VFD SW addition Aquavar AV2V2S050D.pdf
PDF 604 KB Posted
- Attached to
- Z1DA--608-23-116 SPS Compliance Corrections Construction Federal contract opportunity
- Solicitation number
- 36C24123B0006
About this file
This is an invitation for bid issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 1. The solicitation is for Z1DA--608-23-116 SPS Compliance Corrections Construction. The IFB requires construction services to correct deficiencies identified during a Space Planning System compliance review at the VA Medical Center in Washington, DC. Bids are due by 2:00 PM Eastern on August 15, 2022 and the contract is to be awarded by September 15, 2022. Pricing is to be provided as firm fixed price for the base period of performance. The solicitation is set aside for verified service-disabled veteran-owned small businesses.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24123B0006 0002.docx | DOCX document | |
| 36C24123B0006 0001.docx | DOCX document | |
| Facility drawings with CSB - bare.pdf | ||
| Med Req 50098-1520-EN US R.pdf | ||
| Technical-Information-SSH - existing pumps set 1022-9SH184JM2-2.pdf | ||
| PRE-AWARD CONTRACTOR EVALUATION FORM.pdf | ||
| 36C24123B0006.docx | DOCX document | |
| EndoDry Site Requirements.pdf | ||
| Instrument Air compressor spec sheet.pdf | ||
| New medivators installation 50098-15.pdf | ||
| Medivator installation specs.pdf | ||
| VFD old AC shop abb acs550-u1-046a-2.pdf | ||
| PH-WHV-Spec-sheet-LR expansion tank - replace with WHV 75 or eqiv.pdf | ||
| SAM WD NH NH20230021 revised 040723.pdf | ||
| Medivator Specs.pdf | ||
| Sterlizer utility requirements.jpg | JPG image | |
| 608-23-116 project sketches.pdf | ||
| SOW - 608-23-116 SPS steam and sterilization r1.docx | DOCX document |
Show all 18
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Variable Speed Pump Control
Installation Programming & Operation
Models covered:
All AV2 Model
AQUAVAR II Controllers software revision 120
AQUAVAR® AV II
IM131R01
UL®
AQUAVAR II Controller Model _________________ Transducer Model_______________________ AQUAVAR II Serial Number _________________ Transducer Rating_______________________ Date purchased _________________ Purchased from _________________
Pump Model _________________ Software Version _______________________
Pump Code Number _________________
Program Record Please use the following to record the final values programmed into the AQUAVAR controller after installa-tion.
Required Value____________________ (select) Level 2____________________________ (%) Autostart ________________________ (on/off) Intensity 1 _________________________ (%) Password ________________________ (value) Intensity 2 _________________________ (%) Window ___________________________ (%) Pressure Increase ___________________ (PSI) Ramp Hysteresis _____________________ (%) Pressure Decrease___________________ (PSI) Ramp 1 _______________________ (seconds) Enable Sequence Control______________ (Hz) Ramp 2 _______________________ (seconds) Switch Interval ___________________ (hours) Ramp 3 _______________________ (seconds) Optional Value _________________________ Ramp 4 _______________________ (seconds) Synchron Limit _____________________ (Hz) Max. Frequency _____________________ (Hz) Sychron Window ____________________ (Hz) Min. Frequency ______________________ (Hz) Pump Address _________________ (# or off) Config. F Min. __________ (F –>0/F –>F min.) ADC Reference ___________________ (select) Stop - Delay F Min._______________ (seconds) Freq. Lifting________________________ (Hz) Sensor Adjust _______________ (out of range) Lift Intensity________________________ (%) Sensor Curve _____________ (linear/quadratic) Analog out ______________________ (select) Sensor Range - 20mA=362.6 __________ (PSI) Pressure Unit ____________________ (select) Mode___________________________ (select) Test Run After__________________ (in hours)
(actuator/controller/multicontroller/synch.) Test Frequency______________________ (Hz) Regulation Mode _________________ (normal) Conveyor Limit _____________________ (PSI) Start Value _________________________ (PSI) Delay Time ____________________ (seconds) Config. Second Value _________________ (off) Error Reset ______________________ (on/off) Relay Config.__________________ (run motor) Display Contrast_____________________ (%) Offset Input ____________________________ Lock Function ____________________ (on/off) Level 1 ____________________________ (%)
AQUAVAR II Controller Owner’s Information Record
Index System Design
Important Safety Instructions
Installation Procedures Materials Checklist
1. Mounting the AQUAVAR II Controller
2. Electrical Connections
3. Pump Priming
4. Run Test
Programming
1. The Main Menu - Setting One Pump Constant Pressure
2. Single Pump - Pump Protection
• To Set Run-Out Protection
• To Set Low/No Flow Protection
3. Single Pump - System Curve Compensation
• Entering Compensation Values
• Circulator Applications
4. Single Pump Constant Flow
5. Single Pump - Level Control Applications
6. Single Pump - Submersible
7. Setting a Second Required Value
8. Variable Second Required Value
9. Multiple Pump Constant Pressure and System Curve Compensation
• Synchronous Control
10. Multiple Pump - Pump Protection
• To Set Low/No Flow Protection
Operator Custom Features and Displays
• Jog Mode
• Window
• Ramp Hysteresis
• Ramp Settings
• Ramp 1-4
• Maximum Frequency
• Minimum Frequency
• Config. F Min
• Stop-Delay F Min
• Sensor Adjustment
• Sensor Curve
• Mode
• Start Value
• Config. Required Value 2
• Relay Config
• Submenu Offset
• Regulation Mode
• Submenu Sequence Control
• Actual Value Increase
Index
Index (continued) Operator Custom Features and Displays (continued)
• Actual Value Decrease
• Enable Sequence Control
• Switch Interval
• Source Required Value
• Submenu Synchronous Control
• Synchronous Limit
• Synchronous Window
• Pump Sequence
• Bus
• Pump - Address
• ADC Reference
• Frequency Lifting
• Lift Intensity
• Reference
• Analog Out
• Pressure Units
• Test Run
• Submenu Test Run Manual
• Submenu Errors
• Clear Errors
• Operating Hours
• Total Run Time
• Display Contrast
• Set Password
• Lock Functions
• Heating On
• Default Values
• Save ??
Repair of Faults and Errors
• Lack of Water
• Conveyor Control
• Error 1-8
• Pressure Sensor Error
• Inverter Error
• External Device Error
• Active Fault / Warning and Fault History Mode
• Aquavar II Electrical Fault Codes
Programming Flow Chart
Help Windows
Appendix A - Pressure Transducer Data
• Technical Characteristics
Appendix B - AQUAVAR Controller Technical Data and Terminals Appendix C - Interference Suppression Measures
Index
System Design - Typical Constant Pressure Systems
The following diagrams show typical single pump and multi-pump systems using the AQUAVAR con-troller. Connection can be made directly to a water supply or water can be drawn from a supply tank or well. In the case of supply tanks and wells, level switches, (item 10) can be used to shut down the pumps when water is low. In the direct connection, a pressure switch on the suction side (item 8) can be used.
A diaphragm pressure tank is used on the discharge side of the pump or pumps to maintain pres-sure in the line when there is no demand. This will keep the pumps from continuing to run. With the AQUAVAR controller, it is not necessary to have a large tank for supply purposes. In selecting a tank, make sure it can withstand maximum system pressure. The tank should have a capacity of at least 10% of the maximum system flow rate in gpm. Pre-charge the tank to the following:
System Design
1 Pump with AQUAVAR controller 2 Diaphragm tank 3 Distribution panel 4 Gate valves 5 Check valves 6 Foot valves 8 Incoming pressure switch 9 Pressure gauges 10 Level switches 11 Supply tank 14 Pressure transmitter
(Included with AQUAVAR) *
Closed loop circulator systems may not require a pressure tank.
Note
Systems MUST be designed by qualified technicians only.
Note
PSI Set Pressure 15 30 45 60 75 90 105 120 135 150 PSI Tank Pre-charge 12 21 37 52 64 77 95 110 125 138
Diagram 2 Single Pump Layout
Diagram 1 Multiple Pump Layout
Indirect connection via tank
Suction out or a well Direct connection
5 4
5 4
5 4
*Check with tank pressure limitations before precharge.
Important: Read all safety information prior to installation of the AQUAVAR controller.
1. This manual is intended to assist in the installation, operation, and repair of the AQUAVAR controller and must be kept with the AQUAVAR controller.
2. To avoid serious or fatal personnel injury or major property damage, read and follow all safety instructions in this manual.
This is a SAFETY ALERT SYMBOL. When you see this symbol on the pump or in the manual, look for one of the following signal words and be alert to the potential for personal injury or property damage.
Warns of hazards that WILL cause serious personal injury, death, or major property damage.
Warns of hazards that CAN cause serious personal injury, death, or major property damage.
Warns of hazards that CAN cause personal injury or property damage.
Indicates special instructions which are very important and must be followed.
Note
Safety Instructions
DANGER
WARNING
CAUTION
NOTICE
All operating instructions must be read, understood, and followed by the operating personnel. Goulds Pumps accepts no liability for damages or operating disorders which are the result of non-compliance with the operating instructions. When in doubt, call for assistance.
Note
Safety Instructions
3. Installation and maintenance MUST be performed by properly trained and qualified personnel.
4. Review all instructions and warnings prior to performing any work on the AQUAVAR controller.
5. Any safety decals MUST be left on the AQUAVAR controller unit and pump.
6. In addition to instructions contained in this manual, you must meet any local safety, electrical, or plumbing codes and requirements. Installation, maintenance, or repair work must only be carried out by trained, skilled, and qualified personnel, using proper protective gear and tools.
7. The AQUAVAR controller drive head must be disconnected from the main power supply before attempting any operation in the electrical or mechanical part of the system.
Safety Instructions
When in operation, the motor can be stopped, but power remains at the drive head. The motor and pump could start unexpectedly and produce serious injury. When the AQUAVAR controller drive head is connected to the main power supply, the inverter power supply and master control unit are also connected to the power supply.
Inspect AQUAVAR controller for any damage after unpacking from shipping crates.
Report any damage immediately to the carrier or distributor/dealer immediately.
Note
Note
FAILURE TO DISCONNECT ELECTRICAL POWER BEFORE ATTEMPTING ANY
MAINTENANCE CAN CAUSE SHOCK, BURNS, OR DEATH.
WARNING!
WARNING
Hazardous voltage can shock, burn or cause death.
8. The AQUAVAR controller has electronic safety devices which will stop the motor in the event of electrical or thermal faults. This does not remove power to the AQUAVAR controller.
9. The system must be properly grounded before being put into operation. Use a common ground for the entire system.
10. High voltage tests of the AQUAVAR controller may damage the electronic components.
Before carrying out such a test, bridge the incoming and outgoing terminals L1 - L2 - L3 - U - V - W. Isolate the motor from the AQUAVAR controller drive to avoid incorrect capacitor metering inside the AQUAVAR controller.
Safety Instructions
FAILURE TO DISCONNECT AND LOCKOUT ELECTRICAL POWER AND WAIT
FIVE MINUTES FOR CAPACITOR DISCHARGE BEFORE SERVICING AQUAVAR
CONTROLLER CAN CAUSE SHOCK, BURNS, OR DEATH.
WARNING!
TOUCHING THESE COMPONENTS SERIOUSLY ENDANGERS LIFE! Voltages of up to 800 volts are possible (higher if there is a fault).
Before removing the AQUAVAR controller drive top cover, the system must be discon-nected from the main power supply. After switching off the power supply, you must wait at least 5 minutes before starting work on or inside the AQUAVAR controller drive head. This allows the capacitors in the circuit to be discharged by the discharge resistors.
Note
Care must be taken when connecting external control wires and jumpers to avoid short circuit to neighboring components.
Note
Repair of electrical faults can lead to the automatic restart of the motor and pump.
You must remove all main line power to the AQUAVAR controller before attempting to correct a fault.
Note
WARNING
Hazardous voltage can shock, burn or cause death.
Step 1- Identify Materials The following materials are provided with the AQUAVAR II controller. Please familiarize yourself with each prior to installation.
Part Quantity
1. AQUAVAR Controller 1
2. Pressure Transducer Assembly 1
a. Pressure transducer - 25 bar 1/4” NPT
b. Transducer adapter - (available as 1/4” NPT female threads & 3/8 B male thread per separate part only) See price book. UNI ISO/228/1 (British Standard pipe threads)
c. 30 ft. transducer cord (standard) for AV II.
THE AQUAVAR CONTROLLER AND PUMP MUST BE TOTALLY DISCONNECTED FROM ALL
POWER SUPPLY SOURCES BEFORE BEGINNING INSTALLATION OR REPAIR.
WARNING
FAILURE TO DISCONNECT ELECTRICAL POWER BEFORE ATTEMPTING ANY MAINTE-
NANCE CAN CAUSE SHOCK, BURNS, OR DEATH.
WARNING!
WARNING
Hazardous voltage can shock, burn or cause death.
3 . 4 5
1 . 0 7
3⁄4” HEX
1⁄4” NPT
2c 2a 2b (If needed.)
Installation Procedures
YOU MUST USE THE CABLE THAT IS PROVIDED WITH THE TRANSDUCER. DO NOT USE
DIFFERENT CABLES OR OLDER STYLE CABLES.
Installation Procedures
Step 2 - Mounting the AQUAVAR II controller:
AQUAVAR Controller The AQUAVAR controller may be installed as a wall or panel mounted unit. The AQUAVAR controller may be mounted up to 60 feet away from the pump motor*. In addition, alternative motor enclosures may be selected such as ODP, explosion proof or wash down motors in addition to the TEFC enclo-sure required for on the pump mounting.
Typical applications for the AQUAVAR Wall Mount controller include:
1. Hazardous environment applications including high heat, humidity or combustibility.
2. Installation to an existing pumping system with non-standard motors.
3. Installations where the operator desires all controls to be grouped together.
Mounting of the AQUAVAR II Controller
1. An alternative mounting style is used in the AQUAVAR II controller configuration.
In this style, the AQUAVAR II controller is supplied with a fan and mounting bracket already installed and can be mounted to a wall or panel.
2. The mounting bolts for all units should be 1⁄4". The length of bolt and the strength of the mounting surface must be adequate to support the weight of the AQUAVAR II controller.
3. The AQUAVAR II controller may be positioned up to 60 feet from the pump motor. The pump motor must be three phase. Unlike the standard AQUAVAR controller, the motor may be ODP, TEFC or explosion proof.*
4. Mount the AQUAVAR controller to the panel, wall or frame using bolts at the points indicated on the following drawings. Be sure the unit is level and secured to the mounting surface before continuing.
5. Ensure plenty of airflow for the AQUAVAR controller, when mounting.
*NOTE: If the AQUAVAR II controller is more than 60 feet wire length to motor, then the use of a load reactor (impedance coil) is required.
Step 2 - Mounting the AQUAVAR controller: (continued)
Power Rating Weight HP Pounds Kilograms 1 24.0 10.9 2 24.0 10.9 3 24.0 10.9 5 24.0 10.9
71⁄2 24.0 10.9 10 24.0 10.9 15 28.0 12.7 20 28.0 12.7
HP Rating A B C D E F G in (mm) in (mm) in (mm) in (mm) in (mm) in (mm) in (mm)
1 – 10 (230 – 3)
3.20 7.88 16.50 9.32 17.44 12.08 0.28
1 – 5 (230 – 1) (81.28) (200.15) (419.10) (236.70) (442.98) (306.71) (7.11)
1 – 20 (575) 15 – 20 (230 – 3) 71⁄2 – 10 (230 – 1) 3.20 7.88 19.25 11.44 20.19 13.51 0.28 25 – 40 (460) (81.28) (200.15) (488.95) (290.53) (512.83) (343.20) (7.11) 25 – 40 (575) 25 – 75 (460) 3.20 7.88 28.00 12.68 31.37 14.00 0.42 25 – 75 (575) (81.28) (200.15) (711.20) (322.07) (796.80) (355.60) (10.67)
Note that the E-dimension in the 50-75 HP is maximum overall height to the conduit box rather than the bottom of the foot.
Diagram 3
WEIGHTS OF MODELS - Table 1: NEMA 12
Electrical Connections
Installation Procedures
FAILURE TO DISCONNECT AND LOCKOUT ELECTRICAL POWER AND WAIT
FIVE MINUTES FOR CAPACITOR DISCHARGE BEFORE SERVICING AQUAVAR
CONTROLLER CAN CAUSE SHOCK, BURNS, OR DEATH.
WARNING!
WARNING!
Installation and maintenance must only be performed by properly trained and qualified personnel equipped with the proper tools.
Note
INSTALL AN ALL LEG DISCONNECT SWITCH NEAR THE MOTOR.
INSTALL, GROUND, AND WIRE ACCORDING TO LOCAL AND
NATIONAL ELECTRICAL CODE REQUIREMENTS.
DISCONNECT AND LOCKOUT ELECTRICAL POWER BEFORE
INSTALLING OR SERVICING.
MOTORS WITH AUTOMATIC THERMAL PROTECTION MAY OPEN THEIR
ELECTRICAL CIRCUIT WHEN A THERMAL OVERLOAD EXISTS. THIS CAN
CAUSE THE MOTOR TO START UNEXPECTEDLY AND WITHOUT WARNING.
ELECTRICAL SUPPLY MUST MATCH PUMP’S AND AQUAVAR CONTROLLER NAME
PLATE SPECIFICATIONS. INCORRECT VOLTAGE OR WIRING CAN CAUSE FIRE
DAMAGE, AND VOIDS WARRANTY.
WARNING
Hazardous voltage can shock, burn or cause death.
WARNING
Hazardous voltage can shock, burn or cause death.
Power Rating Weight HP Pounds Kilograms 25 52.0 23.6 30 52.0 23.6 40 60.0 27.2 50 107.0 48.6 60 107.0 48.6 75 107.0 48.6
Electrical Connections continued
Step 3 - Preliminary Inspection Before storing or installing the AQUAVAR controller, thoroughly inspect the device for possible shipping damage. Upon receipt:
1. Remove the controller from its package and inspect exterior for shipping damage. If damage is apparent, notify the shipping agent and your sales representative.
2. Remove the cover and inspect the controller for any apparent damage or foreign objects.
Ensure that all mounting hardware and terminal connection hardware is properly seated, securely fastened and undamaged.
3. Read the technical data label affixed to the controller and ensure that the correct horsepower and input voltage for the application had been purchased.
4. If you will store the controller after receipt, place it in its original packaging and store in a clean, dry place free from direct sunlight or corrosive fumes, where the ambient temperature is not less than -20ºC (-4ºF) or greater than +65ºC (+149ºF).
Step 4 - Installation Precautions Improper installation of the AQUAVAR controller will greatly reduce its life. Be sure to observe the following precautions when selection a mounting location. Failure to observe these precautions will void the warranty!
1. Do not install the controller in a place subjected to high temperature, high humidity, excessive vibration, corrosive gases or liquids or airborne dust or metallic particles. See Technical Data Appendix B for temperature, humidity and maximum vibration limits or contact factory.
2. Do not mount the controller near heat-radiating elements or in direct sunlight.
3. Mount the controller vertically and do not restrict the air flow to the heat sink fins.
4. The controller generates heat. Allow sufficient space around the unit for heat dissipation.
Installation Procedures
CAUTION!
EQUIPMENT DAMAGE HAZARD - DO NOT OPERATE OR INSTALL ANY CON-
TROLLER THAT APPEARS DAMAGED. FAILURE TO OBSERVE THIS INSTRUC-
TION CAN RESULT IN INJURY OR EQUIPMENT DAMAGE.
Step 5 - Considerations for Mounting AQUAVAR Controllers in Host Enclosures
The AQUAVAR controller is available from stock in a variety of enclosures that meet the requirements of almost any application. Yet, special applications (such as use in washdown environments or in integrated systems) may make it desirable to mount AQUAVAR controllers in a host enclosure.
When the AQUAVAR controllers are mounted in a host enclosure, the watts dissipated by the drives must be dissipated by the host enclosure. If this is not accomplished, the control circuitry of the AQUAVAR controller will be damaged.
Two techniques are available for mounting AQUAVAR controllers in a host enclosure:
• The controllers may be entirely enclosed in the host enclosure or
• The controllers may be mounted with their cooling fins outside of the host enclosure.
The following sections discuss these two mounting techniques in greater detail.
Models Entirely Enclosed in the Host Enclosure When an AQUAVAR controller is entirely enclosed in a host enclosure, the host enclosure must be properly sized to dissipate the heat generated by the controller and any other power-dissipated by the various models of the AQUAVAR controller at various switching frequencies. Use this information to adequately size the host enclosure.
Models with Fins External to the Host Enclosure By mounting an AQUAVAR controller so that its heatsink fins are outside of the host enclosure, you may select a smaller host enclosure than that required when the controller is mounted entirely inside the host enclosure. For most applications with this type of mounting, typically you will not need such additional cooling devices as fans, heat exchangers or air conditioners.
The amount by which the load on the host enclosure is reduced is the amount of watts dissipated by the heatsinks of the controllers. Table 3 shows the watts dissipated by each AQUAVAR model after deducting the amount of watts dissipated by the heatsinks of the model. Use the values shown in the table to adequately size the host enclosure.
AQUAVAR Switching Frequency Max. Switching Model Watts Dissipated Watts Dissipated Watts Dissipated Frequency for AV2V- at 4 kHz at 7 kHz at 10 kHz Rated Current (kHz)
2S010D 37 44 51 10 2S020D 59 71 81 10 2S030D 77 92 106 10 2S050D 162 212 220 10 2S075D 195 251 271 10 2S100D 267 312 354 10 20010D 37 44 51 10 20020D 59 71 81 10 20030D 77 92 106 10 20050D 112 135 156 10 20075D 162 212 220 10 20100D 195 251 (1) — 6 20150D (2) (2) (2) (2) 20200D (2) (2) (2) (2) 40010D 33 43 53 10 40020D 52 69 84 10 40030D 68 90 110 10 40050D 99 131 161 10 40075D 112 144 174 10 40100D 139 180 217 10 40150D 170 210 255 (1) 9 40200D 200 245 — 7 40250D 280 383 — 7 40300D 335 371 (1) — 5 40400D 398 (1) — — 2.5 40500D 600 670 (1) — 5 40600D 710 (1) — — 4 40750D 720 (1) — — 2 50010D 40 52 64 10 50020D 62 83 101 10 50030D 82 108 132 10 50050D 85 115 155 10 50075D 91 131 172 10 50100D 112 160 — 8 50150D 164 — 282 (1) 9 50200D 218 277 (1) — 6 50250D 286 364 (1) — 6 50300D 343 388 (1) — 5 50400D 417 — — 4 50500D 700 — — 4 50600D 720 (1) — — 3 50750D 745 (1) — — 2
(1) Dissipation at rated current and maximum switching frequency.
Table 2: Required Dissipation for Models Entirely Inside an Enclosure
AQUAVAR Model Watts Dissipated
AV2V2S010D 19
AV2V2S020D 20
AV2V2S030D 27
AV2V20010D 19
AV2V20020D 20
AV2V20030D 27
AV2V20050D 29
AV2V20070D 36
AV2V20100D 34
AV2V20150D 68
AV2V20200D 73
AV2V40010D 20
AV2V40020D 21
AV2V40030D 27
AV2V40050D 30
AV2V40070D 36
AV2V40100D 40
AV2V40150D 46
AV2V40200D 50
AV2V40250D 75
AV2V40300D 76
AV2V40400D 80
AV2V40500D 134
AV2V40600D 145
AV2V40750D 150
AV2V50010D 20
AV2V50020D 21
AV2V50030D 27
AV2V50050D 30
AV2V50070D 33
AV2V50100D 39
AV2V50150D 43
AV2V50200D 44
AV2V50250D 73
AV2V50300D 78
AV2V50400D 82
AV2V50500D 135
AV2V50600D 143
AV2V50750D 152
Table 3: Required Dissipation When Fins are External to the Enclosure
Electrical Connections continued
Step 6 - Maintenance Minimum Torque Values to Secure Cover
If you remove the cover of an IP55 AQUAVAR controller, it is imperative that the cover be closed and re-secured with sufficient tightness to maintain environmental integrity. The table below specifies the torque values for the bolts that secure the covers on the various models.
Step 7 - General Wiring Information Wiring Practices
When making power and control connections, observe these precautions:
• Follow all Federal, State, NEC codes and local codes.
• Never connect input AC power to the motor output terminals T1/U, T2/V or T3/W – or damage to the controller will result.
• Power wiring to the motor must have the maximum possible separation from all other power wiring. Do not run in the same conduit, this separation reduces the possibility of coupling electrical noise between circuits.
• Cross conduits at right angles whenever power and control wiring cross.
• Good wiring practice also requires separation of control circuit wiring from all power wiring.
Since power delivered from the controller contains high frequencies which may cause interference with other equipment, do not run control wires in the same conduit or raceway with power or motor wiring.
Considerations for Power Wiring Power wiring refers to the line and load connections made to terminals L1/R, L2/S, L3/T and T1/U, T2/V, T3/W respectively. Select power wiring as follows:
• Use only UL recognized wire. (Shielded or armored wire is recommended for power and motor wiring.)
• Wire voltage rating must be a minimum of 300 V for 230 Vac systems and 600 V (Class 1 wire) for 460 Vac and 575 Vac systems.
AV2 Enclosure Type Torque Value
English Metric 1-20 HP, 230 Vac input 12 in-lbs 1.35 Nm
IP55 1-20 HP, 460 and 575 Vac input 18 in-lbs 2.03 Nm 25-75 HP, 460 and 575 Vac input 12 in-lbs 1.35 Nm
• Use circuit breakers on the incoming power lines.
• Grounding must be in accordance with NEC and CEC. If multiple AQUAVAR controllers are installed near each other, each must be connected to ground. Take care to not form a ground loop. Maintain a common ground.
• Wire must be made of copper and rated 60 / 75ºC (unless otherwise specified in the table below). Refer to Tables 4, 5 and 6 for recommended wire gauges and temperature ratings.
Considerations for Control Wiring Control wiring refers to the wires connected to the control terminal strip. Select control wiring as follows:
• Shielded wire is recommended to prevent electrical noise interference from causing improper operation or nuisance tripping.
• Use only UL™ recognized wire.
• Wire voltage rating must be at least 300 V for 230 Vac systems.
Installation Procedures
Model Wire Size 208 Vac Wire Size 230 Vac Number AWG mm2 AWG mm2
AV2V2S010D 14 2.5 14 2.5
AV2V2S020D 12 4.0 12 4.0
AV2V2S030D 10 6.0 10 6.0
AV2V2S050D 8 10.0 8 10.0
AV2V2S075D 6 16.0 6 16.0
AV2V2S100D 4 25.0 4 25.0
AV2V20010D 14 2.5 14 2.5
AV2V20020D 14 2.5 14 2.5
AV2V20030D 12 4.0 14 2.5
AV2V20050D 10 6.0 10 6.0
AV2V20070D 8 10.0 8 10.0
AV2V20100D 81 10.01 8 10.0
AV2V20150D 61 16.01 61 16.01
AV2V20200D 61 16.01 61 16.01
(1) Use wire rated 90ºC in an environment where the ambient temperature is greater than 40ºC (122ºF).
Table 4: Recommended Wire Gauges (230 Vac Models)
Model Number Wire Size AWG mm2
AV2V50010D 14 2.5
AV2V50020D 14 2.5
AV2V50030D 14 2.5
AV2V50050D 14 2.5
AV2V50075D 14 2.5
AV2V50100D 12 4.0
AV2V50150D 10 6.0
AV2V50200D 8 10.0
AV2V50250D 8 10.0
AV2V50300D 8 10.0
AV2V50400D 61 16.01
AV2V50500D 41 25.01
AV2V50600D 41 25.01
AV2V50750D 21 35.01
(1) Use wire rated 90ºC in an environment where the ambient temperature is greater than 40ºC (122ºF).
Installation Procedures
Electrical Connections continued Table 5: Recommended Wire Gauges (460 Vac Models)
Model Number Wire Size AWG mm2
AV2V40010D 14 2.5
AV2V40020D 14 2.5
AV2V40030D 14 2.5
AV2V40050D 14 2.5
AV2V40075D 12 4.0
AV2V40100D 12 4.0
AV2V40150D 10 6.0
AV2V40200D 101 6.01
AV2V40250D 81 10.01
AV2V40300D 61 16.01
AV2V40400D 61 16.01
AV2V40500D 31 35.0
AV2V40600D 21 35.01
AV2V40750D 11 50.01
(1) Use wire rated 90ºC in an environment where the ambient temperature is greater than 40ºC (122ºF).
Table 6: Recommended Wire Gauges (575 Vac Models)
Step 8 - Input Line Requirements Line Voltage
See the Power and Current Ratings table for the allowable fluctuation of AC line voltage for your particular model. A supply voltage above or below the limits given in the table will cause the drive to trip with either an overvoltage or undervoltage fault.
When supplying line voltages other than the factory default values (either 230 Vac, 460 Vac or 575 Vac depending on the model), set the Supply Voltage parameter to the appropriate value.
Exercise caution when applying the AQUAVAR controller on low-line conditions.
For example, and AQUAVAR controller will operate properly on a 208 Vac line – but the maximum output voltage will be limited to 208 Vac. Now if a motor rated for 230 Vac line voltage is controlled by this drive, higher motor currents and increased heating will result.
Therefore, ensure that the voltage rating of the motor matches the applied line voltage. If other than 60 Hz output is desired, proper V/Hz can be programmed into the AVII by setting the Nom Mtr Voltage and Nom Mtr Freq parameters.
Use of Isolation Transformers and Line Reactors The AQUAVAR controller is is perfectly suitable in most cases for direct connection to a power source as specified in this manual and the technical nameplate affixed to the unit. There are however a few cases where a properly sized isolation transformer or line reactor should be employed to minimize the risk of drive malfunctionor damage or nuisance tripping:
• As noted in Table 7, transformer sizing, when line capacity is greater than 10 times the KVA rating of the drive. Consult the factory for assistance in sizing the reactor.
• When power factor correction capacitors are employed on the drive’s power source.
• When the power source is known to be subject to transient power interruptions or significant voltage spikes.
• When the power source supplying the drive also supplies large devices such as DC drives that contain controller rectifiers.
Table 7: Transformer Sizing for the AQUAVAR Controller Controller HP 1 2 3 5 7.5 10 15 20 25 30 40 50 60 75
Transformer kVA 2 4 5 9 13 18 23 28 36 42 56 70 90 112
Phase Imbalance Phase voltage imbalance of the input AC source can cause unbalanced currents and excessive heat in the drive’s input rectifier diodes and DC bus capacitors. Phase imbalance can also damage motors running directly across the line.
Step 9 - Terminals Found on the Power Board Description of the Terminals
Diagram 4 shows the power terminals for the AQUAVAR controller. Table 8 describes the terminals.
Table 8: Description of Power Terminals
Terminal Description
TB1 Terminal Group GND Earth ground.
L1/R These terminals are the line connections for three-phase models. (Single-phase L2/S models will only have the L1/R terminal, with the other two terminals being L3/T replaced by a terminal labeled N.)
T1/U T2/V These terminals are for motor connections.
T3W
Installation Procedures
CAUTION!
EQUIPMENT DAMAGE HAZARD - NEVER USE POWER-FACTOR CORRECTION
CAPACITORS ON MOTOR TERMINALS T1/U, T2/V OR T3/W. DOING SO WILL
DAMAGE THE SEMICONDUCTORS. FAILURE TO OBSERVE THIS INSTRUC-
TION CAN RESULT IN INJURY OR EQUIPMENT DAMAGE.
G N
D
L1 /R
L2 /S
L3 /T
B– B + D B
T1 /U
T2 /V
T3 /W
G N
D
Diagram 4: AQUAVAR Controller Power Terminals
Typical Power Connections Diagram 5 shows the terminal connections for line power and motor output. See Step 8 for input line requirements.
Note that when testing for a ground fault, do not short any motor lead (T1/U, T2/V or T3/W) back to an input phase (L1/R, L2/S or L3/T).
As shown in Diagram 5, it is necessary to provide fuses and a disconnect switch for the input AC line in accordance with all applicable electrical codes. The drive is able to withstand a 110% over load for 60 s. For maximum protection of the drive, use the fuses listed in Tables 9, 10 and 11 found below and on the next page. The recommended supplier is Bussman.
Table 9: Recommended Fuses (230 Vac Models)
Fuse Size 208 Vac Fuse Size 230 VacModel Number
JJS/JJN1 JJS/JJN1
AV2V2S010D 15 10
AV2V2S020D 20 20
AV2V2S030D 30 30
AV2V2S050D 45 45
AV2V2S075D 60 60
AV2V2S100D 80 80
AV2V20010D 10 6
AV2V20020D 15 10
AV2V20030D 20 15
AV2V20050D 30 25
AV2V20075D 40 35
AV2V20100D 50 40
AV2V20150D 70 60
AV2V20200D 70 60
(1) For sizes up to and including 30 A, KTK fuses may be substituted.
Installation Procedures
AV2V Drive
Motor
Fuses
Disconnect Switch
Th re e- Ph as e
A C
P ow er
L1/R
L2/S
L3/T
T1/U
T2/V
T3/W
GND
GND
Diagram 5: Connections for Power Wiring
Electrical Connections continued Table 10: Recommended Fuses (460 Vac Models)
Fuse Size 380 Vac Fuse Size 460 VacModel Number
JJS/JJN1 JJS/JJN1
AV2V40010D 6 6
AV2V40020D 6 6
AV2V40030D 10 10
AV2V40050D 15 15
AV2V40075D 20 20
AV2V40100D 20 20
AV2V40150D 40 35
AV2V40200D 50 40
AV2V40250D 60 50
AV2V40300D 70 60
AV2V40400D 80 60
AV2V40500D 90 90
AV2V40600D 110 110
AV2V40750D 150 150
(1) For sizes up to and including 30 A, KTK fuses may be substituted.
Table 11: Recommended Fuses (575 Vac Models)
Fuse Size 575 VacModel Number
JJS/JJN1
AV2V50010D 6
AV2V50020D 6
AV2V50030D 10
AV2V50050D 10
AV2V50075D 15
AV2V50100D 20
AV2V50150D 30
AV2V50200D 35
AV2V50250D 50
AV2V50300D 50
AV2V50400D 70
AV2V50500D 70
AV2V50600D 80
AV2V50750D 100
(1) For sizes up to and including 30 A, KTK fuses may be substituted.
1. The wires routed from the terminal block U, V, W, and ground screw, should now be connected to the motor leads using the motor nameplate and Diagram 6 for reference. Always refer to motor wiring nameplate.
2. Pressure Transducer Installation and Wiring It is recommended that the transducer be mounted in the discharge piping. The location should be in a non-turbulent, straight piece of pipe. See layout on page 5. Locate the adapter for the pressure transducer, if needed.
Installation Procedures
220 Volt 460 Volt
AQUAVAR
W U
V
GROUND = PE
AQUAVAR
GROUND = PE
W U
V
Diagram 6
BROWN – 3
WHITE – 2
+ 5VDC
GND
SIO +
SIO -
15 V IN (4-20 mA)
RS-485
connected to drive “Run Signal” fault signal
Current Signal Input (4-20 mA)
Analog signal output (0-10V) connected to drive
Motor thermo or PTC * low Water or jumper * external on or jumper *
Ub (max 100 mA) actual value signal shieldingX1
X2 Multi-pump
Transducer connection
X5
NO
CC
NC
NO
CC
NC
Digital Input Voltage Signal Input (0-10Vor 2-10V)
X2
1X1
X5
X6 4 3 2 1
RS485
6 – CONNECTED TO DRIVE
5 – CONNECTED TO DRIVE JUMPER
4 – CONNECTED TO DRIVE JUMPER
3 – CONNECTED TO DRIVE
2 – ANALOG OUT (PRESSURE)
1 – RETURN SIGNAL
X9
* NOTE: Jumpers are installed from the factory.
Must remove to wire motor thermal, low water switch or external ON/OFF if used.
- 24 VDC
+ 24 VDC
+ 24 VDC
FAULT RELAY
Diagram 7
Electrical Connections continued
3. Place the square gasket over the end of the transducer, plug the cable connector on, and tighten the screw.
• The transducer is supplied with 1⁄4” NPT threads for direct mounting in the discharge piping.
4. Now select one of the remaining ports in the AQUAVAR controller to route the transducer cable.
Route the transducer cable through the strain relief, cut to length and connect to locations X1 #2 and #3 as shown in Diagram 7. (Note: Control board is mounted to the inside front cover of the drive enclosure.) The brown wire is connected to X1 #3 and the white wire to X1 #2.
Tighten strain relief.
5. Terminals Found on the AV II Drive Control Board (Internal Drive) Description of the Control Terminals: Figure 8 shows the control terminals found on the I/O board of the AV II drive. (The actual control board cannot be accessed by the user.) These terminals are prewired by the factory with color coded wires below.
Note that due to labeling constraints, the labels for some terminals start on the left (either on the side or top of the terminal block), are interrupted by the terminal screw, and then finish on the right (either on the side or top of the terminal block). For example, terminal A11 is labeled with A on the left side of the block and 11 to the right of the terminal screw on top of the block. Similarly, terminal NC2 is labeled with N to the left of the terminal screw on top of the block and then C2 on the right side of the block.
As is shown in the figure, the terminals are divided into four terminal blocks, each of which pulls apart for ease of field wiring:
• TB1 - analog input, analog output and digital output terminals.
• TB2 - output relay 1 (R1).
• TB3 - output relay 2 (R2).
• TB4 - digital input terminals.
Table 12 starting on the next page describes the control terminals.
Cable connector will fit on one way only! Do not force on or damage may occur.
Note
TB1
A0
CM
A1
CM
CM
CM
CM
PQ
C1
C1
C1
DIP Switches
A0
CM
A1
CM
A
A
A
CM
CM
CM
D
DQ
DQ
DQ
R N
N
TB2
Yellow Wire
White Wire
Black Wire
On side of terminal block TB4
TB3
CM
EN
D
D D
D
D
D D
D D
D
R
N
N
CM
EN
C2
C2
O2
On side of terminal block
Black Wire
Jumper
Orange Wire
Blue Wire
Red Wire
Enhanced Keypad
Port
Diagram 8
Electrical Connections continued Table 12: Description of AV II Drive Control Terminals (Internal Drive)
Terminal Description TB2 Terminal Block
Common terminal for the first auxiliary relay. The function of the relay is RC1 set by parameter R1 Configure. The default setting is for the relay to activate when a fault is detected (Drv Flted).
NC1 Normally-closed contact for the first auxiliary relay. It will open when the relay is activated.
NO1 Normally-open contact for the first auxiliary relay. It will close when the relay is activated.
TB3 Terminal Block (Drive Run Contacts) Common terminal for the second auxiliary relay. The function of the relay
RC2 is set by parameter ROUT R2 Config. The default setting is for the relay to activate when the drive is running.
The contact ratings are 115 VAC at 1 A or 230 VAC at 0.5 A.
NC2 Normally-closed contact for the second auxiliary relay. It will open when the relay is activated.
NO2 Normally-open contact for the second auxiliary relay. It will close when the relay is activated.
TB4 Terminal Block Enable terminal. A jumper is placed between this terminal and the +2 terminal at the factory. You may replace this with a contact if desired. The
EN circuit from EN to +24 must be closed for the drive to operate.
Note that unlike all other terminals, this terminal cannot be configured for “pull-down logic.” That is, a high input to this terminal is always regarded as true – and must be present if the drive is to operate.
Digital inputs. The function of a digital input is configured by the
D3 to D10 parameter with the same name as the digital input in the DI Configure parameter group.
Digital input. In 3-wire control, this must be a Stop input. In 2-wire
D2 control, it may be configured to another function with parameter D2 Configure.
D1 Digital input. This must be a Start or Run input.
6. For multi-pump systems: Use a three core shielded cable to connect terminals 1, 2, and 3 on X5 between the AQUAVAR controller units. These are the RS-485 interface connections.
(See Diagram 11 and 13). Note: either RS485 port can be used.
• Connect pump one to pump two, two to three, and three to four (maximum is 4 pumps).
7. External pressure switch or float switch- (if used) to check incoming pressure and low/no suction. Connect to terminal block X1 at the 6 and 7 location. Refer to Diagram 11.
When using a suction pressure switch, set the cut off at the maximum NPSH required by the pump.
8. External on/off If used to turn the AQUAVAR controller on or off from an external panel or controller, connect to terminal block X1 at the 4 and 5 location (refer to Diagram 7, page 24).
9. Analog output of pressure A meter can be connected to X9 pins 2 and 1 for remote display of actual system pressure.
The meter must be 0-10 VDC volt with no more than 2 mA.
10. Second Sensor Input The ground pin (X1-10) used for analog output can also be used to bridge a connection for a second sensor. This can be digital (on/off) such as a switch which would be connected between X1-10 and X1-14. Another choice is a sensor with a voltage signal of 0-10V or 2-10V which would be connected to X1-10 and X1-13. A final choice is a 4-20 mA current sensor which would be connected to pins X1-10 and X1-12.
Installation Procedures
Power supplies using G.F.I. breakers will cause nuisance tripping which will result in the AQUAVAR controller displaying an “undervoltage” fault.
Note
If an external switch is NOT used, install a jumper wire between X1 Locations 4 and 5.
Note
X2
1X1
X5
X2
1X1
X5
X2
1X1
X5
Diagram 9
Pump Priming Refer to your pump operation manual for instructions on pump priming. You will need to unscrew the pressure transducer and adapter if you used the pump fill plug for mounting. When priming is complete, replace the pressure transducer and check for leaks!
Run Test
Instructions
1. Check all wiring.
All motors used with the AQUAVAR controller are three phase. You will need to check the direction of rotation of the motor shaft. If you have followed all of the previous steps carefully, you should now be ready to apply power to the AQUAVAR controller unit.
2. Close discharge valve.
Make sure the discharge valve is closed.
Apply power to the AQUAVAR controller. The first screen appears for 2 seconds and shows the software version and manufacture date. The next screen will appear automatically *If auto start is preprogrammed “ON”, pump will start immediately.
3. Check Power Light Check the AQUAVAR controller panel. The “power on” light should be illuminated and the display should say “No Autostart - disable inverter.” If either of these conditions is not present, turn off all power to the AQUAVAR controller and recheck all connections.
To change the display language on the AQUAVAR controller, press the “ ” key and the up arrow key at the same time. A scrolling line will appear on the bottom of the screen and tell you which button to push for the language you want. After selecting the language, press the up arrow to return to the main display.
Note
FAILURE TO DISCONNECT AND LOCKOUT ELECTRICAL POWER AND WAIT
FIVE MINUTES FOR CAPACITOR DISCHARGE BEFORE SERVICING AQUAVAR
CONTROLLER CAN CAUSE SHOCK, BURNS, OR DEATH.
WARNING!WARNING
Hazardous voltage can shock, burn or cause death.
Installation Procedures
DO NOT APPLY POWER TO THE AQUAVAR CONTROLLER OR PUMP UNTIL ELECTRI-
CAL CONNECTIONS HAVE BEEN REVIEWED BY A QUALIFIED ELECTRICIAN AND
MEET ALL APPLICABLE STATE AND LOCAL REQUIREMENTS.
WARNING
Screen
NO AUTOSTART - DISABLE INVERTER
ITT Industries SW:120 Date: 10/30/00
4. Check Display.
* If these conditions exist, proceed.
If NOT, check all wiring.
5. Drive Component Keypad (Internal Drive) The AQUAVAR II units have an additional keypad inside the cabinet. You will need to use this keypad one time for initial system set up. Once set, all other functions are programmed with the main display on the front panel. Below are the instructions for initial programming of the internal keypad.
This keypad provides access to a comprehensive set of parameters that allow the AV II drive to meet the needs of almost any application. To make customization as simple as possible, two levels of programming are available.
Programming Mode
A. Programming mode is entered by pressing the PROG key.
B. To program a parameter’s value, per form the following steps:
C. Press PROG to initiate programming.
D. The Operate display will change to the list of parameters. An arrowhead indicates which one is selected.
E. If the desired parameter is indicated by the arrowhead, press ENTER to select the parameter and display its current value. If the indicated parameter is not the one you want to program, use the up or down arrow keys to move the arrowhead to the desired parameter and then press ENTER to select the parameter and display its current value.
F. After the ENTER key is pressed, the value for the parameter will be displayed. For exam-ple, parameter Motor voltage may range from 100V to 690 V and you may configure any value within that range as shown on the motor nameplate.
Installation Procedures
Screen
NO AUTOSTART - DISABLED INV.
Can Parameter Be Changed?
P V
Unlocked — Yes.
Locked — No.
Sample display for parameters assigned a value
Sample display for parameters assigned a function
MIN FREQUENCY
V0301 160.05 Hz
STOP TYPE
P0403 CST to Stp
Name of Parameter
Data Value
Units
10-Character Description of Assigned Function
Memory Address
Memory Address
Diagram 11
2 Line by 16 Character Display
RUN WARNING FAULT PROG POWER
FWD
REV
SHIFT ENTER
PROG
STOP
Diagram 10
G. Use the up or down arrow keys to change the parameter’s value to the desired value.
H. Press ENTER to save the new value. (If you do not wish to save the new value, press
SHIFT.)
I. The new value is stored, or discarded, and then the list of parameters is shown.
J. You may now select another parameter or return to the Operate mode by pressing the PROG key.
6. You need to set up the AQUAVAR controller for the type of pump motor you are using. Press the
PROG key to display the list of functions. Use the up or down arrow to scroll to the NOM MTR CURRENT parameter.
7. Press the ENTER key and then the up and down arrows to change the value to match the SFA (Service Factor Amps) shown on your pump motor data plate. Once complete, press ENTER again. (Maximum S.F. amps is 10% above nominal controller output amps.) See pages 86 and 87.
8. Scroll to the NOM MTR VOLTAGE parameter and press ENTER. Use the up and down arrows to enter the voltage on the motor nameplate. For multi-voltage motors, select the voltage to match your line voltage. Press ENTER to save the value.
9. Scroll to the NOM MTR FREQ parameter and press ENTER. Use the up and down arrows to enter the maximum frequency for the motor design you are using. This would be either 50 Hz or 60 Hz. Press ENTER to save the value.
10. Scroll to the NOM MTR RPM parameter and press ENTER. Use the up and down arrows to enter the maximum RPM for the motor you are using. THis can be found on the motor nameplates. Press ENTER to save the value.
11. Scroll to the SUPPLY VOLTAGE parameter. Press ENTER and use the up and down arrows to put in the voltage available on the input line. Press ENTER to save the value.
12. Scroll to the Language parameter. Press the ENTER key and use the up and down arrows to change the display language if needed. Press ENTER to save the value.
13. Press the PROG key again, close the panel door and go back to the main AQUAVAR display.
14. Press the down arrow key The next display will be:
15. Press the up arrow to turn on the AQUAVAR II controller.
16. Open the discharge valve slowly until the pump starts.
Observe the rotation of the pump shaft or motor fan.
17. Close the discharge valve.
18. Press the down arrow to turn off the AQUAVAR II controller.
Installation Procedures (continued)
INVERTER STOP - ON -> START
RUN LIGHT ON
Installation Procedures continued
19. If the direction of rotation was correct, proceed to the Programming section beginning on the following page.
20. If the direction was not correct, remove all power from the AQUAVAR II controller and wait five minutes.
Open the motor conduit box and exchange any two of the three motor leads. Close the conduit box.
Repeat steps 15 through 18 to check the direction of the motor shaft rotation.
Programming Programming of the AQUAVAR II controller is accom-plished by using the three pressure sensitive but-tons on the control panel along with the two line LCD display.
The format of the program is a series of menus which can be scrolled through by using the select button. Each screen display is used to provide information about the operation of the system or to change one or more of the operating parameters.
Changes are made by pushing the up or down arrows.
I. The Main Menu - Setting Single Pump Constant Pressure Diagram 15 shows the display screens in a flow chart format. Refer to this flow chart for the next 6 steps.
There are ten display screens in the main menu which will allow you to set the required system pressure, save it, and turn the system on. Several of these display screens were already used during the test run.
After power has been turned on, the “Power on” light should be illuminated and the display should briefly show the software version and date, then show “No Autostart - disable inverter.”
Programming
Diagram 12
Instructions
1. Check Power Light
2. Press the down arrow to advance the display to:
3. Press Select to advance the display to:
4. Enter the pressure you want the pump to maintain (constant pressure) for your system.
Press the until the reading shows the value you want. Use the down arrow to back up if you have gone too far.
For example: if you need a constant pressure of 50 PSI in your system at various demand rates, you would enter 50 as the value by using the .
5. Autostart setting
Press to advance the display to:
(This displays the autostart setting.)
Push to turn the autostart function on.
If the autostart function is on, the AQUAVAR II controller will automatically turn on and resume activity when power is restored after a failure. If autostart is off, the AQUAVAR II controller must be manually turned on by the operator after a power failure. Be sure the dis charge valve is closed to prevent pump start.
Programming
REQ. PRESS - XXX PSI
AUTO START - OFF
AUTO START - ON
Screen
REQUIRED VALUE - XXX PSI
NO AUTOSTART - DISABLE INVERTER
Screen
If “Inverter Locked” is displayed, the external on/off switch is in the off position or con-tacts at X1:4 and 5 are not jumpered.
Note
INVERTER STOP - ON->START
REQUIRED VALVE - XXX PSI
6. Press to advance the display to:
This display shows the last recorded error or fault encountered by the AQUAVAR controller.
7. Press to advance the display to:
This in the error which occurred before the last one.
8. Press to advance the display to:
The error before error 2.
9. Press to advance the display to:
The error before error 3.
10. Press to advance the display to:
The error before error 4.
11. Press to advance the display to:
This is the total amount of run time of the motor. It can be reset using a method described later.
12. Saving changes Press to advance the display to:
13. Press and hold down BOTH arrows at the same time until the display changes to:
This will allow you to save the changes you have made in the microprocessor memory.
14. After about five seconds the display will automatically return to:
Push . The AQUAVAR II controller will begin to automatically maintain system pressure at the point you have selected and the display will show the pressure set point.
Programming
SAVE ??? +
SAVE ??? SAVED
INVERTER STOP - ON->START
If the AQUAVAR II controller is not maintaining the rating you selected, check the sen-sor adjustment procedures on page 60 or check rotation again.
Note
ERROR 5*
* TOTAL RUN TIME
0000:00
If you have advanced past a window and want to return to it, press and at the same time to back up.
Note
* ERROR 1
ERROR 2
* ERROR 3
* ERROR 4
AQUAVAR II Controller Program Flow Chart Single Pump Constant Pressure
II. Single Pump - Pump Protection The AQUAVAR II controller has the ability to protect the pump by shutting it off in low/no suction or run out conditions.
To set run out protection:
For steps 1 through 8, refer to the flow chart on page 36.
Instructions
1. Password The password protection prevents untrained personnel from accidentally changing the base settings.
• From the main menu, hold down the key for 2-3 seconds until the display changes to:
Programming
Diagram 13
FAILURE TO SAVE SETTINGS AFTER PROGRAMMING RESULTS IN LOSS OF
PROGRAM VALUES WHEN POWER IS REMOVED!
WARNING
REQUIRED
VALUE
50 PSI
Auto-START
ON ERROR 1 ERROR 2 ERROR 3 ERROR 4 ERROR 5
TOTAL RUN
TIME
0000: 41
SAVE ??
– + v
SW Ver.
Date:
ITT Ind.
50 PSI
Press • long
Low/no suction protection can be managed by the installation of a suction line pressure switch, or float switch for a tank. This switch is connected to the AQUAVAR II controller as described earlier in the Electrical Installation section. The cut off setting for this switch should be the maximum NPSH required by the pump.
Note
PASSWORD 0000
Screen
2. Press the key until you reach the number
66. You will now be able to access all of the alternate menus for all AQUAVAR controller optional controls.
3. Press to advance the display to the next window:
The jog mode is very useful because it allows you to check on the actual outgoing frequency and system pressure. By pressing either or the controller changes to manual, and you can change the frequency to set any constant speed. The Aquavar returns to normal auto-matic operation when you leave the jog mode window.
4. Continue to briefly touch the key to scroll past all of the windows and submenus until you reach:
5. Hold the key down for 2-3 seconds until the display changes to:
6. Set the minimum pressure the system is allowed to maintain before shutting down. For example, if the set point for the system is 50 PSI, and the operator will allow anything above 41 PSI, then the conveyor limit would be set at 40 PSI. This function can also be turned off by pressing until “disabled” is shown.
To set timed protection:
7. Delay Time Enter the amount of time that the pump is…