP. BD PT/GYP. BD

PT/GYP. BD PT/GYP. BD PT/GYP. BD PT/GYP. BD

OFFICE PT/GYP. BD PT/GYP. BD PT/GYP. BD PT/GYP. BD108

OFFICE PT/GYP. BD PT/GYP. BD PT/GYP. BD PT/GYP. BD

PT/M-GYP.

BD

24X48 ACT

24X48 ACT

VB PT/GYP. BD PT/GYP. BD PT/GYP. BD PT/GYP. BD 106

VB PT/GYP. BD PT/GYP. BD PT/GYP. BD PT/GYP. BD 105

24X48 ACT

WOMEN RESTROOM

112 112MEN RESTROOM

VB

VB

VB

VB

VB

VB

OFFICE

PT/GYP. BD PT/GYP. BD PT/GYP. BD PT/GYP. BD

PT/GYP. BD PT/GYP. BD PT/GYP. BD PT/GYP. BD

OFFICE

VB

TAF ROOM

PT/M-GYP.

BD

PT/M-GYP.

BD

PT/M-GYP.

BD

PT/M-GYP.

BD

PT/M-GYP.

BD

PT/M-GYP.

BD

PT/M-GYP.

BD

PT/M-GYP.

BD

PT/M-GYP.

BD

PT/M-GYP.

BD

PT/M-GYP.

BD

FRP 4FT HIGH BEHIND MOP BASIN,

BOTH DIRECTIONS

24X48 ACT

JANITOR CLOSET

8'-0"

8'-0"

12'-8"

8'-0"

8'-0"

8'-0"

10'-0"

8'-0"

8'-0"

8'-0"

8'-0"

8'-0"

24X48 ACT

24X48 ACT

24X48 ACT

24X48 ACT

SOUND-PROOFING TOP OF

WALL GUARD TO CEILING

PT/GYP. BD PT/GYP. BD PT/GYP. BD PT/GYP. BD PT/GYP. BD

PT/M-GYP.

BD

CONC

CONC

CONC

CONC

CONC

CONC

CONC

CONC

CONC

CONC

CONC

CONC

ACT- ACOUSTICAL CEILING TILE

CONC - SEALED CONCRETE

FRP - FIBERGLASS REINFORCED PLASTIC

GYP. BD - GYPSUM BOARD

M-GYP. BD - MOISTURE RESISTANT GYPSUM BOARD

SGB- SUSPENDED GYPSUM BOARD

EXTERIOR COLOR SCHEDULE

(NOTE: CONTRACTOR TO MATCH COLORS LISTED.)

ROOF

COUNTY MATERIALS CREAM #12-080C

MTL TRIM

SNOW GUARDS

SOFFIT

EXPOSED LINTELS

SMOOTH SURFACE CMU & FOR

TWO CENTER ACCENT BANDS

SPLIT FACE CMU TOP & BOTTOM

SMOOTH FACE BANDS

CMU MORTAR

ALUM DOORS & FRAMES

(INTERIOR & EXTERIOR)

EXTERIOR GLASS

EXTERIOR HOLLOW MTL

DOORS & FRAMES

INTERIOR HOLLOW MTL

DOORS & FRAMES

INTERIOR COLORS

NUMBER NAME FLOOR

100 VESTIBULE

101 HALLWAY

MECHANICAL ROOM103

SUPERVISOR OFFICE

104 BREAK ROOM

OFFICE108

OFFICE109

WOMEN RESTROOM

112 MEN RESTROOM

OFFICE

OFFICE

TAF ROOM

JANITOR CLOSET

BASE WALLS CEILING MISC

INTERIOR WOOD DOORS

COUNTY MATERIALS MUSHROOM #12-028A

COUNTY MATERIALS WHITE CEMENT #1385

DARK BRONZE

CLEAR LOW-E INSULATING

EXTERIOR FACE DOOR & FRAME DARK BRONZE.

INTERIOR FACE DOOR & FRAME SW 6126 NAVAJO WHITE.

MATCH EXISTING COLOR OF ADJACENT

BLDG 222, 223,225 & 227

DARK BRONZE

DARK BRONZE

DARK BRONZE

DARK BRONZE

TRIMCO SANDSTONEEXTERIOR CAULK

EXTERIOR HOLLOW MTL DOOR &

FRAME EXTERIOR FACE DOOR & FRAME BRONZE

MINWAX 210B GOLDEN OAK

S10 6126 NAVAJO WHITE

MECHANICAL ROOM INTERIOR FACE DOORS & FRAME SW7066 GRAY MATTERS.

4 3 1 8

3 1 8

7 1 8

3 1 1

3 1 8

7 1 8

7 1 8

3 1 8

7 1 8

7 1 8

3 1 8

3 1 1

3 1 8

1. GYPSUM BOARD - SHERWIN WILLIAMS SW6385, DOVER WHITE.

2. NOT USED.

3. VINYL BASE JOHNSONITE 28 - MEDIUM GRAY.

4. SEALER.

5. NOT USED.

6. NOT USED.

7. VINYL BASE JOHNSONITE 63-BURNT UMBER.

8. CEILING TILE & GRID - WHITE.

9. TOILET PARTITIONS - SCRANTON PRODUCTS GLACIER GRAY.

SCALE: 1/4"=1'-0"

FRAME TYPES

SCALE: 1/4"=1'-0"

DOOR TYPES

CBA

B224-A8.1

A nt ho ny

L an e M in ne ap ol is , M

N

P:

-4

-3

2, F : 6

-4

-3

2985 SOUTH RIDGE ROAD, SUITE B

GREEN BAY, WI 54304

SPRINKLER SYSTEM WATER FLOW SWITCH

SPRINKLER SYSTEM TAMPER SWITCH

WEATHER PROOF FIRE SPEAKER/STROBE

F.A. AUDIO / VISUAL (SPEAKER/STROBE)

WG = WIRE GUARD PROTECTED

GAS DETECTOR

MAGNETIC DOOR HOLDER

STROBE LIGHT

END OF LINE RESISTER

X = EXTERIOR

F.A. HORN

X

HEAT DETECTOR WITH AUXILIARY CONTACTS

SMOKE DETECTOR WITH AUXILIARY CONTACTS

MOUNTING HEIGHTS FOR FIRE ALARM DEVICES:

MAGNETIC DOOR HOLDERS = AS SPECIFIED

FIRE ALARM CONTROL PANEL(FACP)

HEAT DETECTOR

DUCT SMOKE DETECTOR

SMOKE DETECTOR

CARBON MONOXIDE DETECTOR

MANUAL PULL STATION = 48"

HORN/STROBE = 80"

STROBE LIGHTS = 80"

FIRE ALARM ANNUNCIATOR

MANUAL PULL STATION

NOTES:

FIRE ALARM SYMBOL LEGEND

RESCUE ASSISTANCE ANNUNCIATOR

RESCUE ASSISTANCE CALL STATION

F0.0

NOT TO SCALE

FIRE PROTECTION RISER DIAGRAM

1. WATER SERVICE FROM POST INDICATOR VALVE

2. 6"X6"X6" TEE

3. 2” FULL PORT BALL VALVE WITH BLIND FLANGE FOR RISER PUMP OUT

4. DOUBLE CHECK BACKFLOW PREVENTER

5. RISING STEM GATE VALVE WITH TAMPER SWITCH

6. PRESSURE GAGE

7. DRY PIPE VALVE (TRIM NOT SHOWN)

8. MAIN DRAIN

9. MAIN DRAIN VALVE

10. CHECK VALVE

11. FIRE DEPARTMENT CONNECTION

12. BALL DRIP VALVE

13. WATER FLOW SWITCH

14. ALARM GONG

15. LINE DRAIN

16. 1” AIR COMPRESSOR CONNECTION FOR PLUMBING SYSTEM BLOWOUT

TO DRY

SPRINKLER

SYSTEM

NOTE:

SIZES AND ORIENTATIOIN

MAY CHANGE FROM BUILDING

TO BUILDING.

TO BUILDING

WATER SERVICE

CBA

B224-F0.0

A nt ho ny

L an e M in ne ap ol is , M

N

P:

-4

-3

2, F : 6

-4

-3

2985 SOUTH RIDGE ROAD, SUITE B

GREEN BAY, WI 54304

6"

NEW COMBINED 6"FIRE PROTECTION/

DOMESTIC WATER SERVICE.

(BY FIRE PROTECTION CONTRACTOR)

DRY PIPE SPRINKLER RISER

FIRE DEPARTMENT CONNECTION

5" STORZ FLUSH MOUNTED

WALL TYPE

INSPECTORS TEST CONNECTION

LIGHT HAZARD OCCUPANCY

DESIGN FOR 0.10 GPM/SQ. FT.

COVERAGE FOR ENTIRE BLDG.

INCLUDING ATTIC SPACE AREA

CONTRACTOR SHALL DESIGN/BUILD A DRY PIPE SYSTEM IN ACCORDANCE WITH NFPA 13 (2007) AND UFC 3-600-01 FIRE PROTECTION ENGINEERING FOR FACILITIES, WITH ALL REQUIRED FIRE ALARM SYSTEM SUPERVISORY SWITCHES, SENSORS, AND FIRE DEPARTMENT CONNECTIONS. THE SYSTEM SHALL PROVIDE COVERAGE FOR THE ENTIRE BUILDING, INCLUDING THE ATTIC SPACE AREA. ALL SYSTEM MATERIAL, HANGER COMPONENTS AND INSTALLATION METHODS SHALL BE IN COMPLIANCE NFPA 13 (2007). TESTING STATIONS SHALL BE INSTALLED AT THE END OF EACH SPRINKLER RISER, WITH THE DISCHARGE PIPE INSTALLED THROUGH THE WALLS. THE TEST VALVES SHALL BE INSTALLED AT THE END OF EACH RISER IN THE SUSPENDED CEILING.

BUILDING IS SUBJECT TO DEACTIVATION DURING WINTER MONTHS; THEREFORE SPRINKLER HEAD PENDANTS SHALL BE CHARGED WITH AN INERT GAS TO PREVENT WATER FROM ACCUMULATING IN THEM. IN ADDITION, ALL PIPING SHALL BE INSTALLED WITH SUFFICIENT PITCH TO ENSURE ALL WATER WILL COMPLETELY DRAIN FROM THE SYSTEM AFTER ALL TESTS. THE FIRE LATERAL SHALL CONTAIN A "TEE" WITH A PLUG IMMEDIATELY AFTER PENETRATING THE CONCRETE FLOOR; THE "TEE" IS TO ALLOW THE RISER TO BE PUMPED OUT UPON DEACTIVATION.

CONTRACTOR SHALL DETERMINE VOLUME AND PRESSURE OF INCOMING WATER SUPPLY FROM WATER FLOW TEST DATA AND THEN DESIGN SYSTEM TO NFPA 13

LIGHT HAZARD OCCUPANCY REQUIREMENTS. GOVERNMENT WILL PROVIDE FLOW TEST DATA.

1.

2.

3.

GENERAL NOTES

DRY PIPE SPRINKLER

SYSTEM AIR COMPRESSOR

6" REDUCED PRESSURE

PRINCIPLE BACKFLOW PREVENTER

6" INV EL 94.00

F1.2

SCALE: 3/16"= 1'-0"

FIRE PROTECTION PLAN

CBA

B224-F1.2

A nt ho ny

L an e M in ne ap ol is , M

N

P:

-4

-3

2, F : 6

-4

-3

2985 SOUTH RIDGE ROAD, SUITE B

GREEN BAY, WI 54304

NOTE: SOME SYMBOLS LISTED IN THIS SCHEDULE MAY NOT APPEAR ON DRAWINGS.

HVAC CONTRACTOR

SITE UTILITY CONTRACTOR

GENERAL CONTRACTOR

FIRE PROTECTION CONTRACTOR

ELECTRICAL CONTRACTOR

HC

EC

FPC

SC

GC

ABOVE FINISH FLOOR

VENT THROUGH ROOF

DIRECTION OF FLOW

PIPE DOWN OR DROP

WATER HAMMER ARRESTOR

FLUSH CLEANOUT/WALL CLEANOUT

PIPE SIZE (FIXTURE UNIT VALUE)

PRESSURE REDUCING VALVE

BACKFLOW PREVENTER

PLUMBING CONTRACTOR

WASTE STACK

VENT STACK

VTR

AFF

PC

VS

WS

WHA

FCO/WCO

PIPE CAP

PIPE UP OR RISE

CHECK VALVE

BALANCING VALVE

GAS COCK

GATE VALVE

BALL, CHECK & BALANCING VALVE

S…