TARTA_TASK8_-_Transit_Hub_Elevator_Addition_-_Dwgs.pdf
PDF 11 MB Posted
- Attached to
- Transit Hub Elevator Addition
- Solicitation number
- 2026-REQ-071
- Issued by
- Lucas County, Ohio
About this file
This is a set of architectural and engineering drawings for the Transit Hub Elevator Addition project at the Toledo Area Regional Transit Authority (TARTA) facility located at 612 N. Huron Street, Toledo, Ohio 43604. The project scope includes the addition of a new passenger elevator on the exterior of the building to provide accessibility to all building levels and the demolition of an exterior loading area. The elevator addition will be approximately 74 square feet and connect basement, first floor, and roof parking levels. The project team includes Richard L. Bowen & Associates Inc. as the architect, DGL Consulting Engineers LLC as the structural and survey engineer, and Heapy Engineering as the electrical, plumbing, and mechanical engineer. The drawing set is dated July 31, 2026 for the bid set phase and includes comprehensive plans covering architectural, structural, plumbing, mechanical, and electrical systems across multiple floor levels.
The project must comply with the 2024 Ohio Building Code, 2024 Ohio Existing Building Code, 2024 Ohio Mechanical Code, 2024 Ohio Plumbing Code, 2023 NFPA 70 National Electrical Code, 2017 Ohio Fire Code, and relevant accessibility standards including ICC A117.1 and ASME A17.1/CSA B44 elevator standards. The building is classified as Type IB construction with a gross building area of 100,495 square feet in the Downtown Commercial zoning district. The existing structure includes moderate-hazard storage on the basement level, business use with accessory assembly on the first floor, and low-hazard storage on the roof parking level. All existing conditions must be verified prior to commencement of work, and all existing utilities must be located before starting any excavation or digging operations.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TARTA
612 N. HURON ST,
TOLEDO, OH 43604
419.243.7433 (PH)
CONTACT PERSON: KATTIE BOND
RICHARD L. BOWEN & ASSOCIATES INC.
2019 CENTER STREET, SUITE 500
CLEVELAND, OHIO 44113
216.389.2156 (PH)
CONTACT PERSON: KEN EMLING
STRUCTURAL ENGINEER
ARCHITECT
OWNER
DGL CONSULTING ENGINEERS, LLC
6060 ROCKSIDE WOODS BLVD N, SUITE 317
INDEPENDENCE, OH 44131
440.527.1202 (PH)
CONTACT PERSON: KYLE LAYTON
ELECTRICAL ENGINEER
HEAPY ENGINEERING
1422 EUCLID AVE. STE 1162
CLEVELAND, OH 44115
216.862-5846 (PH)
CONTACT PERSON: TIM KRZYWICKI
SURVEY ENGINEER
DGL CONSULTING ENGINEERS, LLC
6060 ROCKSIDE WOODS BLVD N, SUITE 317
INDEPENDENCE, OH 44131
440.527.1202 (PH)
CONTACT PERSON: KYLE LAYTON
PLUMBING ENGINEER
HEAPY ENGINEERING
1422 EUCLID AVE. STE 1162
CLEVELAND, OH 44115
216.862.5846 (PH)
CONTACT PERSON: TIM KRZYWICKI
MECHANICAL ENGINEER
HEAPY ENGINEERING
1422 EUCLID AVE. STE 1162
CLEVELAND, OH 44115
216.862-5846 (PH)
CONTACT PERSON: TIM KRZYWICKI
1. ALL EXISTING CONDITIONS TO BE VERIFIED PRIOR TO COMMENCEMENT OF WORK. IN
THE EVENT OF ANY DISCREPANCIES, REPORT SAID ANOMALIES TO THE ARCHITECT.
2. LOCATE ALL EXISTING UTILITIES AND SERVICES PRIOR TO START OF WORK.
3. DO NOT SCALE DRAWINGS. NOTIFY ARCHITECT FOR ALL DIMENSION QUESTIONS.
4. DIMENSIONS ARE FROM THE FACE OF MASONRY FOR MASONRY WALLS, U.N.O.
5. FOR GYPSUM WALLS, DIMENSIONS ARE TO FACE OF GYPSUM BOARD, U.N.O.
6. FOR EXISTING WALLS, DIMENSIONS ARE TO EXISTING WALL FACE, U.N.O.
7. DIMENSIONS WITH “HOLD, MIN, MAX, CLEAR” ARE TO FINISHED FACE, U.N.O.
UNDERGROUND UTILITIES
TWO WORKING DAYS BEFORE DIGGING CALL #800-362-2764 (TOLL FREE). OHIO UTILITIES
PROTECTION SERVICE . NON-MEMBERS MUST BE CALLED DIRECTLY
ISSUES AND REVISIONS
DateNo.
NOTICE
THIS ARCHITECTURAL AND
ENGINEERING DRAWING IS GIVEN
IN CONFIDENCE. NO USE OR
DISSEMINATION MAY BE MADE
WITHOUT PRIOR WRITTEN
CONSENT OF THE ARCHITECT.
ALL RIGHTS ARE HEREBY
SPECIFICALLY RESERVED.
DRAWING NO.
RLB NO.:
CHECKED BY:
DRAWN BY:
Description
C en te r
S t, S ui te
C le ve la nd
O hi o
P ho ne
(2
1-
F ax
6)
-8 w w w .r lb a.
co m
© 2026 RICHARD L. BOWEN + ASSOCIATES, INC.
E
LE
V A
T O
R A
D D
IT
IO
N
8/
/2
4:
:5
P
M A ut od es k
D oc s:
//T
A R
T A
D ow nt ow n
T ra ns it
H ub
/A R
C H
_T A
R T
A -D ow nt ow n
T ra ns it
H ub
_1
-0
8.
rv t
- ELEVATOR ADDITION
T A
R T
A D
O W
N T
O W
N T
R A
N S
IT
H
U B
13828.8
N . H
U R
O N
S T
T
O
LE
D O
, O H
C O
V E
R S
H E
E T
NP
DJK & SS
CS
JULY 31, 2026
612 N. HURON ST., TOLEDO, OH 43604BID SET
DRAWING INDEX
NUMBER NAME
GENERAL
CS COVER SHEET
CODE AND LIFE SAFETY
AG0.1 ABBREVIATIONS, SYMBOLS, LEGENDS, AND CODE DATA
AG1.1 LIFE SAFETY PLAN - BASEMENT
AG1.2 LIFE SAFETY PLAN - FIRST FLOOR
AG2.1 LIFE SAFETY PLAN - ROOF
ARCHITECTURAL
AD1.1 ENLARGED DEMOLITION PLANS
A0.1 PARTITION SCHEDULE AND DETAILS
A1.1 OVERALL FLOOR PLAN - BASEMENT
A1.2 OVERALL FLOOR PLAN - FIRST FLOOR
A2.1 OVERALL ROOF PLAN
A5.1 WALL AND PARTIAL BUILDING SECTIONS
A6.1 DOOR AND FENESTRATION ELEVATION, SCHEDULE, AND DETAILS
A7.1 ENLARGED ELEVATOR PLANS, ELEVATIONS, AND DETAILS
A7.2 ELEVATOR PLAN AND SECTION DETAILS
A9.0 INTERIOR FINISHES PLAN, ELEVATION, SCHEDULE AND DETAILS
STRUCTURAL
S0.1 STRUCTURAL NOTES AND SPECIFICATIONS
S1.1 ELEVATOR FOUNDATION & BASEMENT PLANS
S1.2 ELEVATOR FIRST FLOOR WALL PANS
S1.3 ELEVATOR PARKING LEVEL AND ROOF PLANS
S2.1 ELEVATOR SHAFT MASONRY ELEVATIONS
S5.1 CONCRETE AND MASONRY DETAILS
PLUMBING
P0.1 PLUMBING LEGEND, INDEX & GENERAL NOTES
P0.2 PLUMBING SCHEDULES, DETAILS, AND DIAGRAMS
P2.1 PLUMBING PLAN - BASEMENT - NEW WORK
P2.2 PLUMBING PLAN - FIRST FLOOR - NEW WORK
GENERAL PROJECT NOTES INDEX OF DRAWINGSSITE LOCATION MAP
PROJECT SITE
PROJECT TEAM
DRAWING INDEX
NUMBER NAME
MECHANICAL
M0.1 MECHANICAL LEGEND, INDEX & GENERAL NOTES
M0.2 MECHANICAL SCHEDULES
M2.3 MECHANICAL PLAN - ROOF - NEW WORK
ELECTRICAL
E0.1 ELECTRICAL LEGEND, INDEX & GENERAL NOTES
E0.5 ELECTRICAL DETAILS
E2.1 ELECTRICAL BASEMENT FLOOR LIGHTING PLAN - NEW WORK
E3.1 ELECTRICAL BASEMENT FLOOR POWER & SYSTEMS PLAN - NEW WORK
E3.3 ELECTRICAL ROOF FLOOR POWER & SYSTEM PLAN - NEW WORK
07/17/26 OWNER REVIEW
08/31/26 BID SET
TARTA DOWNTOWN TRANSIT HUB
ALIGN
NOTE: THIS LEGEND DOES NOT ASSUME THAT
ALL ABBREVIATIONS ARE USED.
RFG
PNL
PLAM
PERIM
RWC
MOULD
REQ
P/L
MAX
MFR
MATL
MECH
MAINT
MIN
MET
MTD
NOM
NTS
NO.
NIC
ORD
OPP
OPNG
PLS
PTD
PLBG
PART'N
PLYWD
PROJ
RAD
R/W
REP
REINF
RECT
REBAR
CT
CORR
CPT
CRS
DIA
DIM
DF
DS
DP
DR
DN
DBL
DEM
DET
EF
EL
EA
ENCL
EL
ELEC
DWG
E.J.
LIN
IRWC
INTMD
HDWD
INT
JAN
INV
INSUL
LAV
LAM
LLH
LLV
HVAC
HORIZ
HM
DEEP
ENCLOSED (SURE)
EXPANSION JOINT
EACH FACE
ELEVATION
ELEVATOR
ELECTRICAL
DOOR
DETAIL
EACH
DRAWING
LF
JB
JT
DRINKING FOUNTAIN
DEMISING
DIAMETER
DIMENSION
DOWN SPOUT
DOWN
DOUBLE
CERAMIC TILE
CORRIDOR
CARPET TILE
COURSE
ID
HR
IMPACT RESISTANT WALLCOVERING
LONG LEG HORIZONTAL
LONG LEG VERTICAL
LAMINATED
LINOLEUM
LAVATORY
LINEAR FEET
JANITOR
JUNCTION BOX
JOINT
AIR CONDITIONING
HEATING, VENTILATING,
INTERMEDIATE
INTERIOR
INVERT
INSULATION
INSIDE DIAMETER
HARDWOOD
HOUR
HORIZONTAL(LY)
HOLLOW METAL
RM
RD
CCT
CAR
C/L
ACOUST
AB
ACT
A/C
BM
BRG
APPROX
ARCH
ALUM
BLDG
BLKG
AFF
ALT
ADJ
CBB
COL
CLG
CLO
CMU
C/C
C/L
BTM
BUR
CONC
CONF
CONST
CONT
CONTR
BR
CJ
L
X
FOLDING DOORFLDR
GFCMU
GLCMU
GLB
GWB
FTG
FRTW
FSS
HDWE
GYPLS
GALV
CENTER LINE
CUBICLE CURTAIN TRACK
CARPET (ROLL GOODS/BROADLOOM)
CEMENTITIOUS BACKER BOARD
CONCRETE MASONRY UNIT
COLUMN
CONCRETE
CONFERENCE
CONSTRUCTION
CONTINUOUS
CONTRACTOR
CEILING
CLOSET
H
HD
HC
GL
CONSTRUCTION JOINT
CENTER TO CENTER
BUILT UP ROOFING
BOTTOM
CENTER LINE
BEAM
BEARING
BUILDING
BLOCKING
BRICK
GA
GB
GC
FR
FM
FT
GROUND FACE CONCRETE
MASONRY UNITS
MASONRY UNITS
GLAZED FACE CONCRETE
GYPSUM WALL BOARD
GYPSUM PLASTER
HIGH, HEIGHT
HAND DRYER
HANDICAPPED
HARDWARE
GLASS BLOCK
GLASS, GLAZING
PT
QT
PR
FACTORY MUTUAL
FIRE RETARDANT TREATED WOOD
FOLDING SHOWER SEAT
GENERAL CONTRACTOR
FOOTING
GAUGE
GRAB BAR
GALVANIZED
FIRE RATED
FOOT
PL
OC
OD
FIXT
EQUIP
ETC
EW
FHC
FEC
EWC
EXT
EXIST
FIN
ACOUSTICAL CEILING TILE
AIR CONDITION(ER) (ING)
ABOVE FINISHED FLOOR
APPROXIMATELY
ARCHITECTURAL
ALUMINUM
ALTERNATE
ADJUSTABLE
ACOUSTICAL
ANCHOR BOLT
NUMBER
FH
FL
FE
FD
ANGLE
AND
AT
BY
EQ
FIRE EXTINGUISHER
FIRE HOSE CABINET
FIRE EXTINGUISHER CABINET
ELECTRIC WATER COOLER
FIXTURE
FIRE HYDRANT
FINISH
FLOOR
FLOOR DRAIN
EXTERIOR
EXISTING
MO
MH
EQUAL
EQUIPMENT
ET CETERA
EACH WAY
M
WPT
W/O
WWF
RECESSED FOOT GRILLE
RAIN WATER CONDUCTOR
REINFORCING BAR
RIGHT-OF-WAY
ROOM
REQUIRED
ROOF DRAIN
REPRESENTATIVE
REINFORCEMENT
RECTANGULAR
WC
W/
WR
WD
WOOD - PRESERVATIVE TREATED
WASTE RECEPTACLE
WELDED WIRE FABRIC
WATER CLOSET
WITHOUT
WOOD
WITH
STORAGE
NOT TO SCALE
STOR
SUSP
TEMP
T/BM
SUPPL
STRUCT
T&G
THR
TKBD
T/JST
TOM
TOS
T/ST
UNO
VEST
VERT
PLASTIC LAMINATE
PAINTED (PAINTED FINISH)
PRESSURE TREATED
QUARRY TILE
PLYWOOD
RADIUS
PANEL
PLASTER
PLUMBING
PROJECT
PAIR
VCT
V
TYP
TTD
OUTSIDE DIAMETER
OVERFLOW ROOF DRAIN
PERIMETER
PROPERTY LINE
PLATE
PARTITION
ON CENTER
OPPOSITE
OPENING
SVT
SV
TACK BOARD
TOP OF MASONRY
TOILET TISSUE DISPENSER
UNLESS NOTED OTHERWISE
VINYL COMPOSITION TILE
VINYL
VESTIBULE
VERTICAL
TOP OF SLAB
TYPICAL
TOP OF STEEL
TONGUE AND GROOVE
TEMPERED
TOP OF BEAM
THRESHOLD
TOP OF JOIST
SOLID VINYL TILE
SHEET VINYL
SUSPENDED
SUPPLEMENTARY
STRUCTURAL
SRGB
SOG
SFCMU
SGB
SPEC
S/H
NOT IN CONTRACT
MASONRY OPENING
NOMINAL
NUMBER
MOULDING
MOUNTED
MANUFACTURER
MECHANICAL
MINIMUM
METAL
MANHOLE
SQ
STC
SS
STL
STD
SK
SIM
MIRROR
MAXIMUM
MATERIAL
MAINTENANCE
SF
SC
SAG-RESISTANT GYPSUM BOARD
STRUCTURAL GLAZED BLOCK
SOUND TRANSMISSION CLASS
SQUARE
STAINLESS STEEL
STEEL
STANDARD
SLAB ON GRADE
MASONRY UNITS
SIMILAR
SPECIFICATIONS
SINK
SPLIT FACE CONCRETE
SEALER/HARDENER
SQUARE FOOT
SOLID CORE
AHJ AUTHORITY HAVING JURISDICTION
O OF
F.O.M. FACE OF MASONRY
FND FOUNDATION
RO ROUGH OPENING
RCP REFLECTED CEILING PLAN
ELEV ELEVATION
VIF VERIFY IN FIELD
E.T.R. EXISTING TO REMAIN
EARTH (UNDISTURBED)
EARTH (COMPACT FILL)
CONCRETE
STONE/GRAVEL FILL
CONCRETE MASONRY UNIT (CMU)
STEEL
SOLID WOOD
RIGID INSULATION
ALUMINUM
BRICK
GYPSUM WALL BOARD
NOT IN CONTRACT
RIVER ROCK
STUCCO
FINISH WOOD
EXISTING CONSTRUCTION
CMU - SOLID
CMU - HOLLOW
PLYWOOD
ACOUSTIC CEILING TILE
CONTINUOUS WOOD FRAMING
WOOD BLOCKING
BATT INSULATION
CELULAR INSULATION
INTERIOR ELEVATION
EXTERIOR ELEVATION
ROOM FINISH TAG
(SEE FINISH PLANS)
KEYNOTE
WINDOW/GLAZING TAG
CEILING TAG
(SEE RCP's)
ALIGN GEOMETRY
DOOR TAG
(SEE FLOOR PLANS)
BUILDING SECTION
WALL SECTION
DETAIL SECTION
DETAIL REFERENCE
VIEW #
SHEET #
SHEET #
VIEW #
SHEET #
VIEW #
SHEET #
VIEW #
ENLARGED PLAN /
DETAIL CALLOUT
VIEW #
SHEET #
SHEET #
VIEW #
SHEET #
VIEW #
STRUCTURAL LEVELS
EXISTING
GRID HEAD
NEW
GRID HEAD
Level 1
0' - 0"
LEVEL NAME
ELEVATION
DEMOLITION NOTE
(SEE DEMOLITION PLANS)
PROJECT
NORTH
TRUE
NORTH
NORTH ARROW
CEILING
TYPE
CEILING
HEIGHT
WALL TAG
(SEE FLOOR PLANS)
WALL TYPE
FIRE RATING
ROOM TAG
(SEE FLOOR PLANS)
DESCRIPTION
SPEC REFERENCE
STRUCTURAL GRIDS
SHEET #
VIEW #
DOOR #
EXTERIOR MATERIAL TAG
(SEE EXTERIOR ELEVATIONS)
ROOM
NAME
ROOM
NUMBER AREA
(IF APPLCABLE)
IGNORE (INTERNAL USE ONLY)
FLOORING TRANSITION TAG
(SEE FINISH PLANS)
FLOORING
TYPE
W
F
B
ROOM
NUMBER
WALLS
BASE
FLOOR
ROOM NAME
INTERIOR MATERIAL TAG
(SEE INTERIOR ELEVATIONS)??-#
EQUIPMENT / ACCESSORY
TAG??-#
SIGNAGE TAG
(SEE SIGNAGE PLANS)SN-#
SCOPE WILL INCLUDE THE ADDITION OF NEW PASSENGER ELEVATOR AT THE EXTERIOR TO PROVIDE ACCESSIBILITY TO ALL
BUILDING LEVELS AND DEMOLITION OF AN EXTERIOR LOADING AREA.
GENERAL AND BUILDING AREA
APPLICABLE CODE:
2024, OHIO BUILDING CODE
2024 OHIO EXISTING BUILDING CODE
2024 OHIO BUILDING CODE
2024 OHIO MECHANICAL CODE
2024 OHIO PLUMBING CODE
2023 NFPA 70 (NATIONAL ELECTRICAL CODE)
2017 OHIO FIRE CODE
2017 IECC (INTERNATIONAL ENERGY CONSERVATION CODE)
2017 ICC A117.1 ACCESSIBILITY AND USABLE BUILDINGS AND FACILITIES
ASME A17.1/CSA B44, ASME A17.7/CSA B44.7 (ELEVATOR)
PARCEL ID AND AREA 154-4184 (612 N. HURON ST. TOLEDO) – GROSS BUILDING AREA (GBA) 100,495 SF
ZONING CD (10CD) - DOWNTOWN COMMERCIAL, MARKET AREA 2006C
USE AND OCCUPANCY
(OBC CHAPTER 3)
BASEMENT LEVEL: MODERATE-HAZARD STORAGE (S-1)
FIRST FLOOR: BUSINESS (B) WITH ACCESSORY ASSEMBLY (A-3) SPACES
ROOF PARKING: LOW-HAZARD STORAGE (S-2)
NO CHANGE, EXISTING TO REMAIN.
CONSTRUCTION
CLASSIFICATION
(OBC 602)
TYPE IB.
EXISTING; NO CHANGE. EXTERIOR WALL ASSEMBLIES WILL MATCH EXISTING.
MEANS OF EGRESS
(CHAPTER 10)
180 FEET MAXIMUM ALLOWABLE (SPRINKLERED).
26' - 5" EXISTING / 38' - 5" PROPOSED AT ELEVATOR HOISTWAY ONLY.
BUILDING FLOOR AREA
(OBC TABLE 506.2)
UNLIMITED. ELEVATOR ADDITION: 74 SF
FIRE-RESISTANT RATINGS
(TABLE 601)
TYPE IB
PRIMARY STRUCTURE: 2-HOUR REQUIRED EXISTING TO REMAIN.
BEARING WALL, EXTERIOR: 2-HOUR REQUIRED N/A
BEARING WALL, INTERIOR: 2-HOUR REQUIRED N/A
NON-BEARING WALL, INTERIOR: 0-HOUR REQUIRED 0-HOUR PROVIDED
FLOOR CONSTRUCTION: 2-HOUR REQUIRED EXISTING TO REMAIN.
ROOF CONSTRUCTION: 1-HOUR REQUIRED 1-HOUR PROVIDED
2024 OHIO EXISTING BUILDING CODE
PRESCRIPTIVE COMPLIANCE METHOD
THE PROJECT WILL COMPLY WITH THE PRESCRIPTIVE COMPLIANCE METHOD WHERE
SECTIONS 302 THROUGH 309 AND APPLICABLE SECTIONS OF CHAPTER 5 WILL APPLY FOR
ADDITIONS.
APPLICABILITY
(301.3, 301.3.1)
EXISTING MATERIALS
(302.3)
MATERIALS ALREADY IN USE IN A BUILDING IN COMPLIANCE WITH REQUIREMENTS OR
APPROVALS IN EFFECT AT THE TIME OF THEIR ERECTION OR INSTALLATION SHALL BE
PERMITTED TO REMAIN IN USE UNLESS DETERMINED BY THE BUILDING OFFICIAL TO
BE UNSAFE.
COMPLIES. ABATEMENT WILL BE CONDUCTED FOR INSULATION THAT MAY CONTAIN
ASBESTOS.
NEW AND REPLACED
MATERIALS
(302.4)
EXCEPT AS OTHERWISE REQUIRED OR PERMITTED BY THIS CODE, MATERIALS PERMITTED
BY THE APPLICABLE CODE FOR NEW CONSTRUCTION SHALL BE USED. LIKE MATERIALS
SHALL BE PERMITTED FOR REPAIRS AND ALTERATIONS, PROVIDED THAT UNSAFE
CONDITIONS ARE NOT CREATED. HAZARDOUS MATERIALS SHALL NOT BE USED WHERE THE
CODE FOR NEW CONSTRUCTION WOULD NOT PERMIT THEIR USE IN BUILDINGS OF SIMILAR
OCCUPANCY, PURPOSE AND LOCATION.
COMPLIES. NEW AND REPLACED MATERIALS ARE NON-HAZARDOUS
NEW STRUCTURAL
MEMBERS AND
CONNECTIONS
(302.4.1)
NEW STRUCTURAL MEMBERS AND CONNECTIONS SHALL COMPLY WITH THE DETAILING
PROVISIONS OF THE BUILDING CODE FOR NEW BUILDINGS OF SIMILAR STRUCTURE,
PURPOSE AND LOCATION.
COMPLIES. MODIFICATIONS TO STRUCTURE WHERE ADDITION OCCURS IS NOTED ON
THE STRUCTURAL DRAWINGS AND WILL BE REQUIRED TO MEET CURRENT CODE. REFER
STRUCTURAL DWGS.
ADDITIONS
(306.6)
COMPLIES. THE NEW ELEVATOR AND ITS COMPONENTS WILL BE ACCESSIBLE. THE
ELEVATOR DOES NOT AFFECT ACCESSIBILITY TO A PRIMARY FUNCTION. ALL OTHER
ELEVATORS ARE EXISTING TO REMAIN.
ACCESSIBLE MEANS OF
EGRESS
(306.7.2)
COMPLIES. THE WORK DOES NOT INCLUDE ANY ADDITION OF MEANS OF EGRESS. ALL
MEANS OF EGRESS ARE EXISTING TO REMAIN.
MAINTENANCE AND
REPAIRS
(306.3)
COMPLIES. GIVEN THE FOOTPRINT AT THE EXTERIOR WALL, THE WORK DOES NOT AFFECT
EXISTING ACCESSIBILITY OR MEANS OF EGRESS. THE CONTRACTOR WILL BE REQUIRED TO
MAINTAIN ACCESSIBLE MEANS OF EGRESS FOR WORKERS DURING DEMOLITION AND NEW
WORK.
ADDITIONS AND
REPLACEMENTS
(309.2)
COMPLIES. SEE REFERENCES TO CHAPTERS 14 AND 26 BELOW.
2024 OHIO BUILDING CODE
TYPE I CONSTRUCTION
(OBC 503.1.3)
BUILDINGS OF TYPE I CONSTRUCTION PERMITTED TO BE OF UNLIMITED TABULAR BUILDING
HEIGHTS AND AREAS ARE NOT SUBJECT TO THE SPECIAL REQUIREMENTS THAT ALLOW
UNLIMITED AREA BUILDINGS IN SECTION 507 OR UNLIMITED BUILDING HEIGHT IN SECTIONS
503.1.1 AND 504.3 OR INCREASED BUILDING HEIGHTS AND AREAS FOR OTHER TYPES OF
CONSTRUCTION.
BUILDING HEIGHT
(OBC TABLE 504.3)
VERTICAL OPENING
(712)
WHERE EXTERIOR WALLS SERVE AS A PART OF A REQUIRED SHAFT ENCLOSURE, SUCH
WALLS SHALL COMPLY WITH THE REQUIREMENTS OF SECTION 705 FOR EXTERIOR WALLS
AND THE FIRE-RESISTANCE-RATED ENCLOSURE REQUIREMENTS SHALL NOT APPLY.
FIRE RESISTANCE
RATING
(713.4)
SHAFT ENCLOSURE FIRE RATING WHERE CONNECTING LESS THAN FOUR STORIES
1 HR REQUIRED / 1 HR PROVIDED.
EXTERIOR WALLS
FIRE-RESISTANCE
(TABLE 705.5)
FIRE-SEPARATION DISTANCE (18' - 7") IS GREATER THAN 10 AND LESS THAN 30
1 HR REQUIRED / 1 HOUR PROVIDED
MAX AREA OF EXTERIOR
WALL OPENING
(TABLE 705.8)
75% ALLOWABLE (UP, S)
NEW EXTERIOR UNPROTECTED OPENING AT ELEVATOR ADDITION = 18.38 SF (1.87% OF NEW
EXTERIOR WALL)
CONTINUITY
(713.5)
JOINT AT SHAFT ENCLOSURE SHALL BE CONTINUOUS WITH EXISTING RATED FLOOR.
ENCLOSURE AT TOP
(713.12)
TOP OF SHAFT ENCLOSURE EXTENDS TO THE UNDERSIDE OF ROOF DECK. ROOF DECK
COMPLIES WITH IB CONSTRUCTION.
OPENING FIRE
PROTECTION
ASSEMBLIES, RATINGS
AND MARKINGS
(TABLE 716.1 (2))
MIN FIRE DOOR AND FIRE SHUTTER ASSEMBLY
1 HR REQUIRED / 1 HR PROVIDED.
FIRE & SMOKE PROTECTION FEATURES
(CHAPTER 7)
FIRE PROTECTION RATINGS
(CHAPTER 6)
ACCESSIBILITY FOR
EXISTING BUILDINGS
(306.1)
COMPLIES. THE ELEVATOR IS DESIGNED TO BE ACCESSIBLE IN ACCORDANCE WITH THE
APPLICABLE SECTIONS OF THIS CODE AND THE APPLICABLE SECTIONS OF THE ICC A117.1
STANDARD REFERENCED IN CHAPTER 16 AND ASME A17.1/CSA B44, ASME A17.7/CSA B44.7
ELEVATORS
(306.7.7)
COMPLIES. THE WORK INCLUDES A NEW ELEVATOR THAT COMPLIES WITH ASME A17.1/CSA
B44, ASME A17.7/CSA B44.7
ADDITIONS
(CHAPTER 5)
COMPLIANCE METHODS
(CHAPTER 3)
GENERAL
(502.1)
COMPLIES. SEE REFERENCES TO REQUIREMENTS OF THE BUILDING CODE FOR NEW
CONSTRUCTION BELOW.
NOT EXCEEDING
ALLOWABLE HEIGHT
(502.1.2.2)
COMPLIES. ADDITION DOES NOT CREATE A FIRE AREA. ADDITION INCLUDES HOISTWAY
SHAFT AND LOBBY ON AN OPEN ROOF. ADDITION DOES NOT EXCEED ALLOWABLE HEIGHT.
180 FEET MAXIMUM ALLOWABLE. 26' - 5" EXISTING / 38' - 5" PROPOSED AT ELEVATOR
HOISTWAY ONLY.
RISK CATEGORY RISK CATEGORY II.
MULTIPLE OCCUPANCIES
(1004.4)
ALL MEANS OF EGRESS ARE EXISTING TO REMAIN. WORK IS LIMITED TO ELEVATOR
ADDITION; AND DOES NOT INCLUDE ADDITIONAL OCCUPIED AREAS OR OCCUPANT LOAD.
ACCESSIBILITY
(CHAPTER 11)
MULTIPLE OCCUPANCIES
(1004.4)
EXIT ACCESS TRAVEL
DISTANCE
(TABLE 1017.2)
A-3 200 FEET MAX. REQUIRED EXISTING TO REMAIN
B 200 FEET MAX. REQUIRED EXISTING TO REMAIN
S-1 300 FEET MAX. REQUIRED EXISTING TO REMAIN
S-2 300 FEET MAX. REQUIRED EXISTING TO REMAIN. 55'-9" PROVIDED WITHIN
AREA OF WORK. SEE PLAN.
REQUIRED / PROVIDED
PARKING GARAGE
ENTRANCES
(1105.1.2)
ACCESSIBLE ENTRANCE REQUIRED / PROVIDED
HOISTWAY OPENING
PROTECTION
(1020.2.1)
ELEVATOR LOBBIES ARE NOT PART OF THE EXISTING MEANS OF EGRESS SYSTEM.
HOISTWAY OPENING PROTECTION IS NOT PROVIDED.
MULTISTORY BUILDINGS
AND FACILITIES
(1104.4)
ELEVATOR ADDITION CONNECTING ALL LEVELS IS FULLY ACCESSIBLE.
ELEVATOR REQUIREMENTS
(CHAPTER 30)
EMERGENCY ELEVATOR
COMMUNICATION SYSTEMS
(3001.2)
TWO-WAY COMMUNICATION SYSTEM REQUIRED / PROVIDED
ACCESSIBILITY
(3001.4)
THE PASSENGER ELEVATOR IS ACCESSIBLE. HOWEVER, IT WILL NOT SERVE AS PART OF AN
ACCESSIBLE MEANS OF EGRESS SINCE THE OCCUPIED ROOF IS LESS THAN FOUR STORIES
ABOVE THE LEVEL OF EXIT DISCHARGE.
HOISTWAY ENCLOSURES
(3002)
SHAFT ENCLOSURE COMPLIES WITH CHAPTER 7. REFER TO APPLICABLE CODE SECTIONS
ON SHEET AG0.1
EMERGENCY SIGNS
(3002.3)
SIGNAGE REQUIRED / PROVIDED BY MANUFACTURER
EMERGENCY DOORS
(3002.5)
NOT REQUIRED / NOT PROVIDED
FIRE FIGHTERS’
EMERGENCY OPERATION.
(3003.2)
REQUIRED / PROVIDED
FIRE FIGHTERS’
EMERGENCY OPERATION
(3003.2)
PHASE I AND II REQUIRED / PROVIDED
HOISTWAY OPENING
PROTECTION
(3006.2)
NOT REQUIRED / NOT PROVIDED
HOISTWAY DOES NOT CONNECT MORE THAN THREE STORIES.
ASME A17.1
HYDRAULIC ELEVATOR
(PART 3.4.1)
BOTTOM CLEARANCE MIN. 24" BETWEEN PIT FLOOR AND LOWEST MECHANICAL OR
STRUCTURAL PART, EQUIPMENT, OR DEVICE INSTALLED BENEATH THE CAR PLATFORM
REQUIRED / PROVIDED.
PITS
(PART 2.2.2.3, 2.2.2.5)
ELEVATOR PIT FEATURES ZERO FIRE SPRINKLER AND UNDER 25'-0" TRAVEL. PIT WALLS AND
SLAB WILL RECEIVE WATERPROOFING TREATMENT TO RESIST WATER INFILTRATION AS
PERMANENT PROVISION TO PREVENT ACCUMULATION OF GROUND WATER.
SUMP PUMP REQUIRED / PROVIDED.
PIT ACCESS
(PART 2.2.4.1)
PIT ACCESS REQUIRED / PROVIDED BY MEANS OF LOWEST HOISTWAY DOOR.
PIT LADDER
(PART 2.2.4.2)
PIT LADDER REQUIRED / PROVIDED
PIT LIGHTING
(PART 2.2.5)
PIT LIGHTING REQUIRED / PROVIDED
HOISTWAY OPENING
PROTECTION
(3006.3)
1 HR REQUIRED / 1 HR PROVIDED
ROOFTOP STRUCTURES
(CHAPTER 15)
ROOF COVERING
CLASSIFICATION
(TABLE 1505.1)
CLASS B REQUIRED / CLASS A PROVIDED
2018 INTERNATIONAL ENERGY CONSERVATION CODE (IECC)
CLIMATE ZONE: 5A
OPAQUE THERMAL
ENVELOPE
(TABLE C402.1.4)
ROOF INSULATION ENTIRELY ABOVE DECK: R-30 CI
WALLS ABOVE GRADE, MASS: R-11.4 CI
WALLS BELOW GRADE: R-7.5 CI
SLAB-ON-GRADE FLOORS, UNHEATED: R-10 FOR 24" BELOW
OPAQUE DOORS, SWINGING: U-0.37
FENESTRATION
(TABLE C402.4)
VERTICAL FENESTRATIONS
FIXED FENESTRATION 0.38 REQUIRED / PROVIDED
ENTRANCE DOORS 0.77 REQUIRED / PROVIDED
SHGC PF < 0.2 (N) 0.51 REQUIRED / PROVIDED
(SEW) 0.38 REQUIRED / PROVIDED
VERTICAL FENESTRATION
(C402.4.1)
IN CLIMATE ZONES 1-6, A MAXIMUM OF 40% OF THE GROSS ABOVE-GRADE WALL AREA
SHALL BE PERMITTED TO BE VERTICAL FENESTRATION PROVIDED.
EXISTING GLAZING TO REMAIN: 16.93% (<40%)
EXISTING + ADDED GLAZING (ELEVATOR LOBBY): 17.13% (<40%)
IN BUILDINGS THREE OR MORE STORIES ABOVE GRADE, NOT LESS THAN 25% OF THE NET
FLOOR AREA IS WITHIN DAYLIGHT ZONE.
GLAZING AT BASEMENT AND FIRST FLOOR EXISTING REMAIN.
GLAZING AT ROOF ELEVATOR LOBBY 100% AREA IS WITHIN DAYLIGHT ZONE
VISIBLE TRANSMITTANCE (VT) OF VERTICAL FENESTRATION IS NOT LESS THAN 1.1 TIMES
SHGC.
ISSUES AND REVISIONS
DateNo.
NOTICE
THIS ARCHITECTURAL AND
ENGINEERING DRAWING IS GIVEN
IN CONFIDENCE. NO USE OR
DISSEMINATION MAY BE MADE
WITHOUT PRIOR WRITTEN
CONSENT OF THE ARCHITECT.
ALL RIGHTS ARE HEREBY
SPECIFICALLY RESERVED.
DRAWING NO.
RLB NO.:
CHECKED BY:
DRAWN BY:
Description
C en te r
S t, S ui te
C le ve la nd
O hi o
P ho ne
(2
1-
6)
-8 w w w .r lb a.
co m
© 2026 RICHARD L. BOWEN + ASSOCIATES, INC.
E
LE
V A
T O
R A
D D
IT
IO
N
8/
/2
4:
:5
P
M A ut od es k
D oc s:
//T
A R
T A
D ow nt ow n
T ra ns it
H ub
/A R
C H
_T A
R T
A -D ow nt ow n
T ra ns it
H ub
_1
-0
8.
rv t
T A
R T
A D
O W
N T
O W
N T
R A
N S
IT
H
U B
13828.8
N . H
U R
O N
S T
T
O
LE
D O
, O H
A B
B R
E V
IA
T
IO
N
S , S
Y M
B O
LS
, L
E G
E N
D S
A N
D C
O D
E D
A T
A
NP
AG0.1
ABBREVIATIONS
MATERIALS
SYMBOLS CODE DATA
07/17/26 OWNER REVIEW
DJK & SS
FE-1
FE-1
F E
-1
FE-1
FE-1
FE-1
FE-1
F E
-1
807 SF
2.7 OCC LOAD
807 SF
PAINT AREA
2172 SF
7.2 OCC LOAD
2172 SF
MECHANICAL /
ELECTRICAL
1222 SF
4.1 OCC LOAD
1222 SF
SHOP
1750 SF
5.8 OCC LOAD
1750 SF
STORAGE
OCCUPANCY LEGEND
STORAGE S1
STORAGE S2
1849 SF
6.2 OCC LOAD
1849 SF
WORKSHOP
301 SF
1.0 OCC LOAD
301 SF
CONTROL ROOM
20558 SF
68.5 OCC LOAD
20558 SF
STORAGE
3394 SF
11.3 OCC LOAD
3394 SF
LOADING DOCK
498 SF
1.7 OCC LOAD
498 SF
LOADING DOCK
223 SF
0.7 OCC LOAD
223 SF
IT ROOM
E X
IT
EXIT
E X
IT
EXISTING FIRE
PROTECTION
RISER TO REMAIN
ELEVATOR
EL-1
AREA OF WORK
AREA OF WORK
EXISTING TO REMAIN
EXISTING 1 HOUR FIRE BARRIER
EXISTING 2 HOUR FIRE BARRIER
LIFE SAFETY LEGEND
EXISTING EGRESS
EXIT PATH
ILLUMINATED EXIT SIGN
(COORDINATE WITH ELEC)
FEET
EXIT
## EXIT INFORMATION
# OF OCCUPANTS
MAX # OF
OCCUPANTS
EXISTING EGRESS
COMMON PATH OF TRAVEL
FE-1
EXISTING RECESSED FIRE
EXTINGUISHER CABINETFEC-1
EXISTING SURFACE MOUNTED
FIRE EXTINGUISHER CABINETFEC-2
EXISTING FIRE EXTINGUISHER
WITH WALL BRACKET
CODE REQUIRED SIGNAGE
ISSUES AND REVISIONS
DateNo.
NOTICE
THIS ARCHITECTURAL AND
ENGINEERING DRAWING IS GIVEN
IN CONFIDENCE. NO USE OR
DISSEMINATION MAY BE MADE
WITHOUT PRIOR WRITTEN
CONSENT OF THE ARCHITECT.
ALL RIGHTS ARE HEREBY
SPECIFICALLY RESERVED.
DRAWING NO.
RLB NO.:
CHECKED BY:
DRAWN BY:
Description
C en te r
S t, S ui te
C le ve la nd
O hi o
P ho ne
(2
1-
6)
-8 w w w .r lb a.
co m
© 2026 RICHARD L. BOWEN + ASSOCIATES, INC.
E
LE
V A
T O
R A
D D
IT
IO
N
8/
/2
4:
:5
P
M A ut od es k
D oc s:
//T
A R
T A
D ow nt ow n
T ra ns it
H ub
/A R
C H
_T A
R T
A -D ow nt ow n
T ra ns it
H ub
_1
-0
8.
rv t
T A
R T
A D
O W
N T
O W
N T
R A
N S
IT
H
U B
13828.8
N . H
U R
O N
S T
T
O
LE
D O
, O H
LI
F
E S
A F
E T
Y P
LA
N
B
A S
E M
E N
T
NP
KH
AG1.1
SCALE: 1/8" = 1'-0"AG1.1
LIFE SAFETY PLAN - BASEMENT1
PROVIDED FOR REFERENCE ONLY. SCOPE OF WORK DOES NOT INCLUDE ADDITIONAL OCCUPANT LOAD.
07/17/26 OWNER REVIEW
E
C -2
UP
DN
UP
DN
DN
FE-1
OCCUPANCY LEGEND
ASSEMBLY A-3
BUSINESS B
1744 SF
116.2 OCC LOAD
1744 SF
MULTIPURPOSE
ROOM
1009 SF
20.2 OCC LOAD
1009 SF
SIMULATION
398 SF
8.0 OCC LOAD
398 SF
CLASSROOM
509 SF
33.9 OCC LOAD
509 SF
BREAKROOM
1694 SF
11.3 OCC LOAD
1694 SF
SHELL SPACE
(OFFICE)
749 SF
49.9 OCC LOAD
749 SF
MULTIPURPOSE
ROOM216 SF
0.7 OCC LOAD
216 SF
STORAGE
212 SF
0.7 OCC LOAD
212 SF
I.T ROOM
898 SF
6.0 OCC LOAD
898 SF
SHELL SPACE
(OFFICE)
1087 SF
7.2 OCC LOAD
1087 SF
OFFICES
1042 SF
6.9 OCC LOAD
1042 SF
SHELL SPACE
(OFFICE)
131 SF
0.9 OCC LOAD
131 SF
OFFICE
135 SF
2.1 OCC LOAD
135 SF
CHANGING
260 SF
5.2 OCC LOAD
260 SF
UNIFORM / LOCKERS
136 SF
0.9 OCC LOAD
136 SF
OFFICE
94 SF
0.3 OCC LOAD
94 SF
STORAGE
203 SF
0.7 OCC LOAD
203 SF
UTILITY
153 SF
0.5 OCC LOAD
153 SF
MEP
348 SF
2.3 OCC LOAD
348 SF
QUIET ROOM
1412 SF
9.4 OCC LOAD
1412 SF
CALL CENTER
83 SF
0.3 OCC LOAD
83 SF
CONTROL ROOM
309 SF
6.2 OCC LOAD
309 SF
CONFERENCE
220 SF
1.5 OCC LOAD
220 SF
OFFICE
90 SF
0.3 OCC LOAD
90 SF
STORAGE
337 SF
2.2 OCC LOAD
337 SF
LOBBY
384 SF
2.6 OCC LOAD
384 SF
LOBBY
420 SF
2.8 OCC LOAD
420 SF
JANITOR / STORAGE
1444 SF
9.6 OCC LOAD
1444 SF
OFFICE
46 SF
0.2 OCC LOAD
46 SF
HVAC
150 SF
1.0 OCC LOAD
150 SF
LOUNGE
E X
IT
EXIT
EXIT
LINE OF OPERABLE PARTITION
62 OCCUPANTS
WHEN DIVIDED
54 OCCUPANTS
WHEN DIVIDED
ACCESSORY USE
(AREA <10% GROSS AREA)
ACCESSORY USE
(AREA <10% GROSS AREA)
238 SF
1.6 OCC LOAD
238 SF
OFFICE
692 SF
46.1 OCC LOAD
692 SF
BREAK ROOM
1614 SF
10.8 OCC LOAD
1614 SF
OFFICE
339 SF
2.3 OCC LOAD
339 SF
OFFICE
2944 SF
29.4 OCC LOAD
2944 SF
CONCOURSE
682 SF
4.5 OCC LOAD
682 SF
OFFICES
187 SF
0.6 OCC LOAD
187 SF
STORAGE
EXISTING RAMP UP
ELEVATOR
EL-1
618 SF
2.1 OCC LOAD
618 SF
MARKETING
AREA OF WORK
EXISTING TO REMAIN
EXISTING 1 HOUR FIRE BARRIER
EXISTING 2 HOUR FIRE BARRIER
LIFE SAFETY LEGEND
EXISTING EGRESS
EXIT PATH
ILLUMINATED EXIT SIGN
(COORDINATE WITH ELEC)
FEET
EXIT
## EXIT INFORMATION
# OF OCCUPANTS
MAX # OF
OCCUPANTS
EXISTING EGRESS
COMMON PATH OF TRAVEL
FE-1
EXISTING RECESSED FIRE
EXTINGUISHER CABINETFEC-1
EXISTING SURFACE MOUNTED
FIRE EXTINGUISHER CABINETFEC-2
EXISTING FIRE EXTINGUISHER
WITH WALL BRACKET
CODE REQUIRED SIGNAGE
ISSUES AND REVISIONS
DateNo.
NOTICE
THIS ARCHITECTURAL AND
ENGINEERING DRAWING IS GIVEN
IN CONFIDENCE. NO USE OR
DISSEMINATION MAY BE MADE
WITHOUT PRIOR WRITTEN
CONSENT OF THE ARCHITECT.
ALL RIGHTS ARE HEREBY
SPECIFICALLY RESERVED.
DRAWING NO.
RLB NO.:
CHECKED BY:
DRAWN BY:
Description
C en te r
S t, S ui te
C le ve la nd
O hi o
P ho ne
(2
1-
6)
-8 w w w .r lb a.
co m
© 2026 RICHARD L. BOWEN + ASSOCIATES, INC.
E
LE
V A
T O
R A
D D
IT
IO
N
8/
/2
4:
:0
P
M A ut od es k
D oc s:
//T
A R
T A
D ow nt ow n
T ra ns it
H ub
/A R
C H
_T A
R T
A -D ow nt ow n
T ra ns it
H ub
_1
-0
8.
rv t
T A
R T
A D
O W
N T
O W
N T
R A
N S
IT
H
U B
13828.8
N . H
U R
O N
S T
T
O
LE
D O
, O H
LI
F
E S
A F
E T
Y P
LA
N
F
IR
S
T F
LO
O
R
NP
KH
AG1.2
SCALE: 1/8" = 1'-0"AG1.2
LIFE SAFETY PLAN - FIRST FLOOR1
PROVIDED FOR REFERENCE ONLY. SCOPE OF WORK DOES NOT INCLUDE ADDITIONAL OCCUPANT LOAD.
07/17/26 OWNER REVIEW
OCCUPANCY LEGEND
STORAGE S2
31019 SF
155.1 OCC LOAD
31019 SF
PARKING
88 SF
0.6 OCC LOAD
88 SF
ELEV. LOBBY
53' - 9"
ELEVATOR
EL-1
AREA OF WORK
EXISTING TO REMAIN
EXISTING 1 HOUR FIRE BARRIER
EXISTING 2 HOUR FIRE BARRIER
LIFE SAFETY LEGEND
EXISTING EGRESS
EXIT PATH
ILLUMINATED EXIT SIGN
(COORDINATE WITH ELEC)
FEET
EXIT
## EXIT INFORMATION
# OF OCCUPANTS
MAX # OF
OCCUPANTS
EXISTING EGRESS
COMMON PATH OF TRAVEL
FE-1
EXISTING RECESSED FIRE
EXTINGUISHER CABINETFEC-1
EXISTING SURFACE MOUNTED
FIRE EXTINGUISHER CABINETFEC-2
EXISTING FIRE EXTINGUISHER
WITH WALL BRACKET
CODE REQUIRED SIGNAGE
ISSUES AND REVISIONS
DateNo.
NOTICE
THIS ARCHITECTURAL AND
ENGINEERING DRAWING IS GIVEN
IN CONFIDENCE. NO USE OR
DISSEMINATION MAY BE MADE
WITHOUT PRIOR WRITTEN
CONSENT OF THE ARCHITECT.
ALL RIGHTS ARE HEREBY
SPECIFICALLY RESERVED.
DRAWING NO.
RLB NO.:
CHECKED BY:
DRAWN BY:
Description
C en te r
S t, S ui te
C le ve la nd
O hi o
P ho ne
(2
1-
6)
-8 w w w .r lb a.
co m
© 2026 RICHARD L. BOWEN + ASSOCIATES, INC.
E
LE
V A
T O
R A
D D
IT
IO
N
8/
/2
4:
:0
P
M A ut od es k
D oc s:
//T
A R
T A
D ow nt ow n
T ra ns it
H ub
/A R
C H
_T A
R T
A -D ow nt ow n
T ra ns it
H ub
_1
-0
8.
rv t
T A
R T
A D
O W
N T
O W
N T
R A
N S
IT
H
U B
13828.8
N . H
U R
O N
S T
T
O
LE
D O
, O H
LI
F
E S
A F
E T
Y P
LA
N
R
O O
F
NP
KH
AG2.1
SCALE: 1/8" = 1'-0"AG2.1
LIFE SAFETY PLAN - ROOF1
PROVIDED FOR REFERENCE ONLY. SCOPE OF WORK DOES NOT INCLUDE ADDITIONAL OCCUPANT LOAD.
07/17/26 OWNER REVIEW
UP
5 6 7
C
A
B
D7
V.I.F.
12' - 9 1/2"
V.I.F.
9' - 7 1/4"
REF STRUCT.
20' - 0"
R E
F S
T R
U C
T
D2
8'
D26
D26
D26
D26
20' - 0" 20' - 0"
D11
D10
D11
D10
5 6 7
C
A
B
D8
8'
20' - 0" 20' - 0"
D6
D8D8
D26
D26
D26
D26
D26 D12
D21
D41
D12
5 6 7
C
A
B
D25D9
1' - 2"
V.I.F.
10' - 8"
20' - 0" 20' - 0" 20' - 0"
8'
EXISTING EXPANSION JOINT
AND COVER TO REMAIN
D1
V .I.
F
V.I.F.
25' - 6"
V.I.F.
19' - 9"
1. THIS DRAWING IS FOR GENERAL INFORMATION ONLY AND DOES NOT INDICATE ALL DEMOLITION REQUIREMENTS. REFER TO ALL DRAWINGS, SPECIFICATIONS, AND FIELD CONDITIONS TO DETERMINE THE FULL SCOPE AND SPECIFIC REMOVAL REQUIREMENTS.
2. REMOVE EXISTING ELEMENTS AS INDICATED BY DASHED LINES. SURFACES OF EXISTING AREAS WHICH HAVE BEEN ALTERED BY DEMOLITION NOT SPECIFICALLY CALLED FOR SHALL BE REPAIRED AND FINISHED TO MATCH THE ADJACENT SURFACES. PROTECT ALL REMAINING SURFACES, FLOORS, WALLS AND CEILINGS FROM AREAS OF DEMOLITION AND CONSTRUCTION.
3. INTERIOR RENOVATION SCOPE NOT RELATED TO ELEVATOR UNDER SEPARATE CONTRACT. COORDINATE WITH OWNER.
4. REFER TO STRUCTURAL, MECHANICAL, ELECTRICAL AND PLUMBING DRAWINGS FOR ADDITIONAL DEMOLITION ITEMS AND REQUIREMENTS.
5. FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS. REPORT ALL DISCREPANCIES TO THE ARCHITECT.
6. PROTECT EXISTING SURFACES TO REMAIN DURING DEMOLITION. DAMAGE TO SURFACES NOT BEING DEMOLISHED SHALL BE REPAIRED AT THE
CONTRACTOR'S EXPENSE.
7. IN AREAS WHERE DEMOLITION CAUSES UNEVENNESS AND/OR VOIDS IN THE FLOORS, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING AND
FLOOR LEVELING TO LEVEL THE FLOOR WITH ADJACENT SURFACES. REFER TO SECTION 035416 FOR LEVELING AND MATERIAL REQUIREMENTS.
8. COORDINATE TEMPORARY FACILITIES AND LAY DOWN AREA WITH OWNER.
9. COORDINATE DISCONNECTION OF UTILITIES WITH OWNER PRIOR TO START OF WORK.
GENERAL NOTES - DEMOLITION
D27
STORAGE
AREA
ISSUES AND REVISIONS
DateNo.
NOTICE
THIS ARCHITECTURAL AND
ENGINEERING DRAWING IS GIVEN
IN CONFIDENCE. NO USE OR
DISSEMINATION MAY BE MADE
WITHOUT PRIOR WRITTEN
CONSENT OF THE ARCHITECT.
ALL RIGHTS ARE HEREBY
SPECIFICALLY RESERVED.
DRAWING NO.
RLB NO.:
CHECKED BY:
DRAWN BY:
Description
C en te r
S t, S ui te
C le ve la nd , O hi o
P ho ne
(2
1-
(2
1-w w w
.r lb a.
co m
© 2026 RICHARD L. BOWEN + ASSOCIATES, INC.
KEYPLAN
E
LE
V A
T O
R A
D D
IT
IO
N
8/
/2
5:
:5
P
M A ut od es k
D oc s:
//T
A R
T A
D ow nt ow n
T ra ns it
H ub
/A R
C H
_T A
R T
A -D ow nt ow n
T ra ns it
H ub
_1
-0
8.
rv t
T A
R T
A D
O W
N T
O W
N T
R A
N S
IT
H
U B
13828.8
N . H
U R
O N
S T
T
O
LE
D O
, O H
E N
LA
R
G E
D D
E M
O
LI
T
IO
N P
LA
N
S
NP
AD1.1
SCALE: 1/4" = 1'-0"AD1.1
ENLARGED DEMOLITION FLOOR PLAN - BASEMENT1
DEMOLITION SCHEDULE
TAG WORK DESCRIPTION
51 REMOVE SECURITY GATE FRAME, HARDWARE, ANCHORS AND ATTACHMENTS. PREPARE EXPOSED WALL SURFACES FOR NEW
WORK.
D1 CLEAN AND PREPARE EXISTING SLAB FOR NEW WORK. REFER STRUCTURAL DWGS.
D2 REMOVE CONCRETE SLAB IN PREPARATION OF NEW WORK. REFER STRUCTURAL DWGS.
D6 REMOVE PORTION OF EXTERIOR WALL ASSEMBLY IN PREPARATION OF NEW WORK.
D7 REMOVE PORTION OF EXTERIOR WALL ASSEMBLY AND FOUNDATION AND PREPARE FOR NEW WORK. REFER STRUCTURAL DWGS.
D8 REMOVE EXTERIOR WINDOW FRAME, GLAZING, ANCHORS AND ATTACHMENTS IN THEIR ENTIRETY.
D9 REMOVE PORTION OF LEDGE WALL. PREPARE ADJACENT SURFACE FOR NEW WORK.
D10 REMOVE PORTION OF PARTITION WALL. PREPARATION ADJACENT SURFACES TO RECEIVE NEW FINISHES.
D11 REMOVE DOOR, FRAME, HARDWARE, ANCHORS AND ATTACHMENTS. RE-USE EXISTING ELECTRICAL AND DATA INFRASTRUCTURE FOR NEW DOORS. SEE ELECTRICAL DRAWINGS. PREPARE THRESHOLD TO RECEIVE NEW FLOOR FINISH.
SCALE: 1/4" = 1'-0"AD1.1
ENLARGED DEMOLITION PLAN - FIRST FLOOR2
SCALE: 1/4" = 1'-0"AD1.1
ENLARGED DEMOLITION PLAN - ROOF3
SCALE: 1/4" = 1'-0"AD1.1
ENLARGED DEMOLITION FLOOR PLAN - BASEMENT4
07/17/26 OWNER REVIEW
08/31/26 BID SET
DEMOLITION SCHEDULE
TAG WORK DESCRIPTION
D12 REMOVE MASONRY WALL AS INDICATED IN PLAN. REMOVE WALL BASE, COVERINGS, PANELING AND ALL OTHER FINISH MATERIALS. CLEAN AND PREPARE EXPOSED ADJACENT SURFACES, FLOOR, AND EXISTING TO REMAIN MASONRY SUBSTRATE PER
SPECIFICATIONS TO RECEIVE NEW FINISHES.
D21 REMOVE PLUMBING FIXTURES, SUPPORT, ATTACHMENTS, AND ACCESSORIES. MODIFY PIPING FOR NEW WORKS. PATCH WALL
PRIOR TO APPLYING NEW FINISHES. REFER TO PLUMBING DRAWINGS.
D25 MODIFY EXISTING HANDRAIL IN THE SAME PLACE.
D26 SCOPE NOT IN CONTRACT
D27 REMOVE LOADING DOCK SLAB, ENCLOSURE, OVERHEAD DOORS, FRAME, HARDWARE, ANCHORS AND ATTACHMENTS IN THEIR
ENTIRETY.
D41 REMOVE COUNTERTOPS, CABINETS, SUPPORT BRACKETS, HARDWARE, ANCHORS AND ATTACHMENTS.
6"
CEILING
(SEE RCP)
FLOOR OR ROOF
STRUCTURE ABOVE
FLOOR OR ROOF
STRUCTURE ABOVE
PD-F2 PD-F4
6"
CEILING
(SEE RCP)
FLOOR OR ROOF
STRUCTURE ABOVE
PD-F3
EXISTING SUBSTRATE
SEE SCHEDULE SEE SCHEDULE SEE SCHEDULE
SHIMS AS REQ'D
METAL TRACK
092216.C
5/8 INCH GYPSUM BOARD
092116.A
ACOUSTICAL JOINT SEALANT
079200.E
ACOUSTICAL JOINT SEALANT
079200.E
5/8 INCH GYPSUM BOARD
092116.A
METAL TRACK
092216.C
DEFLECTION TRACK
092216.D
5/8 INCH GYPSUM BOARD
092116.A
METAL TRACK
092216.C
ACOUSTICAL JOINT SEALANT
079200.E
DEFLECTION TRACK
092216.D
ACOUSTICAL JOINT SEALANT
079200.E
SEE SCHEDULE
PD-M1
FLOOR OR ROOF
STRUCTURE ABOVE
(AT NON-RATED
PARTITIONS, PACK JOINT
WITH BATT INSULATION
TO STRUCTURE ABOVE.)
REFER TO STRUCTURAL DRAWINGS
FOR GROUTING REQUIREMENTS
SEE SCHEDULE
PD-M2
REFER TO STRUCTURAL DRAWINGS
FOR GROUTING REQUIREMENTS
CEILING
(SEE RCP)
CEILING
(SEE RCP)
EXTEND CMU BLOCK A
MINIMUM OF ONE
COURSE ABOVE HIGHEST
ADJACENT CEILING
DRILL AND GROUT USING
HILTI HIT-HY200; 8" EMBED
U.N.O. - SEE STRUCTURAL
S E
E S
T R
U C
T U
R A
L
DRILL AND GROUT USING
HILTI HIT-HY200; 8" EMBED
U.N.O. - SEE STRUCTURAL
S E
E S
T R
U C
T U
R A
L
HEAD OF WALL JOINT
FIRESTOPPING
078400.D
JOINT REINFORCEMENT - SEE
STRUCTURAL
042000.S
JOINT REINFORCEMENT - SEE
STRUCTURAL
042000.S
STEEL LINTEL - SEE
STRUCTURAL
051200.B
8" M
IN
CONCRETE MASONRY UNIT -
AS SCHEDULED
042000.X1
CONCRETE MASONRY UNIT -
AS SCHEDULED
042000.X1
SOUND BATT INSULATION - AS
SCHEDULED
092116.X1
SOUND BATT INSULATION - AS
SCHEDULED
092116.X1
SOUND BATT INSULATION - AS
SCHEDULED
092116.X1
METAL STUD FRAMING - AS
SCHEDULED
092216.X1
METAL STUD FRAMING - AS
SCHEDULED
092216.X1
METAL STUD FRAMING - AS
SCHEDULED
092216.X1
1. ALL PARTITIONS MAY NOT BE UTILIZED. PARTITION TAGS AND DETAIL NUMBERS MAY NOT BE SEQUENTIAL. REFER TO PARTITION SCHEDULE.
2. FLOOR PLAN DIMENSIONS FOR GYPSUM WALL BOARD PARTITIONS ARE FACE OF FINISH (U.N.O.).
3. AT NON-RATED WALLS, ALL PENETRATIONS TO BE SEALED WITH ACOUSTICAL SEALANT AND BACKER ROD (U.N.O.).
4. AT RATED WALLS, ABOVE CEILING, STENCIL IN 2" BLACK LETTERING @ 25'-0" O.C. THE FOLLOWING: "# HOUR RATED WALL -FIRESTOP ALL
PENETRATIONS".
5. ALL GYPSUM WALL BOARD TO BE TYPE "X" (U.N.O.).
6. PROVIDE ABUSE RESISTANT GYPSUM WALL BOARD AT CORRIDOR AND LOBBY WALLS ON CIRCULATION SIDE.
7. PROVIDE CEMENTITIOUS BACKER BOARD IN LIEU OF GYPSUM BOARD WHERE TILE OCCURS.
8. PROVIDE MOISTURE AND MOLD RESISTANT GYPSUM BOARD AT ALL TOILET ROOM WALLS WHERE TILE DOES NOT OCCUR.
9. PROVIDE CONTROL JOINTS IN ALL GYPSUM BOARD WALLS THAT EXCEED 30 FEET IN LENGTH. CONTROL JOINTS SHALL BE SPACED NOT MORE THAN 30
FEET APART ON CENTER. WHERE POSSIBLE, ALIGN JOINT WITH EDGE OF DOOR FRAME.
10. PROVIDE FACTORY BULLNOSE END WALL AND OUTSIDE CORNER UNITS AT CMU WALLS.
11. REFER TO STRUCTURAL DRAWINGS FOR ADDITIONAL REINFORCING REQUIREMENTS AT CMU WALLS.
12. WHERE GYPSUM BOARD WALLS EXCEED HEIGHT LIMITATIONS SET BY MANUFACTURE, PROVIDE DIAGONAL BRACING AT 4'-0" O.C. MAX.
13. PARTITION TAG MODIFIERS:
NOTE: TAG MODIFIERS ARE FOR REFERENCE PURPOSES ONLY. REFER TO PARTITION SCHEDULE FOR ATTENUATION REQUIREMENTS AND TOP OF WALL
DETAILS.
PARTITION
GROUP
A = INSULATED
K = KNEE WALL
P = PARTIAL HEIGHT
ISSUES AND REVISIONS
DateNo.
NOTICE
THIS ARCHITECTURAL AND
ENGINEERING DRAWING IS GIVEN
IN CONFIDENCE. NO USE OR
DISSEMINATION MAY BE MADE
WITHOUT PRIOR WRITTEN
CONSENT OF THE ARCHITECT.
ALL RIGHTS ARE HEREBY
SPECIFICALLY RESERVED.
DRAWING NO.
RLB NO.:
CHECKED BY:
DRAWN BY:
Description
C en te r
S t, S ui te
C le ve la nd
O hi o
P ho ne
(2
1-
6)
-8 w w w .r lb a.
co m
© 2026 RICHARD L. BOWEN + ASSOCIATES, INC.
E
LE
V A
T O
R A
D D
IT
IO
N
8/
/2
4:
:0
P
M A ut od es k
D oc s:
//T
A R
T A
D ow nt ow n
T ra ns it
H ub
/A R
C H
_T A
R T
A -D ow nt ow n
T ra ns it
H ub
_1
-0
8.
rv t
T A
R T
A D
O W
N T
O W
N T
R A
N S
IT
H
U B
13828.8
N . H
U R
O N
S T
T
O
LE
D O
, O H
P A
R T
IT
IO
N S
C H
E D
U
LE
A N
D D
E T
A
IL
S
NP
A0.1
GENERAL PARTITION NOTES
SCALE: 3" = 1'-0"A0.1
PARTITION DETAILS1
PARTITION SCHEDULE ELEVATOR
TAG
BATT
INSULATION
PARTIAL
HEIGHT
PARTITION
DETAIL
FIRE RATING DEPTH STC
RATING NOTESHOURS TEST OVERALL FRAME
GROUP F: SINGLE SIDED GWB
F1P - ● PD-F1 0 - 1 1/2" 7/8" -
F4P - ● PD-F2 0 - 4 1/4" 3 5/8" -
F6 - - PD-F3 0 - 3 1/8" 2 1/2" -
GROUP M: CONCRETE MASONRY UNITS
M7 - - PD-M1 1 U904 7 5/8" -
07/17/26 OWNER REVIEW
FE-1
F E
-1
FE-1
FE-1
FE-1
FE-1
F E
-1
UP
3A
3A
4A
4A
FF
EE
DD
CC
AA
GG
HH
II
3B
3B
4B
4B
A5.1
B
A5.1
-3'-8"
0'-0"
E X
IS
T
IN
G
S E
C U
R
IT
Y
G A
T E
T O
R E
M A
IN
SINK
-2'-4"
-2'-4"
0'-0"
BUILDING &
GROUNDS
WORKSHOP
WC
WC
STORAGE
AREA
NEW DOCK
AREA
CORRIDOR
140A
RISER
CLOSET
ELEVATOR
EL-1
SIM
A7.1
A5.1
/A
.2
4'
0"
8'
TOOTH IN INFILL OF DEMO'D OPENING
WITH EXISTING, ALIGN COURSING. MATCH
WIDTH AND FINISHES WITH ADJACENT
EXISTING
R E
F S
T R
U C
T
REF STRUCT.
20' - 0"
NEW WALLS AND
DOORS NIC.
REINFORCED CONCRETE SLAB
ON GRADE - SEE STRUCTURAL
033000.A
GENERAL NOTES - FLOOR PLAN
1. ALL INTERIOR PARTITION DIMENSIONS ARE TO FACE OF CONCRETE BLOCK, FACE OF
GYPSUM WALL BOARD, OR FACE OF EXISTING WALL UNLESS OTHERWISE NOTED.
2. ALL MASONRY OPENING DIMENSIONS ARE NOMINAL (NOM.) UNLESS OTHERWISE
NOTED.
3. VERIFY ALL DIMENSIONS AND CONDITIONS IN THE FIELD PRIOR TO COMMENCEMENT
OF WORK. WHEN DIMENSIONS AND/OR CONDITIONS AS INDICATED ON THE DRAWINGS
CONFLICT WITH ACTUAL, CONTACT ARCHITECT FOR CLARIFICATION BEFORE
PROCEEDING WITH WORK.
4. NO ATTEMPT HAS BEEN MADE TO SHOW SECTION CUTS OR DETAIL DESIGNATORS AT
ALL LOCATIONS WHERE SIMILAR CONDITIONS OCCUR. ANY MATERIAL INDICATIONS OR
NOTES SHOWN ON ONE SECTION (USUALLY THE FIRST SECTION OF EACH SHEET),
ELEVATION OR DETAIL ALSO APPLY TO ALL SIMILAR CONDITIONS ON OTHER
SECTIONS, ELEVATIONS, OR DETAILS.
5. SECTIONS AND DETAILS ARE TYPICAL FOR ALL LOCATIONS AT WHICH SIMILAR
CONDITIONS OCCUR UNLESS NOTED AS APPLICABLE TO A SPECIFIC LOCATION ONLY.
EXISTING TO REMAIN
ISSUES AND REVISIONS
DateNo.
NOTICE
THIS ARCHITECTURAL AND
ENGINEERING DRAWING IS GIVEN
IN CONFIDENCE. NO USE OR
DISSEMINATION MAY BE MADE
WITHOUT PRIOR WRITTEN
CONSENT OF THE ARCHITECT.
ALL RIGHTS ARE HEREBY
SPECIFICALLY RESERVED.
DRAWING NO.
RLB NO.:
CHECKED BY:
DRAWN BY:
Description
C en te r
S t, S ui te
C le ve la nd
O hi o
P ho ne
(2
1-
6)
-8 w w w .r lb a.
co m
© 2026 RICHARD L. BOWEN + ASSOCIATES, INC.
E
LE
V A
T O
R A
D D
IT
IO
N
8/
/2
4:
:0
P
M A ut od es k
D oc s:
//T
A R
T A
D ow nt ow n
T ra ns it
H ub
/A R
C H
_T A
R T
A -D ow nt ow n
T ra ns it
H ub
_1
-0
8.
rv t
T A
R T
A D
O W
N T
O W
N T
R A
N S
IT
H
U B
13828.8
N . H
U R
O N
S T
T
O
LE
D O
, O H
O V
E R
A
LL
F
LO
O R
P
LA
N
B A
S E
M E
N T
NP
A1.1
SCALE: 1/8" = 1'-0"A1.1
BASEMENT FLOOR PLAN1
07/17/26 OWNER REVIEW
C -2
FE-1
2 3A 4A
FF
EE
DD
CC
AA
GG
HH
II
3B
3B
4B
4B
A5.1
BB
ABANDONED
GAS METER
0"
RAMP ABOVE
EXISTING VEHICLE GATE
WITH PEDESTAL
COMMUNICATION AND CARD
READER TO REMAIN.
LOBBY
QUIET
ROOM
MECH
OFFICE
STORAGE
UTILITY
CLASSROOM
DRIVER
SIMULATION
AREA
BREAKROOM
580 SF
MARKETING
MULTIPURPOSE
ROOM A
118A
QA OFFICE
OFFICE
OFFICE
OFFICE
CONFERENCE
ROOM
OFFICE
MULTIPURPOSE
ROOM
ELEVATOR
CONTROL
ROOM
OFFICE
OFFICE
OFFICE
UNISEX
UNIFORM
STORAGE
STREET
SUPERVISOR
VESTIBULE
STORAGE
LOUNGE
HVAC
COMMUNITY
ROOM
CALL
CENTER
FUTURE
TENANT
SPACE
MENS
RESTROOM
WOMENS
RESTROOM
FUTURE
TENANT
SPACE
IT
CORRIDOR
ELEVATOR
LOBBY
CORRIDOR
CORRIDOR
MOTHERS
ROOM
CORRIDOR
STORAGE &
JANITOR
ELEC
CORRIDOR
CONF.
109A
CHANGING
ROOM
ETR.
ETR.
UNISEX
UNISEX
UNISEX
MULTIPURPOSE
ROOM B
118B
SF9
MECH
STORAGE
OFFICE
CEO
OFFICE
MECH
MECH
SOFFIT ABOVE
FUTURE
TENANT
SPACE
OFFICE
CHANGING
ROOM
(ADA)
SOFFIT ABOVE
ELEVATOR
EL-1
ADMIN
OFFICE
SIM
A7.1
A5.1
3/A6.32/A6.3
/A
.3
/A
.2
6/A6.3
5/A6.3
/A
.3
A8.10
A8.10
A7.11
A7.11
10/A7.6
GENERAL NOTES - FLOOR PLAN
1. ALL INTERIOR PARTITION DIMENSIONS ARE TO FACE OF CONCRETE BLOCK, FACE OF
GYPSUM WALL BOARD, OR FACE OF EXISTING WALL UNLESS OTHERWISE NOTED.
2. ALL MASONRY OPENING DIMENSIONS ARE NOMINAL (NOM.) UNLESS OTHERWISE
NOTED.
3. VERIFY ALL DIMENSIONS AND CONDITIONS IN THE FIELD PRIOR TO COMMENCEMENT
OF WORK. WHEN DIMENSIONS AND/OR CONDITIONS AS INDICATED ON THE DRAWINGS
CONFLICT WITH ACTUAL, CONTACT ARCHITECT FOR CLARIFICATION BEFORE
PROCEEDING WITH WORK.
4. NO ATTEMPT HAS BEEN MADE TO SHOW SECTION CUTS OR DETAIL DESIGNATORS AT
ALL LOCATIONS WHERE SIMILAR CONDITIONS OCCUR. ANY MATERIAL INDICATIONS OR
NOTES SHOWN ON ONE SECTION (USUALLY THE FIRST SECTION OF EACH SHEET),
ELEVATION OR DETAIL ALSO APPLY TO ALL SIMILAR CONDITIONS ON OTHER
SECTIONS, ELEVATIONS, OR DETAILS.
5. SECTIONS AND DETAILS ARE TYPICAL FOR ALL LOCATIONS AT WHICH SIMILAR
CONDITIONS OCCUR UNLESS NOTED AS APPLICABLE TO A SPECIFIC LOCATION ONLY.
EXISTING TO REMAIN
SCALE: 1/8" = 1'-0"A1.2
FIRST FLOOR PLAN1
ISSUES AND REVISIONS
DateNo.
NOTICE
THIS ARCHITECTURAL AND
ENGINEERING DRAWING IS GIVEN
IN CONFIDENCE. NO USE OR
DISSEMINATION MAY BE MADE
WITHOUT PRIOR WRITTEN
CONSENT OF THE ARCHITECT.
ALL RIGHTS ARE HEREBY
SPECIFICALLY RESERVED.
DRAWING NO.
RLB NO.:
CHECKED BY:
DRAWN BY:
Description
C en te r
S t, S ui te
C le ve la nd
O hi o
P ho ne
(2
1-
6)
-8 w w w .r lb a.
co m
© 2026 RICHARD L. BOWEN + ASSOCIATES, INC.
E
LE
V A
T O
R A
D D
IT
IO
N
8/
/2
4:
:0
P
M A ut od es k
D oc s:
//T
A R
T A
D ow nt ow n
T ra ns it
H ub
/A R
C H
_T A
R T
A -D ow nt ow n
T ra ns it
H ub
_1
-0
8.
rv t
T A
R T
A D
O W
N T
O W
N T
R A
N S
IT
H
U B
13828.8
N . H
U R
O N
S T
T
O
LE
D O
, O H
O V
E R
A
LL
F
LO
O R
P
LA
N
F
IR
S T
F
LO
O R
NP
A1.2
07/17/26 OWNER REVIEW
3A
3A
4A
4A
FF
EE
DD
CC
AA
GG
HH
II
143B
3B
4B
4B
EXISTING RAMP DN
A5.1 A7.1
EXISTING
STAIRWAY TO
REMAIN
EXISTING STAIRWAY & MECH.
PENTHOUSE TO REMAIN
EXISTING MECHANICAL
UNIT TO REMAIN
EXISTING EXPANSION
JOINT TO REMAIN
BB
ALL EXISTING PAVEMENT MARKINGS,
POLE LIGHTS, AND OTHER
FURNISHINGS TO REMAIN.
EXISTING STANDARD PARKING: 65
EXISTING ACCESSIBLE PARKING: 4 (6%)
TOTAL EXISTING PARKING: 69
ALL EXISTING PAVEMENT MARKINGS,
POLE LIGHTS, AND OTHER
FURNISHINGS TO REMAIN.
EXISTING EXHAUST
FAN TO REMAIN
EXISTING HVAC
EQUIPMENT TO REMAIN
EXISTING HVAC
EQUIPMENT TO REMAIN
19' - 9" 26' - 4"
9'
/8
EXISTING ROOF DRAIN TO
REMAIN, TYP.
EXISTING ROOF DRAIN TO
REMAIN, TYP.
EXISTING ROOF DRAIN TO
REMAIN, TYP.
A5.1
A5.10
ISSUES AND REVISIONS
DateNo.
NOTICE
THIS ARCHITECTURAL AND
ENGINEERING DRAWING IS GIVEN
IN CONFIDENCE. NO USE OR
DISSEMINATION MAY BE MADE
WITHOUT PRIOR WRITTEN
CONSENT OF THE ARCHITECT.
ALL RIGHTS ARE HEREBY
SPECIFICALLY RESERVED.
DRAWING NO.
RLB NO.:
CHECKED BY:
DRAWN BY:
Description
C en te r
S t, S ui te
C le ve la nd
O hi o
P ho ne
(2
1-
6)
-8 w w w .r lb a.
co m
© 2026 RICHARD L. BOWEN + ASSOCIATES, INC.
E
LE
V A
T O
R A
D D
IT
IO
N
8/
/2
4:
:0
P
M A ut od es k
D oc s:
//T
A R
T A
D ow nt ow n
T ra ns it
H ub
/A R
C H
_T A
R T
A -D ow nt ow n
T ra ns it
H ub
_1
-0
8.
rv t
T A
R T
A D
O W
N T
O W
N T
R A
N S
IT
H
U B
13828.8
N . H
U R
O N
S T
T
O
LE
D O
, O H
O V
E R
A
LL
R O
O F
P
LA
N
NP
A2.1
SCALE: 1/8" = 1'-0"A2.1
02 PARKING LEVEL PLAN1
07/17/26 OWNER REVIEW
FIRST FLOOR
0"
BASEMENT
-11' - 8"
ROOF
11' - 2"
A
A7.2
A7.2
A7.2
1/2" / 1'-0" A7.2
CONCRETE MASONRY UNIT
042000.A
INSULATED METAL WALL
PANELS
074213.C
C
LE
A R
O P
E N
IN
G
7'
1/ 2"
STEEL LINTEL - SEE
STRUCTURAL
PENDANT LIGHT FIXTURE - SEE
ELECT.
260000.D
METAL FURRING CHANNEL
092216.B
PIT ACCESS LADDER
055133.E
OPP. SIDE (SEE PLANS)
PAINTED HPC-1
P E
R M
A N
U F
A C
T U
R E
R
M
IN
STRUCTURAL STEEL FRAMING
051200
2" M
IN
INSULATED METAL WALL
PANELS
074213.C
STEEL FRAMING - SEE
STRUCTURAL
PAINT PT-1
FLOOR FINISH MAY OCCUR.
REFER FINISH PLANS
FLOOR FINISH MAY OCCUR.
REFER FINISH PLANS
A7.2
M
IN
A F
F
A7.2
FULLY ADHERED TPO
MEMBRANE
075423.A
FOUNDATION DRAIN MAY
OCCUR - SEE STRUCTURAL
SLOPE GRADE AWAY
FROM WALL ASSEMBLY.
CONCRETE MASONRY UNIT
042000.A
METAL FURRING CHANNEL
092216.B
P
IT
D E
P T
H
4' -0
M
IN
INSULATED METAL WALL
PANELS
074213.C
STRUCTURAL STEEL FRAMING
051200
REINFORCED CONCRETE
FOOTING - SEE STRUCTURAL
033000.F
10 5/8"
CONCRETE FACED INSULATION
PANEL
POLY-ISO BOARD INSULATION
072100.D
P A
N E
L H
T
V A
R
IE
S
4"
8"
B
A7.2
C O
O R
D W
/M A
N F
2'
M
IN
. C
LR
C
LE
A R
O P
E N
IN
G
7'
C
LE
A R
O P
E N
IN
G
7'
1-HR RATED AT HOISTWAY
SPRAY-APPLIED
FIREPROOFING
078100.A
T R
A V
E L
D
IS
T A
N C
E
HYDRAULIC ELEVATOR
142400
STEEL FRAMING - SEE
STRUCTURAL
PAINT PT-1
PAINT HPC-1
ACOUSTICAL CEILING PANEL
095100.A
REFER CEILING PLANS
ADA CURB RAMP CURB. REFER
STRUCTURAL
B /O
F
IX
T U
R E
7'
HVAC EQUIP - SEE HVAC
230000.C
ROOF
11' - 2"
GROUT FILLED STEEL PIPE
BOLLARD
055000.L
PLASTIC BOLLARD COVER
055000.M
REFER STRUCTURAL.
1/4" RADIUS AT OUTSIDE
EDGES.
REINFORCED CONCRETE SLAB
ON DECKING - SEE
STRUCTURAL
EXISTING CONCRETE
ROOF.
5'
INSULATED METAL WALL
PANELS
074213.C
CONCRETE MASONRY UNIT
042000.A
SIM
A7.2
3-5/8 INCH COLD-FORMED
METAL FRAMING
054000.A
METAL FURRING CHANNEL
092216.B
R-VALUE: 30
SIM
A7.2
FIRST FLOOR
0"
BASEMENT
-11' - 8"
ROOF
11' - 2"
P
IT
D E
P T
H
4'
M
IN
/4
REFER STRUCTURAL
2' - 0"
FOUNDATION DRAIN MAY
OCCUR - SEE STRUCTURAL
CONCRETE FACED INSULATION
PANEL
FLUID-APPLIED WATERPROOFING
071400.A
REINFORCED CONCRETE
FOOTING - SEE STRUCTURAL
CONCRETE MASONRY UNIT
042000.A
SLOPE GRADE AWAY
FROM WALL.
POLY-ISO BOARD INSULATION
072100.D
SIM
A7.2
SIM
A7.2
FIRST FLOOR
0"
BASEMENT
-11' - 8"
ROOF
11' - 2"
CONCRETE MASONRY UNIT
042000.A
BRICK VENEER
042000.C
3'
E X
IS
T
IN
G
T O
R E
M A
IN
EXISTING LOADING
DOCK TO REMAIN
MATCH EXISTING
COLOR AND
COURSING
SCALE: 1/2" = 1'-0"A5.1
PARTIAL BUILDING SECTION - ELEVATOR4
SCALE: 3/4" = 1'-0"A5.1
WALL SECTION3
ISSUES AND REVISIONS
DateNo.
NOTICE
THIS ARCHITECTURAL AND
ENGINEERING DRAWING IS GIVEN
IN CONFIDENCE. NO USE OR
DISSEMINATION MAY BE MADE
WITHOUT PRIOR WRITTEN
CONSENT OF THE ARCHITECT.
ALL RIGHTS ARE HEREBY
SPECIFICALLY RESERVED.
DRAWING NO.
RLB NO.:
CHECKED BY:
DRAWN BY:
Description
C en te r
S t, S ui te
C le ve la nd
O hi o
P ho ne
(2
1-
6)
-8 w w w .r lb a.
co m
© 2026 RICHARD L. BOWEN + ASSOCIATES, INC.
E
LE
V A
T O
R A
D D
IT
IO
N
8/
/2
4:
:1
P
M A ut od es k
D oc s:
//T
A R
T A
D ow nt ow n
T ra ns it
H ub
/A R
C H
_T A
R T
A -D ow nt ow n
T ra ns it
H ub
_1
-0
8.
rv t
T A
R T
A D
O W
N T
O W
N T
R A
N S
IT
H
U B
13828.8
N . H
U R
O N
S T
T
O
LE
D O
, O H
W A
LL
A
N D
P A
R T
IA
L
B U
IL
D
IN
G
S E
C T
IO
N
S
NP
A5.1SCALE: 1/2" = 1'-0"A5.1
WALL SECTION2
SCALE: 3/4" = 1'-0"A5.1
WALL SECTION1
07/17/26 OWNER REVIEW
8" 6'
0"
IG-1 IG-1
A6.1
A6.1
A6.1
A6.1
A6.1
A6.1
A6.1
2" 3' - 3" 3' - 4"
FL
(FULL LITE)
SEE SCHEDULE
1'
6"
6" 6"
S E
E S
C H
E D
U
LE
GENERAL NOTES - DOOR ASSEMBLIES
1. REFER TO SECTION 08 71 00 FOR DOOR HARDWARE SETS, FINISHES, AND PERFORMANCE
REQUIREMENTS.
2. REFER TO DOOR SCHEDULE FOR DOOR PANEL AND FRAME INFORMATION
3. CARD READERS, ELECTRIC STRIKES, AND OTHER ELECTRIFIED HARDWARE MAY OCCUR.
REFER TO ELECTRICAL DRAWINGS FOR CONDUIT ROUGH-IN LOCATIONS.
4. REINFORCE STOREFRONT FRAMING AT EXTERIOR DOOR JAMBS.
5. FURNISH AND INSTALL DOOR HARDWARE, INCLUDING CLOSERS AND THRESHOLDS IN
COMPLIANCE WITH ADA AND BUILDING CODE REQUIREMENTS.
6. CURTAINWALL FRAMING IS FACTORY FINISHED, U.N.O.
7. DOOR AND FRAME FIELD FINISHES SHALL BE SPRAY-APPLIED OR ROLLED TO ELIMINATE
BRUSH MARKS.
8. ALL ACCESS CONTROL DOORS TO BE FAIL-SAFE, U.N.O.
9. REFER TO SPECIFICATIONS FOR ELEVATOR ELEVATOR JAMB FINISH.
5/8 INCH GYPSUM BOARD
092116.A
PAINTED FINISH
3" 7/8" 7 5/8" 2 1/2"
INSULATED METAL WALL
PANELS
074213.C
BASE EXTRUSION
W/WEEP HOLES
CONTINUOUS SEALANT UNDER
CLOSURE FLASHING
BACKER ROD AND SEALANT
079200.B
GLAZED ENTRANCE DOOR
084313.F STEEL LINTEL - SEE
STRUCTURAL
CONCRETE MASONRY UNIT
042000.A
METAL SUB-FRAMING
1/
2"
GROUT SOLID
5/8 INCH GYPSUM BOARD
092116.A
BACKER ROD AND SEALANT -
BOTH SIDES
079200.D
ALUMINUM STOP
GLAZED ENTRANCE DOOR
084313.F
CURTAIN WALL FRAMING
084413.A
2 PIECE EXTRUSION CAP
CONCRETE MASONRY UNIT
042000.A
COLD-FORMED FURRING
CHANNEL
054000.E
4"
5/ 8"
1/
2"
GROUT SOLID.
GYP ABOVE
FINISH FLOOR, REFER TO
FLOOR FINISH PLAN
HC ACCESSIBLE
THRESHOLD SET ON BED OF
CONTINUOUS SEALANT AND
SECURED TO FLOOR SLAB
BOTTOM DOOR SEAL AS
SCHEDULED FOR FIRE-
RATING OR EXTERIOR
WEATHERSEAL
FINISH TYPE CHANGE TYPE
ACROSS DOOR OPENING.
GLAZED ENTRANCE DOOR
084313.F
ALUMINUM STOREFRONT
FRAMING
084313.A
GYP. BD. WALL AND BASE
BEYOND. MITER WALL BASE
AT CORNERS.
INSULATED METAL PANEL
JAMB BYOND
BACKER ROD AND SEALANT -
BOTH SIDES
079200.D
BRAKE METAL TRIM
057500.C
COLOR TO MATCH
STOREFRONT FRAMING
INSULATED GLAZING
088000.E
SILL FLASHING
076200.S
CONCRETE MASONRY UNIT
042000.A
FINISH FLOOR
8"
GROUT SOLID
INSULATED METAL WALL
PANELS
074213.C
CONCRETE MASONRY UNIT
042000.A
5/8 INCH GYPSUM BOARD
092116.A
BACKER ROD AND SEALANT -
BOTH SIDES
079200.D
METAL FURRING CHANNEL
092216.B
COLD-FORMED FURRING
CHANNEL
054000.E
2 PIECE EXTRUSION CAP
ALUMINUM STOREFRONT
FRAMING
084313.A
5/8 INCH GYPSUM BOARD
092116.A
2 PIECE EXTRUSION CAP
PAINTED FINISH
2"
INSULATED METAL WALL
PANELS
074213.C
ALUMINUM STOREFRONT
FRAMING
084313.ABACKER ROD AND SEALANT -
BOTH SIDES
079200.D
INSULATED GLAZING
088000.E
CONCRETE MASONRY UNIT
042000.A
INSULATED GLAZING
088000.E
ALUMINUM STOREFRONT
FRAMING
084313.A
GLAZED ENTRANCE DOOR
084313.F
ALUMINUM STOP
SCALE: 3" = 1'-0"A6.1
HEAD DETAIL6
SCALE: 3" = 1'-0"A6.1
JAMB DETAIL4
SCALE: 3" = 1'-0"A6.1
SILL DETAIL2
SCALE: 3" = 1'-0"A6.1
JAMB DETAIL5
SCALE: 3" = 1'-0"A6.1
HEAD DETAIL7
SCALE: 1/4" = 1'-0"
CW-1 (EXTERIOR) ROOF
ISSUES AND REVISIONS
DateNo.
NOTICE
THIS ARCHITECTURAL AND
ENGINEERING DRAWING IS GIVEN
IN CONFIDENCE. NO USE OR
DISSEMINATION MAY BE MADE
WITHOUT PRIOR WRITTEN
CONSENT OF THE ARCHITECT.
ALL RIGHTS ARE HEREBY
SPECIFICALLY RESERVED.
DRAWING NO.
RLB NO.:
CHECKED BY:
DRAWN BY:
Description
C en te r
S t, S ui te
C le ve la nd
O hi o
P ho ne
(2
1-
6)
-8 w w w .r lb a.
co m
© 2026 RICHARD L. BOWEN + ASSOCIATES, INC.
E
LE
V A
T O
R A
D D
IT
IO
N
8/
/2
4:
:1
P
M A ut od es k
D oc s:
//T
A R
T A
D ow nt ow n
T ra ns it
H ub
/A R
C H
_T A
R T
A -D ow nt ow n
T ra ns it
H ub
_1
-0
8.
rv t
T A
R T
A D
O W
N T
O W
N T
R A
N S
IT
H
U B
13828.8
N . H
U R
O N
S T
T
O
LE
D O
, O H
D O
O R
A N
D F
E N
E S
T R
A T
IO
N
E
LE
V A
T
IO
N
S C
H E
D U
LE
, A
N D
D E
T A
IL
S
NP
A6.1
DOOR, FRAME & HARDWARE SCHEDULE - ELEVATOR
TAG ROOM NAME ROOM #
SLAB INFORMATION FRAME INFORMATION DETAIL DESIGNATIONS
HDWR
SET
ELECTRONIC / MAGNETIC HINGES EGRESS STOPS
RATE
D APPURTENCES EXTERIOR
NOTES TAGTHICKNESS TYPE MATERIAL FINISH GLAZING TYPE MASONRY
OPENING
DEPTH MATERIAL FINISH HEAD JAMB SILL C
A
R D
R E
A D
E R
E L
E C
T R
IC
S
T R
IK
E
P O
S . S
W
IT
C H
P O
W E
R S
U P
P L
Y
P O
W E
R T
R A
N S
F E
R
W
IR
IN
G
H A
R N
E S
S
M O
R T
IS
E
P
A
IR
C O
N T
IN
U
O U
S
E X
IT
D
E V
IC
E
C L
O S
E R
W A
L L
O V
E R
H E
A D
S P
R
IN
G
S M
O K
E S
E A
L
A C
O U
S T
IC
S
E A
L
K
IC
K P
L A
T E
A S
T R
A G
A L
F L
U S
H B
O L
T
T H
R E
S H
O L
D
W E
A T
H E
R S
T R
IP
S W
E E
P
WIDTH HEIGHT
ROOF
155 ELEV. LOBBY 155 1 3/4" FL GL/ALUM BLACK ANOD. IG-1 CW 3' - 0" 7' - 4" ALUM BLACK ANOD. 6/A6.1 3/A6.1 & 4/A6.1
1/A6.1 01 Yes Yes Yes Yes Yes Yes 1.5 No Yes PUSH No Yes No Yes No No No No Yes Yes Yes 155
SCALE: 1/4" = 1'-0"
DOOR TYPE LEGEND
SCALE: 3" = 1'-0"A6.1
SILL DETAIL - EXTERIOR STOREFRONT1
SCALE: 3" = 1'-0"A6.1
MULLION DETAIL3
GLAZING SCHEDULE
TAG DESCRIPTION SPEC REFERENCE
IG-1 1" INSULATED GLASS 088000.E
07/17/26 OWNER REVIEW
A
LI
G N
A
LI
G N
C
A
A5.1
A7.19A7.1 10
A7.1
ELEV.
LOBBY
A7.1
1' - 4 1/2" 10' - 3"
GROUT FILLED STEEL PIPE
BOLLARD
055000.L
GROUT FILLED STEEL PIPE
BOLLARD
055000.L
8'
/8
9'
/8
5'
6'
R2' - 0" R2' - 0"
2'
0"
1' - 6" 1' - 6"
5' - 0" 6' - 0" 5' - 0"
/8
19' - 9"
REINFORCED CONCRETE SLAB
ON GRADE - SEE STRUCTURAL
033000.A
SLOPE AWAY FROM LOBBY
DOOR IN COORDINATION WITH
EXISTING ROOF SLOPES
CLEAR HOISTWAY
8'-4" MIN.
A5.12
A5.1
9 1/4"
REFER ELEVATIONS
ODOT-COMPLIANT ADA
CURB RAMP. REFER
STRUCTURAL DWGS.
0'-6"
MODIFY EXISTING HANDRAIL
TO TERMINATE AT NEW
WALL, BOTH SIDES.
A7.2
A5.1
GROUT FILLED STEEL PIPE
BOLLARD
055000.L
GROUT FILLED STEEL PIPE
BOLLARD
055000.L
CW1
ELEVATOR
EL-1
B
M7
F4P
F4P
F1P
1' - 6" 1' - 6"
7'
3/A9.0
5'
/A
.0
9/A9.07/A9.0
F1P
FIRST FLOOR
0"
ROOF
11' - 2"
A
A5.1
A5.1
IMP-1
MTL-1
EXISTING PARAPET WALL TO
REMAIN. PATCH AND PAINT ANY
AREAS DAMAGED BY
CONSTRUCTION TO MATCH
ADJACENT EXITING
MATCH EXISTING
GRADE
MTL-7
3' - 0" 3' - 0" 3' - 0" ± 1' - 7 7/8"
HDPE-1
CONCRETE CURB.
REFER STRUCTURAL
DWS.
PANEL JOINTS
7'
PC-1
B
EQ. EQ.
PRE-FORMED CORNER
PR-FORMED CORNER
FIRST FLOOR
0"
ROOF
11' - 2"
A 2
A5.1
A5.1
GROUT FILLED STEEL PIPE
BOLLARD
055000.L
CONCRETE CURB. REFER
STRUCTURAL DWS.
HDPE-1
MTL-7
IMP-1
MTL-1
MATCH EXISTING GRADE
± 1' - 7 7/8" 3' - 0" 3' - 0" 3' - 0"
EXISTING PARAPET WALL TO
REMAIN. PATCH AND PAINT ANY
AREAS DAMAGED BY
CONSTRUCTION TO MATCH
ADJACENT EXITING
PC-1
7'
B
EQ. EQ.
PRE-FORMED CORNER
PRE-FORMED CORNER
PANEL JOINTS
ROOF
11' - 2"
A5.1
CW1
PANEL JOINTS
IMP-1
HDPE-1
HDPE-1
3' - 4"3' - 5"
AL-1
A
LI
G N
P A
N E
L
JO
IN
T
W /O
P E
N
IN
7'
7'
/4
4"
MTL-1
PRE-FORMED CORNER
PRE-FORMED CORNER
6"
ADA ACTUATOR
A
EQ EQ
EQ EQ
E Q
3'
/8
E
Q
PENDANT LIGHT FIXTURE - SEE
ELECT.
260000.D
6'
8'
1/ 4"
2' - 4"
CLEAR HOISTWAY
8' - 4"
ELEV.
LOBBY
O.T.S.
ELEVATOR
EL-1
B
CLEAR HOISTWAY
8' - 4"
FIRST FLOOR
0"
ROOF
11' - 2"
A5.1
MODIFY EXISTING HANDRAIL
TO TERMINATE AT NEW
WALL, BOTH SIDES.
MATCH EXISTING GRADE
IMP-1
MTL-1
MTL-7
EQ EQ
PANEL JOINT
PREFABRICATED
CORNER PANEL
PC-1
BRICK INFILL. ALIGN
COURSING WITH EXISTING
ADJACENT BRICK
7'
E Q
E Q
2'
BR-1
V .I.
F
4'
/8
A
A5.1
A7.19A7.1 10
A7.1
A5.1W A
LL
-W
A
LL
6'
ELEVATOR
LOBBY
A7.2
CLEAR HOISTWAY
8' - 4"
ELEVATOR
EL-1
M8
CLEAR OPENING
3' - 6"
F6
A
A5.1
A5.1
SIM
A7.2
ELEVATOR
EL-1
M8 1
CLEAR OPENING
3' - 6"
CORRIDOR
140A
W A
LL
W A
LL
6'
CLEAR HOISTWAY
8' - 4"
A
A5.1
A5.1
A5.1
/2
10' - 3"
/4
EQ EQ
PANEL JOINT. ALIGN WITH VERTICAL
PANEL JOIN ON SOUTH FACADE.
REFER STRUCTURAL
LAP SEAM, INSULATED ROOF
PANELS
074116.A
GUTTER
074116.H
DOWNSPOUT
074116.J
/2
B
GENERAL NOTES - EXTERIOR ELEVATIONS
1. REFER TO MATERIALS SCHEDULE FOR MATERIAL TAG DESCRIPTIONS.
2. PATCH AND PAINT ANY AREAS DAMAGED BY CONSTRUCTION TO MATCH ADJACENT EXISTING.
3. "SN-#" REFERS TO SIGNAGE.
ISSUES AND REVISIONS
DateNo.
NOTICE
THIS ARCHITECTURAL AND
ENGINEERING DRAWING IS GIVEN
IN CONFIDENCE. NO USE OR
DISSEMINATION MAY BE MADE
WITHOUT PRIOR WRITTEN
CONSENT OF THE ARCHITECT.
ALL RIGHTS ARE HEREBY
SPECIFICALLY RESERVED.
DRAWING NO.
RLB NO.:
CHECKED BY:
DRAWN BY:
Description
C en te r
S t, S ui te
C le ve la nd
O hi o
P ho ne
(2
1-
6)
-8 w w w .r lb a.
co m
© 2026 RICHARD L. BOWEN + ASSOCIATES, INC.
E
LE
V A
T O
R A
D D
IT
IO
N
8/
/2
4:
:1
P
M A ut od es k
D oc s:
//T
A R
T A
D ow nt ow n
T ra ns it
H ub
/A R
C H
_T A
R T
A -D ow nt ow n
T ra ns it
H ub
_1
-0
8.
rv t
T A
R T
A D
O W
N T
O W
N T
R A
N S
IT
H
U B
13828.8
N . H
U R
O N
S T
T
O
LE
D O
, O H
E N
LA
R
G E
D E
LE
V
A T
O R
P
LA
N S
E
LE
V A
T
IO
N S
, A N
D D
E T
A
IL
S
NP
A7.1
SCALE: 1/4" = 1'-0"A7.1
ENLARGED ELEVATOR PLAN - ROOF LEVEL3
SCALE: 1/4" = 1'-0"A7.1
PARTIAL EXTERIOR ELEVATION - EAST9
SCALE: 1/4" = 1'-0"A7.1
PARTIAL EXTERIOR ELEVATION - WEST10
SCALE: 1/4" = 1'-0"A7.1
PARTIAL EXTERIOR ELEVATION - NORTH7
SCALE: 1/4" = 1'-0"A7.1
ELEVATOR AREA REFLECTED CEILING PLAN4
SCALE: 1/4" = 1'-0"A7.1
PARTIAL EXTERIOR ELEVATION - SOUTH8
SCALE: 1/4" = 1'-0"A7.1
ENLARGED ELEVATOR PLAN - FIRST FLOOR2
SCALE: 1/4" = 1'-0"A7.1
ENLARGED ELEVATOR PLAN - BASEMENT LEVEL1
SCALE: 1/4" = 1'-0"A7.1
ELEVATOR AREA ROOF PLAN5
EXTERIOR FINISH SCHEDULE
TAG DESCRIPTION COLOR
SPEC
REFERENCE
AL-2 STOREFRONT FRAMING TBD…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .