This document is a 27 15 00 - Communications Horizontal Cabling specification for the Colorado Air National Guard Space Control Facility at Peterson Air Force Base. It details the requirements for the horizontal communications cabling system, including UTP and F/UTP cable, coaxial cable, multimode fiber optic cable, cable connecting hardware, telecommunications outlets, cable management, identification, and testing. Key requirements include compliance with TIA/EIA-568-C standards, use of Category 6 cabling, maximum cable lengths, grounding, and quality assurance provisions such as installer qualifications and field testing. The specification covers the installation, identification, and testing of the communications cabling infrastructure.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

COLORADO AIR NATIONAL GUARD 19 June 2020

SPACE CONTROL FACILITY

PETERSON AIR FORCE BASE B-3 Final Submittal

COMMUNICATIONS HORIZONTAL CABLING 27 15 00 - 1

SECTION 27 15 00 - COMMUNICATIONS HORIZONTAL CABLING

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. UTP and F/UTP cabling.

2. Coaxial cable.

3. 850 nanometer laser-optimized 50/125 micrometer multimode optical fiber cable (OM3).

4. Cable connecting hardware, patch panels, and cross-connects.

5. Telecommunications outlet/connectors.

6. Cabling system identification products.

7. Cable management system.

B. Related Requirements:

1. Section 27 13 00 "Communications Backbone Cabling" for voice and data cabling associated with system panels and devices.

1.3 DEFINITIONS

A. BICSI: Building Industry Consulting Service International.

B. Cross-Connect: A facility enabling the termination of cable elements and their interconnection or cross-connection.

C. EMI: Electromagnetic interference.

D. IDC: Insulation displacement connector.

E. LAN: Local area network.

F. Outlet/Connectors: A connecting device in the work area on which horizontal cable or outlet cable terminates.

G. RCDD: Registered Communications Distribution Designer.

H. UTP: Unshielded twisted pair.

COMMUNICATIONS HORIZONTAL CABLING 27 15 00 - 2

1.4 ADMINISTRATIVE REQUIREMENTS

A. Coordinate layout and installation of telecommunications cabling with Contracting Officer's telecommunications and LAN equipment and service suppliers.

B. Coordinate telecommunications outlet/connector locations with location of power receptacles at each work area.

1.5 ACTION SUBMITTALS

A. Product Data: For each type of product.

1. For coaxial cable, include the following installation data for each type used:

a. Nominal OD.

b. Minimum bending radius.

c. Maximum pulling tension.

B. Shop Drawings:

1. System Labeling Schedules: Electronic copy of labeling schedules, in software and format selected by Contracting Officer.

2. System Labeling Schedules: Electronic copy of labeling schedules that are part of the cabling and asset identification system of the software.

3. Cabling administration drawings and printouts.

4. Wiring diagrams to show typical wiring schematics, including the following:

a. Cross-connects.

b. Patch panels.

c. Patch cables.

5. Cross-connects and patch panels. Detail mounting assemblies and show elevations and physical relationship between the installed components.

1.6 INFORMATIONAL SUBMITTALS

A. Qualification Data: For Installer, qualified layout technician, installation supervisor, and field inspector.

B. Source quality-control reports.

C. Field quality-control reports.

1.7 CLOSEOUT SUBMITTALS

A. Maintenance Data: For splices and connectors to include in maintenance manuals.

COMMUNICATIONS HORIZONTAL CABLING 27 15 00 - 3

B. Software and Firmware Operational Documentation:

1. Software operating and upgrade manuals.

2. Program Software Backup: On magnetic media or compact disk, complete with data files.

3. Device address list.

4. Printout of software application and graphic screens.

1.8 MAINTENANCE MATERIAL SUBMITTALS

A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.

1. Patch-Panel Units: One of each type.

2. Connecting Blocks: One of each type.

3. Device Plates: One of each type.

4. Multiuser Telecommunications Outlet Assemblies: One of each type.

1.9 QUALITY ASSURANCE

A. Installer Qualifications: Cabling Installer must have personnel certified by BICSI on staff.

1. Layout Responsibility: Preparation of Shop Drawings by an RCDD.

2. Installation Supervision: Installation shall be under the direct supervision of Registered

Technician or Level 2 Installer, who shall be present at all times when Work of this Section is performed at Project site.

3. Testing Supervisor: Currently certified by BICSI as an RCDD to supervise on-site testing.

B. Testing Agency Qualifications: An NRTL.

1. Testing Agency's Field Supervisor: Currently certified by BICSI as an RCDD to supervise on-site testing.

1.10 DELIVERY, STORAGE, AND HANDLING

A. Test cables upon receipt at Project site.

1. Test optical fiber cables to determine the continuity of the strand end to end. Use optical loss test set.

2. Test optical fiber cables while on reels. Use an optical time domain reflectometer to verify the cable length and locate cable defects, splices, and connector; including the loss value of each. Retain test data and include the record in maintenance data.

3. Test each pair of UTP cable for open and short circuits.

COMMUNICATIONS HORIZONTAL CABLING 27 15 00 - 4

PART 2 - PRODUCTS

2.1 HORIZONTAL CABLING DESCRIPTION

A. Horizontal cable and its connecting hardware provide the means of transporting signals between the telecommunications outlet/connector and the horizontal cross-connect located in the communications equipment room. This cabling and its connecting hardware are called a "permanent link," a term that is used in the testing protocols.

1. TIA/EIA-568-C.1 requires that a minimum of two telecommunications outlet/connectors be installed for each work area.

2. Horizontal cabling shall contain no more than one transition point or consolidation point between the horizontal cross-connect and the telecommunications outlet/connector.

3. Bridged taps and splices shall not be installed in the horizontal cabling.

4. Splitters shall not be installed as part of the optical fiber cabling.

B. A work area is approximately 100 sq. ft. and includes the components that extend from the telecommunications outlet/connectors to the station equipment.

C. The maximum allowable horizontal cable length is 295 feet. This maximum allowable length does not include an allowance for the length of 16 feet to the workstation equipment or in the horizontal cross-connect.

2.2 PERFORMANCE REQUIREMENTS

A. General Performance: Horizontal cabling system shall comply with transmission standards in TIA/EIA-568-C.1 when tested according to test procedures of this standard.

B. Surface-Burning Characteristics: Comply with ASTM E 84; testing by a qualified testing agency. Identify products with appropriate markings of applicable testing agency.

1. Flame-Spread Index: 25 or less.

2. Smoke-Developed Index: 50 or less.

C. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

D. Grounding: Comply with TIA-607-C.

2.3 UTP AND F/UTP CABLE

A. Description: 100-ohm, four-pair UTP, 4 pair, 23 AWG, covered with a thermoplastic jacket.

Jacket color as indicated on drawings

1. Comply with ICEA S-90-661 for mechanical properties.

2. Comply with TIA/EIA-568-C.1 for performance specifications.

COMMUNICATIONS HORIZONTAL CABLING 27 15 00 - 5

3. Comply with TIA/EIA-568-C.2, Category 6.

4. Listed and labeled by an NRTL acceptable to authorities having jurisdiction as complying with UL 444 and NFPA 70 for the following types:

a. Communications, General Purpose: Type CM or CMG; or MPP, CMP, MPR, CMR, MP, or MPG.

b. Communications Plenum Rated: Type CMP or MPP, complying with NFPA 262.

c. Communications Riser Rated: Type CMR; or MPP, CMP, or MPR, complying with UL 1666.

d. Communications, Limited Purpose: Type CMX; or MPP, CMP, MPR, CMR, MP, MPG, CM, or CMG.

e. Multipurpose: Type MP or MPG; or MPP or MPR.

f. Multipurpose, Plenum Rated: Type MPP, complying with NFPA 262.

g. Multipurpose, Riser Rated: Type MPR or MPP, complying with UL 1666.

B. Description: 100-ohm, four-pair F/UTP, 4 pair, 23 AWG, covered with a thermoplastic jacket.

Jacket color as indicated on drawings

1. Comply with ICEA S-90-661 for mechanical properties.

2. Comply with TIA/EIA-568-C.1 for performance specifications.

3. Comply with TIA/EIA-568-C.2, Category 6.

4. Listed and labeled by an NRTL acceptable to authorities having jurisdiction as complying with UL 444 and NFPA 70 for the following types:

a. Communications, General Purpose: Type CM or CMG; or MPP, CMP, MPR, CMR, MP, or MPG.

b. Communications Plenum Rated: Type CMP or MPP, complying with NFPA 262.

c. Communications Riser Rated: Type CMR; or MPP, CMP, or MPR, complying with UL 1666.

d. Communications, Limited Purpose: Type CMX; or MPP, CMP, MPR, CMR, MP, MPG, CM, or CMG.

e. Multipurpose: Type MP or MPG; or MPP or MPR.

f. Multipurpose, Plenum Rated: Type MPP, complying with NFPA 262.

g. Multipurpose, Riser Rated: Type MPR or MPP, complying with UL 1666.

2.4 F/UTP AND UTP CABLE HARDWARE

A. General Requirements for Cable Connecting Hardware: Comply with TIA/EIA-568-C.2, IDC type, with modules designed for punch-down caps or tools. Cables shall be terminated with connecting hardware of same category or higher.

B. Connecting Blocks: 110-style IDC for Category 6. Provide blocks for the number of cables terminated on the block, plus 25 percent spare. Integral with connector bodies, including plugs and jacks where indicated.

C. Cross-Connect: Modular array of connecting blocks arranged to terminate building cables and permit interconnection between cables.

COMMUNICATIONS HORIZONTAL CABLING 27 15 00 - 6

1. Number of Terminals per Field: One for each conductor in assigned cables.

D. Patch Panel: Modular panels housing multiple-numbered jack units with IDC-type connectors at each jack for permanent termination of pair groups of installed cables.

1. Number of Jacks per Field: One for each four-pair UTP cable indicated, plus spares and blank positions adequate to suit specified expansion criteria.

2. Number of Jacks per Field: One for each four-pair F/UTP cable indicated, plus spares and blank positions adequate to suit specified expansion criteria.

E. Jacks and Jack Assemblies: Modular, color-coded, eight-position modular receptacle units with integral IDC-type terminals.

F. Patch Cords: Factory-made, four-pair cables in 36-inch 48-inch lengths; terminated with eight-position modular plug at each end.

1. Patch cords shall have bend-relief-compliant boots and color-coded icons to ensure Category 6 performance. Patch cords shall have latch guards to protect against snagging.

2. Patch cords shall have color-coded boots for circuit identification.

2.5 COAXIAL CABLE

A. General Cable Characteristics: Broadband type, recommended by cable manufacturer specifically for broadband data transmission applications. Coaxial cable and accessories shall have 75-ohm nominal impedance with a return loss of 20 dB maximum from 7 to 806 MHz.

B. RG-6/U: NFPA 70, Type CATV or CM.

1. No. 16 AWG, solid, copper-covered steel conductor; gas-injected, foam-PE insulation.

2. Double shielded with 100 percent aluminum-foil shield and 60 percent aluminum braid.

3. Jacketed with black PVC or PE.

4. Suitable for indoor installations.

C. NFPA and UL compliance, listed and labeled by an NRTL acceptable to authorities having jurisdiction as complying with UL 1655 and with NFPA 70 "Radio and Television Equipment" and "Community Antenna Television and Radio Distribution" Articles. Types are as follows:

1. CATV Cable: Type CATV, or CATVP or CATVR.

2. CATV Plenum Rated: Type CATVP, complying with NFPA 262.

3. CATV Riser Rated: Type CATVR; or CATVP, CATVR, or CATV, complying with

UL 1666.

4. CATV Limited Rating: Type CATVX.

2.6 COAXIAL CABLE HARDWARE

A. Coaxial-Cable Connectors: Type BNC, 75 ohms.

COMMUNICATIONS HORIZONTAL CABLING 27 15 00 - 7

2.7 850 NANOMETER LASER-OPTIMIZED, 50/125 MICROMETER, MULTIMODE OPTICAL

FIBER CABLE (OM3)

A. Description: Multimode, 50/125-micrometer, multi-fiber, nonconductive, tight buffer, optical fiber cable.

B. Standards:

1. Comply with ICEA S-83-596 for mechanical properties.

2. Comply with TIA-568-C.3 for performance specifications.

3. Comply with TIA-492AAAC for detailed specifications.

C. Maximum Attenuation: 3.50 dB/km at 850 nm; 1.5 dB/km at 1300 nm.

D. Minimum Overfilled Modal Bandwidth-length Product: 1500 MHz-km at 850 nm; 500 MHz-km at 1300 nm.

E. Minimum Effective Modal Bandwidth-length Product: 2000 MHz-km at 850 nm.

F. Jacket:

1. Jacket Color: As indicated on drawings.

2. Cable cordage jacket, fiber, unit, and group color shall be according to TIA-598-D.

3. Imprinted with fiber count, fiber type, and aggregate length at regular intervals not to exceed 40 inches.

G. Listed and labeled by an NRTL acceptable to authorities having jurisdiction as complying with UL 444, UL 1651, and NFPA 70 for the following types:

1. Plenum Rated, Nonconductive: Type OFNP, complying with NFPA 262.

2. Plenum Rated, Nonconductive: Type OFNP in listed plenum communications raceway.

3. Plenum Rated, Nonconductive: Type OFNP or Type OFNR in metallic conduit.

4. Plenum Rated, Nonconductive: Type OFNP, complying with NFPA 262; Type OFNP in listed plenum communications raceway; or Type OFNP or Type OFNR in metallic conduit.

5. Plenum Rated, Conductive: Type OFCP, complying with NFPA 262.

6. Plenum Rated, Conductive: Type OFCP or Type OFNP in listed plenum communications raceway.

7. Plenum Rated, Conductive: Type OFNG, Type OFCP, Type OFNP, Type OFCR, or

Type OFNR in metallic conduit installed per NFPA 70, Article 300.22, "Wiring in Ducts, Plenums, and Other Air-Handling Spaces."

2.8 OPTICAL FIBER CABLE HARDWARE

A. Standards:

1. Comply with Fiber Optic Connector Intermateability Standard (FOCIS) specifications of the TIA-604 series.

COMMUNICATIONS HORIZONTAL CABLING 27 15 00 - 8

2. Comply with TIA-568-C.3.

B. Cross-Connects and Patch Panels: Modular panels housing multiple-numbered, duplex cable connectors.

1. Number of Connectors per Field: One for each fiber of cable or cables assigned to field, plus spares and blank positions adequate to suit specified expansion criteria.

C. Patch Cords: Factory-made, single-fiber cables in 36-inch lengths.

D. Connector Type: Duplex anaerobic multimode type LC complying with TIA-604-10-B connectors.

E. Plugs and Plug Assemblies:

1. Male; color-coded modular telecommunications connector designed for termination of a single optical fiber cable.

2. Insertion loss not more than 0.25 dB.

3. Marked to indicate transmission performance.

F. Jacks and Jack Assemblies:

1. Female; quick-connect, simplex and duplex; fixed telecommunications connector designed for termination of a single optical fiber cable.

2. Insertion loss not more than 0.25 dB.

3. Marked to indicate transmission performance.

4. Designed to snap-in to a patch panel or faceplate.

2.9 TELECOMMUNICATIONS OUTLET/CONNECTORS

A. Jacks: 100-ohm, balanced, twisted-pair connector; four-pair, eight-position modular. Comply with TIA/EIA-568-C.1.

B. Workstation Outlets: Multiple-port-connector assemblies mounted in single or multigang faceplate.

1. Plastic Faceplate: High-impact plastic. Coordinate color with Section 26 27 26 "Wiring Devices."

2. Metal Faceplate: Stainless steel, complying with requirements in Section 26 27 26 "Wiring Devices."

3. For use with snap-in jacks accommodating any combination of F/UTP, UTP, optical fiber, and coaxial work area cords.

a. Flush mounting jacks, positioning the cord at a 45-degree angle.

4. Legend: Factory labeled by silk-screening or engraving for stainless steel faceplates.

5. Legend: Machine printed, in the field, using adhesive-tape label.

6. Legend: Snap-in, clear-label covers and machine-printed paper inserts.

COMMUNICATIONS HORIZONTAL CABLING 27 15 00 - 9

2.10 GROUNDING

A. Comply with requirements in Section 26 05 26 "Grounding and Bonding for Electrical Systems" for grounding conductors and connectors.

B. Comply with TIA-607-C.

2.11 IDENTIFICATION PRODUCTS

A. Comply with TIA/EIA-606-B and UL 969 for labeling materials, including label stocks, laminating adhesives, and inks used by label printers.

B. Comply with requirements in Section 26 05 53 "Identification for Electrical Systems."

2.12 SOURCE QUALITY CONTROL

A. Testing Agency: Engage a qualified testing agency to evaluate cables.

B. Factory test Fiber, UTP and F/UTP cables according to TIA/EIA-568-C.2.

C. Factory-sweep test coaxial cables at frequencies from 5 MHz to 1 GHz. Sweep test shall test the frequency response, or attenuation over frequency, of a cable by generating a voltage whose frequency is varied through the specified frequency range and graphing the results.

D. Cable will be considered defective if it does not pass tests and inspections.

E. Prepare test and inspection reports.

PART 3 - EXECUTION

3.1 ENTRANCE FACILITIES

A. Coordinate backbone cabling with the protectors and demarcation point provided by communications service provider.

3.2 WIRING METHODS

A. Install cables in pathways and cable trays except within consoles, cabinets, desks, and counters and except in accessible ceiling spaces and in gypsum board partitions where unenclosed wiring method may be used. Conceal pathways and cables except in unfinished spaces.

1. Install plenum cable in environmental air spaces, including plenum ceilings.

2. Comply with requirements in Section 27 05 28 "Pathways for Communications Systems."

COMMUNICATIONS HORIZONTAL CABLING 27 15 00 - 10

3. Comply with requirements in Section 27 05 36 "Cable Trays for Communications Systems."

B. Conceal conductors and cables in accessible ceilings, walls, and floors where possible.

C. Wiring within Enclosures:

1. Bundle, lace, and train conductors to terminal points with no excess and without exceeding manufacturer's limitations on bending radii.

2. Install lacing bars and distribution spools.

3. Install conductors parallel with or at right angles to sides and back of enclosure.

3.3 INSTALLATION OF CABLES

A. Comply with NECA 1.

B. General Requirements for Cabling:

1. Comply with TIA/EIA-568-C.1.

2. Comply with BICSI ITSIM 7th Edition, Ch. 5, "Cable Installation."

3. Install 110-style IDC termination hardware unless otherwise indicated.

4. Terminate conductors; no cable shall contain unterminated elements. Make terminations only at indicated outlets, terminals, cross-connects, and patch panels.

5. Cables may not be spliced. Secure and support cables at intervals not exceeding 30 inches and not more than 6 inches from cabinets, boxes, fittings, outlets, racks, frames, and terminals.

6. Install lacing bars to restrain cables, to prevent straining connections, and to prevent bending cables to smaller radii than minimums recommended by manufacturer.

7. Bundle, lace, and train conductors to terminal points without exceeding manufacturer's limitations on bending radii, but not less than radii specified in BICSI ITSIM, Chapter 5, "Cabling Termination Practices". Install lacing bars and distribution spools.

8. Do not install bruised, kinked, scored, deformed, or abraded cable. Do not splice cable between termination, tap, or junction points. Remove and discard cable if damaged during installation and replace it with new cable.

9. Cold-Weather Installation: Bring cable to room temperature before dereeling. Heat lamps shall not be used for heating.

10. In the communications equipment room, install a 10-foot-long service loop on each end of cable.

11. Pulling Cable: Comply with BICSI ITSIM 7th Edition, Chapter 5, "Cable Installation."

Monitor cable pull tensions.

C. UTP and F/UTP Cable Installation:

1. Comply with TIA/EIA-568-C.2.

2. Do not untwist F/UTP and UTP cables more than 1/2 inch from the point of termination to maintain cable geometry.

D. Open-Cable Installation:

COMMUNICATIONS HORIZONTAL CABLING 27 15 00 - 11

1. Install cabling with horizontal and vertical cable guides in telecommunications spaces with terminating hardware and interconnection equipment.

2. Suspend F/UTP, UTP cable not in a wireway or pathway a minimum of 8 inches above ceilings by cable supports not more than 60 inches apart.

3. Cable shall not be run through structural members or in contact with pipes, ducts, or other potentially damaging items.

E. Group connecting hardware for cables into separate logical fields.

F. Separation from EMI Sources:

1. Comply with BICSI TDMM, 13th Edition and TIA-569-D for separating unshielded copper voice and data communication cable from potential EMI sources, including electrical power lines and equipment.

2. Separation between open communications cables or cables in nonmetallic raceways and unshielded power conductors and electrical equipment shall be as follows:

a. Electrical Equipment Rating Less Than 2 kVA: A minimum of 5 inches.

b. Electrical Equipment Rating between 2 and 5 kVA: A minimum of 12 inches.

c. Electrical Equipment Rating More Than 5 kVA: A minimum of 24 inches.

3. Separation between communications cables in grounded metallic raceways and unshielded power lines or electrical equipment shall be as follows:

a. Electrical Equipment Rating Less Than 2 kVA: A minimum of 2-1/2 inches.

b. Electrical Equipment Rating between 2 and 5 kVA: A minimum of 6.

c. Electrical Equipment Rating More Than 5 kVA: A minimum of 12 inches.

4. Separation between communications cables in grounded metallic raceways and power lines and electrical equipment located in grounded metallic conduits or enclosures shall be as follows:

a. Electrical Equipment Rating Less Than 2 kVA: No requirement.

b. Electrical Equipment Rating between 2 and 5 kVA: A minimum of 3 inches

c. Electrical Equipment Rating More Than 5 kVA: A minimum of 6 inches.

5. Separation between Communications Cables and Electrical Motors and Transformers, 5 kVA or HP and Larger: A minimum of 48 inches.

6. Separation between Communications Cables and Fluorescent Fixtures: A minimum of 5 inches.

3.4 GROUNDING

A. Install grounding according to BICSI TDMM, Chapter 8 "Bonding, and Grounding (Earthing)".

B. Comply with TIA-607-C.

COMMUNICATIONS HORIZONTAL CABLING 27 15 00 - 12

C. Bond metallic equipment to the grounding bus bar, using not smaller than No. 6 AWG equipment grounding conductor.

3.5 IDENTIFICATION

A. Identify system components, wiring, and cabling complying with TIA/EIA-606-B. Comply with requirements for identification specified in Section 26 05 53 "Identification for Electrical Systems."

1. Administration Class: 2.

2. Color-code cross-connect fields. Apply colors to voice and data service backboards, connections, covers, and labels.

B. Using cable management system software specified in Part 2, develop Cabling Administration Drawings for system identification, testing, and management. Use unique, alphanumeric designation for each cable and label cable, jacks, connectors, and terminals to which it connects with same designation. At completion, cable and asset management software shall reflect as-built conditions.

C. Comply with requirements in Section 09 91 23 "Interior Painting" for painting backboards. For fire-resistant plywood, do not paint over manufacturer's label.

D. Paint and label colors for equipment identification shall comply with TIA/EIA-606-B for Class 2 level of administration, including optional identification requirements of this standard.

E. Cable Schedule: Post in prominent location in each equipment room and wiring closet. List incoming and outgoing cables and their designations, origins, and destinations. Protect with rigid frame and clear plastic cover. Furnish an electronic copy of final comprehensive schedules for Project.

F. Cabling Administration Drawings: Show building floor plans with cabling administration-point labeling. Identify labeling convention and show labels for telecommunications closets, terminal hardware and positions, horizontal cables, work areas and workstation terminal positions, grounding buses and pathways, and equipment grounding conductors. Follow convention of TIA/EIA-606-B. Furnish electronic record of all drawings, in software and format selected by Contracting Officer.

G. Cable and Wire Identification:

1. Label each cable within 4 inches of each termination and tap, where it is accessible in a cabinet or junction or outlet box, and elsewhere as indicated.

2. Each wire connected to building-mounted devices is not required to be numbered at device if color of wire is consistent with associated wire connected and numbered within panel or cabinet.

3. Exposed Cables and Cables in Cable Trays and Wire Troughs: Label each cable at intervals not exceeding 15 feet

4. Label each terminal strip and screw terminal in each cabinet, rack, or panel.

COMMUNICATIONS HORIZONTAL CABLING 27 15 00 - 13

a. Individually number wiring conductors connected to terminal strips and identify each cable or wiring group being extended from a panel or cabinet to a building-mounted device shall be identified with name and number of particular device as shown.

b. Label each unit and field within distribution racks and frames.

5. Identification within Connector Fields in Equipment Rooms and Wiring Closets: Label each connector and each discrete unit of cable-terminating and connecting hardware.

Where similar jacks and plugs are used for both voice and data communication cabling, use a different color for jacks and plugs of each service.

H. Labels shall be preprinted or computer-printed type with printing area and font color that contrasts with cable jacket color but still complies with requirements in TIA/EIA-606-B.

1. Cables use flexible vinyl or polyester that flex as cables are bent.

3.6 FIELD QUALITY CONTROL

A. Testing Agency: Engage a qualified testing agency to perform tests and inspections.

B. Manufacturer's Field Service: Engage a factory-authorized service representative to test and inspect components, assemblies, and equipment installations, including connections.

C. Perform the following tests and inspections with the assistance of a factory-authorized service representative:

1. Visually inspect F/UTP, UTP and optical fiber cable jacket materials for NRTL certification markings. Inspect cabling terminations in communications equipment rooms for compliance with color-coding for pin assignments and inspect cabling connections for compliance with TIA-568-C.1.

2. Visually confirm Category 6, marking of outlets, cover plates, outlet/connectors, and patch panels.

3. Visually inspect cable placement, cable termination, grounding and bonding, equipment and patch cords, and labeling of all components.

4. Test UTP backbone copper cabling for DC loop resistance, shorts, opens, intermittent faults, and polarity between conductors. Test operation of shorting bars in connection blocks. Test cables after termination but not cross-connection.

a. Test instruments shall meet or exceed applicable requirements in TIA-568-C.2.

Perform tests with a tester that complies with performance requirements in "Test Instruments (Normative)" Annex, complying with measurement accuracy specified in "Measurement Accuracy (Informative)" Annex. Use only test cords and adapters that are qualified by test equipment manufacturer for channel or link test configuration.

5. F/UTP and UTP Performance Tests:

1124618408E Highlight

COMMUNICATIONS HORIZONTAL CABLING 27 15 00 - 14

a. Test for each outlet. Perform the following tests according to TIA-568-C.1 and

TIA-568-C.2:

1) Wire map.

2) Length (physical vs. electrical, and length requirements).

3) Insertion loss.

4) Near-end crosstalk (NEXT) loss.

5) Power sum near-end crosstalk (PSNEXT) loss.

6) Equal-level far-end crosstalk (ELFEXT).

7) Power sum equal-level far-end crosstalk (PSELFEXT).

8) Return loss.

9) Propagation delay.

10) Delay skew.

6. Optical Fiber Cable Tests:

a. Link End-to-End Attenuation Tests:

1) Multimode Horizontal Link Measurements: Test at 850 or 1300 nm in one direction according to TIA-526-14-C, Method B, One Reference Jumper.

2) Attenuation test results for horizontal links shall be less than 2.0 dB.

Attenuation test results shall be less than those calculated according to equation in TIA-568-C.1.

b. Test instruments shall meet or exceed applicable requirements in TIA 568-C.1.

Use only test cords and adapters that are qualified by test equipment manufacturer for channel or link test configuration.

D. Document data for each measurement. Data for submittals shall be printed in a summary report that is formatted similar to Table 10.1 in BICSI TDMM 13th Edition, or transferred from the instrument to the computer, saved as text files, and printed and submitted.

E. End-to-end cabling will be considered defective if it does not pass tests and inspections.

F. Prepare test and inspection reports.

END OF SECTION 27 15 00