This document outlines a federal contract opportunity for generator and electrical upgrades at an Air National Guard base in Tulsa, Oklahoma. The solicitation seeks a single firm fixed-price contract to provide all plant, labor, transportation, materials, tools, equipment, appliances and supervision necessary to upgrade the generator and electric components. The North American Industry Classification code is 236220 with a size standard of $39.5 million. The estimated value is between $100,000 and $250,000. Requests for information are due by May 19, 2022 and award will be made to the responsible bidder offering the most advantageous price. The opportunity is set aside 100% for small businesses. The soliciting agency is the Department of the Army National Guard.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Date: RFI No.

IFB Reference (Sect/Para/Page) RFI QUESTION GOVERNMENT RESPONSE

5/10/2022 1 Para 5: Bid Option 1 What areas require installation of bay lighting?

The remainder of the structure that is not covered the base bid for bay lighting. Two spaces, total area: 25 ft W x 40 ft L x 20 ft H and 65 ft W by 40 ft L by 20 ft W.

5/10/2022 2 Para 8: Bid Option 4 Specify size of water line. Contractor to feed frost proof yard hydrant via 1 inch line.

5/10/2022 2 Para 8: Bid Option 4 Location of frost proof yard hydrant Install hydrant on N wall of enclosed bay of B027. Install on E corner of N wall.

5/13/2022 4 SOW, Pg 3, Para 2

In the base bid note 2, it calls for a 240V disconnect.

Which is single phase. Note 2,b, calls for a 50A 2-pole 240V breaker to feed the 240V disconnect. The power that is available is 120/208V 3-phase. Is this feed supposed to be 208V single phase?

Contractor should expect to provide transformer to feed the required 240V disconnect.

5/13/2022 5 SOW, Pg 5, Para 6, Bid Option 2

In bid option #2, It calls out to feed a new 200A panel from an existing 75kva transformer. During the walk through this transformer was already feeding another 200A panel. There is not enough power to feed another 200A panel from this transformer. Where is another option to feed this panel?

Bid Option 2 is no longer required.

5/13/2022 6 SOW, Pg 3, Para 1 Are we responsible for demo and disposal of the existing generator?

Reference note in SOW. The government will disconnect and remove the existing generator.

5/13/2022 7 SOW, Pg 5, Para 7, Bid Option 3 In bid option #3 it calls for us to install a new 100a 120V 8 space subpanel. Where will this panel be fed from?

There is a junction box ~5 feet from the new panel location.

That junction box has existing 4" conduit running to a transformer on the SW side of the building. The expected run to that transformer should not exceed 100 feet

5/13/2022 8 Automatic Transfer Switch Do you have a data sheet for the automatic transfer switch that is going to be installed prior to the generator installation.

Yes, please see the attached data sheet for the OTEC1200 transfer switch.

Pre-Bid RFI Log for Generator and Electrical Upgrades