Instrument Air compressor spec sheet.pdf
PDF 634 KB Posted
- Attached to
- Z1DA--608-23-116 SPS Compliance Corrections Construction Federal contract opportunity
- Solicitation number
- 36C24123B0006
About this file
This document contains a specification sheet for an instrument air compressor package and an associated federal contract opportunity. The specification sheet provides details on an enclosed scroll compressor package with integrated dryer for laboratory air between 20-30 horsepower. Key details include the compressor unit made up of three or four scroll compressor modules each with a 5, 7.5, or 7.5 horsepower motor, cooling system, regulation system, microprocessor control, and integrated refrigerated dryer. Dimensions and mounting details are also specified. The associated federal contract opportunity is a solicitation from the Department of Veterans Affairs Veterans Health Administration for compliance corrections construction at the SPS location with an unspecified description and response due date.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24123B0006 0002.docx | DOCX document | |
| 36C24123B0006 0001.docx | DOCX document | |
| EndoDry Site Requirements.pdf | ||
| New medivators installation 50098-15.pdf | ||
| Medivator Specs.pdf | ||
| Sterlizer utility requirements.jpg | JPG image | |
| 608-23-116 project sketches.pdf | ||
| SOW - 608-23-116 SPS steam and sterilization r1.docx | DOCX document | |
| Facility drawings with CSB - bare.pdf | ||
| Med Req 50098-1520-EN US R.pdf | ||
| VFD SW addition Aquavar AV2V2S050D.pdf | ||
| Technical-Information-SSH - existing pumps set 1022-9SH184JM2-2.pdf | ||
| PRE-AWARD CONTRACTOR EVALUATION FORM.pdf | ||
| 36C24123B0006.docx | DOCX document | |
| Medivator installation specs.pdf | ||
| VFD old AC shop abb acs550-u1-046a-2.pdf | ||
| PH-WHV-Spec-sheet-LR expansion tank - replace with WHV 75 or eqiv.pdf | ||
| SAM WD NH NH20230021 revised 040723.pdf |
Show all 18
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LDS-104-05
2205 6105 73.01
01 May 2021
H
P
SC
RO
LL
W
IT
H
D
RY
ER
BeaconMedæs • 1059 Paragon Way, Rock Hill, SC 29730 • Phone: (803) 817-5600 • Fax: (803) 817-5750 • www.beaconmedaes.com
Laboratory Air Oil-Free Scroll Compressor with Enclosure and Integrated Dryer (20-30 Hp)
SPECIFICATION
Enclosed Scroll Compressor The laboratory air oil-free scroll compressor package is fl oor mounted and enclosed in a steel, sound-insulated canopy. The package is equipped with an integrated refrigerated dryer. The compressor is designed and supplied as a complete package with all necessary equipment, including but not limited to the following components:
• Inlet fi lter
• Three or Four air compressor elements
• Three or Four drive motors
• Aftercooler
• Refrigerated dryer
• Starter and regulation system
• Control system All components are mounted within a common six-sided low sound enclosure with solid base frame.
The enclosed scroll package provides air quality that qualifi es to be in the category “Class 0” in terms of oil content as defi ned by standard ISO 8573-1:2001 Part 1.
Compressor Unit Compressor Module: The compressor package is made up of three or four compressor modules, each consisting of a compressor element belt driven by an electric motor, and a radial fan mounted on the drive shaft of the compressor element. Each module is equipped with a temperature sensor to monitor the element housing temperature.
• LES20 - Four 5 Hp Scroll compressor modules
• LES22 - Three 7.5 Hp Scroll compressor modules
• LES30 - Four 7.5 Hp Scroll compressor modules Compression Element: Each compressor element consists of a fi xed scroll housing and an orbiting scroll rotor. The element and housing are pressure die cast aluminum. The crankshaft and pulley are cast iron. The element is V-belt driven using belts with ZPZ profi le. Bolts for adjusting belt tension are easily accessible via removable panels.
Drive Motor: Each compressor module is belt driven by a totally enclosed and air cooled IP55 Class F motor, complying with IE3 Premium effi ciency standards for optimum performance and reliability. The motor bearings are greased for life and do not require special attention.
Starter: Each compressor is factory equipped with a direct on line starter. The starter is mounted and wired within the UL listed compressor control cubicle.
Cooling System: Each compressor element is equipped with a radial fan mounted as part of the element to generate cooling air across the element. The compressor package is fi tted with an aluminum block aftercooler for cooling of the compressed air.
The cooling system includes a fan, driven by an electric motor, to generate cooling air for the aftercooler.
Regulation System: The compressor regulation system keeps the net pressure between programmable limits by automatically starting and stopping the compressor modules.
Compressor Control: The compressor package has a microprocessor controller with advanced graphics, capable of controlling and monitoring the modules. The unique Variable Air Delivery control system automatically starts and stops the compressor modules to exactly match the air demand. The controller distributes the running time evenly among the compressor modules by selecting the module with the lowest hours and starting that one fi rst and stopping the unit with the most run hours fi rst when applicable. The controller prevents simultaneous stopping and starting of the individual modules.
The microprocessor allows for programming of two pressure bands for loading and unloading. Time based start/stop and changeover for net pressure is programmable. The compressor is equipped with auxiliary contacts for external indication of run status, automatic or manual run control, general warning and general shutdown conditions.
The control system has the capability to control and monitor the following functions:
• Delivery air pressure
• Element outlet temperature
• Compressor status
• Motor overload status
• Delivery air temperature
• Running hours
• Regulator hours
• Ambient temperature Compressor Protection: The microprocessor provides service requirement indication, warning and shutdown indication and alarms. Additional protective functions inlcude emergency stop, element outlet temperature, drive overload, service warnings, and ambient temperature warning and shutdown.
Inlet Air Filter A paper cartridge type fi lter is provided. The fi lter has a rated effi ciency of SAE fi ne. The fi lter removes 98% of all dust particles greater than 1 micron, 99.5% of particles greater than 2 microns and 99.9% of particles greater than 3 microns in size. The inlet fi lter is factory installed.
Compressor Enclosure The compressor module is enclosed in a steel, sound-insulated canopy with removable panels to provide access for maintenance.
The sound insulating material is a fl ame retardant polyurethane.
Integrated Dryer The compressor is fi tted with an integrated refrigerated dryer.
The dryer is integrated inside the canopy and controlled by the compressor’s primary controller. The dryer uses R134A refrigerant. The refrigerant compressor is a hermetic piston type design. The dryer includes an air-to-air heat exchanger to pre-cool the incoming compressed air and reheat the exiting compressed air. The condenser has aluminum fi ns and copper tubes. The condensate is automatically drained by an electronic condensate drain.
BeaconMedæs 1059 Paragon Way Rock Hill, SC 29730 Phone: (803) 817-5600 Fax: (803) 817-5750 www.beaconmedaes.com
LDS-104-05
2205 6105 73.01
01 May 2021
Notes: 1. Unit performance measured according to ISO 1217, Annex C, latest edition. Reference conditions: Absolute inlet pressure 14.5 psig; intake air temperature 68° F.
2. Noise level measured at a distance of 1m according to Pneurop/CAGI PN8NTC2 test code.
Scroll Compressor Package Specifi cations
System Model No. HP
Max.
Working Pressure
(psig)
Eff ective Working Pressure
(psig)
Capacity
FAD1
(cfm)
Noise Level2
Package FLA
Weight (Lbs.)
208V 60 Hz
230V 60 Hz
460V 60 Hz
400V 50 Hz
LES20-115-RD 20 112.4 97.9 55.1 63 68 62 31 35 1345
LES20-145-RD 20 141.4 126.9 47.9 63 68 62 31 35 1345
LES22-115-RD 22 112.4 97.9 64.9 64 84 73 37 40 1329
LES22-145-RD 22 141.4 126.9 49.8 64 84 73 37 40 1329
LES30-115-RD 30 112.4 97.9 86.0 65 109 94 48 52 1581
LES30-145-RD 30 141.4 126.9 62.9 65 109 94 48 52 1581
.6
1"
12.7" 38.6"
7.
9"
Center of Gravity
Model No. L W H
LES20-xxx-RD 32.7” 12.1” 27.9”
LES22-xxx-RD 33.1” 12.2” 25.9”
LES30-xxx-RD 31.9” 12” 30.7”
COMPRESSOR
MOUNTING HOLES
Ø0.6”(4X)
.3
3.9"
ELECTRIC CABLE
PASSAGE M52(F)
AUTOMATIC DRAIN
TUBE Ø0.31”
AMBIENT SENSOR
MANUAL DRAIN
G 1/8”F
COMPRESSED
AIR OUTLET G 1”F 35
.1
6.
8"
W
29.5"
2" 1.6"(2x)
19.7"
3.
3"
(4 x)
31.2(2x)"
5.8"
2.8"
1.8"
8.3"(2x)
64.1" 0.
6"
(4 x)
.6
H
7.9"(4x)
L
COOLING AIR OUTLET OF
AFTERCOOLER AND DRYER
COOLING AIR OUTLET
OF COMPRESSOR
CABINET
VENTILATION
COOLING AIR INLET OF
AFTERCOOLER AND DRYER
COOLING AIR INLETOF
COMPRESSOR AND CABINET
1.2"
8.
9"
5.1"
11.7"20.4"8"22.5"0.4" 11 7"20 4"8"22 5"0 4"
VALVE
ROTATION
1.
4"
.3
"* 11.9"
0.
2"
11.4"
7.
9"
9.
7"
.2
File details come from the government source that posted it. Updated .