This is an Addendum No. 02 to a Request for Proposal (RFP) issued by the Michigan Department of Technology, Management and Budget (DTMB), State Facilities Administration Design and Construction Division, for the Detroit Lab–Northville Lab Relocation project (File Number 551_26434.MNB). The addendum extends the RFP due date to October 8th, 2026, and allocates $4,000 in reimbursables within the design phase for asbestos and lead testing in demolition areas. The document provides detailed technical specifications and schedules related to the Michigan State Police Metropolitan Detroit Forensic Science Laboratory project, including electrical, mechanical, and plumbing design drawings. The attachments include floor plans for Part A and Part B, a bidders conference attendance record dated September 15, 2026, and twelve electrical, mechanical, and plumbing schedules (SmithGroup sheet numbers E0.2, E7.1, E7.2, E7.3, E7.4, E7.5, M5.1, M5.2, M7.1, M7.2, M7.3, and P5.1). The addendum was issued on September 24, 2026, and approved by Project Director Chris M. Bahjet.
The technical specifications encompass comprehensive MEP (mechanical, electrical, and plumbing) design documentation for a forensic science laboratory relocation. The electrical schedules detail lighting fixtures, mechanical equipment, and panel schedules with specific voltage ratings, amperage requirements, and circuit configurations across multiple locations. Mechanical schedules include HVAC systems such as rooftop units (RTU-6 through RTU-9), exhaust fans, supply fans, heating hot water systems with boilers and pumps, volume control boxes, and steam generators. Plumbing specifications cover domestic water riser diagrams with detailed pipe sizing, fixture locations, and water distribution systems across multiple floors. The design incorporates laboratory-specific systems including fume hoods, specialized HVAC controls, and equipment for crime laboratory operations. All schedules reference the project number 551/12270.DCS and include revision dates through July 26, 2013, with addendum updates through July 10, 2013.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFP Billable Rate (Rev 2-26) 26434.pdf | ||
| RFP Addeudm #1 551_26434_MNB.pdf | ||
| Project Statement 26434.pdf | ||
| SAMPLE Billable Rate Contract (Rev 04-25).pdf | ||
| Mechanical Equipment 26434.xlsx | XLSX spreadsheet | |
| Addendum 1 - Mechanical Equipment 26434.xlsx | XLSX spreadsheet |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DTMB-0414 RFP (Rev 2/22)
DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET
State Facilities Administration Design and Construction Division
REQUEST FOR PROPOSAL
ADDENDUM NO. 02
This form identifies an Addendum to a Request for Proposal for Professional Services, and incorporates interpretations or clarifications, modifications, and other information into the Request for Proposals.
Addenda will be numbered by the Project Director and distributed through SIGMA Vendor VSS as an attachment.
TO:
ALL PROPOSERS
DATE ISSUED
9/24/2026
PROJECT NAME
Detroit Lab- Northville Lab Relocation
FILE NUMBER
551_26434.MNB
PROJECT DIRECTOR
Mustaf (Chris) Bahjet
PROPOSAL DUE DATE:
October 8th, 2026
ADDENDUM ITEMS:
Consider the following as part of the request for proposal.
1. Extend RFP due date to October 8th, 2026.
2. Allocate $4,000 as reimbursables in any design phase as you see fit to perform asbestos and lead testing in the areas where there will be demolition.
3 Attachments.
A. Floor Plans for part A & part B.
B. Attendance record.
C. Twelve electrical, mechanical and plumbing schedules. SmithGroup sheet numbers, E0.2, E7.1, E7.2, E7.3, E7.4, E7.5, M5.1, M5.2, M7.1, M7.2, M7.3 & P5.1.
APPROVED BY: PROJECT DIRECTOR Chris M. Bahjet
DATE 9/24/2026
http://www.buy4michigan.com/
Space A
Space B
DTMB 517-879-6789
FEEDER & BRANCH CIRCUIT SIZING SCHEDULE -
NONLINEAR LOADS
DRAWING NOTES
(FOR 460V., 3 PHASE MOTORS) (NOTES 3,4,5)
MOTOR CIRCUIT SIZING SCHEDULE
FEEDER & BRANCH CIRCUIT SIZING SCHEDULE -
GENERAL PURPOSE
TRANSFORMER CIRCUIT SIZING SCHEDULE - GENERAL PURPOSE TYPE
(NOTE 8)
TRANSFORMER CIRCUIT SIZING SCHEDULE -NONLINEAR LOAD TYPE
(NOTE 8)
120V. SINGLE PHASE CIRCUIT LENGTH TABLE208V. SINGLE PHASE CIRCUIT LENGTH TABLE 208V. THREE PHASE CIRCUIT LENGTH TABLE
480V., THREE PHASE CIRCUIT LENGTH TABLE
(FOR 208V., 3 PHASE MOTORS NOTES 3,4,5)
MOTOR CIRCUIT SIZING SCHEDULE
277V. SINGLE PHASE CIRCUIT LENGTH TABLE
CONDUIT SIZE
3/4"
3/4"
2 1/2"
1"(1 1/4")
1"(1 1/4")
2 1/2"
3 1/2"
3-3 1/2"
2-3 1/2"
6-3 1/2"
5-3 1/2"
4-3 1/2"
2-2 1/2"
1 1/4"(1 1/2")
2-3"
1 1/2"
2-4"
5 WIRE
(NOTE-7)
2-4"
175 2/0 6 2"
2-1/0
2-1/0
3-2/0
4-3/0
6-250
5-4/0
6-400
2-500
2-500
3-400
4-350
5-400
6-3"
2-3 1/2"
5-3"
4-3"
3-3"
2-3 1/2"
2-2
2-2
2-1
350 500
2-4/0
2-250
2-350
3/0
4/0
3 1/2"
2-2 1/2"
2-3"
2-3"
4"
2 1/2"
3"
3"
2"
15-20
25-30
35-40
45-50
80-90
OVERCURRENT
DEVICE RATING
(AMPERES)
108 3/4"
3(2)
2(1)
1(1/0)
1/0
6(4)
6(4)
4(2)
8(6)
1 1/4"
1 1/2"
1 1/2"(2")
2"
1 1/4"
1"(1 1/4")
1"(1 1/4")
3/4"(1")
E.G.
WIRE SIZE - AWG OR KCMIL
PHASE
& NEUTRAL
3/4"
3/4"
4 WIRE
(2PH & 2N)
25A., 3W.
45A., 3W.
70A., 3W.
125A., 3W.
175A., 3W.
350A., 3W.
225A., 3W.
112 1/2
200/175A.
400/350A.
400/225A.
30/25A.
60/45A.
100/70A.
200/125A.
100/100A.
400/400A.
200/175A.
400/300A.
600/600A.
800/800A.
60/60A.
400A., 5W.-NL
600A., 5W.-NL
800A., 5W.-NL
60A., 5W.-NL
100A., 5W.-NL
175A., 5W.-NL
300A., 5W.-NL
400A
300A
225A
225A
200A
PRIMARY CIRCUIT (480V.)
PRIMARY FEEDER
20A., 3W.
25A., 3W.
45A., 3W.
70A., 3W.
125A., 3W.
175A., 3W.
350A., 3W.
225A., 3W.
PRIMARY FEEDER
20A., 3W.
9 30/20A.
TRANSF. KVA
9 30/20A.
112 1/2
200/175A.
400/350A.
400/225A.
30/25A.
60/45A.
100/70A.
200/125A.
TRANSF. KVA
SWITCH/FUSE OR
CIRCUIT BREAKER
200/200A.
200/200A.
400/250A.
400/350A.
100/100A.
200/125A.
100/80A.
200/150A.
175A
150A
125A
30A., 4W.30/30A.
SWITCH/FUSE OR
CIRCUIT BREAKER
30/30A.
SECONDARY FEEDER
30A., 5W.-NL
100/100A.
400/400A.
200/175A.
400/300A.
600/600A.
800/800A.
60/60A.
400A., 4W.
600A., 4W.
800A., 4W.
100A., 4W.
60A., 4W.
175A., 4W.
300A., 4W.
SECONDARY CIRCUIT (208/120V.)
SWITCH/FUSE OR
CIRCUIT BREAKER
2/04
3/0
4/0
1/0
6 2"
2 1/2"
3"
2"
6 1 1/2"
1 1/2"
1 1/2"
1 1/2"
1. BASED ON THHN/THWN, 90°., 600V., INSULATED, COPPER WIRE APPLIED
AT 75°FOR TERMINATIONS RATED AT 60°C/75°C AND 75°C. FOR
TERMINATIONS RATED AT 60°C PROVIDE WIRE AND CONDUIT SIZES
INDICATED IN PARENTHESIS.
2. BASED ON WIRE OUTSIDE DIAMETERS AND RIGID METALLIC CONDUIT
INSIDE DIAMETERS
3. AS PROVIDED IN THE NEC. DO NOT REDUCE CONDUIT SIZE FOR NON-
RIGID METALLIC APPLICATION. REFER TO NEC FOR CONDUIT TYPES
MORE RESTRICTIVE THAN RIGID
4. METALLIC.
5. BASED ON MOTOR FULL LOAD AMPERES AS PROVIDED BY THE NEC.
6. BASED ON MOTOR RUNNING OVERLOAD PROTECTION PROVIDED BY
THERMAL OVERLOAD RELAYS.
7. MOTOR STARTING TYPE BASED ON 460V., 3 PHASE, FULL VOLTAGE NON-
REVERSING EXCEPT FOR MOTORS SIZED 75HP OR GREATER WHICH ARE
BASED ON 460V., 3 PHASE, PART WINDING REDUCED VOLTAGE
STARTING.
8. TRANSFORMER CIRCUITS BASED ON 480V TO 208/120V., 3 PHASE, 4
WIRE,DRY TYPE.
9. PROVIDE THREE PHASE WIRES AND ONE DOUBLE AMPACITY NEUTRAL
FOR 110 AMPACITY CIRCUITS AND LESS. PROVIDE THREE PHASE WIRES
AND TWO NEUTRAL WIRES, SIZES AS INDICATED FOR 125 AMPACITY
CIRCUITS AND GREATER.
CIRCUIT SIZING SCHEDULES NOTES:
175 2/0 6 1 1/2"2 1/2" 2" 2"2"
BREAKER
CIRCUIT
1 1/2"
2 1/2"
2-2 1/2"
3-2 1/2"
4-2 1/2"
5-2 1/2"
6-2 1/2"
1 1/2 30/6A.
7 1/2
35A30/25A.
30/30A.
60/40A.
60/50A.
60/60A. 100A
75A
60A
50A
30/10A.
30/15A.
30/20A.
30/6A.
30A
20A
15A
SWITCH/FUSEMOTOR HP
3/4
1/2
30/3A.
30/3A.
30/6A.
4-3 1/2"
6-4"
2-4"
5-4"
3-4"
2-4"
4" 4"
4"
2-3 1/2"
4"
2-3"
2-3"
3"
3 1/2"
2 1/2"
3"
3"
2-500
2-600
3-400
4-350
5-400
6-4002000
1600 5-4/0
6-250
2-1/0
2-1/0
3-2/0
4-3/0
2-3"
2-3"
3/0
4/0
2-4/0
2-250
2-350
3"3
2-2
2-2
2-1
3 3"
2-2"
2-2"
2"
2"
12 12 3/4"1
10 3/4"
3/4"
1"
1"
3/4"
3/4"
3/4"
3/4"
3/4"
STARTER
SIZE/TYPE
PHASE
CONDUIT & WIRE
E.G.
CONDUIT
3/4"
3/4"
3/4"
6-3"
3-3"
4-3"
5-3"
2-3"
2-3"
6-3"
2-3 1/2"
3-3"
4-3"
5-3"
2-4"
3"
2-2 1/2"
4"
2-2"
2-3"
2 1/2"
3"
2"
2"
3 1/2"
2-2 1/2"
2-3"
4"
2-2 1/2"
2 1/2"
3"
2"
2 1/2"
3/4"(1")
3/4"(1")
3/4"
3/4"
3/4"
3/4"
1"(1 1/4")
1 1/4"
1 1/4"
1 1/4"
2 WIRE
1" 1"
1 1/4"(1 1/2")
2"
2"
2" 2"
2"
2"
1 1/2"
1"
1 1/4"
1 1/4"
1"(1 1/4")
3/4"
3/4"
6 WIRE
(3PH & 3N)
NOTE
10835-40
8(6)
6(4)
6(4)
4(2)
3(2)
2(1)
1/0
1(1/0)125
45-50
80-90
8 1"
PHASE
& NEUTRAL
WIRE SIZE - AWG OR KCMIL
15-20
25-30
OVERCURRENT
DEVICE RATING
(AMPERES) E.G.
3/4" 3/4"
1 1/4"(1 1/2")1 1/4"(1 1/2")
1 1/2"
1 1/2"
1 1/4"
3/4"(1")
3/4"(1")
3/4"
1"(1 1/4")
2"
1 1/2"(2")
1 1/4"
1"(1 1/4")
1"(1 1/4")
1 1/4"
3/4"(1")
CONDUIT SIZE
3/4"
3/4"
3 WIRE
3/4"
3/4"
4 WIRE
(3PH & 1N)
NOTE
1000A., 4W.300 500A., 3W.600/500A. 1200/1000A.
CIRCUIT BREAKER
SWITCH/FUSE OR
1307 1165907480600
NO.8
MAXIMUM LENGTH IN FEET
CIRCUIT MAXIMUM DISTANCE TABLES
1. CIRCUIT MAXIMUM DISTANCE IS BASED ON NEC CHAPTER 9,
TABLE 8 CONDUCTOR PROPERTIES FOR COATED COPPER
CONDUCTORS AT 75 DEGREES CELSIUS.
2. MAXIMUM CIRCUIT LOAD FOR DISTANCE IS BASED ON NEC 220-
10(b)
486020260 48 - --
NOTES:
LOAD(AMPS)LOAD(AMPS)
-24
-40
NO.8
NO.12
(AMPS)
NO.10
16 151
405255
243153
191 304
- 58
20-
NO.4
NO.6
607382
110 174
NO.12
NO.10
(AMPS)
73 116
MAXIMUM LENGTH IN FEET
14401800
AMPACITY
BREAKER
MAX.
CIRCUIT
AMPACITY
BREAKER
MAX.
CIRCUIT
2344860117- -- --
LOAD(AMPS)
11624 -
NO.4
NO.6
NO.10
(AMPS)
NO.12
23312
294 468
177 281
221 351139
NO.6
NO.4
NO.8
MAXIMUM LENGTH IN FEET
BREAKER
AMPACITY
CIRCUIT
MAX.
13461120 999
11771089
1137- 980-
818 102980100 650
200250
240300
350 280
777-
MAXIMUM LENGTH IN FEET
509-
(AMPS)
CIRCUIT
MAX.
LOAD
AMPACITY
BREAKER
(AMPS)
NO.6
NO.10NO.12
269-
403253
NO.8
739-
1/0
NO.2NO.4
NO.1 2504/0
3/02/0
10431569 -
-1107869
9491120 745 1110
1569 -
4-350
2-2502-4/02-3/0
3-4002-500 3-300
2-350
6-5005-400 6-400
2-2 1/2"
2-2"
2"
2"
1"
2-4
2-4
2-4
600/500A.
200/125A.
100/100A.
60/60A.
60/50A.
60/40A.
30/10A.
30/10A.
20A
15A
15A
15A
15A
15A
CONDUIT & WIRE
E.G.
CONDUIT
3/4"
3/4"
3/4"
BREAKER
CIRCUIT STARTER
SIZE/TYPE
PHASE
SWITCH/FUSE
3/4
1/2
30/4A.
30/6.25A.
30/8A.
MOTOR HP
10 3/4"
3/4"
3/4"
3/4"
3/4"
60A
50A
35A
1 1/2"
1 1/2"
1"
1"
250A
200A
175A
3/0
1/0
4/0
125A
110A
100A
90A 6 10 3/4"
7 1/2
30/17.5A.
30/25A.
200/200A.
400/250A.
200/175A.
20 100/90A.
3"
2-2"
800A
600A
500A
400A
300A
2-4/0
2-250
2-400
400/400A.
600/600A.
400/300A.
1 1/2 3/4"
SYSTEM/EQUIPMENT
BONDING JUMPER
(GROUND WIRE)
#8
#8
#8
#4 #2
#1/0
#2/0
#3/0
#3/0
SECONDARY FEEDER
SYSTEM/EQUIPMENT
BONDING JUMPER
(GROUND WIRE)
#8
#8
#8
#4 #2
#1/0
#2/0
#3/0
15A
15A
15A
15A
15A
(AMPS)
NO.12
NO.10
MAXIMUM LENGTH IN FEETBREAKER AMPACITY
PRIMARY CIRCUIT (480V.) SECONDARY CIRCUIT (208/120V.)
DRAWING NUMBER
PROJECT NUMBER
SCALE
DRAWING TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
Pl ot
D at e:
MICHIGAN STATE POLICE
METROPOLITAN DETROIT
FORENSIC SCIENCE LABORATORY
500 GRISWOLD
SUITE 1700
DETROIT, MI 48226
313.983.3600 www.smithgroupjjr.com
DTMB PROJECT NUMBER:
551/12270.DCS
7/
/2
4:
:5
PM
ELECTRICAL
SCHEDULES
E0.2 22580.322
LIGHTING FIXTURE SCHEDULE - CRIME LAB
TYPE DESCRIPTION MANUFACTURER MODEL LOAD LAMP VOLTAGE MOUNTING COMMENTS
F1 2X4 FLUORESCENT DIRECT/INDIRECT LITHONIA 2AV 64 VA 2-32W T8 277 V RECESSED DIMMING BALLAST WHERE INDICATED
F1A SAME AS "F1" EXCEPT 3 LAMPS 96 VA 3-32W T8 277 V RECESSED
F2 2X4 FLUORESCENT TROFFER LITHONIA GT8 64 VA 2-32W T8 277 V RECESSED ACRYLIC PRISMATIC LENS
F2A SAME AS "F2" EXCEPT 120V 64 VA 2-32W T8 120 V RECESSED
F3 6" ROUND LENSED DOWNLIGHT LITHONIA LF6N 32 VA 1-32W TRT 277 V RECESSED
F3A SAME AS "F3" EXCEPT WITH DIMMING BALLAST 32 VA 1-32W TRT 277 V RECESSED
F3B SAME AS "F3" EXCEPT 120V 32 VA 1-32W TRT 120 V RECESSED
F4A 8" ROUND LENSED SHOWER LIGHT LITHONIA LF8N 32 VA 1-32W TRT 120 V RECESSED U.L. WET LABEL F5 4' FLUORESCENT INDUSTRIAL LITHONIA L232 64 VA 2-32W T8 277 V SUSPENDED WIRE GUARD
F5A SAME AS "F5" EXCEPT 120V. 64 VA 2-32W T8 120 V SUSPENDED
F6 4' STAGGERED LINEAR FLOURESCENT COVE LIGHT WILLIAMS 72SS6 64 VA 2-32W T8 277 V RECESSED INSTALL IN COVE
F6A SAME AS "F6" EXCEPT 3' LENGTH 50 VA 2-25W T8 277 V RECESSED
F6B SAME AS "F6" EXCEPT 2' LENGTH 34 VA 2-17W T8 277 V RECESSED
F6C SAME AS "F6" EXCEPT 120V 64 VA 2-32W T8 120 V RECESSED
F7 6' FLUORESCENT DIRECT/INDIRECT COOPER PANELIT 52DIP 64 VA 2-32W T8 277 V SUSPENDED 2 LAMPS PER CROSS SECTION; MOUNT 18"
BELOW CEILING U.O.N.; DIMMING BALLAST
F8 4' FLUORESCENT ENCLOSED WRAPAROUND LITHONIA DMW 64 VA 2-32W T8 277 V SUSPENDED
F8A SAME AS "F8" EXCEPT 120V 64 VA 2-32W T8 120 V SUSPENDED
MEP GMP DESIGN ASSIST PACKAGE 03OCT12
MEP GMP DESIGN ASSIST PACKAGE 03MAR13
STATUS SET 17APR13
50% CD 21MAY13
ISSUE 3 25JUNE13
PERMIT/CONSTRUCTION SET 26JULY13
DRAWING NUMBER
PROJECT NUMBER
SCALE
DRAWING TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
Pl ot
D at e:
MICHIGAN STATE POLICE
METROPOLITAN DETROIT
FORENSIC SCIENCE LABORATORY
500 GRISWOLD
SUITE 1700
DETROIT, MI 48226
313.983.3600 www.smithgroupjjr.com
DTMB PROJECT NUMBER:
551/12270.DCS
7/
/2
4:
:5
PM
MECHANICAL
EQUIPMENT
SCHEDULE
E7.1 22580.322
MECHANICAL EQUIPMENT SCHEDULE - CRIME LAB
TAG PANEL
CIRCUIT
NUMBER
Motor
VOLTAGE PHASE
TOTAL POWER
LOAD VFD
DISC. SWITCH COMBINATION
STARTER
NEMA SIZE
PHASE & NEUTRAL GROUND CONDUIT
COMMENTSHP1 HP2 AMPS POLES FUSED SETS
NO. OF
WIRES AWG
NO. OF
WIRES AWG SETS SIZE
AC-1 RP-CL1A 16,18 0 0 208 V 1 2912 VA No 30 A 2 1 2 #12 1 #12 1 3/4'' AC-2 RP-3SC 17,19 0 0 208 V 1 2912 VA No 30 A 2 1 2 #12 1 #12 1 3/4'' AC-3 RP-3SC 18,20 0 0 208 V 1 5200 VA No 60 A 2 1 2 #8 1 #10 1 3/4''
ACCU-1 RP-CL1A 16,18 0 0 208 V 1 0 VA No 30 A 2 1 2 #12 1 #12 1 3/4'' PACKAGE UNIT ACCU-2 RP-3SC 17,19 0 0 208 V 1 0 VA No 30 A 2 1 2 #12 1 #12 1 3/4'' PACKAGE UNIT ACCU-3 RP-3SC 18,20 0 0 208 V 1 0 VA No 30 A 2 1 2 #12 1 #12 1 3/4'' PACKAGE UNIT
B-1 RP-PENT1A 10 0 0 120 V 1 200 VA No 1 2 #12 1 #12 1 3/4'' B-2 RP-PENT1A 12 0 0 120 V 1 200 VA No 1 2 #12 1 #12 1 3/4''
BCU-1 PP-P2S1B 6 1.5 0 480 V 3 20563 VA No 60 A 3 1 3 #8 1 #10 1 3/4'' BCU-2 PP-P2S1B 4 3 0 480 V 3 75715 VA No 30 A 3 1 3 #1/0 1 #12 1 1 1/2''
COMP-1 PP-P2S1B 5 5 0 480 V 3 6057 VA No 30 A 3 1 3 #12 1 #12 1 3/4'' DWH-1 PP-P2S1B 8 0 0 480 V 3 24000 VA No 60 A 3 1 3 #12 1 #10 1 3/4'' EF-1 PP-P2S1B 7 0 0 480 V 3 0 VA No 30 A 3 1 3 #12 1 #12 1 3/4'' EF-1 PP-P2S1B 7 0.63 0.75 480 V 3 1275 VA No 1 3 #12 1 #12 1 3/4'' EF-2 RP-3SA 21 0.16 0.25 120 V 1 529 VA No 30 A 2 1 2 #12 1 #12 1 3/4'' EF-3 RP-CL1A 15 0.217 0.25 120 V 1 667 VA No 1 2 #12 1 #12 1 3/4'' EF-4 RP-CL1A 15 0.217 0.25 120 V 1 667 VA No 1 2 #12 1 #12 1 3/4''
HHWP-1 PP-4 1 5 0 480 V 3 6057 VA Yes 30 A 3 1 3 #12 1 #12 1 3/4'' HHWP-2 PP-4 2 5 0 480 V 3 6057 VA Yes 30 A 3 1 3 #12 1 #12 1 3/4'' HHWP-3 PP-4 3 1.5 0 480 V 3 2391 VA Yes 30 A 3 1 3 #12 1 #12 1 3/4'' HHWP-4 PP-4 4 1.5 0 480 V 3 2391 VA Yes 30 A 3 1 3 #12 1 #12 1 3/4'' KEF-1 PP-4SS 2 5 0 480 V 3 6057 VA Yes 30 A 3 1 3 #12 1 #12 1 3/4'' KEF-2 RP-4NA 2 0.25 0 120 V 1 667 VA No 30 A 2 1 2 #12 1 #12 1 3/4'' LEF-1 PP-PENTEM2 8 23.9 25 480 V 3 27098 VA Yes 60 A 3 1 3 #12 1 #8 1 3/4'' LEF-2 PP-PENTEM2 9 23.9 25 480 V 3 27098 VA Yes 60 A 3 1 3 #12 1 #8 1 3/4'' LEF-3 PP-PENTEM2 10 23.9 25 480 V 3 27098 VA Yes 60 A 3 1 3 #12 1 #8 1 3/4'' LEF-4 PP-4 9 13.65 15 480 V 3 16737 VA Yes 60 A 3 1 3 #12 1 #10 1 3/4'' MAU-1 PP-4SS 3 0 0 480 V 3 16064 VA Yes 60 A 3 1 3 #10 1 #10 1 3/4'' PACKAGE UNIT RO-1 PP-P2S1B 9 0 0.75 480 V 3 1330 VA No 30 A 3 1 3 #12 1 #12 1 3/4'' RTU-6 PP-2M2 2 40 0 480 V 3 156212 VA No 400 A 3 1 3 250 kcmil 1 #3 1 2 1/2'' PACKAGE UNIT RTU-7 PP-2M2 3 15 0 480 V 3 200047 VA No 400 A 3 1 3 400 kcmil 1 #3 1 3'' PACKAGE UNIT RTU-8 PP-2M3 1 15 0 480 V 3 200047 VA No 400 A 3 1 3 400 kcmil 1 #3 1 3'' PACKAGE UNIT RTU-9 PP-2M3 2 15 0 480 V 3 200047 VA No 400 A 3 1 3 400 kcmil 1 #3 1 3'' PACKAGE UNIT SGU-1 RP-3SC 30,32,34 0 0 208 V 3 7200 VA No 30 A 3 1 3 #10 1 #12 1 3/4'' SGU-2 RP-3SB 33,35,37 0 0 208 V 3 7200 VA No 30 A 3 1 3 #10 1 #12 1 3/4'' SGU-3 RP-3SB 36,38,40 0 0 208 V 3 7200 VA No 30 A 3 1 3 #10 1 #12 1 3/4'' SGU-4 RP-3SC 37,39 0 0 208 V 1 4160 VA No 30 A 2 1 2 #10 1 #12 1 3/4''
125 A
ISSUE 3 25JUNE13
ADDENDUM 1 10JULY13
SCALE
DRAWING TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
Pl ot
D at e:
MICHIGAN STATE POLICE
METROPOLITAN DETROIT
FORENSIC SCIENCE LABORATORY
500 GRISWOLD
SUITE 1700
DETROIT, MI 48226
313.983.3600 www.smithgroupjjr.com
DTMB PROJECT NUMBER:
551/12270.DCS
7/
/2
4:
:5
PM
ELECTRICAL PANEL
SCHEDULES
E7.2 22580.322
Notes:
Total Est. Demand: 154 A Total Conn.: 161 A
Total Est. Demand: 128.3 kVA Power 27098 VA 80.00% 21678 VA Total Conn. Load: 133.7 kVA
HVAC 106576 VA 100.00% 106576 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 161 A Total Conn. Load: 133.7 kVA
10 LEF-3 3 60 A 60 A 27.1 kVA 9 LEF-2 3 60 A 60 A 27.1 kVA 8 LEF-1 3 60 A 60 A 27.1 kVA 7 Space -- -- -- 0.0 kVA -- 6 Space -- -- -- 0.0 kVA -- 5 Space -- -- -- 0.0 kVA -- 4 Spare 3 -- 30 A 0.0 kVA 3 CU-803 3 30 A 25 A 14.1 kVA 2 CU-802 3 30 A 30 A 19.1 kVA 1 CU-801 3 30 A 30 A 19.1 kVA
CKT Circuit Description # of Poles Switch Fuse Load Remarks
Enclosure: Type 1 Mounting: Surface Wires: 3 Mains Rating: 200 A
Supply From: PP-1C1 (NORTH) Phases: 3 Mains Type: MLO Location: MECHANICAL 801 Volts: 480 A.I.C. Rating:
PP-PENTEM2
Notes:
Total Est. Demand: 1045 A Total Conn.: 1045 A
Total Est. Demand: 868.7 kVA Total Conn. Load: 868.7 kVA
HVAC 868659 VA 100.00% 868659 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 1045 A Total Conn. Load: 868.7 kVA
4 RTU-11 3 400 A 350 A 256.2 kVA 3 RTU-7 3 400 A 350 A 200.0 kVA 2 RTU-6 3 400 A 350 A 156.2 kVA 1 RTU-5 3 400 A 350 A 256.2 kVA
CKT Circuit Description # of Poles Switch Fuse Load Remarks
Enclosure: Type 1 MCB Raiting: 1600 A Mounting: Surface Wires: 3 Mains Rating: 1600 A
Supply From: SUB - 2 Phases: 3 Mains Type:
Location: Space FGT 307 Volts: 480 A.I.C. Rating:
PP-2M2
Notes:
Total Est. Demand: 481 A Total Conn.: 481 A
Total Est. Demand: 400.1 kVA Total Conn. Load: 400.1 kVA
HVAC 400094 VA 100.00% 400094 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 481 A Total Conn. Load: 400.1 kVA
4 RTU-12 (EXISTING/ FUTURE 911 CALL CENTER) 3 400 A 350 A 0.0 kVA 3 Spare 1 -- 350 A 0.0 kVA 2 RTU-9 3 400 A 350 A 200.0 kVA 1 RTU-8 3 400 A 350 A 200.0 kVA
CKT Circuit Description # of Poles Switch Fuse Load Remarks
Enclosure: Type 1 MCB Raiting: 1600 A Mounting: Surface Wires: 3 Mains Rating: 1600 A
Supply From: ATS 4 Phases: 3 Mains Type:
Location: Space FGT 307 Volts: 480 A.I.C. Rating:
PP-2M3
Notes:
Total Est. Demand: 93 A Total Conn.: 158 A
Total Est. Demand: 33589 VA Receptacle 56340 VA 58.87% 33170 VA Total Conn. Load: 56864 VA Power 524 VA 80.00% 419 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 209 A 193 A 98 A Total Load: 23564 VA 21600 VA 11700 VA
41 Spare 20 A 1 0 0 1 20 A Spare 42 39 Spare 20 A 1 0 0 1 20 A Spare 40 37 Power INSTR. LAB 1 370 - FUME HOOD 20 A 1 524 0 1 20 A Spare 38 35 Receptacle INSTR. LAB 1 370 - MISC. 20 A 1 900 900 1 20 A Receptacle INSTR. LAB 1 370 - MISC. 36 33 Receptacle INSTR. LAB 1 370 - MASS SPECT. 20 A 1 1800 1800 1 20 A Receptacle INSTR. LAB 1 370 - MASS SPECT. 34 31 Receptacle INSTR. LAB 1 370 - GAS CHROM. 20 A 1 1920 1920 1 20 A Receptacle INSTR. LAB 1 370 - GAS CHROM. 32 29 Receptacle INSTR. LAB 1 370 - PUMPS 20 A 1 1140 1140 1 20 A Receptacle INSTR. LAB 1 370 - PUMPS 30 27 Receptacle INSTR. LAB 1 370 - MASS SPECT. 20 A 1 1800 1800 1 20 A Receptacle INSTR. LAB 1 370 - MASS SPECT. 28 25 Receptacle INSTR. LAB 1 370 - GAS CHROM. 20 A 1 1920 1920 1 20 A Receptacle INSTR. LAB 1 370 - GAS CHROM. 26 23 Receptacle INSTR. LAB 1 370 - MISC. 20 A 1 720 900 1 20 A Receptacle INSTR. LAB 1 370 - MISC. 24 21 Receptacle INSTR. LAB 1 370 - MASS SPECT. 20 A 1 1800 1800 1 20 A Receptacle INSTR. LAB 1 370 - MASS SPECT. 22 19 Receptacle INSTR. LAB 1 370 - GAS CHROM. 20 A 1 1920 1920 1 20 A Receptacle INSTR. LAB 1 370 - GAS CHROM. 20 17 Receptacle INSTR. LAB 1 370 - PUMPS 20 A 1 1140 1140 1 20 A Receptacle INSTR. LAB 1 370 - PUMPS 18 15 Receptacle INSTR. LAB 1 370 - MASS SPECT. 20 A 1 1800 1800 1 20 A Receptacle INSTR. LAB 1 370 - MASS SPECT. 16 13 Receptacle INSTR. LAB 1 370 - GAS CHROM. 20 A 1 1920 1920 1 20 A Receptacle INSTR. LAB 1 370 - GAS CHROM. 14 11 Receptacle INSTR. LAB 1 370 - MISC. 20 A 1 720 720 1 20 A Receptacle INSTR. LAB 1 370 - MISC. 12 9 Receptacle INSTR. LAB 1 370 - MASS SPECT. 20 A 1 1800 1800 1 20 A Receptacle INSTR. LAB 1 370 - MASS SPECT. 10 7 Receptacle INSTR. LAB 1 370 - GAS CHROM. 20 A 1 1920 1920 1 20 A Receptacle INSTR. LAB 1 370 - GAS CHROM. 8 5 Receptacle INSTR. LAB 1 370 - PUMPS 20 A 1 1140 1140 1 20 A Receptacle INSTR. LAB 1 370 - PUMPS 6 3 Receptacle INSTR. LAB 1 370 - MASS SPECT. 20 A 1 1800 1800 1 20 A Receptacle INSTR. LAB 1 370 - MASS SPECT. 4 1 Receptacle INSTR. LAB 1 370 - GAS CHROM. 20 A 1 1920 1920 1 20 A Receptacle INSTR. LAB 1 370 - GAS CHROM. 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1 Mounting: Flush Wires: 4 Mains Rating: 200 A
Supply From: RP-CL-UPS Phases: 3 Mains Type: MCB Location: INSTR. LAB 1 370 Volts: 208Y/120 A.I.C. Rating: 10,000
Branch Panel: RP-CL-UPS-1
LIGHTING BRANCH CIRCUITS ARE NOT LOADED MORE THAN 80% OF THE RATING OF THE OVER-CURRENT PROTECTION DEVICE AMPACITY RATING FOR DEMAND FACTOR FOR CONTINUOUS
LOADS PER NEC 210.19(A), 210.20(A) AND 215.2(A).
Notes:
Total Est. Demand: 30 A Total Conn.: 30 A
Total Est. Demand: 25144 VA Total Conn. Load: 25144 VA
Lighting 25144 VA 100.00% 25144 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 40 A 34 A 20 A Total Load: 10592 VA 8952 VA 5600 VA
29 Space -- -- 0 0 -- -- Space 30 27 Space -- -- 0 0 -- -- Space 28 25 Space -- -- 0 0 -- -- Space 26 23 Space -- -- 0 0 -- -- Space 24 21 Space -- -- 0 0 -- -- Space 22 19 Spare 20 A 1 0 0 1 20 A Spare 20 17 Spare 20 A 1 0 0 1 20 A Spare 18 15 Spare 20 A 1 0 0 1 20 A Spare 16 13 Spare 20 A 1 0 0 1 20 A Spare 14 11 Spare 20 A 1 0 0 1 20 A Spare 12 9 Lighting Room 376, 375, 377, 378, 379, 382 20 A 1 1368 2432 1 20 A Lighting Room 347B, 373, 320, 342 10 7 Lighting Room 317, 310, 311, 309, 312 20 A 1 2592 2112 1 20 A Lighting Room 308, 305, 307, 306, 347A, 304, 30... 8 5 Lighting BIOLOGY UNIT LAB 323 20 A 1 2880 2720 1 20 A Lighting Room 327, 326, 321, 324, 325, 322, 319,... 6 3 Lighting Room 337, 339, 332 20 A 1 2432 2720 1 20 A Lighting Room 341, 340, 336, 335, 334, 333, 331,... 4 1 Lighting Room 370, 368 20 A 1 3456 2432 1 20 A Lighting Room 367, 366, 372, 371, 348, 346, 345,... 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 Mounting: Surface Wires: 4 Mains Rating: 100 A
Supply From: PP-P2S1B Phases: 3 Mains Type: MLO Location: ELEC. ROOM 381 Volts: 480Y/277 A.I.C. Rating: 14,000
Branch Panel: LP-CL
Notes:
Total Est. Demand: 0 A Total Conn.: 0 A
Total Est. Demand: 0.0 kVA Total Conn. Load: 0.0 kVA
HVAC 0 VA 0.00% 0 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 0 A Total Conn. Load: 0.0 kVA
12 Space -- -- -- 0.0 kVA -- 11 Space -- -- -- 0.0 kVA -- 10 Space -- -- -- 0.0 kVA -- 9 Space -- -- -- 0.0 kVA -- 8 Spare 3 -- 200 A 0.0 kVA 7 RP-P2S2G 3 400 A 200 A 0.0 kVA 6 RP-P2S2F 3 400 A 200 A 0.0 kVA 5 RP-P2S2E 3 400 A 200 A 0.0 kVA 4 RP-P2S2D 3 400 A 200 A 0.0 kVA 3 RP-P2S2C 3 400 A 200 A 0.0 kVA 2 RP-P2S2B 3 400 A 200 A 0.0 kVA 1 RP-P2S2A 3 400 A 200 A 0.0 kVA
CKT Circuit Description # of Poles Switch Fuse Load Remarks
Enclosure: Type 1 MCB Rating: 800 A Mounting: Surface Wires: 4 Mains Rating: 800 A
Supply From: T-P2S2A Phases: 3 Mains Type:
Location: MECH-1 242-1 Volts: 208Y/120 A.I.C. Rating:
DP-P2S2A
LIGHTING BRANCH CIRCUITS ARE NOT LOADED MORE THAN 80% OF THE RATING OF THE OVER-CURRENT PROTECTION DEVICE AMPACITY RATING FOR DEMAND FACTOR FOR CONTINUOUS
LOADS PER NEC 210.19(A), 210.20(A) AND 215.2(A).
Notes:
Total Est. Demand: 9 A Total Conn.: 9 A
Total Est. Demand: 7742 VA Total Conn. Load: 7742 VA
Lighting 7742 VA 100.00% 7742 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 12 A 7 A 9 A Total Load: 3260 VA 2061 VA 2421 VA
11 Spare 20 A 1 0 0 1 20 A Spare 12 9 Spare 20 A 1 0 0 1 20 A Spare 10 7 Spare 20 A 1 0 0 1 20 A Spare 8 5 Lighting Room 341, 340, 337, 336, 335, 332, 334,... 20 A 1 2421 0 1 20 A Spare 6 3 Lighting Room 322, 318, 310, 309, 317, 302, 306,... 20 A 1 1345 716 1 20 A Lighting Room 101, 111, 115, 113, 140 4 1 Lighting Room 370, 372, 367, 374, 377, 378, 375,... 20 A 1 2066 1194 1 20 A Lighting Room 348, 344, 347B, 342, 320, 301, 373 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 Mounting: Surface Wires: 4 Mains Rating: 30 A
Supply From: LP-4EM Phases: 3 Mains Type: MCB Location: ELEC. ROOM 381 Volts: 480Y/277 A.I.C. Rating: 14,000
Branch Panel: LP-CLEM
Notes:
RECEPTACLES 2520 VA 100.00% 2520 VA Total Est. Demand: 59 A Appliance 1440 VA 100.00% 1440 VA Total Conn.: 70 A Mechanical Equipment 529 VA 100.00% 529 VA Total Est. Demand: 21109 VA Receptacle 17000 VA 79.41% 13500 VA Total Conn. Load: 25389 VA Power 3900 VA 80.00% 3120 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 76 A 66 A 70 A Total Load: 9110 VA 7969 VA 8310 VA
41 42 39 40 37 38 35 36 33 Receptacle MECH. ROOM 245 20 A 1 540 34 31 Power 20 A 1 1050 200 1 20 A Power 32 29 Receptacle 20 A 1 720 1050 1 20 A Power 30 27 Receptacle 20 A 1 720 1080 1 20 A Receptacle 28 25 Receptacle 20 A 1 540 720 1 20 A Receptacle 26 23 Receptacle 20 A 1 1440 720 1 20 A Receptacle 24 21 EF-2 20 A 1 529 540 1 20 A Receptacle 22 19 Receptacle 20 A 1 1200 720 1 20 A Receptacle 20 17 Receptacle 20 A 1 1000 720 1 20 A Receptacle 18 15 Power 20 A 1 600 360 -- -- -- 16 13 Receptacle 20 A 1 1200 540 -- -- -- 14 11 Power 20 A 1 400 720 3 20 A Receptacle 12 9 Appliance 20 A 1 1440 720 1 20 A Receptacle 10 7 Power 20 A 1 600 1080 1 20 A Receptacles 8 5 Receptacle 20 A 1 1000 540 1 20 A Receptacle 6 3 Receptacle 20 A 1 360 1080 1 20 A Receptacle 4 1 Receptacle 20 A 1 720 540 1 20 A Receptacle 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1 Mounting: Surface Wires: 4 Mains Rating: 225 A
Supply From: DP-1SA Phases: 3 Mains Type: MLO Location: EXISTING ELECTRICAL ROOM... Volts: 208Y/120 A.I.C. Rating: 10,000
Branch Panel: RP-3SA
Notes:
Total Est. Demand: 79 A Total Conn.: 91 A
Total Est. Demand: 28580 VA Mechanical Equipment 14400 VA 100.00% 14400 VA Total Conn. Load: 32760 VA Receptacle 18360 VA 77.23% 14180 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 99 A 90 A 85 A Total Load: 11820 VA 10740 VA 10200 VA
41 Spare 20 A 1 0 0 1 20 A Spare 42 39 Spare 20 A 1 0 2400 -- -- -- 40 37 -- -- -- 2400 2400 -- -- -- 38
35 -- -- -- 2400 2400 3 20 A SGU-3 36
33 SGU-2 20 A 3 2400 360 -- -- -- 34
31 -- -- -- 180 360 -- -- -- 32 29 -- -- -- 180 360 3 20 A Receptacle 30 27 Receptacle 20 A 3 180 540 1 20 A Receptacle 28 25 -- -- -- 180 720 -- -- -- 26 23 -- -- -- 180 720 -- -- -- 24 21 Receptacle 20 A 3 180 720 3 20 A Receptacle 22 19 -- -- -- 720 540 -- -- -- 20 17 -- -- -- 720 540 -- -- -- 18 15 Receptacle 20 A 3 720 540 3 20 A Receptacle 16 13 -- -- -- 720 900 1 20 A Receptacle 14 11 -- -- -- 720 540 -- -- -- 12 9 Receptacle 20 A 3 720 540 -- -- -- 10 7 -- -- -- 720 540 3 20 A Receptacle 8 5 -- -- -- 720 720 -- -- -- 6 3 Furnature Power - Cont. Sub. Unit Office 367 20 A 3 720 720 -- -- -- 4 1 Receptacles - Cont. Sub. Unit Office 367 20 A 1 720 720 3 20 A Furnature Power - Cont. Sub. Unit Office 367 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1 Mounting: Surface Wires: 4 Mains Rating: 225 A
Supply From: DP-1SA Phases: 3 Mains Type: MLO Location: EXISTING ELECTRICAL ROOM... Volts: 208Y/120 A.I.C. Rating: 10,000
Branch Panel: RP-3SB
(EXISTING) (EXISTING) (EXISTING)
(NEW) (NEW) (EXISTING)
(EXISTING)(EXISTING)
NOTE: DASHED LINES INDICATE SCOPE FOR FORENSIC SCIENCE LAB ON EXISTING PANELS TYPICAL.
50% CD 21MAY13
ISSUE 3 25JUNE13
SCALE
DRAWING TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
Pl ot
D at e:
MICHIGAN STATE POLICE
METROPOLITAN DETROIT
FORENSIC SCIENCE LABORATORY
500 GRISWOLD
SUITE 1700
DETROIT, MI 48226
313.983.3600 www.smithgroupjjr.com
DTMB PROJECT NUMBER:
551/12270.DCS
7/
/2
4:
:0
PM
ELECTRICAL PANEL
SCHEDULES
E7.3 22580.322
Notes:
Total Est. Demand: 100 A Total Conn.: 109 A
Mechanical Equipment 19472 VA 100.00% 19472 VA Total Est. Demand: 36166 VA Receptacle 13740 VA 86.39% 11870 VA Total Conn. Load: 39242 VA Power 6030 VA 80.00% 4824 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 114 A 95 A 123 A Total Load: 13396 VA 11360 VA 14486 VA
41 Spare 20 A 1 0 0 1 20 A Spare 42 39 -- -- -- 2080 0 1 20 A Spare 40 37 SGU-2 20 A 2 2080 0 1 20 A Spare 38 35 Spare 20 A 1 0 0 1 20 A Spare 36 33 Spare 20 A 1 0 2400 -- -- -- 34 31 Spare 20 A 1 0 2400 -- -- -- 32 29 Shoot Tank Power Room 340 20 A 1 2880 2400 3 20 A SGU-1 30 27 Vending Machine Receptacle 20 A 1 200 900 1 20 A Corridor Electric Water Heaters 28 25 Vending Machine Receptacle 20 A 1 200 200 1 20 A Vending Machine Receptacle 26 23 Microwave Receptacle BREAKROOM 348 20 A 1 1200 200 1 20 A Vending Machine Receptacle 24 21 Disposal Receptacle BREAKROOM 348 20 A 1 1200 600 1 20 A Dishwasher Power BREAKROOM 348 22 19 -- -- -- 1456 2600 -- -- -- 20
17 AC-2 20 A 2 1456 2600 2 20 A AC-3 18
15 -- -- -- 720 200 1 20 A Door Power Supplies 16 13 -- -- -- 1080 400 1 20 A Door Power Supplies 14 11 Surface Raceway Rooms 340 & 341 20 A 3 1080 540 1 20 A Receptacle SHOOT TANK 340 12 9 Corridor Receptacles 20 A 1 900 540 1 20 A Receptacle MEETING 346 10 7 Receptacles Rooms 333, 341, 343, 344 20 A 1 900 360 1 20 A Receptacle BREAKROOM 348 8 5 Refrigerator Receptacle BREAKROOM 348 20 A 1 1050 1080 1 20 A Receptacle Room 329, 328 6 3 Receptacles MEETING 345 20 A 1 720 900 1 20 A Receptacles - Corridor & Room 339 4 1 Coffee Maker Receptacle BREAKROOM 348 20 A 1 1000 720 1 20 A Receptacle Room 330, 331A, 321, 324 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1 Mounting: Surface Wires: 4 Mains Rating: 225 A
Supply From: DP-1SA Phases: 3 Mains Type: MLO Location: EXISTING ELECTRICAL ROOM... Volts: 208Y/120 A.I.C. Rating: 10,000
Branch Panel: RP-3SC
Notes:
Total Est. Demand: 52 A Total Conn.: 74 A
Total Est. Demand: 18900 VA Receptacle 24440 VA 70.46% 17220 VA Total Conn. Load: 26540 VA Power 2100 VA 80.00% 1680 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 75 A 75 A 72 A Total Load: 9000 VA 8960 VA 8580 VA
41 Spare 20 A 1 0 0 1 20 A Spare 42 39 Spare 20 A 1 0 0 1 20 A Spare 40 37 Spare 20 A 1 0 0 1 20 A Spare 38 35 -- -- -- 360 0 1 20 A Spare 36 33 -- -- -- 360 0 1 20 A Spare 34 31 Surface Raceway Receptacles BIO. UNIT LAB 323 20 A 3 360 540 1 20 A Receptacle BIOLOGY UNIT LAB 323 32 29 Refrigerator BIOLOGY UNIT LAB 323 20 A 1 1050 1080 1 20 A Receptacle BIOLOGY UNIT LAB 323 30 27 Freezer BIOLOGY UNIT LAB 323 20 A 1 500 1080 1 20 A Receptacle Room 327, 326 28 25 Receptacle MICROSCOPE 325 20 A 1 360 540 1 20 A Receptacle BIOLOGY UNIT LAB 323 26 23 Refrigerator BIOLOGY UNIT LAB 323 20 A 1 1050 720 -- -- -- 24 21 Receptacle BIOLOGY UNIT LAB 323 20 A 1 1080 900 -- -- -- 22 19 -- -- -- 720 900 3 20 A Surface Raceway Receptacles MICROSCOPE 325 20 17 -- -- -- 720 720 -- -- -- 18 15 Surface Raceway Receptacles BIO. UNIT LAB 323 20 A 3 1080 720 -- -- -- 16 13 Receptacle BIOLOGY UNIT LAB 323 20 A 1 720 900 3 20 A Surface Raceway Receptacles Room 323, 326, 327 14 11 -- -- -- 720 720 -- -- -- 12 9 -- -- -- 720 900 -- -- -- 10 7 Surface Raceway Receptacles BIO. UNIT LAB 323 20 A 3 900 900 3 20 A Surface Raceway Receptacles BIO. UNIT LAB 323 8 5 -- -- -- 720 720 -- -- -- 6 3 -- -- -- 900 720 -- -- -- 4 1 Surface Raceway Receptacles BIO. UNIT LAB 323 20 A 3 1260 900 3 20 A Surface Raceway Receptacles BIO. UNIT LAB 323 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1 Mounting: FLUSH Wires: 4 Mains Rating: 225 A
Supply From: DP-P2S3A (SOUTH) Phases: 3 Mains Type: MCB Location: BIOLOGY UNIT LAB 323A Volts: 208Y/120 A.I.C. Rating: 10,000
Branch Panel: RP-CL3A
Notes:
Total Est. Demand: 46 A Total Conn.: 62 A
Receptacle 21420 VA 73.34% 15710 VA Total Est. Demand: 16710 VA Power 0 VA 0.00% 0 VA Total Conn. Load: 22420 VA Equipment 1000 VA 100.00% 1000 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 72 A 56 A 61 A Total Load: 8560 VA 6660 VA 7200 VA
41 Spare 20 A 1 0 0 1 20 A Spare 42 39 Spare 20 A 1 0 0 1 20 A Spare 40 37 Spare 20 A 1 0 0 1 20 A Spare 38 35 Spare 20 A 1 0 0 1 20 A Spare 36 33 Spare 20 A 1 0 0 1 20 A Spare 34 31 Spare 20 A 1 0 0 1 20 A Spare 32 29 Receptacle GSR 337 20 A 1 720 720 1 20 A Receptacle FIRING RANGE 341 30 27 Spare 0 A 1 0 0 -- -- -- 28 25 Receptacle GSR 337 20 A 1 360 1000 2 20 A Target Retrieval System FIRING RANGE 341 26 23 -- -- -- 900 900 -- -- -- 24 21 -- -- -- 900 1080 -- -- -- 22 19 Surface Raceway Receptacle FIREARMS LAB 332 20 A 3 1080 1260 3 20 A Surface Raceway Receptacle FIREARMS LAB 332 20 17 -- -- -- 540 540 -- -- -- 18 15 -- -- -- 900 540 -- -- -- 16 13 Surface Raceway Receptacle IBIS 335 20 A 3 1080 540 3 20 A Surface Raceway Receptacles IBIS TECHS 336 14 11 -- -- -- 540 900 -- -- -- 12 9 -- -- -- 720 900 -- -- -- 10 7 Surface Raceway Receptacle FIREARMS LAB 332 20 A 3 720 900 3 20 A Surface Raceway Receptacle FIREARMS LAB 332 8 5 -- -- -- 900 540 -- -- -- 6 3 -- -- -- 900 720 -- -- -- 4 1 Surface Raceway Receptacle MICROSCOPY 334 20 A 3 900 720 3 20 A Surface Raceway Receptacles MICROSCOPY 334 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1 Mounting: FLUSH Wires: 4 Mains Rating: 225 A
Supply From: DP-P2S3A (SOUTH) Phases: 3 Mains Type: MCB Location: FIREARMS UNIT LAB 332A Volts: 208Y/120 A.I.C. Rating: 10,000
Branch Panel: RP-CL3B
Notes:
Total Est. Demand: 0 A Total Conn.: 0 A
Total Est. Demand: 0 VA Total Conn. Load: 0 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 0 A 0 A 0 A Total Load: 0 VA 0 VA 0 VA
41 Spare 20 A 1 0 0 1 20 A Spare 42 39 Spare 20 A 1 0 0 1 20 A Spare 40 37 Spare 20 A 1 0 0 1 20 A Spare 38 35 Spare 20 A 1 0 0 1 20 A Spare 36 33 Spare 20 A 1 0 0 1 20 A Spare 34 31 Spare 20 A 1 0 0 1 20 A Spare 32 29 Spare 20 A 1 0 0 1 20 A Spare 30 27 Spare 20 A 1 0 0 1 20 A Spare 28 25 Spare 20 A 1 0 0 1 20 A Spare 26 23 Spare 20 A 1 0 0 1 20 A Spare 24 21 Spare 20 A 1 0 0 1 20 A Spare 22 19 Spare 20 A 1 0 0 1 20 A Spare 20 17 Spare 20 A 1 0 0 1 20 A Spare 18 15 Spare 20 A 1 0 0 1 20 A Spare 16 13 Spare 20 A 1 0 0 1 20 A Spare 14 11 Spare 20 A 1 0 0 1 20 A Spare 12 9 Spare 20 A 1 0 0 1 20 A Spare 10 7 Spare 20 A 1 0 0 1 20 A Spare 8 5 Spare 20 A 1 0 0 1 20 A Spare 6 3 Spare 20 A 1 0 0 1 20 A Spare 4 1 Spare 20 A 1 0 0 1 20 A Spare 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1 Mounting: FLUSH Wires: 4 Mains Rating: 225 A
Supply From: DP-P2S3A (SOUTH) Phases: 3 Mains Type: MCB Location: EXPANSION SPACE 350 Volts: 208Y/120 A.I.C. Rating: 10,000
Branch Panel: RP-CL3C
Notes:
Total Est. Demand: 0 A Total Conn.: 0 A
Total Est. Demand: 0 VA Total Conn. Load: 0 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 0 A 0 A 0 A Total Load: 0 VA 0 VA 0 VA
41 Spare 20 A 1 0 0 1 20 A Spare 42 39 Spare 20 A 1 0 0 1 20 A Spare 40 37 Spare 20 A 1 0 0 1 20 A Spare 38 35 Spare 20 A 1 0 0 1 20 A Spare 36 33 Spare 20 A 1 0 0 1 20 A Spare 34 31 Spare 20 A 1 0 0 1 20 A Spare 32 29 Spare 20 A 1 0 0 1 20 A Spare 30 27 Spare 20 A 1 0 0 1 20 A Spare 28 25 Spare 20 A 1 0 0 1 20 A Spare 26 23 Spare 20 A 1 0 0 1 20 A Spare 24 21 Spare 20 A 1 0 0 1 20 A Spare 22 19 Spare 20 A 1 0 0 1 20 A Spare 20 17 Spare 20 A 1 0 0 1 20 A Spare 18 15 Spare 20 A 1 0 0 1 20 A Spare 16 13 Spare 20 A 1 0 0 1 20 A Spare 14 11 Spare 20 A 1 0 0 1 20 A Spare 12 9 Spare 20 A 1 0 0 1 20 A Spare 10 7 Spare 20 A 1 0 0 1 20 A Spare 8 5 Spare 20 A 1 0 0 1 20 A Spare 6 3 Spare 20 A 1 0 0 1 20 A Spare 4 1 Spare 20 A 1 0 0 1 20 A Spare 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1 Mounting: FLUSH Wires: 4 Mains Rating: 225 A
Supply From: DP-P2S3A (SOUTH) Phases: 3 Mains Type: MCB Location: EXPANSION SPACE 358 Volts: 208Y/120 A.I.C. Rating: 10,000
Branch Panel: RP-CL3D
Notes:
Total Est. Demand: 21 A Total Conn.: 22 A
Total Est. Demand: 7400 VA Receptacle 5720 VA 100.00% 5720 VA Total Conn. Load: 7820 VA Power 2100 VA 80.00% 1680 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 25 A 21 A 19 A Total Load: 3030 VA 2480 VA 2310 VA
41 Spare 20 A 1 0 0 1 20 A Spare 42 39 Spare 20 A 1 0 0 1 20 A Spare 40 37 Spare 20 A 1 0 0 1 20 A Spare 38 35 Spare 20 A 1 0 0 1 20 A Spare 36 33 Spare 20 A 1 0 0 1 20 A Spare 34 31 Spare 20 A 1 0 0 1 20 A Spare 32 29 Spare 20 A 1 0 0 1 20 A Spare 30 27 Spare 20 A 1 0 0 1 20 A Spare 28 25 Spare 20 A 1 0 0 1 20 A Spare 26 23 Spare 20 A 1 0 0 1 20 A Spare 24 21 Spare 20 A 1 0 0 1 20 A Spare 22 19 Spare 20 A 1 0 0 1 20 A Spare 20 17 Spare 20 A 1 0 0 1 20 A Spare 18 15 Freezer Receptacle EVIDENCE STORAGE 305 20 A 1 500 0 1 20 A Spare 16 13 Receptacle EVIDENCE PRE-SCREENING 306 20 A 1 540 0 1 20 A Spare 14 11 -- -- -- 720 0 1 20 A Spare 12 9 -- -- -- 720 0 1 20 A Spare 10 7 Surface Raceway Recept. EVID. PRE-SCR. 306 20 A 3 720 0 1 20 A Spare 8 5 -- -- -- 540 1050 1 20 A Refrigerator DRUG STOR 308 6 3 -- -- -- 540 720 1 20 A Receptacle Room 308, 305, 307 4 1 Surface Raceway Recept. EVIDENCE STOR. 305 20 A 3 720 1050 1 20 A Refrigerator EVIDENCE STORAGE 305 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1 Mounting: FLUSH Wires: 4 Mains Rating: 225 A
Supply From: DP-P2S3A (SOUTH) Phases: 3 Mains Type: MCB Location: CRIME LAB 347A Volts: 208Y/120 A.I.C. Rating: 10,000
Branch Panel: RP-CL3E
Notes:
Total Est. Demand: 51 A Total Conn.: 62 A
Total Est. Demand: 18550 VA Receptacle 14220 VA 85.16% 12110 VA Total Conn. Load: 22270 VA Power 8050 VA 80.00% 6440 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 68 A 62 A 57 A Total Load: 8063 VA 7373 VA 6833 VA
41 Spare 20 A 1 0 0 1 20 A Spare 42 39 Spare 20 A 1 0 0 1 20 A Spare 40 37 Spare 20 A 1 0 0 1 20 A Spare 38 35 Spare 20 A 1 0 0 1 20 A Spare 36 33 Spare 20 A 1 0 0 1 20 A Spare 34 31 Spare 20 A 1 0 0 1 20 A Spare 32 29 Spare 20 A 1 0 0 1 20 A Spare 30 27 Spare 20 A 1 0 0 1 20 A Spare 28 25 -- -- -- 2333 0 1 20 A Spare 26 23 -- -- -- 2333 0 1 20 A Spare 24 21 Power CONT SUB UNIT LAB 368 - GLASS... 20 A 3 2333 360 -- -- -- 22 19 -- -- -- 720 540 -- -- -- 20 17 -- -- -- 720 540 3 20 A Raceway Receptacles BULK EXAM 372 18 15 Raceway Receptacles CONT. SUB. UNIT LAB 368 20 A 3 900 720 -- -- -- 16 13 -- -- -- 360 900 -- -- -- 14 11 -- -- -- 540 900 3 20 A Raceway Receptacles CONT. SUB. UNIT LAB 368 12 9 Raceway Receptacles CONT. SUB. UNIT LAB 368 20 A 3 540 360 -- -- -- 10 7 Receptacle BULK EXAM 372 20 A 1 360 720 -- -- -- 8 5 Receptacle CONT. SUB. UNIT LAB 368 20 A 1 1080 720 3 20 A Raceway Receptacles CONT. SUB. UNIT LAB 368 6 3 Receptacle CONT. SUB. UNIT LAB 368 20 A 1 1080 1080 1 20 A Receptacle CONT. SUB. UNIT LAB 368 4 1 Refrigerator CONT. SUB. UNIT LAB 368 20 A 1 1050 1080 1 20 A Receptacle CONT. SUB. UNIT LAB 368 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1 Mounting: FLUSH Wires: 4 Mains Rating: 225 A
Supply From: DP-P2S3A (NORTH) Phases: 3 Mains Type: MCB Location: CONTROLLED SUBSTANCE UNIT LAB 368 Volts: 208Y/120 A.I.C. Rating: 10,000
Branch Panel: RP-CL3F
Notes:
Total Est. Demand: 14 A Total Conn.: 14 A
Total Est. Demand: 5220 VA Total Conn. Load: 5220 VA
Receptacle 5220 VA 100.00% 5220 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 17 A 17 A 11 A Total Load: 1980 VA 1980 VA 1260 VA
41 Spare 20 A 1 0 0 1 20 A Spare 42 39 Spare 20 A 1 0 0 1 20 A Spare 40 37 Spare 20 A 1 0 0 1 20 A Spare 38 35 Spare 20 A 1 0 0 1 20 A Spare 36 33 Spare 20 A 1 0 0 1 20 A Spare 34 31 Spare 20 A 1 0 0 1 20 A Spare 32 29 Spare 20 A 1 0 0 1 20 A Spare 30 27 Spare 20 A 1 0 0 1 20 A Spare 28 25 Spare 20 A 1 0 0 1 20 A Spare 26 23 Spare 20 A 1 0 0 1 20 A Spare 24 21 Spare 20 A 1 0 0 1 20 A Spare 22 19 Spare 20 A 1 0 0 1 20 A Spare 20 17 Spare 20 A 1 0 0 1 20 A Spare 18 15 Spare 20 A 1 0 0 1 20 A Spare 16 13 Spare 20 A 1 0 0 1 20 A Spare 14 11 -- -- -- 180 0 1 20 A Spare 12 9 -- -- -- 540 180 1 20 A Receptacle INSTR. LAB 1 370 10 7 Surface Raceway Receptacles INSTR. LAB 1 370 20 A 3 540 540 -- -- -- 8 5 -- -- -- 540 540 -- -- -- 6 3 -- -- -- 720 540 3 20 A Surface Raceway Receptacles INSTR. LAB 1 370 4 1 Surface Raceway Receptacles INSTR. LAB 1 370 20 A 3 900 0 1 20 A Spare 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1 Mounting: FLUSH Wires: 4 Mains Rating: 225 A
Supply From: DP-P2S3A (NORTH) Phases: 3 Mains Type: MCB Location: INSTR. LAB 1 370 Volts: 208Y/120 A.I.C. Rating: 10,000
Branch Panel: RP-CL3G
(EXISTING) (NEW)
Notes:
Total Est. Demand: 48 A Mechanical Equipment 4246 VA 100.00% 4246 VA Total Conn.: 49 A Receptacle 6480 VA 100.00% 6480 VA Total Est. Demand: 17166 VA Power 2850 VA 80.00% 2280 VA Total Conn. Load: 17736 VA Lighting 4160 VA 100.00% 4160 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 46 A 49 A 54 A Total Load: 5532 VA 5810 VA 6394 VA
41 Space -- -- 0 0 -- -- Space 42 39 Space -- -- 0 0 -- -- Space 40 37 Space -- -- 0 0 -- -- Space 38 35 Space -- -- 0 0 -- -- Space 36 33 Space -- -- 0 0 -- -- Space 34 31 Spare 20 A 1 0 0 1 20 A Spare 32 29 Spare 20 A 1 0 0 1 20 A Spare 30 27 Spare 20 A 1 0 0 1 20 A Spare 28 25 Spare 20 A 1 0 0 1 20 A Spare 26 23 Spare 20 A 1 0 0 1 20 A Spare 24 21 Spare 20 A 1 0 0 1 20 A Spare 22 19 Receptacle CRIME LAB LOADING DOCK 140 20 A 1 180 0 1 20 A Spare 20 17 Electric Water Cooler 20 A 1 450 1456 -- -- -- 18
15 EF-3 & EF-4 20 A 1 1334 1456 2 20 A AC-1 16
13 Lighting Room 101, 106B, 108B, 109B, 111B, 140 20 A 1 960 1152 1 20 A Lighting Room 113, 112, 114, 116, 115 14 11 Power Room 101 - East Overhead Doors 20 A 1 1000 2048 1 20 A Lighting Room 101, 102B, 103 12 9 Door Power Supplies 20 A 1 400 1000 1 20 A Power Room 101 - West Overhead Doors 10 7 Receptacle Room 108B, 109B, 111B 20 A 1 900 720 1 20 A Receptacle CRIME LAB LOADING DOCK 140 8 5 Receptacle Room 101, 104B, 103, 102B, 106B 20 A 1 900 540 -- -- -- 6 3 Receptacle Room 112, 113, 115, 114, 116 20 A 1 900 720 -- -- -- 4 1 Drop Cord Receptacles Room 101 20 A 1 720 900 3 20 A Sureface Raceway Receptacle Room 101 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1 Mounting: FLUSH Wires: 4 Mains Rating: 225 A
Supply From: DP-P2S3A (NORTH) Phases: 3 Mains Type: MCB Location: VEHICLE PROCESSING 101A Volts: 208Y/120 A.I.C. Rating: 10,000
Branch Panel: RP-CL1A (NEW)
(NEW)(NEW)(NEW)
(NEW) (NEW) (NEW)
NOTE: DASHED LINES INDICATE SCOPE FOR FORENSIC SCIENCE LAB ON EXISTING PANELS TYPICAL.
50% CD 21MAY13
ISSUE 3 25JUNE13
SCALE
DRAWING TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
Pl ot
D at e:
MICHIGAN STATE POLICE
METROPOLITAN DETROIT
FORENSIC SCIENCE LABORATORY
500 GRISWOLD
SUITE 1700
DETROIT, MI 48226
313.983.3600 www.smithgroupjjr.com
DTMB PROJECT NUMBER:
551/12270.DCS
7/
/2
4:
:0
PM
ELECTRICAL PANEL
SCHEDULES
E7.4 22580.322
Notes:
Total Est. Demand: 113 A Total Conn.: 186 A
Total Est. Demand: 40889 VA Receptacle 59400 VA 58.42% 34700 VA Total Conn. Load: 67136 VA Power 7736 VA 80.00% 6189 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 238 A 215 A 130 A Total Load: 27156 VA 24432 VA 15548 VA
41 -- -- -- 11700 0 -- -- Space 42 39 -- -- -- 21600 0 -- -- Space 40 37 RP-CL-UPS-1 200 A 3 23564 0 -- -- Space 38 35 Space -- -- 0 0 -- -- Space 36 33 Space -- -- 0 0 -- -- Space 34 31 Space -- -- 0 0 -- -- Space 32 29 Spare 20 A 1 0 0 1 20 A Spare 30 27 Spare 20 A 1 0 0 1 20 A Spare 28 25 Spare 20 A 1 0 0 1 20 A Spare 26 23 Spare 20 A 1 0 0 1 20 A Spare 24 21 Spare 20 A 1 0 0 1 20 A Spare 22 19 Spare 20 A 1 0 0 1 20 A Spare 20 17 Spare 20 A 1 0 180 1 20 A Receptacle STINK ROOM 2 103 - GF-1 18 15 Spare 20 A 1 0 180 1 20 A Receptacle STINK ROOM 1 102 - GF-1 16 13 Spare 20 A 1 0 180 1 20 A Receptacle VEHICLE PROCESSING 101 - GF-1 14 11 Power Room 327, 323 - FUME HOODS 20 A 1 1048 524 1 20 A Power BIOLOGY UNIT LAB 323 - FUME HOOD 12 9 Power TRAINING LAB 318 - FUME HOOD 20 A 1 524 1048 1 20 A Power Room 337, 332 - FUME HOODS 10 7 Power CONT SUB UNIT LAB 368 - FUME HOODS 20 A 1 1048 524 1 20 A Power CONT SUB UNIT LAB 368 - FUME HOOD 8 5 Power CONT SUB UNIT LAB 368 - FUME HOODS 20 A 1 1048 1048 1 20 A Power CONT SUBS UNIT LAB 368 - FUME... 6 3 Receptacle ELEC. ROOM 381 20 A 1 720 360 1 20 A Receptacle EXISTING ELECTRICAL ROOM 300 4 1 Receptacle DATA 374 20 A 1 1440 400 1 20 A Power DATA 374 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1 Mounting: Surface Wires: 4 Mains Rating: 400 A
Supply From: CL-UPS Phases: 3 Mains Type: MCB Location: ELEC. ROOM 381 Volts: 208Y/120 A.I.C. Rating: 10,000
Branch Panel: RP-CL-UPS
Notes:
RECEPTACLES 2520 VA 100.00% 2520 VA
Appliance 1440 VA 100.00% 1440 VA Mechanical Equipment 38647 VA 100.00% 38647 VA Receptacle 126600 VA 53.95% 68300 VA Total Est. Demand: 349 A Power 25030 VA 80.00% 20024 VA Total Conn.: 425 A Lighting 29304 VA 100.00% 29304 VA Total Est. Demand: 290.2 kVA HVAC 128940 VA 100.00% 128940 VA Total Conn. Load: 353.5 kVA Equipment 1000 VA 100.00% 1000 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 425 A Total Conn. Load: 353.5 kVA
15 Spare 1 -- 30 A 0.0 kVA 14 Spare 1 -- 30 A 0.0 kVA 13 Spare 1 -- 60 A 0.0 kVA 12 Spare 1 -- 60 A 0.0 kVA 11 Spare 1 -- 100 A 0.0 kVA 10 Spare 1 -- 100 A 0.0 kVA 9 RO-1 3 30 A 30 A 1.3 kVA 8 DWH-1 3 60 A 40 A 24.0 kVA 7 EF-1 3 30 A 6 A 1.3 kVA 6 BCU-1 3 60 A 40 A 20.6 kVA 5 COMP-1 3 30 A 20 A 6.1 kVA 4 BCU-2 3 200 A 125 A 75.7 kVA 3 LP-CL 3 100 A 100 A 25.1 kVA 2 DP-1SA VIA T-1SA 112.5KVA 3 200 A 175 A 97.4 kVA 1 DP-P2S3A VIA T-P2S3A 225KVA 3 400 A 350 A 102.0 kVA
CKT Circuit Description # of Poles Switch Fuse Load Remarks
Enclosure: Type 1 Mounting: Surface Wires: 4 Mains Rating: 800 A
Supply From: SUB - 4 Phases: 3 Mains Type: MCB Location: ELEC. ROOM 243 Volts: 480Y/277 A.I.C. Rating: SEE SPECS
PP-P2S1B
CRIME LAB LOADS ON EXISTING PANELS
(NEW)
(NEW)
50% CD 21MAY13
ISSUE 3 25JUNE13
SCALE
DRAWING TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
PROJECT NORTH
Pl ot
D at e:
MICHIGAN STATE POLICE
METROPOLITAN DETROIT
FORENSIC SCIENCE LABORATORY
AREA A
AREA B
500 GRISWOLD
SUITE 1700
DETROIT, MI 48226
313.983.3600 www.smithgroupjjr.com
DTMB PROJECT NUMBER:
551/12270.DCS
7/
/2
4:
:1
PM
ELECTRICAL PANEL
SCHEDULES
E7.5 22580.322
Notes:
Total Est. Demand: 180 A Mechanical Equipment 50244 VA 100.00% 50244 VA Total Conn.: 198 A Receptacle 2340 VA 100.00% 2340 VA Total Est. Demand: 149.3 kVA Power 78800 VA 80.00% 63040 VA Total Conn. Load: 165.0 kVA
HVAC 33633 VA 100.00% 33633 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 198 A Total Conn. Load: 165.0 kVA
30 Spare 3 -- 30 A 0.0 kVA 29 Spare 3 -- 30 A 0.0 kVA 28 Spare 3 -- 30 A 0.0 kVA 27 SUPPLY FAN 3 3 30 A 30 A 5.7 kVA 26 BOOSTER PUMP 3 30 A 30 A 6.2 kVA 25 Spare 3 -- 30 A 0.0 kVA 24 Spare 3 -- 30 A 0.0 kVA 23 Spare 3 -- 30 A 0.0 kVA 22 PREHEAT FAN #3 3 100 A 30 A 2.8 kVA 21 PREHEAT FAN #2 3 100 A 30 A 2.8 kVA 20 PREHEAT FAN #1 3 100 A 30 A 2.8 kVA 19 Spare 3 -- 60 A 0.0 kVA 18 Spare 3 -- 60 A 0.0 kVA 17 Spare 3 -- 60 A 0.0 kVA 16 Spare 3 -- 60 A 0.0 kVA 15 Spare 3 -- 100 A 0.0 kVA 14 Spare 3 -- 30 A 0.0 kVA 13 Spare 3 -- 30 A 0.0 kVA 12 EF-8 3 -- 30 A 0.0 kVA 11 Spare 3 -- 60 A 0.0 kVA 10 Spare 3 -- 60 A 0.0 kVA 9 LEF-4 3 60 A 30 A 16.7 kVA 8 PASSENGER ELEVATOR 3 60 A 60 A 33.0 kVA 7 FREIGHT ELEVATOR 3 60 A 60 A 33.0 kVA 6 T-8 75KVA 3 100 A 70 A 3.6 kVA 5 RF-2 3 200 A 200 A 41.4 kVA 4 HHWP-4 3 60 A 10 A 2.4 kVA 3 HHWP-3 3 60 A 10 A 2.4 kVA 2 HHWP-2 3 60 A 15 A 6.1 kVA 1 HHWP-1 3 60 A 15 A 6.1 kVA
CKT Circuit Description # of Poles Switch Fuse Load Remarks
Enclosure: Type 1 Mounting: Surface Wires: 3 Mains Rating: 1200 A
Supply From: SUB - 1 Phases: 3 Mains Type: MLO Location: STORAGE 811 Volts: 480 A.I.C. Rating:
PP-4
Notes:
Total Est. Demand: 10 A Total Conn.: 10 A
Mechanical Equipment 400 VA 100.00% 400 VA Total Est. Demand: 3460 VA Receptacle 2340 VA 100.00% 2340 VA Total Conn. Load: 3640 VA Power 900 VA 80.00% 720 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 15 A 13 A 5 A Total Load: 1620 VA 1460 VA 560 VA
41 42 39 40 37 38 35 36 33 34 31 32 29 30 27 28 25 26 23 24 21 22 19 20 17 18 15 16 13 Receptacle 20 A 1 180 14
11 HEAT EXCHANGE PUMP 20 A 1 0 200 1 20 A B-2 12
9 DWH 20 A 1 0 200 1 20 A B-1 10
7 DWH 20 A 1 0 540 1 20 A Receptacle STORAGE 811 8 5 DWH 20 A 1 0 360 1 20 A Receptacle STORAGE 811 6 3 Receptacle 20 A 1 540 720 1 20 A Receptacle 4
1 CT FEED 20 A 1 180 720 1 20 A TEMP CONTROLS 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating: 225 A Mounting: Surface Wires: 4 Mains Rating: 225 A
Supply From: T-8 Phases: 3 Mains Type: MLO Location: MECHANICAL 801 Volts: 208Y/120 A.I.C. Rating: 10,000
Branch Panel: RP-PENT1A
LIGHTING BRANCH CIRCUITS ARE NOT LOADED MORE THAN 80% OF THE RATING OF THE OVER-CURRENT PROTECTION DEVICE AMPACITY RATING FOR DEMAND FACTOR FOR CONTINUOUS
LOADS PER NEC 210.19(A), 210.20(A) AND 215.2(A).
NOTES:
Total Est. Demand: 25 A Mechanical Equipment 50 VA 100.00% 50 VA Total Conn.: 25 A Power 500 VA 80.00% 400 VA Total Est. Demand: 20868 VA Lighting 19018 VA 100.00% 19018 VA Total Conn. Load: 20968 VA
HVAC 1400 VA 100.00% 1400 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 32 A 23 A 21 A Total Load: 8735 VA 6348 VA 5886 VA
41 -- -- -- 2421 638 -- -- -- 42 39 -- -- -- 2061 338 -- -- -- 40
37 LP-CLEM 30 A 3 3260 975 3 20 A T-4EM 38
35 Spare 20 A 1 0 0 1 20 A Spare 36 33 Spare 20 A 1 0 0 1 20 A Spare 34 31 Spare 20 A 1 0 0 1 20 A Spare 32 29 Spare 20 A 1 0 0 1 20 A Spare 30 27 Spare 20 A 1 0 0 1 20 A Spare 28 25 Spare 20 A 1 0 0 1 20 A Spare 26 23 Spare 20 A 1 0 0 1 20 A Spare 24 21 Spare 20 A 1 0 0 1 20 A Spare 22 19 Spare 20 A 1 0 0 1 20 A Spare 20 17 Spare 20 A 1 0 0 1 20 A Spare 18 15 Spare 20 A 1 0 0 1 20 A Spare 16 13 Lighting Room 245, STR 210, 244, 243, STR 207,... 20 A 1 961 931 1 20 A Lighting Room 440, 439, 446, 444, STR 410, 445,... 14 11 Spare 20 A 1 0 0 1 20 A Spare 12 9 Spare 20 A 1 0 0 1 20 A Spare 10 7 Spare 20 A 1 0 0 1 20 A Spare 8 5 Lighting Room STR 1010, 136, 125A, 125, 129,... 20 A 1 1355 1472 1 20 A Lighting Room 131, 132, 138, 141, STR 109 6 3 Lighting Room STR 309, 312, 319A, 319B, 341,... 20 A 1 1922 2027 1 20 A Lighting Room 333, 340, STR 310, 312, 339, 337,... 4 1 Lighting Room STR 409, 420, 410A, 441, 423, 42... 20 A 1 1065 1543 1 20 A Lighting Room 447, 448, 455, STR 408, STR 405,... 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating:
Mounting: Surface Wires: 4 Mains Rating: 100 A
Supply From: PP-P1EM Phases: 3 Mains Type: MLO Location: ELEC 444 Volts: 480Y/277 A.I.C. Rating: 14,000
Branch Panel: LP-4EM
Notes:
Mechanical Equipment 4246 VA 100.00% 4246 VA Total Est. Demand: 181 A Receptacle 77500 VA 56.45% 43750 VA Total Conn.: 283 A Power 15100 VA 80.00% 12080 VA Total Est. Demand: 65.2 kVA Lighting 4160 VA 100.00% 4160 VA Total Conn. Load: 102.0 kVA Equipment 1000 VA 100.00% 1000 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 283 A Total Conn. Load: 102.0 kVA
6 Space -- -- -- 0.0 kVA -- 5 Spare 3 -- 200 A 0.0 kVA 4 Spare 3 -- 200 A 0.0 kVA 3 RP-CL1A 3 200 A 100 A 17.7 kVA 2 RP-CL3G 3 200 A 100 A 5.2 kVA 1 RP-CL3F 3 200 A 100 A 22.3 kVA
CKT Circuit Description # of Poles Switch Fuse Load Remarks
Enclosure: Type 1 MCB Raiting: 800 A Mounting: Surface Wires: 4 Mains Rating: 800 A
Supply From: T-P2S3A Phases: 3 Mains Type:
Location: ELEC. ROOM-1 243-1 Volts: 208Y/120 A.I.C. Rating:
DP-P2S3A (NORTH)
Notes:
Total Est. Demand: 98 A Total Conn.: 158 A
Receptacle 51580 VA 59.69% 30790 VA Total Est. Demand: 35.2 kVA Power 4200 VA 80.00% 3360 VA Total Conn. Load: 56.8 kVA Equipment 1000 VA 100.00% 1000 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 158 A Total Conn. Load: 56.8 kVA
8 Space -- -- -- 0.0 kVA -- 7 Spare 3 -- 0 A 0.0 kVA 6 Spare 3 -- 0 A 0.0 kVA 5 RP-CL3E 3 200 A 100 A 7.8 kVA 4 RP-CL3D 3 200 A 100 A 0.0 kVA 3 RP-CL3C 3 200 A 100 A 0.0 kVA 2 RP-CL3B 3 200 A 100 A 22.4 kVA 1 RP-CL3A 3 200 A 100 A 26.5 kVA
CKT Circuit Description # of Poles Switch Fuse Load Remarks
Enclosure: Type 1 Mounting: Surface Wires: 4 Mains Rating: 800 A
Supply From: DP-P2S3A (NORTH) Phases: 3 Mains Type: MLO Location: ELEC. ROOM-1 243-1 Volts: 208Y/120 A.I.C. Rating:
DP-P2S3A (SOUTH)
Notes:
Mechanical Equipment 74200 VA 100.00% 74200 VA Receptacle 95736 VA 55.22% 52868 VA Total Est. Demand: 409 A Power 87756 VA 80.00% 70205 VA Total Conn.: 482 A Other 600 VA 100.00% 600 VA Total Est. Demand: 340.0 kVA Lighting 4992 VA 100.00% 4992 VA Total Conn. Load: 400.4 kVA