1) It appears to me that the existing ATS for the 60 KW Generator is existing and to be reused "if possible". Yes

2) Regarding the 125 KW for BLdg. 4200, the one line diagram shows item "20" as the generator feeding the fire pump. The fire pump controller has an integral transfer switch. I do not see where at ATS is to be used at this location either. Am I correct? Yes

3) Who will be responsible for moving the existing the generator from the site to customer’s holding area. Vendor will be responsible.

4) Who will be responsible for fuel for startup and testing? Vendor will be responsible.

5) Who will responsible for start-up? Vendor will be responsible.

6) Who will be responsible for up-dating the Engineer drawings for the added conduit and wire from the disconnect to the 125KW? Vendor will be responsible.