Technical Characteristics FINAL

Technical Characteristics for DOS A-LM Transformers under SBE10017Q5000
Mandatory Technical Compliance "Pass/Fail" Criteria (Ref. M-001)Pass/Fail
1Mandatory Compliance220/240VAC to 110/120VAC
2Auto-Transformer with Polarity Warning* OR Isolation Transformer
3Transformer itself possesses label with UL listed or UL recognized symbols or independent testing agency equivalent ***
4European three-prong SCHUKO plug
5Single Phase
Technical Characteristics
1Ground Fault Interrupter (GFI) safety feature or comparable will discontinue input power if any ground fault current or 10 mA or more is sensed**
2Maximum Wattage: 1000, 2000 (Offer must meet wattage requirements for all line items)
3Unit is thermally protected
4Portable based on handle, size and weight (Offer must provide dimensional specifications and picture)
5Polarity warning light is clearly labeled "Light On, Polarity Reversed" or comparable*
Failure to meet these specifications will result in an unacceptable rating
Notes:
* Polarity warning light must be clearly labeled on the unit "Light on, Polarity Reversed or comparable"
* Unit that is provided with a Green Polarity OK light is acceptable. Must be labeled. Red polarity OK light is not acceptable.
** To prevent potential shock hazards, customer requires a two-pole Ground Fault Interrupter (GFI) safety feature that will
discontinue the supply of input power to the voltage converter unit if any ground fault current or 10 mA or more is sensed.
**The GFI device shall be wired to sense ground fault current paths related to the unit’s metallic components as well as any ground fault
paths via connected appliances plugged into the unit’s output receptacles.
*** If other independent listing agency is used, TÜV, CSA, VDE, online verification site information must be provided.
***GOV reserves the right to accept or reject independent agency listing if NOT verifiable online, i.e.. www.ul.com/database , https://www.tuev-sued.de/product-testing/certificates
***Documentation describing labeling as "UL accepted", "UL approved", or "UL certified" alone will not be accepted. The unit must be appropriately marked.
***CE is not a recognized independent testing agency and will not be accepted.
***The submitted technical data must be verifiable against publically available/online information.
Expected Characteristics and Operating Conditions
All internal wiring should be color coded .
All internal wiring should be temperature rated to withstand heat generated from transformer.
The transformer should be suitable for ambient operation between -5 degree C to 40 degree C.
The transformer windings should be copper not aluminum conductors.
The wiring sizes shall be provided to carry the current carrying capacity of the transformer rating size.
The transformer should rest on raised non-conducting feet of minimum 2cm to assure no contact with the set up surface.

One transformer must be provided with quote for physical inspection and testing in accordance with FAR 52.214-20 Bid Samples