RACEWAY SYMBOLS

JUNCTION BOX

RECEPTACLE SYMBOLS

DUPLEX RECEPTACLE

DOUBLE DUPLEX RECEPTACLE

DENOTES SWITCH LEG FOR SWITCHED OUTLETSa

RECEPTACLE NOTATIONS:

DENOTES DEDICATED OUTLETSD

DENOTES HORIZONTALLY MOUNTED OUTLETSH

DENOTES TAMPER RESISTANT SAFETY OUTLETSTR

DENOTES WEATHER PROOF OUTLETSWP

DENOTES EXPLOSION PROOF CLASS 1 DIVISION 2 OUTLETSX2

DENOTES EXPLOSION PROOF CLASS 1 DIVISION 1 OUTLETSX1

DENOTES GROUND FAULT INTERRUPTER OUTLETSGFCI

DENOTES COMBINATION DUPLEX/USB OUTLETSUSB

DENOTES ISOLATED GROUND OUTLETSIG

DENOTES ELECTRIC WATER COOLER OUTLETSEWC

MULTI-OUTLET RACEWAY - OUTLETS ON CENTER AS

INDICATED ON DRAWINGS AND IN THE SPECIFICATIONS,

MOUNTED 6" ABOVE COUNTER OR AT HEIGHT AS

INDICATED.

A

SERVICE & DISTRIBUTION SYMBOLS

PANELBOARD

EMERGENCY SHADING MODIFIER

MOTOR & EQUIPMENT CONNECTION

SYMBOLS

DOUBLE THROW SWITCH

ENCLOSED CIRCUIT BREAKER

GENERAL SYMBOLS

KEYED NOTE, USED TO DESCRIBE ADDITIONAL

INFORMATION OF WORK REQUIRED, SPECIFIC TO

THE SHEET AND/OR DETAIL IT IS SHOWN WITH.

DETAIL NUMBER / SHEET NUMBER#/E-###

9.###

# KITCHEN EQUIPMENT TAG. # REFERS TO

CORRESPONDING NUMBER IN KITCHEN

EQUIPMENT SCHEDULE.

LINE TYPE KEY

EXISTING TO BE REMOVED BY THIS

CONTRACTOR (DARK DASHED LINE)

EXISTING TO REMAIN WORK

(THIN SOLID LINE)

NEW WORK BY THIS CONTRACTOR

(DARK SOLID LINE)

ONE-LINE EQUIPMENT ENCLOSURE

PANEL DIVISION LINES

SINGLE POLE SWITCH

LUMINAIRE CONTROL SYMBOLS

OCCUPANCY SENSOR CEILING MOUNT (X REPRESENTS

OCCUPANCY/PHOTO SENSOR SCHEDULE DESIGNATION)

LUMINAIRE SYMBOLS

RECESSED LUMINAIRE

RECESSED TROFFER

RECESSED LINEAR

WALL MOUNTED EXIT SIGN

CEILING MOUNTED EXIT SIGN

SURFACE LINEAR

OS

ARROW DENOTES EXIT SIGN CHEVRON

SWITCH NOTATIONS:

3 DENOTES 3-WAY SWITCH

4 DENOTES 4-WAY SWITCH

EMERGENCY SHADING MODIFIER

WALL SURFACE LINEAR

A1

1Ra

LUMINAIRE TYPE

LUMINAIRE CIRCUITRY & CONTROL KEY:

LOWER CASE LETTER INDICATES SWITCHLEG CONTROL

"R" INDICATES LIGHTING CONTROL PANEL

REFER TO LIGHTING CONTROL PANEL SCHEDULE

NUMBER INDICATES BRANCH PANEL CIRCUIT NUMBER

SITE SYMBOLS

M ELECTRIC METER

DEMOLITION GENERAL NOTES:

1. THE INFORMATION SHOWN IS BASED ON EXISTING

DRAWINGS AND SITE OBSERVATIONS TO ASSIST

CONTRACTOR IN BIDDING. THE DRAWINGS ARE INTENDED

TO INDICATE THE SCOPE OF WORK REQUIRED AND DO

NOT INDICATE EVERY BOX, CONDUIT, OR WIRE THAT MUST

BE REMOVED. THE CONTRACTOR SHALL VISIT THE SITE

PRIOR TO SUBMITTING A BID AND VERIFY EXISTING

CONDITIONS.

WHERE LIGHTS, SWITCHES, RECEPTACLES, ETC., ARE

BEING REMOVED ALL ASSOCIATED CONDUIT AND WIRE

BACK TO THE PANELBOARD OR FEEDER JUNCTION BOX

SERVING THE DEVICE SHALL ALSO BE REMOVED, UNLESS

THE CONDUIT CAN BE REUSED FOR NEW CONDUCTORS.

THE CONTRACTOR SHALL DISPOSE OF MATERIAL THE

OWNER DOES NOT WANT TO REUSE OR RETAIN FOR

MAINTENANCE PURPOSES.

EXISTING CONDUIT IN GOOD CONDITION, MAY BE REUSED

IN PLACE. RELOCATED EXISTING CONDUIT SHALL NOT BE

ALLOWED. BONDING CONDUCTORS SHALL BE INSTALLED

IN ALL REUSED CONDUIT TO ASSURE PROPER GROUND

PATH.

MAINTAIN CIRCUIT CONTINUITY OF DEVICES LOCATED

OUTSIDE OF CONSTRUCTION AREA. DEVICE AND

EQUIPMENT REMOVAL IN CERTAIN LOCATIONS MAY

REQUIRE THE INSTALLATION OF A JUNCTION BOX TO

RECONNECT CIRCUITS THAT REMAIN IN OPERATION.

EXTEND CONDUIT AND WIRING AS REQUIRED TO MAINTAIN

POWER TO REMAINING EQUIPMENT.

CONTRACTOR SHALL REMOVE AND INSTALL ALL CEILING

TILES AS REQUIRED FOR THE EXECUTION OF ELECTRICAL

WORK THAT IS OUTSIDE THE CONTRACT LIMITS OF

CONSTRUCTION. CONTRACTOR SHALL REPLACE CEILING

TILES WITH IDENTICAL MATERIAL WHERE DAMAGED BY

THIS CONTRACTOR.

PROVIDE REVISED TYPED CIRCUIT DIRECTORY IN

PANELBOARDS THAT HAVE CIRCUITS REMOVED OR

ADDED CIRCUITS.

REMOVE EXPOSED ABANDONED CONDUIT, INCLUDING

ABANDONED CONDUIT ABOVE ACCESSIBLE CEILING

FINISHES. CUT RACEWAY FLUSH WITH WALLS AND

FLOORS, PATCH SURFACES TO MATCH EXISTING. REMOVE

ALL ASSOCIATED CLAMPS, HANGERS, SUPPORTS, ETC.

ASSOCIATED WITH RACEWAY REMOVAL.

2.

3.

4.

5.

6.

7.

GENERAL NOTES:

1.

2.

3.

4.

5.

6.

7.

8.

9.

THE CONTRACTOR SHALL BECOME FAMILIAR WITH THE

DETAILS OF WORK, VERIFY DIMENSIONS IN THE FIELD,

AND ADVISE THE CONTRACTING OFFICER OF ANY

DISCREPANCY BEFORE PERFORMING ANY WORK.

THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE

WITH THE ADAAG (AMERICANS WITH DISABILITIES ACT

ACCESSIBILITY GUIDELINES).

SEAL ALL RATED PENETRATIONS AS IDENTIFIED IN

DIVISION 1 REQUIREMENTS.

CIRCUIT NUMBERS ARE SHOWN FOR CIRCUIT

IDENTIFICATION. CIRCUITING SHALL AGREE WITH

NUMBERING ON THE PANEL SCHEDULES PROVIDED.

BALANCE THE LOAD ON PANELS AS EVENLY AS POSSIBLE

BETWEEN EACH PHASE. COMMON NEUTRALS MAY [NOT]

BE USED FOR BRANCH CIRCUITS. BALANCE THE LOAD ON

PANEL AS EVENLY AS POSSIBLE BETWEEN EACH PHASE.

A #12 GREEN INSULATED GROUND CONDUCTOR SHALL BE

INSTALLED WITH CIRCUIT CONDUCTORS TO ALL

RECEPTACLES.

CONCEAL ALL CONDUIT IN WALLS, PARTITIONS, ABOVE

CEILING, ETC. UNLESS OTHERWISE INDICATED ON THE

PLANS OR IN THE SPECIFICATIONS. CONDUIT IN

MECHANICAL ROOMS, AND STORAGE ROOMS WITHOUT

CEILINGS MAY BE EXPOSED ON BUILDING STRUCTURE.

WHERE RACEWAY IS REQUIRED ON EXISTING CONCRETE

AND MASONRY WALLS, SURFACE RACEWAY MAY BE USED

IN LIEU OF CHANNELING WALLS TO ALLOW CONCEALED

ROUTING. THE RACEWAY SHALL BE SINGLE CHANNEL

STYLE TYPE WITH IVORY FINISH. THIS APPLIES FOR

BRANCH CIRCUIT CONDUITS UP TO 3/4" SIZE. CONDUITS

LARGER THAN 3/4" MAY BE ROUTED EXPOSED, BUT

INSTALLED PARALLEL AND/OR PERPENDICULAR TO

BUILDING LINES AND RUN AS UNOBTRUSIVELY AS

POSSIBLE.

CONTRACTOR TO PROVIDE SUITABLE MECHANICAL

PROTECTION AROUND ALL CONDUITS STUBBED OUT

FROM FLOORS, WALLS OR CEILINGS DURING

CONSTRUCTION TO PREVENT BENDING OR DAMAGING OF

STUB OUTS DUE TO CARELESSNESS WITH

CONSTRUCTION EQUIPMENT.

CONTRACTOR SHALL BE RESPONSIBLE FOR ALL

OPENINGS REQUIRED IN WALLS. ALL OPENINGS SHALL BE

REPAIRED TO MATCH EXISTING BY A QUALIFIED

CONTRACTOR AT THE EXPENSE OF THIS CONTRACTOR.

ALL CONDUITS THROUGH WALLS SHALL BE GROUTED OR

SEALED INTO OPENINGS.

CONTRACTOR SHALL REMOVE AND REINSTALL ALL

CEILING TILES AS REQUIRED FOR THE EXECUTION OF

ELECTRICAL WORK THAT IS OUTSIDE THE CONTRACT

LIMITS OF CONSTRUCTION. CONTRACTOR SHALL

REPLACE CEILING TILES WITH IDENTICAL MATERIAL

WHERE DAMAGED BY THIS CONTRACTOR.

STEEL CONDUIT

CLASS 1 TYPE A

DIELECTRIC LINK THREADED

COUPLING (SCH. 80 PVC)

SECURE AREA INTERIOR WALL

SEAL WITH ACOUSTICAL FIRE PROOF

SEALANT ALL THE WAY AROUND

1/2" MINIMUM SEPARATION BETWEEN

ONE-LINE SYMBOLS

LOW VOLTAGE CIRCUIT BREAKER

GENERATOR

PANELBOARD (ELEVATION VIEW)

TRANSFORMER

Mead & Hunt, Inc.

2440 Deming Way

Middleton, WI 53562 phone: 608-273-6380 meadhunt.com

SHEET NO.:

SHEET CONTENTS

DO NOT SCALE DRAWINGS

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

ISSUED

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

/1

/2

:2

:0

A

M C

R e v it L o c a l\

-1

.0

-E

-C e n tr a l-jr h

.r v t

M ic h ig a n A ir N a ti o n a l G u a rd

B a tt le

C re e k A ir N a ti o n a l G u a rd

B a s e

B a tt le

C re e k M ic h ig a n

G e n e ra to r

L o a d D ra w in g s

E-001

NOTES, SYMBOLS &

ABBREVIATIONS

3141900-171628.02

RKK

JRH

02/15/2018

JRH

ELECTRICAL ABBREVIATIONS

LFS LIGHTING FIXTURE SCHEDULE

MAU MAKE-UP AIR UNIT

MAX MAXIMUM

MC MECHANICAL CONTRACTOR

MCC MOTOR CONTROL CENTER

MDF MAIN DISTRIBUTION FRAME

MDP MAIN DISTRIBUTION PANEL

MIN. MINIMUM

MNS MASS NOTIFICATION SYSTEM

MTD MOUNTED

MTG MOUNTING

MTS MANUAL TRANSFER SWITCH

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NL/EL NIGHT LIGHT AND EMERGENCY LIGHT

NTS NOT TO SCALE

OC ON CENTER

OFCI OWNER FURNISHED, CONTRACTOR INSTALLED

OFOI OWNER FURNISHED, OWNER INSTALLED

PH PHASE

PNL PANEL

PVC POLYVINYL CHLORIDE

RCP RADIANT CEILING PANEL

RECPT RECEPTACLE

REF REFRIGERATOR

REQ'D REQUIRED

RF RETURN FAN

RGS RIGID GALVANIZED STEEL CONDUIT

MAY ALSO BE REFERENCED AS RMC OR GRC

RMC RIGID METAL CONDUIT

RTU ROOF TOP UNIT

S/N SOLID NEUTRAL

SE SERVICE ENTRANCE

SEC-P SECURITY PANEL

SF SUPPLY FAN

SP SUMP PUMP

SS STAINLESS STEEL

SW SWITCH

SWBK SWITCH BANK

TBR TO BE REMOVED

TCP TEMPERATURE CONTROL PANEL

TFA TO FLOOR ABOVE

TFB TO FLOOR BELOW

TYP TYPICAL

UC UNIT COOLER

UG UNDERGROUND

UH UNIT HEATER

UNO UNLESS NOTED OTHERWISE

UV UNIT VENTILATER

V VOLTS

VER VEHICLE EXHAUST REEL

VFD VARIABLE FREQUENCY DRIVE

VS VERSUS

W WATTS

WCC WATER COOLED CONDENSER

WFE WELDING FUME EXTRACTOR

WH WATER HEATER

WL WET LOCATION LISTED

WP WEATHERPROOF

XFMR TRANSFORMER

XP EXPLOSION PROOF

ELECTRICAL ABBREVIATIONS

3R NEMA 3R RATING

4X NEMA 4X RATING

A AMPERES

A/E ARCHITECT / ENGINEER

AAC ABOVE ACCESSIBLE CEILING

ACCU AIR COOLED CONDENSING UNIT

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHU AIR HANDLING UNIT

ALT ALTERNATE

APE AIRCRAFT PROCESS EQUIPMENT

ATS AUTOMATIC TRANSFER SWITCH

BLDG BUILDING

BRKR BREAKER

C CONDUIT

CB CIRCUIT BREAKER

CF CIRCULATION FAN

CH CHILLER

CHWP CHILLED WATER PUMP

CKT CIRCUIT

CP CIRCULATION PUMP

CRAC COMPUTER ROOM AIR CONDITIONER

CRP CONDENSATION RETURN

CT COOLING TOWER

CUH CABINET UNIT HEATER

DC DROP CORD

DDC DIGITAL CONTROL PANEL

DH DUCT HEATER

DISC DISCONNECT

DO DOOR OPERATOR

DWG DRAWING

E/O ELECTRICAL-TO-OPTICAL CONVERTER

EC ELECTRICAL CONTRACTOR

ECB ENCLOSED CIRCUIT BREAKER

EF EXHAUST FAN

EM EMERGENCY

EMT ELECTRICAL METALLIC TUBING

ES EQUIPMENT SUPPLIER

ETR EXISTING TO REMAIN

EWC ELECTRICAL WATER COOLER

EWH ELECTRICAL WATER HEATER

F FUSED

FA FIRE ALARM

FAF FORCED AIR FURNACE

FCU FAN COIL UNIT

GC GENERAL CONTRACTOR

GD GARBAGE DISPOSAL

GFI GROUND FAULT INTERRUPTER

GND GROUND

GWH GAS WATER HEATER

HD HAND DRYER

HP HORSEPOWER

HVAC HEATING, VENTILATION, AIR CONDITIONING

HWB HOT WATER BOILER

HWP HOT WATER PUMP

IEWH INSTANTANEOUS ELECTRIC WATER HEATER

IH INFRARED HEATER

IMC INTERMEDIATE METALLIC CONDUIT

IWH INSTANTANEOUS WATER HEATER

J-BOX JUNCTION BOX

LBS POUNDS

NO SCALE1

SECURE AREA PENETRATION DETAIL AND AIC RATING (10KAIC) OF EXISTING PANELBOARD.

NOTE: EXISTING PANEL IS SQUARE D TYPE NQ. NEW CIRCUIT BREAKERS (INDICATED IN BOLD) SHALL MATCH MANUFACTURER

Key Notes

Key: A=HACR G=GFI H=HANDLE LOCK C=THRU CONTACTOR I=ISOLATED GROUND S=SHUNT TRIP P=PADLOCK HASP

RECEPTACLES (RM... 29 20/1 900 1,317 20/1 30 LIGHTING EXT LGT(RM 110, 111)

RECEPTACLES (RM... 27 20/1 1,080 901 20/1 28 LIGHTING (RM 108,109,121,122)

RECEPTACLES (RM... 25 20/1 720 720 20/1 26 RECEPTACLES (RM 110)

RECEPTACLES (RM... 23 20/1 720 0 24

RECEPTACLES (RM... 21 20/1 720 720 20/1 22 RECEPTS RM 120

CAMERA PS 19 20/1 500 1,200 20/1 20 ADVANTOR PANEL

17: EXT CAMERA 17 20/1 240 1,200 20/1 18 ADVANTOR PANEL

FMCP 15 20/1 1,500 1,200 20/1 16 ACCESS CONTROL

GEN EPO 13 20/1 120 0 20/1 14 SPARE

CAMERAS 11 20/1 240 0 20/1 12 SPARE

9 | 0 0 20/1 10 SPARE

TANK HEATER 7 20/2 500 1,200 20/1 8 TCP

GENERATOR RECEPT 5 20/1 200 1,200 20/1 6 TCP

BATTERY CHARGER 3 20/1 1,500 0 | 4 -

BATTERY HEATER 1 20/1 300 750 30/2 2 JACKET HEATER

Note Fed No A/P A B C A B C A/P No Fed Note

Key Load to be Cct Brkr Left Phases Right Phases Brkr Cct Load to be Key

Iso Grd

Comments: SPD

Pnl MCA 55 A SE Rated Sub-Feed Brkr #2 None

SCCR 10KAIC

Enclosure NEMA 1 Sub-Feed Brkr #1 None

Mounting Surface MCB Amps/Poles - Delta/Wye Wye Sub-Feed Lugs None

Main Type MLO Wires 4 Branch Brkr Space 30 Poles Phase 3 Feed-Thru Lugs None

Bus Ampacity 100 Volts 208Y/120 Panel Source: DP-XLA

Panelboard: Panel GEN-XLA

F.E.

F .E

POWER GENERAL NOTES:

1. SEE SHEET E-001 FOR SYMBOLS AND ABBREVIATIONS.

SEE SHEET E-700 SERIES DRAWINGS FOR ELECTRICAL ONE-LINE POWER

DISTRIBUTION DIAGRAMS.

2.

DP/XLA

MSB/XHA

ATS/XA

CB/XA

'T/XLA'

MSB/HA

'T/H'

PANEL K

GEN/XLA

PANEL 'H'

9.102

9.101

UPS/XA

PANEL

'UPS/XA'

PANEL

'UPS/XB'

PANEL 'SOC/A'

PANEL 'GCS/C'

PANEL 'GCS/B'

PANEL 'GCS/A'

EXISTING PANEL 'A'

EXISTING PANEL 'MDP'

EXISTING PANEL 'EM'

PANEL 'J'

'T/J'

9.101

9.228

9.228 9.228

'CB/J'

EXISTING

200A DOUBLE

THROW

SWITCH

KEYED NOTES

9.101 ROUTE NEW FEEDER FOR SERVING TRANSFORMER T/J OUTSIDE OF SECURE AREA A.

COORDINATE EXACT ROUTE IN FIELD.

9.102 PROVIDE 12" X 12" X 4" (MIN.) PULLBOX FOR NEW FEEDER SERVING TRANSFORMER T/J.

9.228 SECURE AREA PERIMETER. COORDINATE WITH GENERAL CONTRACTOR, MINIMIZE CO-LOCATE, AND SEAL ALL SECURE AREA PENETRATIONS. SEE DETAIL 1/E-001. CAULK AND SEAL ALL

CONDUIT PENETRATIONS IN A MANNER THAT MAINTAINS ROOM'S SOUND TRANSMISSION

CLASS (STC) RATING OF 45.

Mead & Hunt, Inc.

2440 Deming Way

Middleton, WI 53562 phone: 608-273-6380 meadhunt.com

SHEET NO.:

SHEET CONTENTS

DO NOT SCALE DRAWINGS

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

ISSUED

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

/1

/2

:0

:2

P

M C

R e v it L o c a l\

-1

.0

-E

-C e n tr a l-rk k .r v t

M ic h ig a n A ir N a ti o n a l G u a rd

B a tt le

C re e k A ir N a ti o n a l G u a rd

B a s e

B a tt le

C re e k M ic h ig a n

G e n e ra to r

L o a d D ra w in g s

E-101

FIRST FLOOR PLAN

3141900-171628.02

RKK

MAS

02/15/2018

JRH

1/8" = 1'-0"1

FIRST FLOOR PLAN

WS WS

OS OS OS

OS

OS

OS

OS OS

OS

WS

3a 3b a,b a,b

4b 4a a,b

28a,b

9.201

9.201 9.202

9.203

28a,b

28a,b

28a,b

28a,b

28a,b

28a,b

28a,b

28a,b

28a,b

28a,b

28a,b

28a,b

28a,b

28a,b

28a,b

303030303030303030

30 30

30 30

30GEN/XLA

PANEL H

LIGHTING GENERAL NOTES:

1. SEE SHEET E-001 FOR SYMBOLS AND ABBREVIATIONS.

SEE SHEET E-601 FOR PANEL SCHEDULES2.

3. SEE SHEET E-700 SERVICE DRAWINGS FOR ONE LINE POWER DISTRIBUTION

DIAGRAM.

ALL 120 VOLT LIGHTING ON THIS PLAN SHALL BE WIRED FROM PANEL 'GEN-

XLA' UNLESS NOTED OTHERWISE.

4.

Mead & Hunt, Inc.

2440 Deming Way

Middleton, WI 53562 phone: 608-273-6380 meadhunt.com

SHEET NO.:

SHEET CONTENTS

DO NOT SCALE DRAWINGS

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

ISSUED

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

/1

/2

:0

:2

P

M C

R e v it L o c a l\

-1

.0

-E

-C e n tr a l-rk k .r v t

M ic h ig a n A ir N a ti o n a l G u a rd

B a tt le

C re e k A ir N a ti o n a l G u a rd

B a s e

B a tt le

C re e k M ic h ig a n

G e n e ra to r

L o a d D ra w in g s

E-121

FIRST FLOOR

LIGHTING PLAN

3141900-171628.02

RKK

MAS

02/15/2018

JRH

KEYED NOTES

9.201 DISCONNECT EXISTING BRANCH CIRCUIT IN PANEL H (CIRCUIT 10), PULL

CONDUCTORS BACK TO NEAREST JUNCTION BOX, SPLICE AND RE-ROUTE

TO PANEL GEN-XLA (CIRCUIT 28). REVISE H-10 TO BE SPARE CIRCUIT

BREAKER. EXISTING SWITCHING AND LIGHTING CONTROLS SHALL REMAIN.

9.202 DISCONNECT EXISTING BRANCH CIRCUIT IN PANEL H (CIRCUIT 4), PULL

CONDUCTORS BACK TO NEAREST JUNCTION BOX, SPLICE AND RE-ROUTE

TO PANEL GEN-XLA (CIRCUIT 30). REVISE H-4 TO BE SPARE CIRCUIT

BREAKER. EXISTING SWITCHING AND LIGHTING CONTROLS SHALL REMAIN.

9.203 DISCONNECT EXISTING EXIT SIGN BRANCH CIRCUIT IN PANEL H (CIRCUIT

16), PULL CONDUCTORS BACK TO NEAREST JUNCTION BOX, SPLICE AND

RE-ROUTE TO PANEL GEN-XLA (CIRCUIT 30). REVISE H-16 TO BE SPARE

CIRCUIT BREAKER. EXISTING SWITCHING AND LIGHTING CONTROLS SHALL

REMAIN.

1/8" = 1'-0"1

FIRST FLOOR LIGHTING PLAN

F .E

9.301

23 23

21 21

25 25

POWER GENERAL NOTES:

1. SEE SHEET E-001 FOR SYMBOLS AND ABBREVIATIONS.

2. SEE SHEET E-700 SERIES DRAWINGS FOR ELECTRICAL ONE-LINE POWER

DISTRIBUTION DIAGRAMS.

Mead & Hunt, Inc.

2440 Deming Way

Middleton, WI 53562 phone: 608-273-6380 meadhunt.com

SHEET NO.:

SHEET CONTENTS

DO NOT SCALE DRAWINGS

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

ISSUED

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

/1

/2

:0

:2

P

M C

R e v it L o c a l\

-1

.0

-E

-C e n tr a l-rk k .r v t

M ic h ig a n A ir N a ti o n a l G u a rd

B a tt le

C re e k A ir N a ti o n a l G u a rd

B a s e

B a tt le

C re e k M ic h ig a n

G e n e ra to r

L o a d D ra w in g s

E-131A

FIRST FLOOR PLAN

AREA A - RPA OPS -

POWER

3141900-171628.02

RKK

MAS

02/15/2018

JRH

1/8" = 1'-0"1

FIRST FLOOR PLAN AREA A - RPA OPS - POWER

KEYED NOTES

9.301 DISCONNECT EXISTING BRANCH CIRCUITS IN PANEL H (CIRCUITS

25,27,29,31,33,39), PULL CONDUCTORS BACK TO NEAREST JUNCTION BOX,

SPLICE AND RE-ROUTE TO PANEL GEN-XLA (NEW CIRCUITS ARE INDICATED).

REVISE CIRCUIT BREAKERS IN PANEL H TO BE SPARE.

VFD

A GS

EXISTING MDP

120Y/208V - 3PH, 4W

G

200Y

EXISTING 150KVA TRANSFORMER

J E EM

EXISTING SQUARE D 'QMB' PANELBOARD

GEN

200Y

SPD

240KA EA

L-L L-N N-G

80Y

EXIST

COND.

UNIT

EXIST EXIST EXISTAHU-3

23MCA

(ABI#3)

G

149 156

149 143 149

SITE

REFER TO

SHEET E-702 FOR

CONTINUATION

B

200Y

XFMR T/J

75 KVA

480V PRI, 3PH, 3W

208Y/120V SEC, 3PH 4W

TRAPEZE MOUNTED

9.303

9.302

'CB/J'

200A/3P ENCLOSED

CIRCUIT BREAKER

COPPER FEEDER SCHEDULE

NO. CONDUCTOR SIZES (AWG or KCMIL) CONDUIT

MARK AMPACITY OF SETS PHASE NEUTRAL EQ GND SIZE

20 20 1 3 - # 12 - 1 - # 12 1/2"

20Y 20 1 3 - # 12 1 - # 12 1 - # 12 1/2"

20N 20 1 3 - # 12 1 - # 8 1 - # 12 3/4"

25 25 1 3 - # 10 - 1 - # 10 1/2"

25Y 25 1 3 - # 10 1 - # 10 1 - # 10 1/2"

25N 25 1 3 - # 10 1 - # 10 1 - # 10 1/2"

30 30 1 3 - # 10 - 1 - # 10 3/4"

30Y 30 1 3 - # 10 1 - # 10 1 - # 10 3/4"

30N 30 1 3 - # 10 1 - # 6 1 - # 10 1"

35 35 1 3 - # 8 - 1 - # 10 3/4"

35Y 35 1 3 - # 8 1 - # 8 1 - # 10 3/4"

35N 35 1 3 - # 8 1 - # 8 1 - # 10 3/4"

40 40 1 3 - # 8 - 1 - # 10 3/4"

40Y 40 1 3 - # 8 1 - # 8 1 - # 10 1"

40N 40 1 3 - # 8 1 - # 4 1 - # 10 1"

45 45 1 3 - # 6 - 1 - # 10 3/4"

45Y 45 1 3 - # 6 1 - # 6 1 - # 10 1"

45N 45 1 3 - # 6 1 - # 6 1 - # 10 1"

50 50 1 3 - # 6 - 1 - # 10 1"

50Y 50 1 3 - # 6 1 - # 6 1 - # 10 1-1/4"

50N 50 1 3 - # 6 1 - # 3 1 - # 10 1-1/4"

60 60 1 3 - # 4 - 1 - # 10 1"

60Y 60 1 3 - # 4 1 - # 4 1 - # 10 1-1/4"

60N 60 1 3 - # 4 1 - # 2 1 - # 10 1-1/2"

70 70 1 3 - # 4 - 1 - # 8 1-1/4"

70Y 70 1 3 - # 4 1 - # 4 1 - # 8 1-1/4"

70N 70 1 3 - # 4 1 - # 1/0 1 - # 8 1-1/2"

80 80 1 3 - # 3 - 1 - # 8 1-1/4"

80Y 80 1 3 - # 3 1 - # 3 1 - # 8 1-1/4"

80N 80 1 3 - # 3 1 - # 2/0 1 - # 8 1-1/2"

100 100 1 3 - # 1 - 1 - # 8 1-1/2"

100Y 100 1 3 - # 1 1 - # 1 1 - # 8 1-1/2"

100N 100 1 3 - # 1 1 - # 3/0 1 - # 8 2"

125 125 1 3 - # 1/0 - 1 - # 6 1-1/2"

125Y 125 1 3 - # 1/0 1 - # 1/0 1 - # 6 2"

125N 125 1 3 - # 1/0 1 - 250 1 - # 6 2-1/2"

150 150 1 3 - # 1/0 - 1 - # 6 1-1/2"

150Y 150 1 3 - # 1/0 1 - # 1/0 1 - # 6 2"

150N 150 1 3 - # 2/0 1 - 350 1 - # 4 2-1/2"

175 175 1 3 - # 2/0 - 1 - # 6 2"

175Y 175 1 3 - # 2/0 1 - # 2/0 1 - # 6 2"

175N 175 1 3 - # 3/0 2 - # 2/0 1 - # 4 2-1/2"

200 200 1 3 - # 3/0 - 1 - # 6 2"

200Y 200 1 3 - # 3/0 1 - # 3/0 1 - # 6 2-1/2"

200N 200 1 3 - # 4/0 2 - # 3/0 1 - # 4 3"

225 225 1 3 - # 4/0 - 1 - # 4 2"

225Y 225 1 3 - # 4/0 1 - # 4/0 1 - # 4 2-1/2"

225N 225 1 3 - 250 2 - # 4/0 1 - # 3 3"

250 250 1 3 - 250 - 1 - #4 2-1/2"

250Y 250 1 3 - 250 1 - 250 1 - #4 3"

250N 250 1 3 - 300 2 - 250 1 - # 3 3-1/2"

300 300 1 3 - 350 - 1 - # 4 3"

300Y 300 1 3 - 350 1 - 350 1 - # 4 3-1/2"

300N 300 1 3 - 400 2 - 350 1 - # 3 3-1/2"

350 350 1 3 - 500 - 1 - # 3 3"

350Y 350 1 3 - 500 1 - 500 1 - # 3 3-1/2"

350N 350 2 3 - # 3/0 2 - # 2/0 1 - # 3 2-1/2"

380 380 1 3 - 500 - 1 - # 3 3"

380Y 380 1 3 - 500 1 - 500 1 - # 3 3-1/2"

380N 380 1 3 - 500 1 - 500 1 - # 3 3-1/2"

400 400 1 3 - 500 - 1 - # 3 3"

400Y 400 1 3 - 500 1 - 500 1 - # 3 3-1/2"

400N 400 2 3 - # 4/0 2 - # 3/0 1 - # 1/0 3"

450 450 2 3 - # 4/0 - 1 - # 2 2"

450Y 450 2 3 - # 4/0 1 - # 4/0 1 - # 2 2-1/2"

450N 450 2 3 - # 4/0 1 - # 4/0 1 - # 2 2-1/2"

500 500 2 3 - 250 - 1 - # 2 2-1/2"

500Y 500 2 3 - 250 1 - 250 1 - # 2 3"

500N 500 2 3 - 300 2- 250 1 - # 1 3 - 1/2"

600 600 2 3 - 350 - 1 - # 1 3"

600Y 600 2 3 - 350 1 - 350 1 - # 1 3"

600N 600 2 3 - 400 2 - 350 1 - # 1/0 3 - 1/2"

700 700 2 3 - 500 - 1 - # 1/0 3"

700Y 700 2 3 - 500 1 - 500 1 - # 1/0 3-1/2"

800 800 2 3 - 500 - 1 - # 1/0 3"

800Y 800 2 3 - 500 1 - 500 1 - # 1/0 3 - 1/2"

1000 1000 3 3 - 400 - 1 - # 2/0 3"

1000Y 1000 3 3 - 400 1 - 400 1 - # 2/0 3-1/2"

1200 1200 4 3 - 350 - 1 - # 3/0 3"

1200Y 1200 4 3 - 350 1 - 350 1 - # 3/0 3"

Feeder Schedule Notes 1 THE SCHEDULE IS A SCHEDULE OF TYPICAL FEEDERS AND SOME OF THE SIZES MAY NOT APPLY TO THIS PROJECT.

2 ALL THE CONDUCTOR AMPACITIES ARE BASED ON TABLE 310-16 OF THE NEC FOR COPPER CONDUCTOR TYPE

THHN/THWN-2

3 FEEDER SIZES SHOWN ON THE RISER DIAGRAM INDICATE FEEDER AMPACITIES AND DO NOT NECESSARILY CORRESPOND TO THE CIRCUIT BREAKER AMPACITIES. CERTAIN FEEDERS MAY BE SIZED FOR DERATION FACTORS AND/OR OVERSIZED FOR VOLTAGE DROP PER

NEC REQUIREMENTS.

Mead & Hunt, Inc.

2440 Deming Way

Middleton, WI 53562 phone: 608-273-6380 meadhunt.com

SHEET NO.:

SHEET CONTENTS

DO NOT SCALE DRAWINGS

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

ISSUED

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

/1

/2

:0

:2

P

M C

R e v it L o c a l\

-1

.0

-E

-C e n tr a l-rk k .r v t

M ic h ig a n A ir N a ti o n a l G u a rd

B a tt le

C re e k A ir N a ti o n a l G u a rd

B a s e

B a tt le

C re e k M ic h ig a n

G e n e ra to r

L o a d D ra w in g s

E-701

ELECTRICAL

ONE-LINE DIAGRAM

3141900-171628.02

RKK

MAS

02/15/2018

JRH

NO SCALE1

ELECTRICAL ONE-LINE DIAGRAM

KEYED NOTES

9.302 DISCONNECT AND REMOVE EXISTING FEEDER FROM EXISTING MDP TO

EXISTING DOUBLE THROW SAFETY SWITCH.

9.303 PROVIDE NEW FEEDER FROM EXISTING DOUBLE THROW SWITCH TO NEW

TRANSFORMER

VFD VFD VFD VFD VFD VFDVFD VFD

500KW/625KVA

480V, 3PH, 3W

DIESEL FUELED GENERATOR SET

M

225/3

A

/2

V

P

H W

B U

S D

U C

T

A

/2

V

P

H W

B U

S D

U C

T

A

/2

V

P

H W

B U

S D

U C

T

A

/2

V

P

H W

B U

S D

U C

T

SEE PANEL SCHEDULE

FOR ADDITIONAL INFO

GCS

A

AGCS

B

GCS

C

100/3

400/3

EXISTING XFMR 'T/XLA'

112.5 KVA

480V PRI, 3PH, 3W

208Y/120V SEC, 3PH, 4W

PAD MOUNTED

MSB/XHA - 1200A,

480V - 3PH, 3W

UPS/XA - 400A,

208Y/120V - 3PH, 4W

DP/XLA - 400A,

208Y/120V - 3PH, 4W

BREAKER. I.C. = 25,000RMS. SYM, AMP @ 480V, 3PH

BREAKER. I.C. = 42,000RMS. SYM, AMP @ 208V, 3PH BREAKER. I.C. = 10,000RMS. SYM, AMP @ 208V, 3PH

(4) 100/3

SPACES

(2) 400/3

SPACES

UPS CABINET

UPS "X"

120KVA

GOVERNMENT FURNISHED

CONTRACTOR INSTALLED

BATTERY

BATTERY

UPS

X

STATIC BYPASS

BYPASS DISTRIBUTION CABINET

GENERATOR REMOTE

ANNUNCIATOR PANEL

GENERATOR CONTROL

PANEL

EPO

225/3 225/3 225/3 100/3

SOC

A

A

TO GENERATOR

SWITCHBOARD

800A/3P ENCLOSED

CIRCUIT BREAKER

100% RATED

LSI

REFER TO

SHEET E-701

100/3 225/3

ATS/XA

225/3

A

/2

V

P

H W

B U

S D

U C

T

A

/2

V

P

H W

B U

S D

U C

T

A

/2

V

P

H W

B U

S D

U C

T

A

/2

V

P

H W

B U

S D

U C

T

UPS/XB - 400A,

208Y/120V - 3PH, 4W

BREAKER. I.C. = 42,000RMS. SYM, AMP @ 208V, 3PH

225/3 225/3 225/3

TWB-A TWB-A TWB-A TWB-A TWB-B TWB-B TWB-B TWB-B

175/3200/3

SHUNT

400/3

SHUNT TRIP

400/3

SHUNT TRIP

GEN

XLA

60/3

SPD

240KA EA

L-L L-G

80/3

SPD

100KA EA

L-L L-N N-G

30/3

SPD

100KA EA

L-L L-N N-G

30/3

SPD

100KA EA

L-L L-N N-G

30/3

AHU-1

42.5A

80/3

AHU-2

42.5A

80/3

CH-1

109.5A

125/3

CH-2

109.5A

125/3

CH-3

109.5A

125/3 (7) 100/3

SPACES

CRAC-1

33A

40/3

CRAC-2

33A

40/3

DC-1

33A

40/3

DC-2

33A

40/3

RF-1

7-1/2HP

20/3

RF-2

7-1/2HP

20/3

HWB-1

7.2A

15/3

HWB-2

7.2A

15/3

HWB-3

7.2A

15/3

HWP-1

5HP

15/3

HWP-2

5HP

15/3

HWP-3

1-1/2HP

15/3

HWP-4

1-1/2HP

15/3

HWP-5

1-1/2HP

15/3

CWP-1

10HP

30/3

CWP-2

10HP

30/3

CWP-3

5HP

15/3

CWP-4

5HP

15/3

CWP-5

5HP

15/3

CWP-6

7-1/2HP

20/3

CWP-7

7-1/2HP

20/3

DP/XHA - 400A,

480V - 3PH, 3W

BREAKER. I.C. = 25,000RMS. SYM, AMP @ 480V, 3PH

300/3

SHUNT SHUNT

SEE PANEL SCHEDULE

FOR ADDITIONAL INFO

113113

112 112 113

113104103102106

125/3

REFER

TO

SHEET

E-701

B

9.401

ONE-LINE GENERAL NOTES:

1. REFER TO SHEET E-701 FOR FEEDER SCHEDULE.

Mead & Hunt, Inc.

2440 Deming Way

Middleton, WI 53562 phone: 608-273-6380 meadhunt.com

SHEET NO.:

SHEET CONTENTS

DO NOT SCALE DRAWINGS

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

ISSUED

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

/1

/2

:0

:2

P

M C

R e v it L o c a l\

-1

.0

-E

-C e n tr a l-rk k .r v t

M ic h ig a n A ir N a ti o n a l G u a rd

B a tt le

C re e k A ir N a ti o n a l G u a rd

B a s e

B a tt le

C re e k M ic h ig a n

G e n e ra to r

L o a d D ra w in g s

E-702

ELECTRICAL

ONE-LINE DIAGRAM -

EMERGENCY

3141900-171628.02

RKK

MAS

02/15/2018

JRH

NO SCALE1

ELECTRICAL ONE-LINE DIAGRAM - EMERGENCY

KEYED NOTES

9.401 PROVIDE NEW CIRCUIT BREAKER IN EXISTING SWITCHBOARD. EXISTING

SWITCHBOARD IS SQUARE D, TYPE QED. NEW CIRCUIT BREAKER SHALL

MATCH EXISTING SWITCHBOARD MANUFACTURER AND AIC RATING

(25KAIC).

Sheets
E-001 - NOTES, SYMBOLS & ABBREVIATIONS
E-101 - FIRST FLOOR PLAN
E-121 - FIRST FLOOR LIGHTING PLAN
E-131A - FIRST FLOOR PLAN AREA A - RPA OPS - POWER
E-701 - ELECTRICAL ONE-LINE DIAGRAM
E-702 - ELECTRICAL ONE-LINE DIAGRAM - EMERGENCY

File details come from the government source that posted it. Updated .