TECH LIBRARY 1 SVPP Supplier Manuals Rockwell 1756-td002_-en-e.pdf
PDF 7 MB Posted
- Attached to
- Launch Operations Support Contract (LOSC) Request for Proposal (RFP) – FINAL Federal contract opportunity
- Solicitation number
- FA4610-22-R-0001
About this file
This announcement is a request for proposal for the Launch Operations Support Contract at Vandenberg Air Force Base. The RFP seeks to procure services to support launch operations, including mission planning, processing, and execution. Interested offerors must submit proposals by January 27, 2022. The North American Industry Classification System code for this effort is 561210 Facilities Support Services, with a small business size standard of $41.5 million. Attachments to the RFP include the performance work statement and appendices, government furnished property listing, security classification specifications, Davis-Bacon wage determinations, collective bargaining agreements, and contract data requirements list exhibits. Questions regarding the RFP are due by January 4, 2022 and shall be submitted to the primary and secondary points of contact via email.
View the file
Other files for this federal contract opportunity
Show all 50
Launch Operations Support Contract (LOSC) Request for Proposal (RFP) – FINAL has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Technical Data 1756 ControlLogix I/O Specifications 1756 Series Catalog Numbers
The ControlLogix® architecture provides a wide range of input and output modules to span many applications, from high-speed digital to process control. The ControlLogix architecture uses Producer-Consumer technology, which allows input information and output status to be shared among multiple ControlLogix controllers.
Each ControlLogix I/O module mounts in a ControlLogix chassis and requires either a removable terminal block (RTB) or a 1492 interface module (IFM) to connect all field-side wiring. RTBs and IFMs are not included with the I/O modules. They must be ordered separately.
Topic Page
Available 1756 I/O Modules 2
ControlLogix I/O Accessories 244
Additional Resources 246
Available 1756 I/O Modules
You can select these types of digital I/O modules.
Digital I/O Type Description
Diagnostic These modules provide diagnostic features to the point level. These modules have a D at the end of the catalog number.
Electronic fusing These modules have internal electronic fusing to prevent too much current from flowing through the module. These modules have an E at the end of the catalog number.
Individually isolated These modules have individually isolated inputs or outputs. These modules have an I at the end of the catalog number.
I/O Type Cat. No. Page Cat. No. Page
AC digital 1756-IA8D
1756-IA16
1756-IA16I
1756-IA32
1756-IM16I
1756-IN16
1756-LSC8XIB8I
1756-OA8D
1756-OA8E
1756-OA16
1756-OA16I
1756-ON8
DC digital 1756-IB16
1756-IB16D
1756-IB16I
1756-IB16IF
1756-IB16IOSE
1756-IB32
1756-IC16
1756-IG16
1756-IH16I
1756-IH16ISOE
1756-IV16
1756-IV32
1756-OB8
1756-OB8EI
1756-OB8I
1756-OB16D
1756-OB16E
1756-OB16I
1756-OB16IEF
1756-OB16IEFS
1756-OB16IS
1756-OB32
1756-OC8
1756-OG16
1756-OH8I
1756-OV16E
1756-OV32E
Contact 1756-OW16I
1756-OX8I
Analog 1756-IF6CIS
1756-IF6I
1756-IF8
1756-IF8I
1756-IF16
1756-IF4FXOF2F
1756-IR6I
1756-IRT8I
1756-IR12
1756-IT6I
1756-IT6I2
1756-IT16
1756-OF4
1756-OF6CI
1756-OF6VI
1756-OF8
1756-OF8I
HART interface 1756-IF8H
1756-IF8IH
1756-IF16H
1756-OF8H
1756-OF8IH
Specialty 1756-CFM
1756-HSC
1756-LSC8XIB8I
1756-PLS
2 Rockwell Automation Publication 1756-TD002I-EN-E - June 2015
1756-IA8D
ControlLogix 120V AC diagnostic input module
Table 1 - Diagnostic Specifications - 1756-IA8D
Attribute 1756-IA8D
Open wire Off-state leakage current 1.5 mA min
Loss of power Transition range 46…85V AC
Timestamp of diagnostics ±1 ms
Table 2 - Technical Specifications - 1756-IA8D
Attribute 1756-IA8D
Inputs 8 diagnostic (4 points/group)
Voltage category 120V AC 50/60 Hz
Operating voltage range(1) 79…132V AC, 47…63 Hz
Input voltage, nom 120V AC 50/60 Hz
Input delay time (screw to backplane) Off to On
On to Off
Hardware delay: 10 ms max + filter time User-selectable filter time: 1 or 2 ms Hardware delay: 8 ms max + filter time User-selectable filter time: 9 or 18 ms
Current draw @ 5.1V 100 mA
Current draw @ 24V 3 mA
Total backplane power 0.58 W
Power dissipation, max 4.5 W @ 60 °C (140 °F)
+5V
47 kΩ, 1/2 W, 5% Resistor
47 kΩ, 1/2 W 5% Resistor
Not Used
L2-0
L2-0
L2-0
L2-0
L2-1
L2-1
L2-1
L2-1
L2-1
L1-0 Loss of Field Power
IN-0
IN-1
IN-2
IN-3
IN-4
IN-5
IN-6
IN-7
L1-1 Loss of Field Power
Daisy Chain to Other RTBs
Group
Group 0
Group 1Group 1
L2
L1
ControlLogix Backplane Interface
ControlLogix Backplane Interface
Display
Simplified Schematic
Input
Display Open Wire
GND
GND
+5V
AC INPUT
ST
FLT
0 1 2 3 4 5 6 7
0 1 2 3 4 5 6 7 O K
1756-IA8D
Rockwell Automation Publication 1756-TD002I-EN-E - June 2015 3
Thermal dissipation 15.35 BTU/hr
Off-state voltage, max 20V
Off-state current, max 2.5 mA
On-state current, min 5 mA @ 74V AC
On-state current, max 16 mA @ 132V AC
Inrush current, max 250 mA
Input impedance, max 8.25 kΩ @ 132V AC, 60 Hz
Cyclic update time 200 μs…750 ms
Change of state Software configurable
Timestamp of inputs ±200 μs
Isolation voltage 125V (continuous), basic insulation type, inputs-to-backplane, and input group-to-group No isolation between individual group inputs Routine tested @ 1200V AC for 2 s
Module keying Electronic, software configurable
Removable terminal block housing 1756-TBNH
1756-TBSH
RTB keying User-defined mechanical
Slot width 1
Wire category 1(2)
North American temperature code T4A
Enclosure type None (open-style)
(1) UL certification for 120V 50/60 Hz nominal. Rockwell Automation specified to 74…132V, 47…63 Hz.
(2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Table 3 - Environmental Specifications - 1756-IA8D
Attribute 1756-IA8D
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max 60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…85 °C (-40…185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Table 2 - Technical Specifications - 1756-IA8D (Continued)
Attribute 1756-IA8D 4 Rockwell Automation Publication 1756-TD002I-EN-E - June 2015 http://literature.rockwellautomation.com/idc/groups/literature/documents/in/1770-in041_-en-p.pdf
Emissions CISPR 11, Class A
ESD immunity
IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity
IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80… 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity
IEC 61000-4-4
±4 kV at 5 kHz on signal ports
Surge transient immunity
IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity
IEC 61000-4-6
10V rms with 1 Hz sine-wave 80% AM from 150 kHz…80 MHz
Table 4 - Certifications - 1756-IA8D
Certification(1)
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
1756-IA8D
UL UL Listed Industrial Control Equipment. See UL File E65584.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with:
EN 61131-2; Programmable Controllers)
C-Tick Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
Table 3 - Environmental Specifications - 1756-IA8D (Continued)
Attribute 1756-IA8D Rockwell Automation Publication 1756-TD002I-EN-E - June 2015 5 http://www.ab.com
1756-IA16
ControlLogix 120V AC input module
Table 5 - Technical Specifications - 1756-IA16
Attribute 1756-IA16
Inputs 16 (8 points/group)
Voltage category 120V AC 50/60 Hz
Operating voltage range(1) 74…132V AC, 47…63 Hz
Input voltage, nom 120V AC 50/60 Hz
Input delay time (screw to backplane) Off to On
On to Off
Hardware delay: 10 ms max + filter time User-selectable filter time: 1 or 2 ms Hardware delay: 8 ms max + filter time User-selectable filter time: 9 or 18 ms
Current draw @ 5.1V 100 mA
Current draw @ 24V 2 mA
Total backplane power 0.58 W
Power dissipation, max 5.8 W @ 60 °C (140 °F)
Thermal dissipation 18.41 BTU/hr
Off-state voltage, max 20V
Off-state current, max 2.5 mA
On-state current, min 5 mA @ 74V AC
On-state current, max 13 mA @ 132V AC
L2 L1
Daisy Chain to Other RTBs
Group 0
Group 0
Group 1Group 1
IN-1
IN-3
IN-5
IN-7
L2-0
IN-9
IN-11
IN-13
IN-15
L2-1
IN-0
IN-2
IN-4
IN-6
L2-0
IN-8
IN-10
IN-12
IN-14
L2-1
Simplified Schematic
ControlLogix Backplane Interface
Display
+5V
L2-0
IN-O
GND
AC INPUT
ST
FLT
0 1 2 3 4 5 6 7
0 1 2 3 4 5 6 7 O K
1756-IA16
6 Rockwell Automation Publication 1756-TD002I-EN-E - June 2015
Inrush current, max 250 mA peak (decaying to <37% in 22 ms, without activation)
Input impedance, max 10.15 kΩ @ 132V AC, 60 Hz
Cyclic update time 200 μs…750 ms
Change of state Software configurable
Timestamp of inputs ±200 μs
Isolation voltage 125V (continuous), basic insulation type, inputs-to-backplane, and input group-to-group No isolation between individual group inputs Routine tested @ 1400V AC for 2 s
Module keying Electronic, software configurable
Removable terminal block housing 1756-TBNH
1756-TBSH
RTB keying User-defined mechanical
Slot width 1
Wire category 1(2)
North American temperature code T4
Enclosure type None (open-style)
(1) UL certification for 120V 50/60 Hz nominal. Rockwell Automation specified to 74…132V, 47…63 Hz.
(2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Table 6 - Environmental Specifications - 1756-IA16
Attribute 1756-IA16
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max 60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…85 °C (-40…185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions CISPR 11, Class A
ESD immunity
IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity
IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80… 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
Table 5 - Technical Specifications - 1756-IA16 (Continued)
Attribute 1756-IA16 Rockwell Automation Publication 1756-TD002I-EN-E - June 2015 7
EFT/B immunity
IEC 61000-4-4
±4 kV at 5 kHz on signal ports
Surge transient immunity
IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity
IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Oscillatory surge withstand
IEEE C37.90.1
3 kV
Table 7 - Certifications - 1756-IA16
Certification(1)
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
1756-IA16
UL UL Listed Industrial Control Equipment. See UL File E65584.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with:
EN 61131-2; Programmable Controllers
C-Tick Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
KC Korean Registration of Broadcasting and Communications Equipment, compliant with:
Article 58-2 of Radio Waves Act, Clause 3
Table 6 - Environmental Specifications - 1756-IA16 (Continued)
Attribute 1756-IA16 8 Rockwell Automation Publication 1756-TD002I-EN-E - June 2015
1756-IA16I
ControlLogix 120V AC isolated input module
Table 8 - Technical Specifications - 1756-IA16I
Attribute 1756-IA16I
Inputs 16 individually isolated
Voltage category 120V AC 50/60 Hz
Operating voltage range(1) 79…132V AC, 47…63 Hz
Input voltage, nom 120V AC 50/60 Hz
Input delay time (screw to backplane) Off to On
On to Off
Hardware delay: 10 ms max + filter time User-selectable filter time: 1 or 2 ms Hardware delay: 8 ms max + filter time User-selectable filter time: 9 or 18 ms
Current draw @ 5.1V 125 mA
Current draw @ 24V 3 mA
Total backplane power 0.71 W
Power dissipation, max 4.9 W @ 60 °C (140 °F)
Thermal dissipation 16.71 BTU/hr
Off-state voltage, max 20V
Nonisolated Wiring
Isolated Wiring
Daisy Chain to Other RTBs
L2-0 L2-0 L2-1
L2-2
L2-3
L2-8
L2-4
L2-5
L2-6
L2-7
Not Used
L2-9
L2-10
L2-11
L2-12
L2-13 L2-14
L2-15
L2-15
IN-0
IN-1
IN-2
IN-3
IN-8
IN-4
IN-5
IN-6
IN-7
Not Used
IN-9
IN-10
IN-11
IN-12
IN-13
IN-14
IN-15
Not Used
L2-2
L2-4
L2
L1
L1-0
L1-2
L1-4
Jumper Bar (Cut to Length)
ControlLogix Backplane Interface
Display
Simplified Schematic
+5V
L2-0
IN-O
GND
Additional jumper bars are available as cat. no. 1756-JMPR.
ST 0 1 2 3 4 5 6 7
ST 8 9 10 11 12 13 14 15
O K
AC INPUT
1756-IA161
Rockwell Automation Publication 1756-TD002I-EN-E - June 2015 9
Off-state current, max 2.5 mA
On-state current, min 5 mA @ 79V AC, 47…63 Hz
On-state current, max 15 mA @ 132V AC, 47…63 Hz
Inrush current, max 250 mA
Input impedance, max 8.8 kΩ @ 132V AC, 60 Hz
Cyclic update time 200 μs…750 ms
Change of state Software configurable
Timestamp of inputs ±200 μs
Isolation voltage 125V (continuous), basic insulation type, inputs-to-backplane, and input-to-input Routine tested @ 1200V AC for 2 s
Module keying Electronic, software configurable
Removable terminal block housing 1756-TBCH
1756-TBS6H
RTB keying User-defined mechanical
Slot width 1
Wire category 1(2)
North American temperature code T4A
Enclosure type None (open-style)
(1) UL certification for 120V 50/60 Hz nominal. Rockwell Automation specified to 74…132V, 47…63 Hz.
(2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Table 9 - Environmental Specifications - 1756-IA16I
Attribute 1756-IA16I
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max 60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…85 °C (-40…185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions CISPR 11, Class A
ESD immunity
IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Table 8 - Technical Specifications - 1756-IA16I (Continued)
Attribute 1756-IA16I 10 Rockwell Automation Publication 1756-TD002I-EN-E - June 2015
Radiated RF immunity
IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80… 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity
IEC 61000-4-4
±4 kV at 5 kHz on signal ports
Surge transient immunity
IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity
IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Oscillatory surge withstand
IEEE C37.90.1
3 kV
Table 10 - Certifications - 1756-IA16I
Certification(1)
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
1756-IA16I
UL UL Listed Industrial Control Equipment. See UL File E65584.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with:
EN 61131-2; Programmable Controllers
C-Tick Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
KC Korean Registration of Broadcasting and Communications Equipment, compliant with:
Article 58-2 of Radio Waves Act, Clause 3
Table 9 - Environmental Specifications - 1756-IA16I (Continued)
Attribute 1756-IA16I Rockwell Automation Publication 1756-TD002I-EN-E - June 2015 11
1756-IA32
ControlLogix AC (74…132V) input module
Table 11 - Technical Specifications - 1756-IA32
Attribute 1756-IA32
Inputs 32 (16 points/group)
Voltage category 120V AC 50/60 Hz
Operating voltage range 74…132V AC, 47…63 Hz
Input voltage, nom 120V AC 50/60 Hz
Input delay time (screw to backplane) Off to On
On to Off
Hardware delay: 1.5 ms nom/10 ms max + filter time User-selectable filter time: 1 or 2 ms Hardware delay: 1 ms nom/8 ms max + filter time User-selectable filter time: 9 or 18 ms
Current draw @ 5.1V 165 mA
Current draw @ 24V 2 mA
Total backplane power 0.9 W
Power dissipation, max 6.1 W @ 60 °C (140 °F)
Thermal dissipation 20.8 BTU/hr
Off-state voltage, max 20V
Off-state current, max 2.5 mA
On-state current, min 5 mA @ 74V AC
On-state current, max 15 mA @ 132V AC
IN-0
IN-2
IN-4
IN-6
IN-8
IN-10
IN-12
IN-14
IN-16
IN-18
IN-20
IN-22
IN-24
IN-26
IN-28
IN-30
L2-1
L2-0
IN-1
IN-3
IN-5
IN-7
IN-9
IN-11
IN-13
IN-15
L2-0
IN-17
IN-19
IN-21
IN-23
IN-25
IN-27
IN-29
IN-31
L2-1
L1
L2
Daisy Chain to Other RTBs
1 puorG1 puorG
0 puorG0 puorG
Simplified Schematic
ControlLogix Backplane Interface
Display
+5V
L2-0
IN-O
GND
AC INPUT
O K
ST 0 1 2 3 4 5 6 7
ST 8 9
0 21 3 4 5
1 1 1 11
ST 6 7
8 09 1 2 3
1 2 2 221 1
ST 4 5
6 87 9 0 1
2 2 2 332 2
1756-IA32
12 Rockwell Automation Publication 1756-TD002I-EN-E - June 2015
Inrush current, max 390 mA
Input impedance, max 14.0 kΩ @ 132V AC, 60 Hz
Cyclic update time 200 μs…750 ms
Change of state Software configurable
Timestamp of inputs ±200 μs
Isolation voltage 250V (continuous), basic insulation type, inputs-to-backplane 125V (continuous), basic insulation type, input group-to-group No isolation between individual group inputs Routine tested @ 1350V AC for 2 s
Module keying Electronic, software configurable
Removable terminal block housing 1756-TBCH
1756-TBS6H
RTB keying User-defined mechanical
Slot width 1
Wire category 1(1)
North American temperature code T4
Enclosure type None (open-style)
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Table 12 - Environmental Specifications - 1756-IA32
Attribute 1756-IA32
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max 60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…85 °C (-40…185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions CISPR 11, Class A
ESD immunity
IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity
IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80… 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
Table 11 - Technical Specifications - 1756-IA32 (Continued)
Attribute 1756-IA32 Rockwell Automation Publication 1756-TD002I-EN-E - June 2015 13
IEC 61000-4-4
±4 kV at 5 kHz on signal ports
Surge transient immunity
IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity
IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Table 13 - Certifications - 1756-IA32
Certification(1)
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
1756-IA32
UL UL Listed Industrial Control Equipment. See UL File E65584.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with:
EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
KC Korean Registration of Broadcasting and Communications Equipment, compliant with:
Article 58-2 of Radio Waves Act, Clause 3
Table 12 - Environmental Specifications - 1756-IA32 (Continued)
Attribute 1756-IA32 14 Rockwell Automation Publication 1756-TD002I-EN-E - June 2015
1756-IB16
ControlLogix DC (10…31.2V) input module
Table 14 - Technical Specifications - 1756-IB16
Attribute 1756-IB16
Inputs 16 (8 points/group)
Voltage category 12/24V DC sink
Operating voltage range 10…31.2V DC
Input voltage, nom 24V DC
Input delay time (screw to backplane) Off to On
On to Off
Hardware delay: 290 μs nom/1 ms max + filter time User-selectable filter time: 0, 1, or 2 ms Hardware delay: 700 μs nom/2 ms max + filter time User-selectable filter time: 0, 1, 2, 9, or 18 ms
Current draw @ 5.1V 100 mA
Current draw @ 24V 2 mA
Total backplane power 0.56 W
Power dissipation, max 5.1 W @ 60 °C (140 °F)
Thermal dissipation 17.39 BTU/hr
Off-state voltage, max 5V
Off-state current, max 1.5 mA
On-state current, min 2 mA @ 10V DC
On-state current, max 10 mA @ 31.2V DC
IN-9
IN-11
IN-13
IN-15
GND-1
IN-1
IN-3
IN-5
IN-7
GND-0
IN-8
IN-10
IN-12
IN14
GND-1
IN-0
IN-2
IN-4
IN-6
GND-0
Daisy Chain to Other RTBs
Group 0
Group 0
Group 1Group 1
DC COM
ControlLogix Backplane Interface
Simplified Schematic
Display
GND
GND-0
IN-0
+5V
DC INPUT
ST 0 1 2 3 4 5 6 7
ST 8 9 10 11 12 13 14 15
O K
1756-IB16
Rockwell Automation Publication 1756-TD002I-EN-E - June 2015 15
Inrush current, max 250 mA peak (decaying to < 37% in 22 ms, without activation)
Input impedance, max 3.12 kΩ @ 31.2V DC
Cyclic update time 200 μs…750 ms
Change of state Software configurable
Timestamp of inputs ±200 μs
Isolation voltage 250V (continuous), basic insulation type, inputs-to-backplane, and input group-to-group No isolation between individual group inputs Routine tested @ 1350V AC for 2 s
Module keying Electronic, software configurable
Removable terminal block housing 1756-TBNH
1756-TBSH
RTB keying User-defined mechanical
Slot width 1
Wire category 1(1)
North American temperature code T3C
IEC temperature code T3
Enclosure type None (open-style)
Reverse polarity protection Yes
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Table 15 - Environmental Specifications - 1756-IB16
Attribute 1756-IB16
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max 60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…85 °C (-40…185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions CISPR 11, Class A
ESD immunity
IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Table 14 - Technical Specifications - 1756-IB16 (Continued)
Attribute 1756-IB16 16 Rockwell Automation Publication 1756-TD002I-EN-E - June 2015
Radiated RF immunity
IEC 61000-4-3
10V/m with 1kHz sine-wave 80% AM from 80… 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity
IEC 61000-4-4
±4 kV at 5 kHz on signal ports
Surge transient immunity
IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity
IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Oscillatory surge withstand
IEEE C37.90.1
3 kV
Table 16 - Certifications - 1756-IB16
Certification(1)
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
1756-IB16
UL UL Listed Industrial Control Equipment. See UL File E65584.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with:
EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
Ex European Union 94/9/EC ATEX Directive, compliant with:
• EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
• EN 60079-0; General Requirements II 3 G Ex nA IIC T3 X Gc
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
KC Korean Registration of Broadcasting and Communications Equipment, compliant with:
Article 58-2 of Radio Waves Act, Clause 3
Table 15 - Environmental Specifications - 1756-IB16 (Continued)
Attribute 1756-IB16 Rockwell Automation Publication 1756-TD002I-EN-E - June 2015 17
1756-IB16D
ControlLogix DC (10…30V) diagnostic input module
Table 17 - Diagnostic Specifications - 1756-IB16D
Attribute 1756-IB16D
Open wire Off-state leakage current 1.2 mA min
Timestamp of diagnostics ±1 ms
Table 18 - Technical Specifications - 1756-IB16D
Attribute 1756-IB16D
Inputs 16 diagnostic (4 points/group)
Voltage category 12/24V DC sink
Operating voltage range 10…30V DC
Input voltage, nom 24V DC
Leakage Resistor
Leakage Resistor
Daisy Chain to Other RTBs
Group 0
Group 1
Group 2
Group 3
Group
Group
Group
Group
IN-0
IN-1
IN-2
IN-3
IN-8
IN-4
IN-5
IN-6
IN-7
Not Used
IN-9
IN-10
IN-11
IN-12
IN-13
IN-14
IN-15
Not Used
GND-0
GND-0
GND-0
GND-0
GND-2
GND-1
GND-1
GND-1
GND-1
Not Used
GND-2
GND-2
GND-2
GND-3
GND-3
GND-3
GND-3
GND-3
DC COM
ControlLogix Backplane Interface
Simplified Schematic
Display
GND
Open Wire
GND-0
IN-0
Input +5V
FLT 8 9 10 11 12 13 14 15
ST 0 1 2 3 4 5 6 7
ST 8 9 10 11 12 13 14 15
O K
FLT 0 1 2 3 4 5 6 7
DC INPUT
DIAGNOSTIC
Recommended Leakage Resistor Size 1/4 W, 5% Supply Voltage
3.9K 10V DC
5.6K 12V DC
15K 24V DC
20K 30V DC
1756-IB16D
18 Rockwell Automation Publication 1756-TD002I-EN-E - June 2015
Input delay time (screw to backplane) Off to On
On to Off
Hardware delay: 340 μs nom/1 ms max + filter time User-selectable filter time: 0, 1, or 2 ms
Hardware delay: 740 μs nom/4 ms max + filter time User-selectable filter time: 0, 1, 9, or 18 ms
Current draw @ 5.1V 150 mA
Current draw @ 24V 3 mA
Total backplane power 0.84 W
Power dissipation, max 5.8 W @ 60 °C (140 °F)
Thermal dissipation 19.78 BTU/hr
Off-state voltage, max 5V
Off-state current, max 1.5 mA
On-state current, min 2 mA @ 10V DC
On-state current, max 13 mA @ 30V DC
Inrush current, max 250 mA
Input impedance, max 2.31 kΩ @ 30V DC
Cyclic update time 200 μs…750 ms
Change of state Software configurable
Timestamp of inputs ±200 μs
Isolation voltage 250V (continuous), basic insulation type, inputs-to-backplane, and input group-to-group No isolation between individual group inputs Routine tested @ 1350V AC for 2 s
Module keying Electronic, software configurable
Removable terminal block housing 1756-TBCH
1756-TBS6H
RTB keying User-defined mechanical
Slot width 1
Wire category 1(1)
North American temperature code T3C
IEC temperature code T3
Enclosure type None (open-style)
Reverse polarity protection Yes
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Table 18 - Technical Specifications - 1756-IB16D (Continued)
Attribute 1756-IB16D Rockwell Automation Publication 1756-TD002I-EN-E - June 2015 19
Table 19 - Environmental Specifications - 1756-IB16D
Attribute 1756-IB16D
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max 60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…85 °C (-40…185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions CISPR 11, Class A
ESD immunity
IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity
IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80… 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity
IEC 61000-4-4
±4 kV at 5 kHz on signal ports
Surge transient immunity
IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity
IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz 20 Rockwell Automation Publication 1756-TD002I-EN-E - June 2015
Table 20 - Certifications - 1756-IB16D
Certifications(1)
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
1756-IB16D
UL UL Listed Industrial Control Equipment. See UL File E65584.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with:
EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
KC Korean Registration of Broadcasting and Communications Equipment, compliant with:
Article 58-2 of Radio Waves Act, Clause 3
Ex European Union 94/9/EC ATEX Directive, compliant with:
• EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
• EN 60079-0; General Requirements II 3 G Ex nA IIC T3 X Gc
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations Rockwell Automation Publication 1756-TD002I-EN-E - June 2015 21
1756-IB16I
ControlLogix DC (10…30V) isolated input module
1 2
3 4
5 6
7 8
01 9
21 11
41 31
61 51
81 71
02 91
22 12
42 32
62 52
82 72
03 92
23 13
43 33
63 53
Nonisolated Wiring
Isolated Wiring
Daisy Chain to Other RTBs
GND-0
GND-1
GND-2
GND-3
GND-8
GND-4
GND-5
GND-6
GND-7
Not Used
GND-9
GND-10
GND-11
GND-12
GND-13
GND-14
GND-15
GND-15
IN-0
IN-1
IN-2
IN-3
IN-8
IN-4
IN-5
IN-6
IN-7
Not Used
IN-9
IN-10
IN-11
IN-12
IN-13
IN-14
IN-15
Not Used
DC-5 (-)
DC (-)
Jumper Bar (Cut to Length)
DC-6 (-)
DC-5 (+)
DC-6 (+)
DC (+)
DC-0 (+)
DC-1 (+)
DC-0 (-)
DC-1 (-)
Source Input Wiring
Sink Input Wiring
ControlLogix Backplane Interface
Simplified Schematic
Display
GND-0
GND
IN-0
+5V
Additional jumper bars are available as cat. no. 1756-JMPR.
DC INPUT
ST 0 1 2 3 4 5 6 7
ST 8 9 10 1112 13 14 15
O K
1756-IB161
22 Rockwell Automation Publication 1756-TD002I-EN-E - June 2015
Table 21 - Technical Specifications - 1756-IB16I
Attribute 1756-IB16I
Inputs 16 individually isolated
Voltage category 12/24V DC sink/source
Operating voltage range 10…30V DC
Input voltage, nom 24V DC
Input delay time (screw to backplane) Off to On
On to Off
Hardware delay: 1 ms max + filter time User-selectable filter time: 0, 1, or 2 ms Hardware delay: 4 ms max + filter time User-selectable filter time: 0, 1, 2, 9, or 18 ms
Current draw @ 5.1V 100 mA
Current draw @ 24V 3 mA
Total backplane power 0.58 W
Power dissipation, max 5 W @ 60 °C (140 °F)
Thermal dissipation 17.05 BTU/hr
Off-state voltage, max 5V
Off-state current, max 1.5 mA
On-state current, min 2 mA @ 10V DC
On-state current, max 10 mA @ 30V DC
Inrush current, max 250 mA peak (decaying to < 37% in 22 ms, without activation)
Input impedance, max 3 kΩ @ 30V DC
Cyclic update time 200 μs…750 ms
Change of state Software configurable
Timestamp of inputs ±200 μs
Isolation voltage 250V (continuous), basic insulation type, inputs-to-backplane, and input-to-input Routine tested @ 1350V AC for 2 s
Module keying Electronic, software configurable
Removable terminal block housing 1756-TBCH
1756-TBS6H
RTB keying User-defined mechanical
Slot width 1
Wire category 1(1)
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
North American temperature code T4
IEC temperature code T4
Enclosure type None (open-style)
Reverse polarity protection Yes Rockwell Automation Publication 1756-TD002I-EN-E - June 2015 23
Table 22 - Environmental Specifications - 1756-IB16I
Attribute 1756-IB16I
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max 60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…85 °C (-40…185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions CISPR 1, Class A
ESD immunity
IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity
IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80… 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity
IEC 61000-4-4
±4 kV at 5 kHz on signal ports
Surge transient immunity
IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity
IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Oscillatory surge withstand
IEEE C37.90.1
3 kV 24 Rockwell Automation Publication 1756-TD002I-EN-E - June 2015
Table 23 - Certifications - 1756-IB16I
Certification(1)
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
1756-IB16I
UL UL Listed Industrial Control Equipment. See UL File E65584.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with:
EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
Ex European Union 94/9/EC ATEX Directive, compliant with:
• EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
• EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
KC Korean Registration of Broadcasting and Communications Equipment, compliant with:
Article 58-2 of Radio Waves Act, Clause 3 Rockwell Automation Publication 1756-TD002I-EN-E - June 2015 25
1756-IB16IF
ControlLogix DC (10…30V) sinking or sourcing, isolated, fast input module
01 9
21 11
41 31
61 51
81 71
02 91
22 12
42 32
62 52
82 72
03 92
23 13
43 33
63 53
GND-0
GND-1
GND-2
GND-3
GND-4
GND-5
GND-6
GND-7
Not Used
IN-0
IN-1
IN-2
IN-3
IN-4
IN-5
IN-6
IN-7
Not Used Not Used
DC-5 (-)
DC (-)
DC-6 (-)
DC-5 (+)
DC-6 (+)
DC (+)
DC-1 (+)
DC-2 (+)
DC-1 (-)
DC-2 (-)
GND-8
GND-9
GND-10
GND-11
GND-12
GND-13
GND-14
GND-15
GND-15
IN-8
IN-9
IN-10
IN-11
IN-12
IN-13
IN-14
IN-15
Simplified Schematic
ControlLogix Backplane Interface
Display
GND-x
IN-x
1756-IB16IF
Current Limiter
Daisy Chain to Other RTBs
Source Input Wiring
Jumper Bar Cut to Length
Nonisolated Wiring
Isolated Wiring
Sink Input Wiring
Additional jumper bars may be purchased by using catalog number 1756-JMPR.
DC INPUT
PEER DEVICE
O0 1 2 3 4 5 6 7
8 9 10 11 12 13 14 15 K
ST
ST
Opto-isolator 26 Rockwell Automation Publication 1756-TD002I-EN-E - June 2015
Table 24 - Technical Specifications - 1756-IB16IF
Attribute 1756-IB16IF
Inputs 16 individually isolated
Voltage category 12/24V DC sink/source
Operating voltage range 10…30V DC
Input voltage, nom 24V DC
Input delay time (screw to backplane) Off to On On to Off
14 μs nom/23 μs max + user-configurable filter time of 0…30,000 μs 14 μs nom/23 μs max + user-configurable filter time of 0…30,000 μs
Current draw @ 5.1V 275 mA
Current draw @ 24V 3 mA
Total backplane power 1.47 W
Power dissipation 3.8 W @ 60 °C (140 °F)
Thermal dissipation 12.97 BTU/hr
Off-state voltage, max 5V
Off-state current, max 1.5 mA
On-state current, min 2 mA @ 10V DC
On-state current, max 5 mA @ 30V DC
Input impedance, max 6 kΩ @ 30V DC
Cyclic update time 200 μs…750 ms
Change of state Software configurable
Timestamp of inputs ± 4 μs for inputs < 4 kHz ± 13 μs for inputs > 4 kHz
Isolation voltage 250V (continuous), reinforced insulation type, inputs-to-backplane 250V (continuous), basic insulation type, input-to-input Type tested @ 2300V AC for 60 s inputs-to-backplane Type tested @ 1500V AC for 60 s input-to-input
Module keying Electronic, software configurable
Removable terminal block housing 1756-TBCH
1756-TBS6H
RTB keying User-defined mechanical
Slot width 1
Wire category 1 on signal ports(1)
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
North American temperature code T4A
IEC temperature code T4
Enclosure type None (open-style)
Reverse polarity protection Yes Rockwell Automation Publication 1756-TD002I-EN-E - June 2015 27
Table 25 - Environmental Specifications - 1756-IB16IF
Attribute 1756-IB16IF
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max 60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…85 °C (-40…185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions CISPR 1, Class A
ESD immunity
IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity
IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80… 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity
IEC 61000-4-4
±4 kV at 5 kHz on signal ports
Surge transient immunity
IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity
IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz 28 Rockwell Automation Publication 1756-TD002I-EN-E - June 2015
Table 26 - Certifications - 1756-IB16IF
Certification(1)
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
1756-IB16IF
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
CE European Union 2004/108/IEC EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with:
EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
Ex European Union 94/9/EC ATEX Directive, compliant with:
• EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
• EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc
KC Korean Registration of Broadcasting and Communications Equipment, compliant with:
Article 58-2 of Radio Waves Act, Clause 3 Rockwell Automation Publication 1756-TD002I-EN-E - June 2015 29
1756-IB16ISOE
ControlLogix DC (10…55V) sequence of events input module
Table 27 - Technical Specifications - 1756-IB16ISOE
Attribute 1756-IB16ISOE
Inputs 16 individually isolated, sequence of events
Voltage category 24/48V DC sink/source
Operating voltage range 10…55V DC
Input voltage, nom 24V DC
Input delay time (screw to backplane) Off to On
On to Off
Hardware delay: 10 μs nom/20 μs max + firmware scan: up to 25 μs + filter time: 0…50 ms + ASIC delay: 175 μs (FIFO) or 625 μs (Coordinated System Time per point) Hardware delay: 25 μs nom/50 μs max + firmware scan: up to 25 μs + filter time: 0…50 ms + ASIC delay: 175 μs (FIFO) or 625 μs (Coordinated System Time per point)
Current draw @ 5.1V 320 mA
Current draw @ 24V 2 mA
Total backplane power 1.7 W
Power dissipation, max 5.5 W @ 60 °C (140 °F)
Thermal dissipation 17.22 BTU/hr
Nonisolated Wiring
Isolated Wiring
Daisy Chain to Other RTBs
DC (-)
Jumper Bar (Cut to Length)
)+( 6-CD)-( 6-CD
DC (+)
DC-0 (+)
DC-1 (+)
DC-0 (-)
DC-5 (-)
IN-0
IN-1
IN-2
IN-3
IN-8
IN-4
IN-5
IN-6
IN-7
Not Used
IN-9
IN-10
IN-11
IN-12
IN-13
IN-14
IN-15
Not Used
GND-0
GND-1
GND-2
GND-3
GND-8
GND-4
GND-5
GND-6
GND-7
Not Used
GND-9
GND-10
GND-11
GND-12
GND-13
GND-14
GND-15
GND-15
DC-5 (+)
Sink Input Wiring
Source Input WiringSource Input Wiring
Sink Input WiringControlLogix Backplane
Interface
Simplified Schematic
Display
GND-0
IN-0
Electronic Current Limit Circuit
+5V
Additional jumper bars are available as cat. no. 1756-JMPR.
SOE INPUT
ST 0 1 2 3 4 5 6 7
ST 8 9 10 11 12 13 14 15
O K
1756-IB16ISOE
30 Rockwell Automation Publication 1756-TD002I-EN-E - June 2015
Off-state voltage, max 5V
Off-state current, max 1.5 mA
On-state current, min 2.0 mA @ 9V DC
On-state current, nom 4.5 mA @ 24…31V DC
On-state current, max 5.1 mA @ 48…55V DC
Input impedance, max 10.8 kΩ @ 55V DC
Cyclic update time 200 μs…750 ms
Change of state Software configurable
Timestamp of inputs ±100 μs
Isolation voltage 250V (continuous), basic insulation type, inputs-to-backplane 125V (continuous), basic insulation type, input-to-input Routine tested @ 1350V AC for 2 s
Module keying Electronic, software configurable
Removable terminal block 1756-TBCH
1756-TBS6H
RTB keying User-defined mechanical
Slot width 1
Wire category 1(1)
North American temperature code T4
IEC temperature code T4
Enclosure type None (open-style)
Reverse polarity protection Yes
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Table 28 - Environmental Specifications - 1756-IB16ISOE
Attribute 1756-IB16ISOE
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max 60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…85 °C (-40…185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Table 27 - Technical Specifications - 1756-IB16ISOE (Continued)
Attribute 1756-IB16ISOE Rockwell Automation Publication 1756-TD002I-EN-E - June 2015 31
Emissions CISPR 11, Class A
ESD immunity
IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity
IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80… 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity
IEC 61000-4-4
±4 kV at 5 kHz on signal ports
Surge transient immunity
IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity
IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Oscillatory surge withstand
IEEE C37.90.1
2.5 kV
Table 29 - Certifications - 1756-IB16ISOE
Certification(1)
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
1756-IB16ISOE
UL UL Listed Industrial Control Equipment. See UL File E65584.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with:
EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
Ex European Union 94/9/EC ATEX Directive, compliant with:
• EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
• EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc
KC Korean Registration of Broadcasting and Communications Equipment, compliant with:
Article 58-2 of Radio Waves Act, Clause 3
Table 28 - Environmental Specifications - 1756-IB16ISOE (Continued)
Attribute 1756-IB16ISOE 32 Rockwell Automation Publication 1756-TD002I-EN-E - June 2015
1756-IB32
ControlLogix DC (10…31.2V) input module
Table 30 - Technical Specifications - 1756-IB32
Attribute 1756-IB32
Inputs 32 (16 points/group)
Voltage category 12/24V DC sink
Operating voltage range 10…31.2V DC
Input voltage, nom 24V DC
Input delay time (screw to backplane) Off to On
On to Off
Hardware delay: 380 μs max + filter time User-selectable filter time: 0, 1, or 2 ms Hardware delay: 420 μs max + filter time User-selectable filter time: 0, 1, 2, 9, or 18 ms
Current draw @ 5.1V 120 mA
Current draw @ 24V 2 mA
Total backplane power 0.66 W
Power dissipation, max 6.2 W @ 60 °C (140 °F)
Thermal dissipation 21.1 BTU/hr @ 60 °C (140 °F)
Off-state voltage, max 5V
Off-state current, max 2.27 mA
On-state current, min 4.8 mA @ 10V DC
On-state current, max 5.5 mA @ 31.2V DC
Inrush current, max 250 mA (decaying to < 37% in 22 ms, without activation)
Daisy Chain to Other RTBs
DC COM
0 puorG0 puorG
1 puorG1 puorG
IN-1
IN-3
IN-5
IN-7
GND-0
IN-9
IN-11
IN-13
IN-15
GND-1
IN-17
IN-19
IN-21
IN-23
IN-25
IN-27
IN-29
IN-31
IN-0
IN-2
IN-4
IN-6
GND-0
IN-8
IN-10
IN-12
IN-14
GND-1
IN-16
IN-18
IN-20
IN-22
IN-24
IN-26
IN-28
IN-30
ControlLogix Backplane Interface
Simplified Schematic
Display
GND-0
GND
IN-0
+5V
DC INPUT
O K
ST 0 1 2 3 4 5 6 7
ST 8 9
0 21 3 4 5
1 1 1 11
ST 6 7
8 09 1 2 3
1 2 2 221 1
ST 4 5
6 87 9 0 1
2 2 2 332 2
Current Limiter
1756-IB32
Rockwell Automation Publication 1756-TD002I-EN-E - June 2015 33
Input impedance, max 5.67 kΩ @ 31.2V DC
Cyclic update time 200 μs…750 ms
Change of state Software configurable
Timestamp of inputs ±200 μs
Isolation voltage 250V (continuous), reinforced insulation type, inputs-to-backplane 250V (continuous), basic insulation type, input group-to-group No isolation between individual group inputs Routine tested @ 1350V AC for 2 s
Module keying Electronic, software configurable
Removable terminal block 1756-TBCH
1756-TBS6H
RTB keying User-defined mechanical
Slot width 1
Wire category 1 - on signal ports(1)
North American temperature code T4
IEC temperature code T4
Enclosure type None (open-style)
Reverse polarity protection Yes
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual.