Project 655-22-202 Drawings.pdf
PDF 14 MB Posted
- Solicitation number
- 36C25023B0064
About this file
This federal contract opportunity notice seeks proposals for the removal of an underground storage tank and its replacement with an above-ground storage tank. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10 issued solicitation number 36C25023B0064 to remove an existing underground storage tank (UST) and install a new above-ground storage tank (AST) at its facility. Interested parties must submit proposals by the response due date to be considered for the award, which is expected to be issued in early 2023. The solicitation details the required scope of work, specifications for the new AST, and performance period of 90 calendar days from the award date. Pricing is to be submitted as a firm-fixed price for the total project.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
WEISS STREET
C & O RAILROAD
W T R
M A
IN
W T R
M A
IN
J
SAGINAW VA MEDICAL CENTER
#655-22-202
DEPARTMENT OF VETERANS AFFAIRS
1500 WEISS STREET
SAGINAW, MI 48602
REMOVAL OF UST AND REPLACEMENT WITH
AST FOR GENERATOR IN BUILDING 19
G E N E R A L N O T E S
A. DO NOT SCALE DRAWINGS; DIMENSIONS SHALL GOVERN.
B. THE GENERAL CONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONS AND FIELD CONDITIONS PRIOR TO DEMOLITION AND CONSTRUCTION. IF PROVIDED, THE GENERAL CONTRACTOR SHALL EXAMINE EXISTING BUILDING DOCUMENTS. THE CONTRACTOR SHALL BRING ANY DISCREPANCIES TO THE IMMEDIATE ATTENTION OF THE CONTRACTING OFFICER
REPRESENTATIVE.
C. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR THE PROTECTION OF EXISTING ITEMS TO REMAIN DURING DEMOLITION AND
CONSTRUCTION.
D. IF CONSTRUCTION NOISE IS ANTICIPATED, SUBMIT A WRITTEN REQUEST TO THE C.O.R. FOR THE SCHEDULED TIME OF CONSTRUCTION ACTIVITIES. THE CONTRACTING OFFICER REPRESENTATIVE RESERVES THE RIGHT TO DISCONTINUE NOISY CONSTRUCTION AT ANY TIME. NO RADIOS SHALL BE PERMITTED AT ANY TIME IN WORK AREAS ADJACENT TO OCCUPIED SPACES.
E. ALL WORK SHALL BE DONE IN ACCORDANCE WITH APPLICABLE CODES AND FEDERAL AUTHORITIES, RULES AND REGULATIONS.
F. THESE DOCUMENTS SHOW DESIGN INTENT WITH MINIMUM CONSTRUCTION REQUIREMENTS AND MINIMUM QUALITY OF WORK EXPECTED. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR ALL MEANS, METHODS AND TECHNIQUES FOR CONSTRUCTION
AND EXPECTED QUALITY.
G. ALL MATERIALS UTILIZED ON THIS PROJECT SHALL BE NEW UNLESS OTHERWISE NOTED TO BE SALVAGED AND REFURBISHED.
MATERIAL QUALITY SHALL MEET OR EXCEED APPLICABLE INDUSTRY STANDARDS.
H. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING ALL EQUIPMENT INSTALLATION AND VARYING ALL REQUIRED ROUGH OPENINGS AND ROUGH-IN DIMENSIONS WITH THE EQUIPMENT MANUFACTURER AND C.O.R. PRIOR TO CONSTRUCTION.
I. FIELD VERIFY SIZES AND DIMENSIONS OF ALL EXISTING UTILITIES APPARATUSES IMPACTING NEW CONSTRUCTION. DETERMINE EXACT SIZE AND LOCATION OF PENETRATION WITHIN NEW CONSTRUCTION, TIGHTLY SEAL AND CAULK.
J. GENERAL CONTRACTOR SHALL HOST SUBMITTAL EXCHANGE SOFTWARE FOR THE DURATION OF THE PROJECT.
E X I S T I N G U T I L I T I E S
A. ALL UTILITIES SHOWN ARE APPROXIMATE LOCATIONS DERIVED FROM INVESTIGATIONS AND AVAILABLE RECORDS. THEY SHOULD NOT BE INTERPRETED TO BE EXACT LOCATIONS NOR SHOULD IT BE ASSUMED THAT THEY ARE THE ONLY UTILITIES IN THE AREA.
CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING ALL UNDERGROUND UTILITIES AT EACH WORK LOCATION.
B. PROVIDE ALL SHORING, PLATE STEEL, AND BARRICADES REQUIRED FOR EXCAVATION AND DEMOLITION PROCESS. EXCAVATION
SHALL NOT UNDERMINE EXISTING FOUNDATIONS.
C O N T R A T O R L A Y D O W N A R E A
A. CONTRACTOR SHALL PROVIDE A FENCE AROUND THE CONSTRUCTION AREA PER GENERAL REQUIREMENTS SPECIFICATION.
B. MAINTAIN ACCESS TO ENERGY CENTER (CURVED DRIVEWAY) AND MAIN HOSPITAL LOOP.
C. ENERGY CENTER DRIVEWAY MAY TEMPORARILY BE USED FOR EQUIPMENT - NOTIFY C.O.R. FOR APPROVAL.
PROJECT LOCATION
LAY DOWN
AREA
CONSTRUCTION
FENCE
MAINTAIN ACCESS
M A
IN
T
A
IN
A C
C E
S S
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /S a g in a w V
A
B u ild in g
U
S T
/F F
E S a g in a w
B u ild in g
U
S T
B rv t
/1
/2
:1
:2
P
M
GI001
COVER SHEET
03/14/2023 PQ TD
REMOVAL OF UST AND
REPLACEMENT WITH AST FOR
GENERATOR IN BUILDING 19
655-22-202
1500 WEISS ST. SAGINAW, MI 48602
BID DOCUMENTS
SAGINAW VA
MEDICAL
CENTER Approved: Veteran's Affairs Medical Center
DRAWING LIST
GENERAL
GI001 COVER SHEET
CIVIL
CI001 CIVIL ABBREVIATIONS, SYMBOLS, AND MATERIALS LEGEND
CE101 SEDIMENT CONTROL PLAN
CD101 DEMOLITION PLAN
CS101 HORIZONTAL CONTROL PLAN
CG101 VERTICAL CONTROL PLAN
CU101 OVERALL UTILITY PLAN
CI501 SEDIMENT CONTROL DETAILS
STRUCTURAL
S101 FOUNDATION PLAN AND DETAILS
ARCHITECTURE
A101 FLOOR PLAN
A401 ENLARGED SECTIONS, ELEVATIONS, AND DETAILS
MECHANICAL
M001 MECHANICAL LEGEND
MD100 MECHANICAL DEMOLITION PLAN
MH100 MECHANICAL NEW WORK PLAN
M600 MECHANICAL SCHEDULES
M601 FUEL DIAGRAM AND CONTROLS
ELECTRICAL
E001 LEGEND
EP001 ELECTRICAL PLAN
NTS
B
CAMPUS PLAN
N
NTS
A
3D View
No. Revisions: Date:
BID DOCUMENTS 03/14/2023
NTS
C
CONTRACTOR LAY DOWN AREA
N
N
10/25/2023
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED DRAWN
DRAWING TITLE
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE:ARCHITECT/ENGINEER OF RECORD SEALCONSULTANT
321 4 5 6 7 8 9 10
REMOVAL OF UST AND
REPLACEMENT OF AST FOR
GENERATOR IN BUILDING 19
1500 WEISS ST, SAGINAW, MI 48602
655-22-202
APPROVED: PROJECT DIRECTOR
3/14/2023NO: DATE:
Group, Inc.
11031 SOUTH PIKES PEAK DRIVE #202
PARKER, COLORADO 80138
PH: 303.841.3922
WWW.AES-GRP.COM
BID DOCUMENTS
DWG. OF
3/14/2023
REVISIONS:
BID DOCUMENTS
CIVIL ABBREVIATIONS, SYMBOLS, AND
MATERIALS LEGEND
CI001
1 9
GJVRID
LINETYPE LEGEND
CABLE, COAXIAL - EXISTING
CABLE, COAXIAL
CABLE, FIBER OPTIC - EXISTING
CABLE, FIBER OPTIC
CONSTRUCTION FENCE (CF)
DOMESTIC WATER - EXISTING
DOMESTIC WATER
DRAINAGE BASIN BOUNDARY
ELECTRICAL, OVERHEAD - EXISTING
ELECTRICAL, OVERHEAD
ELECTRICAL, UNDERGROUND - EXISTING
ELECTRICAL, UNDERGROUND
FENCE
FLOWLINE
LINEAR FEATURE - DEMOLITION
LIMITS OF CONSTRUCTION
NATURAL GAS - EXISTING
NATURAL GAS
SANITARY SEWER - EXISTING
SANITARY SEWER
SEDIMENT CONTROL LOG
SILT FENCE (SF)
STORM SEWER - EXISTING
STORM SEWER
MAJOR CONTOUR - EXISTING
MAJOR CONTOUR
MINOR CONTOUR - EXISTING
MINOR CONTOUR
PROPERTY LINE
PROPERTY SETBACK/EASMENT
TELECOM, OVERHEAD - EXISTING
TELECOM, OVERHEAD
TELECOM, UNDERGROUND - EXISTING
TELECOM, UNDERGROUND
CONTOUR LABEL - EXISTING
CONTOUR LABEL
W
SYMBOL LEGEND
BENCHMARK/ELEVATION
CHECK DAM (CD)
EQUIPMENT, ELECTRICAL
FIRE HYDRANT
CLEAN OUT
CONCRETE WASHOUT AREA (CWA)
CULVERT PROTECTION (CP)
CURB SOCK (CS)
HANDICAP PARKING
IRRIGATION CONTROL BOX
INLET PROTECTION (IP)
LIGHT POLE
MANHOLE, ELECTRIC
MANHOLE, SANITARY SEWER
MANHOLE, STORM SEWER
MANHOLE, TELEPHONE/COMMUNICATION
MANHOLE, WATER
METER, ELECTRIC
METER, GAS
METER, WATER
PANEL POINT
POWER POLE
PUMP/ WELL HEAD
SEDIMENT CONTROL BMP
TRANSFORMER
TREE, CONIFEROUS
TREE, DECIDUOUS
VALVE, BUTTERFLY
VALVE, GATE
VEHICLE TRACKING CONTROL (VTC)
WELL
E
S
D
W
MATERIALS LEGEND
AREA OF DEMOLITION
CONCRETE
FLOODPLAIN
FLOODWAY
GRASSED AREA
GRAVEL
SOIL, DISTURBED
SOIL, UNDISTURBED
WETLANDS
E
G
SS
SD x
GAS
GASx
SS x
WTRx
WTR
SD
X X
EO x
EO
EU x
EU
TELOx
TELO
TELUx
TELU
FO
FO x
CTV
CTVx
SF
T
SCL
E
X X X X X X X X X X X
ABBREVIATIONS
ABC AGGREGATE BASE COURSE
ABA ARCHITECTURAL BARRIERS ACT
ADA AMERICANS WITH DISABILITIES
ACT
APA AMERICAN PLYWOOD
ASSOCIATION
AGGR AGGREGATE
ALT ALTERNATE OR ALTITUDE
APPROX APPROXIMATE
ASCE AMERICAN SOCIETY OF CIVIL
ENGINEERS
ASPH ASPHALT
AST ABOVEGROUND STORAGE TANK
AWG AMERICAN WIRE GAUGE
B&F BELL AND FLANGE
B&S BELL AND SPIGOT
BCV BUTTERFLY CHECK VALVE
BF BOTTOM FACE
BFP BACKFLOW PREVENTER
BFV BUTTERFLY VALVE
BITUM BITUMINOUS
BLDG BUILDING
BM BEAM OR BENCHMARK
BRG BEARING
BV BALL VALVE
CB CATCH BASIN OR CEMENT BASE
CD CONSTRUCTION DOCUMENTS
CEM CEMENT
CF CONTRACTOR FURNISHED
CFS CUBIC FEET PER SECOND
CI CAST IRON OR CURB INLET
CIP CAST-IN-PLACE OR CAST IRON
PIPE
CJ CONSTRUCTION JOINT OR
CONTROL JOINT
CL CENTER LINE, CLASS, OR CLOSE
CLR CLEAR
CMP CORRUGATED METAL PIPE
CMU CONCRETE MASONRY UNIT
CO CLEANOUT/CONTRACTING
OFFICER
COMM COMMUNICATION
CONC CONCENTRIC OR CONCRETE
COORD COORDINATE
COR CONTRACTING OFFICER'S
REPRESENTATIVE
COV COVER OR CUT OFF VALVE
CRSI CONCRETE REINFORCING STEEL
INSTITUTE
CS CONTROL SOCK
CSB CONCRETE SPLASH BLOCK
CSP CONCRETE SEWER PIPE
CTR CENTER, CONTOUR, OR COOLING
TOWER RETURN
CTRL CONTROL
CTV CABLE TELEVISION
CU COPPER OR CUBIC
CU FT CUBIC FEET
CU IN CUBIC INCH
CU YD CUBIC YARD
CV CONTROL VALVE
d PENNY (NAIL)
DBL DOUBLE
DEG DEGREE
DEMO DEMOLITION
DEPT DEPARTMENT
DI DROP INLET
DIA DIAMETER
DIAG DIAGONAL DIAGRAM
DIM DIMENSION
DIP DUCTILE IRON PIPE
DIST DISTANCE
DIV DIVISION
DOC DOCUMENT
DOUG FIR DOUGLAS FIR
DOZ DOZEN
DR DRAIN OR DRIVE
DS DOWNSPOUT
DW DOMESTIC WATER
DWG DRAWING
E EAST
EA EACH
EC EDGE OF CURB
EJ EXPANSION JOINT
EL EASEMENT LINE OR ELEVATION
EOS EDGE OF SLAB
EP EDGE OF PAVEMENT (PAVING)
EPA ENVIRONMENTAL PROTECTION
AGENCY
EQ EQUAL
EQUIP EQUIPMENT
EQUIV EQUIVALENT
ES EDGE OF SHOULDER
ESMT EASEMENT
EW EACH WAY
EXIST EXISTING
EXP EXPANSION
EXST GR EXISTING GRADE
F FIRE LINE; FEMALE; FAHRENHEIT
FFE FINISH FLOOR ELEVATION
FH FIRE HYDRANT
FLG FLANGE
FL FLOW LINE
FOC FACE OF CURB
FP FIRE PROTECTION OR FLAGPOLE
FPM FEET PER MINUTE
FPS FEET PER SECOND
FT FEET OR FOOT
FTG FOOTING
FMH FUEL MANHOLE
G GROUND OR NATURAL GAS
GA GAGE
GAL GALLON
GC GENERAL CONTRACTOR
GEN GENERATOR
GIP GALVANIZED IRON PIPE
GPD GALLONS PER DAY
GT GREASE TRAP
GTV GATE VALVE
HAZ MAT HAZARDOUS MATERIALS
HB HOSE BIBB
HC HANDICAP/HANDICAPPED
HDPE HIGH DENSITY POLYETHYLENE
HDWL HEADWALL
HH HAND HOLE
HORIZ HORIZONTAL
HWY HIGHWAY
HYD HYDRANT
HYDR HYDRAULIC
ID INSIDE DIAMETER
INCL INCLUDED
INFO INFORMATION
INV INVERT
IP IRON PIPE
IRREG IRREGULAR
IW IRRIGATION WATER
L ANGLE
LAT LATITUDE
LF LINEAR FEET (FOOT)
LIN LINEAR
LNG LONGITUDE
LOC LOCATION
LONG LONGITUDINAL
LOS LINE OF SIGHT
LPT LOW POINT
LT LIGHT
MAINT MAINTENANCE
MATL MATERIAL
MATV MASTER ANTENNA TELEVISION
SYSTEM
MAX MAXIMUM
MB MAIL BOX
MED MEDIUM
MEMO MEMORANDUM
MER MERIDIAN
MFD MANUFACTURED
MFG MANUFACTURING
MGT MANAGEMENT
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
ML MATERIALS LIST
MN MAGNETIC NORTH
MOD MODEL OR MODIFY
MON MONUMENT
MTG MEETING
MULT MULTIPLE
MUNIC MUNICIPAL
N NORTH
NA NOT APPLICABLE
NDS NATIONAL DESIGN SPECIFICATION
FOR WOOD CONSTRUCTION
NIC NOT IN CONTRACT
NOM NOMINAL
NRCP NON-REINFORCED CONCRETE
PIPE
NTP NOTICE TO PROCEED
NTS NOT TO SCALE
OC ON CENTER
OFD OVERFLOW DRAIN
OPNG OPENING
OZ OUNCE
PA PIPE ANCHOR
PB PULL BOX
PC POINT OF CURVE
PCA PORTLAND CEMENT ASSOCIATION
PCC PRECAST CONCRETE
PCCP CONCRETE PAVEMENT
PERF PERFORATED
PERIM PERIMETER
PERM PERMANENT
PERP PERPENDICULAR
PG PRESSURE GAGE OR PROFILE
GRADE
PI POINT OF INTERSECTION
PIV POST INDICATOR VALVE
PK GAR PARKING GARAGE
PK LOT PARKING LOT
PMPSCT PUMP SUCTION
PE POLYETHYLENE (PLASTIC)
PP POLYPROPYLENE (PLASTIC)
PREP PREPARATION
PREV PREVIOUS
PRKG PARKING
PROP PROPERTY
PRV PRESSURE REGULATOR VALVE
OR PRESSURE RELIEF VALVE
PS CONC PRESTRESSED CONCRETE
PSI POUNDS PER SQUARE INCH
PSL PIPE SLEEVE
PT POST TENSIONED
PVC POLYVINYL CHLORIDE (PLASTIC)
QTR QUARTER
QTY QUANTITY
R RADIUS OR RANGE
RC REINFORCED CONCRETE
RCB REINFORCED CONCRETE BOX
RCP REINFORCED CONCRETE PIPE
RDC REDUCER
REBAR REINFORCING STEEL BARS
REQ REQUIRE
RFI REQUEST FOR INFORMATION
ROW RIGHT OF WAY
RV RELIEF VALVE
RW ROADWAY
SAN SANITARY
SB SPLASH BLOCK
SCHED SCHEDULE
SCL SEDIMENT CONTROL LOG
SD STORM DRAIN
SDMH STORM DRAIN MANHOLE
SECT SECTION
SJ SCORED JOINT
SMH STEAM MANHOLE
SMP SUMP PUMP
SOV SHUT OFF VALVE
SP STANDPIPE OR SUMP PIT
SP EL SPOT ELEVATION
SPKLR SPRINKLER
SQ SQUARE
SQ IN SQUARE INCH
SQ YD SQUARE YARD
SR STEAM RETURN
SS SANITARY SEWER
SSP STAINLESS STEEL PIPE
STA STATION
STD STANDARD
STM STEAM/STORM
SURF SURFACE
SURV SURVEY
SWR SEWER
SYM SYMBOL
TAN TANGENT
TELE TELEPHONE
TEMP TEMPORARY
THRU THROUGH
TBC TOP BACK OF CURB
TOW TOP OF WALL
TOP TOP OF PAVEMENT
TOPO TOPOGRAPHY
TOS TOP OF SLAB
TYP TYPICAL
UFC UNIFORM FACILITIES CRITERIA
UNO UNLESS NOTED OTHERWISE
UST UNDERGROUND STORAGE TANK
UTIL UTILITY
VB VALVE BOX
VC VERTICAL CURVE
VCP VITRIFIED CLAY PIPE
VERT VERTICAL
VIF VERIFY IN FIELD
VOL VOLUME
VTC VEHICLE TRACKING CONTROL
W WASTE, WEST, OR WIDE
WP WATER PUMP
WTR WATER
CS
CS
SCL
SCL
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED DRAWN
DRAWING TITLE
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE:ARCHITECT/ENGINEER OF RECORD SEALCONSULTANT
321 4 5 6 7 8 9 10
REMOVAL OF UST AND
REPLACEMENT OF AST FOR
GENERATOR IN BUILDING 19
1500 WEISS ST, SAGINAW, MI 48602
655-22-202
APPROVED: PROJECT DIRECTOR
3/14/2023NO: DATE:
Group, Inc.
11031 SOUTH PIKES PEAK DRIVE #202
PARKER, COLORADO 80138
PH: 303.841.3922
WWW.AES-GRP.COM
BID DOCUMENTS
DWG. OF
3/14/2023
REVISIONS:
BID DOCUMENTS
SEDIMENT CONTROL PLAN
CE101
2 9
GJVRID
N
0' 20'10'
SCALE: 1" = 10'
SHEET NOTES
1. MAINTAIN SEDIMENT CONTROL AT INDICATED LIMITS OF
CONSTRUCTION FOR PROJECT DURATION.
2. SEE SHEET CI501 FOR SEDIMENT CONTROL DETAILS.
3. REMOVE AND RESEED/MULCH ALL STOCK PILES,
STORAGE/STAGING AREAS AND VEHICLE TRACKING CONTROL
PADS AT THE COMPLETION OF CONSTRUCTION.
EROSION CONTROL BMP LEGEND
LOC LIMITS OF CONSTRUCTION
CF CONSTRUCTION FENCE
RRC RRB FOR CULVERT PROTECTION
SF SILT FENCE
CWA CONCRETE WASHOUT AREA
IP INLET PROTECTION
SSA STABILIZED STAGING AREA
VTC VEHICLE TRACKING CONTROL
CS CURB SOCK
SCL SEDIMENT CONTROL LOG
SYMBOL LEGEND
CONCRETE WASHOUT AREA (CWA)
FLOW DIRECTION
LIMITS OF CONSTRUCTION
SEDIMENT CONTROL BMP TAG
SEDIMENT CONTROL LOG
SEEDING AND MULCHING
SILT FENCE
SCL
# KEY NOTES
1. TEMPORARY FUEL TANK WITH DOUBLE WALL CONSTRUCTION
FOR SPILL CONTAINMENT. SPILL RESPONSE KIT/BARREL TO
BE LOCATED NEAR TANK. MAINTAIN ANY CLEARANCES
REQUIRED BY TANK SUPPLIER OR APPLICABLE CODE.
SF
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
D F
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
3 1
23.17'
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED DRAWN
DRAWING TITLE
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE:ARCHITECT/ENGINEER OF RECORD SEALCONSULTANT
321 4 5 6 7 8 9 10
REMOVAL OF UST AND
REPLACEMENT OF AST FOR
GENERATOR IN BUILDING 19
1500 WEISS ST, SAGINAW, MI 48602
655-22-202
APPROVED: PROJECT DIRECTOR
3/14/2023NO: DATE:
Group, Inc.
11031 SOUTH PIKES PEAK DRIVE #202
PARKER, COLORADO 80138
PH: 303.841.3922
WWW.AES-GRP.COM
BID DOCUMENTS
DWG. OF
3/14/2023
REVISIONS:
BID DOCUMENTS
DEMOLITION PLAN
CD101
3 9
GJVRID
N
0' 20'10'
SCALE: 1" = 10'
SHEET NOTES
1. TIME CUTTING OF ASPHALT TO COINCIDE WITH INSTALLATION
OF PAVING
# KEY NOTES
1. REMOVE UNDERGROUND STORAGE TANK, ALONG WITH
ASSOCIATED PIPING AND WIRING.
2. CLEAR AREA OF VEGETATION.
3. EXISTING ELECTRICAL GEAR, SHORE UP ADJACENT SOIL TO
PREVENT UNDERMINING OF FOUNDATION.
4. REMOVE EXISTING FENCE AND FOUNDATIONS.
5. SEE MECHANICAL DRAWINGS FOR EXTENT OF FUEL PIPING
DEMOLITION AT BUILDING 19 WALL.
6. CONTRACTOR TO VERIFY USAGE OF ELECTRICAL LINES
BEFORE REMOVAL.
N:708975.51 E:13230674.21
N:708967.51 E:13230636.87
N:708993.88 E:13230632.74
N:708975.94 E:13230627.32
N:708965.43 E:13230677.70
N:708959.18 E:13230678.12
18'
.0
0'
N:708970.51 E:13230651.89
N:708962.51 E:13230663.87
.0
0'
37.33'
.7
8'
8.48'
8.31'
6.61'
1.44'
4.46'
APPROXIMATE LOCATION OF FUTURE CURB
COORDINATE WITH ADJACENT ATRIUM PROJECT
SHEET NOTES:
1. ENCLOSURE IS CONSIDERED MISSION CRITICAL FOR THE VA
PHYSICAL SECURITY AND RESILIENCY DESIGN MANUAL.
2. ALL DIMENSIONS ARE TO FACE OF CURB UNLESS OTHERWISE
NOTED.
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED DRAWN
DRAWING TITLE
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE:ARCHITECT/ENGINEER OF RECORD SEALCONSULTANT
321 4 5 6 7 8 9 10
REMOVAL OF UST AND
REPLACEMENT OF AST FOR
GENERATOR IN BUILDING 19
1500 WEISS ST, SAGINAW, MI 48602
655-22-202
APPROVED: PROJECT DIRECTOR
3/14/2023NO: DATE:
Group, Inc.
11031 SOUTH PIKES PEAK DRIVE #202
PARKER, COLORADO 80138
PH: 303.841.3922
WWW.AES-GRP.COM
BID DOCUMENTS
DWG. OF
3/14/2023
REVISIONS:
BID DOCUMENTS
HORIZONTAL CONTROL PLAN
CS101
4 9
GJVRID
N
0' 20'10'
SCALE: 1" = 10'
# KEY NOTES
1. MANUAL BARRIER SEE SPECIFICATIONS FOR INSTALLATION.
2. ABOVE GROUND STORAGE TANK.
3. FOUNDATION PEDESTAL FOR ABOVE GROUND STORAGE
TANK. SEE STRUCTURAL PLANS FOR ADDITIONAL
INFORMATION.
4. COORDINATE WITH ADJACENT ATRIUM PROJECT FOR EXACT
LOCATION OF CANOPY STRUCTURE AND NEW CURB
ALIGNMENT.
5. CONTRACTION JOINT LINE.
6. INSTALL VEHICLE BOLLARD SEE DETAIL ON SHEET CI501,
BOLLARD TO BE OMITTED IF ADJACENT ATRIUM PROJECT
CURB AND GUTTER IS UNDER CONSTRUCTION.
609.26TBC
608.89TBC
8.
FG
8.7
FG
608.14FG
607.73FG
607.91FG
8.
FG 60
8.
FG
7.3
FG
609.3 TW
607.3 TF
8.5
FG
APPROXIMATE LOCATION OF FUTURE CURB
COORDINATE WITH ADJACENT ATRIUM PROJECT
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED DRAWN
DRAWING TITLE
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE:ARCHITECT/ENGINEER OF RECORD SEALCONSULTANT
321 4 5 6 7 8 9 10
REMOVAL OF UST AND
REPLACEMENT OF AST FOR
GENERATOR IN BUILDING 19
1500 WEISS ST, SAGINAW, MI 48602
655-22-202
APPROVED: PROJECT DIRECTOR
3/14/2023NO: DATE:
Group, Inc.
11031 SOUTH PIKES PEAK DRIVE #202
PARKER, COLORADO 80138
PH: 303.841.3922
WWW.AES-GRP.COM
BID DOCUMENTS
DWG. OF
3/14/2023
REVISIONS:
BID DOCUMENTS
VERTICAL CONTROL PLAN
CG101
5 9
GJVRID
N
0' 20'10'
SCALE: 1" = 10'
# KEY NOTES
1. MANUAL BARRIER SEE SPECIFICATIONS FOR INSTALLATION.
2. ABOVE GROUND STORAGE TANK.
3. MATCH EXISTING ELEVATION AT TOP BACK OF CURB.
4. WALL SCUPPER AT LOW POINT. SEE STRUCTURAL DRAWINGS
FOR CMU DETAILS.
5. FOUNDATION PEDESTAL FOR ABOVE GROUND STORAGE
TANK SEE STRUCTURAL DRAWING FOR DETAILS.
6. CONCRETE SLAB TO MATCH ADJACENT EXISTING GRADE.
7. CONCRETE SLAB
8. COORDINATE WITH ADJACENT ATRIUM PROJECT FOR EXACT
LOCATION OF CANOPY STRUCTURE AND NEW CURB
ALIGNMENT.
9. INSTALL VEHICLE BOLLARD SEE DETAIL ON SHEET CI501,
BOLLARD TO BE OMITTED IF ADJACENT ATRIUM PROJECT
CURB AND GUTTER IS UNDER CONSTRUCTION.
APPROXIMATE LOCATION OF FUTURE CURB
COORDINATE WITH ADJACENT ATRIUM PROJECT
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED DRAWN
DRAWING TITLE
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE:ARCHITECT/ENGINEER OF RECORD SEALCONSULTANT
321 4 5 6 7 8 9 10
REMOVAL OF UST AND
REPLACEMENT OF AST FOR
GENERATOR IN BUILDING 19
1500 WEISS ST, SAGINAW, MI 48602
655-22-202
APPROVED: PROJECT DIRECTOR
3/14/2023NO: DATE:
Group, Inc.
11031 SOUTH PIKES PEAK DRIVE #202
PARKER, COLORADO 80138
PH: 303.841.3922
WWW.AES-GRP.COM
BID DOCUMENTS
DWG. OF
3/14/2023
REVISIONS:
BID DOCUMENTS
OVERALL UTILITY PLAN
CU101
6 9
GJVRID
N
0' 20'10'
SCALE: 1" = 10'
# KEY NOTES
1. MANUAL LIFT GATE SEE ARCHITECTURAL PLANS.
2. ABOVE GROUND STORAGE TANK.
3. CONCRETE ENCASE AND/OR SLEEVE ALL EXISTING
CONDUITS.
4. FUEL PIPING-BUILDING PENETRATIONS PER ARCHITECTURAL
AND MECHANICAL PLANS.
5. FOUNDATION PEDESTAL FOR ABOVE GROUND STORAGE
TANK. SEE STRUCTURAL PLANS FOR ADDITIONAL
INFORMATION.
6. INSTALL VEHICLE BOLLARD SEE DETAIL ON SHEET CI501,
BOLLARD TO BE OMITTED IF ADJACENT ATRIUM PROJECT
CURB AND GUTTER IS UNDER CONSTRUCTION.
SHEET NOTES:
1. SEE ELECTRICAL SITE PLAN FOR ADDITIONAL INFORMATION
ON ELECTRICAL EQUIPMENT.
2. SEE SHEET CU101 FOR SEWER LINE PLAN AND PROFILE
3. MAINTAIN MINIMUM 3' COVER ON ALL WATER LINES.
4. PROVIDE DETECTABLE WARNING TAPE AT ALL UTILITIES.
CURB SOCK INSTALLATION NOTES
1. PLACE SOCKS UP GRADIENT OF INLET FLUSH WITH CURB.
2. USE NO FEWER THAN (2) 6" DIAMETER SOCKS IN SEQUENCE, UP GRADIENT OF INLET. NO
FEWER THAN 6 SOCKS SHALL BE USED IF THE 4" SIZE IS CHOSEN.
3. MAINTAIN SEDIMENT CONTROL MEASURES AT ALL TIMES DURING EARTH DISTURBING
ACTIVITIES.
INLET
FLOW
3'-0"
6" A
T C
U R
BS
3/4" GRAVEL
1/4" MESH OR BURLAP
WIRE TIE ENDS
.0
0°
2.50
SCALE:1 CURB SOCK DETAIL
NOT TO SCALE
SIDEWALK NOTES
1. LOCATE EXPANSION JOINTS WHERE SIDEWALK ABUTS CONCRETE DRIVEWAYS, CURB OR OTHER ADJACENT STRUCTURES.
2. PROVIDE ONE-HALF INCH BITUMINOUS JOINT FILLER EXPANSION JOINT LOCATIONS TO EXTEND THE FULL DEPTH OF THE CONCRETE.
3. PLACE 1" DEEP CONTRACTION JOINTS AT INTERVALS OF APPROXIMATELY 15' OR AT A SPACING THAT MATCHES THE ADJACENT CURB.
4. FORMED CONTRACTION JOINTS SHALL BE FINISHED WITH A TOOL HAVING A 1/4" RADIUS.
5. SCORED JOINTS SHALL BE 1/4" DEEP AND PLACED AT THE SPACING INDICATED FOR THE WIDTH OF SIDEWALK OR MATCH SCORED JOINTS OF ADJACENT
CURB.
6. FINISH CONCRETE BY MEANS OF A FLOAT, STEEL TOWEL AND BROOM WITH A FINE BRUSH IN A TRANSVERSE DIRECTION.
7. 1/4" DEEP SCORED JOINTS (TYP) SPACED AT 6' OR EQUAL TO SIDEWALK WIDTH.
8. CONTRACTION JOINTS ARE REQUIRED AT 5-FT INTERVALS WITH EXPANSION JOINT (MIN. 1/2" THICK PREMOLDED BITUMINOUS MATERIAL) SPACING NOT TO
EXCEED 45 FEET AND PLACED AT SIDES OF DRIVEWAY APPROACHES, UTILITY VAULTS, AND WHEELCHAIR RAMPS.
9. SIDEWALKS 10-FT. AND WIDER SHALL HAVE LONGITUDINAL CONTRACTION JOINT(S) AT 5-FT ON CENTER.
MEANDERING CONCRETE SIDEWALK
60' MAX.
EXPANSION JOINT TO EXPANSION JOINT
60' MAX.
SEE NOTE 7
SE
E
PL
AN
SE
E
PL
AN
PLAN
COMPACTED
SUBGRADE
CURB & GUTTER
(IF APPLICABLE)
SEE PLANSEE PLAN
1% MIN.
2%MAX.
4" 4000 PSI PORTLAND
CEMENT CONCRETE (PCC)
SCALE:2 CONCRETE SIDEWALK
NOT TO SCALE
SEE PLANS FOR WIDTH
CONCRETE SIDEWALK ADJACENT TO CURB & GUTTER
3/
4" (T
YP
MIN 2" OF GRANULAR BASE ROCK
(COMPACT TO MIN. 95% MAX DRY
DENSITY PER ASTM D698)
1% MIN.
2%MAX.
SEE PLANS FOR CURB
& GUTTER TYPE
SEE NOTE 2 SEE NOTE 2
A TOOLED JOINT IS REQUIRED WHEN THE
CURB AND SIDEWALK ARE POURED
SEPARATELY OR MONOLITHICALLY.
MIN 2" OF GRANULAR BASE ROCK
(COMPACT TO MIN. 95% MAX DRY
DENSITY PER ASTM D698)
COMPACTED
SUBGRADE
1/4" R. (TYP.) FORMED
JOINTS ONLY
1/4" [6mm] DEEP
SCORED JOINTS
EXPANSION JOINT WITH
1/4" BITUMINOUS JOINT
FILLER
1" SCORED OR SAWCUT
CONTRACTION JOINT.
CLASS "B" CONCRETE
TOP OF CURB
6" 4000 PSI PORTLAND
CEMENT CONCRETE (PCC)
SUBGRADE
(COMPACT TO MIN. 95% MAX.
DRY DENSITY PER ASTM D698)
CONTRACTION JOINT (TYP)
BROOM FINISH
6" OF 1"-0 GRANULAR BASEROCK
(COMPACT TO MIN. 95% MAX DRY
DENSITY PER ASTM D698)
CONCRETE PAVEMENT NOTES
1. SEE PLANS FOR LOCATIONS OF CONCRETE PAVEMENT(S).
2. PCC CONSTRUCTION SHALL CONFORM TO PORTLAND CEMENT ASSOCIATION (PCA) SPECIFICATIONS, UNLESS OTHERWISE SPECIFIED.
3. MAXIMUM JOINT SPACING IS 15 FEET BY 15 FEET.
4. PROPOSED JOINT PATTERN SHALL BE PREPARED BY CONTRACTOR AND SUBMITTED TO ER/COR FOR REVIEW AND APPROVAL PRIOR TO PLACING
PCC.
5. DEPTH OF JOINTS SHALL BE MINIMUM OF 1/3 TO MAXIMUM 1/2 THE PAVEMENT THICKNESS.
6. DESIGN SUBGRADES SHALL BE COMPACTED AND PROOF-ROLLED PRIOR TO PLACEMENT OF BASEROCK. IF SUBGRADE PASSES PROOF-ROLL BUT
FAILS DENSITY TESTING, INSTALL MIN. 4.5 OZ NON-WOVEN GEOTEXTILE FABRIC ON SUBGRADE PRIOR TO PLACEMENT OF BASEROCK. FAILURE OF PROOF-ROLL WILL REQUIRE OVEREXCAVATION OR REPAIR AS DIRECTED BY PROJECT GEOTECHNICAL ENGINEER OR ER/COR.
7. IF SUBGRADE FAILS THE PROOF-ROLL, SUBGRADE SHALL BE OVEREXCAVATED TO FIRM AND UNYIELDING SOIL AND BACKFILLED WITH COMPACTED BASEROCK OVER MIN. 8.0-OZ. NON-WOVEN FABRIC AS REQUIRED TO ALLOW COMPACTION OF UPPER (DESIGN) BASEROCK SECTION AND TO MAINTAIN STRUCTURAL INTEGRITY OF SUBGRADE SOILS. TYPICAL MINIMUM OVEREXCAVATION REQUIRED IS 12-INCHES. NO RUBBER
TIRED EQUIPMENT ALLOWED ON SUBGRADE FOLLOWING OVEREXCAVATION.
8. PASSING PROOF-ROLL ON BASEROCK IS ALSO REQUIRED IMMEDIATELY PRIOR TO PLACING PCC.
9. CONTRACTOR SHALL CONFORM TO ALL RECOMMENDATIONS IN GEOTECHNICAL REPORT.
SECTIONPLAN
SCALE:3 CONCRETE DETAIL
NOT TO SCALE
HAND-TOOLED CONTRACTION JOINT
NOTE
1. CONTRACTION IN SIDEWALK, PATIOS, FLOORS, AND DRIVEWAYS MAY BE MADE BY TOOLING OR
SAWING.
2. HAND-TOOLED JOINTS CAN BE FORMED BY METAL TOOL TO PRODUCE A VERTICAL GROOVE,
APPROXIMATELY 1/4 THE THICKNESS OF THE SLAB, BUT NOT LESS THAT 1" DEEP, OR BY A
HARDBOARD INSERT STRIP APPROXIMATELY 1/4" THICK BY 1" WIDE.
3. SAWED JOINTS ALSO SHOULD BE CUT 1/4 THE THICKNESS OF THE SLAB BUT NOT LESS THAN 1"
DEEP TO FORM A WEAKENED PLANE BELOW WHICH A CRACK WILL FORM. SAW CUTTING
SHOULD BE DONE AS SOON AS POSSIBLE AFTER HARDENING OF THE CONCRETE.
SAWED CONTRACTION JOINT
T
T/
M
IN
T/
M
IN
T
1/4" MAX.
SCALE:4 STANDARD CONTRACTION JOINT
NOT TO SCALE
T = PAVEMENT THICKNESS T = PAVEMENT THICKNESS
JOINT SEAL
MAXIMUM 1/2" RADIUS
EXPANSION & SCORED JOINT DETAIL
SCALE:5 BOLLARD DETAIL
NOT TO SCALE
FLOW
SECTION
SEDIMENT CONTROL LOG INSTALLATION NOTES
1. SEE PLAN VIEW FOR:
-LOCATION AND LENGTH OF SEDIMENT CONTROL LOG.
2. SEDIMENT CONTROL LOGS INDICATED ON INITIAL DESC PLAN SHALL BE INSTALLED PRIOR TO ANY
LAND-DISTURBING ACTIVITIES.
3. SEDIMENT CONTROL LOGS SHALL CONSIST OF STRAW, COMPOST, EXCELSIOR, OR COCONUT
FIBER.
4. NOT FOR USE IN CONCENTRATED FLOW AREAS.
5. TRENCH SEDIMENT CONTROL LOGS INTO THE GROUND A MINIMUM OF 2".
SEDIMENT CONTROL LOG MAINTENANCE NOTES
1. INSPECT SEDIMENT CONTROL LOGS DAILY, DURING AND AFTER ANY STORM EVENT AND MAKE
REPAIRS OR CLEAN OUT UPSTREAM SEDIMENT AS NECESSARY.
2. REMOVE SEDIMENT ACCUMULATED UPSTREAM OF SEDIMENT CONTROL LOGS WHEN SEDIMENT
DEPTH IS WITHIN 12 THE HEIGHT OF THE CREST OF THE LOG.
3. REMOVE SEDIMENT CONTROL LOGS AT THE END OF CONSTRUCTION IF ANY DISTURBED AREA
EXISTS AFTER REMOVAL, RE-SEED AND MULCH OR OTHERWISE STABILIZED IN A MANNER
APPROVED BY THE COR.
3' OC MAX 6" AT END
2' -6
1' -6
" 2" M
IN
TIGHTLY ABUT ENDS
ELEVATION
WOODEN STAKES
SCALE:6
SEDIMENT CONTROL LOG (SCL)
NOT TO SCALE
12" DIAMETER SEDIMENT
CONTROL LOG
16"
TYP
4' -0
4'
-0
"6" TYP
6" M
IN
BOLLARDS TO BE PAINTED
WITH SAFETY YELLOW PAINT
YELLOW REFLECTIVE TAPE
4" DIAMETER SCH. 40 STEEL
PIPE FILL WITH CONCRETE
PAVEMENT
CONCRETE 3,000 PSI
@ 28 DAYS
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED DRAWN
DRAWING TITLE
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE:ARCHITECT/ENGINEER OF RECORD SEALCONSULTANT
321 4 5 6 7 8 9 10
REMOVAL OF UST AND
REPLACEMENT OF AST FOR
GENERATOR IN BUILDING 19
1500 WEISS ST, SAGINAW, MI 48602
655-22-202
APPROVED: PROJECT DIRECTOR
3/14/2023NO: DATE:
Group, Inc.
11031 SOUTH PIKES PEAK DRIVE #202
PARKER, COLORADO 80138
PH: 303.841.3922
WWW.AES-GRP.COM
BID DOCUMENTS
DWG. OF
3/14/2023
REVISIONS:
BID DOCUMENTS
SEDIMENT CONTROL DETAILS
CI501
7 9
GJVRID
A
S101
EXISTING SHOWN
AS DASHED
12' - 0"
TANK FOUNDATION
B
S101
A
S101
6' - 0"
1' - 0"
31' - 4"
/2
D O
O R
O P
E N
IN
G
/2
CONCRETE SLAB
- SEE CIVIL
C
S101
B
S101
B
S101
PROVIDE SLEEVE FOR
EXISTING CONDUIT
PROVIDE SLEEVE OR
CONCRETE ENCASEMENT
FOR EXISTING CONDUIT
(REFER TO CIVIL)
M
IN
B
E L
O W
G R
A D
E
1' - 11" 1' - 2" 1' - 11"
C L
#4 @ 12" O.C.#4 @ 12" O.C.
3/4" CHAMFER
CONCRETE
SEE CIVIL
EXPANSION MATERIAL
1' - 3" 1' - 0" 1' - 3"
C L
M
IN
B
E L
O W
G R
A D
E
#4 @ 12" O.C. (TYP.)
CONCRETE
SEE CIVIL
EXPANSION MATERIAL
ELEVATION VARIES
REFER TO CIVIL
REFER TO ARCH. DRAWINGS
FOR REINFORCEMENT SIZE
AND SPACING
EL. = 609' - 0"
WALL REINFORCEMENT
NOT SHOWN
#4 @ 12" O.C.
#4 @ 12" O.C.
GRADE - SEE CIVIL
B/FTG. EL. = 605' - 5"
B/FTG. EL. = 603' - 8"2
7' - 0"
G E N E R A L N O T E S
A. BEFORE POURING TANK FOUNDATIONS, COORDINATE ALL DIMENSIONS WITH EQUIPMENT
MANUFACTURER.
B. ALL CONCRETE WORK SHALL CONFORM TO THE MOST RECENT EDITION OF ACI 301 & ACI 318-19 CODE
REQUIREMENTS AND DETAILING STANDARDS.
C. ALL READY MIXED CONCRETE SHALL CONFORM TO ASTM C94.
D. USE AIR ENTRAINED CONCRETE (6% + OR - 1.5%) FOR ALL AREAS EXPOSED TO WEATHER, FROST IN
SOIL, OR FREEZE THAW CYCLES.
E. ALL CONCRETE SHALL DEVELOP THE COMPRESSIVE STRENGTHS AT 28 DAYS (F`c) = 4000 psi UNLESS
NOTED OTHERWISE.
F. DETAILING BENDING AND PLACING OF REINFORCING STEEL SHALL BE IN ACCORDANCE WITH THE
LATEST EDITION OF THE ACI CODE SP-66.
G. PROCEDURES FOR PLACEMENT OF CONCRETE SHALL BE IN STRICT CONFORMANCE WITH ACI 304 "RECOMMENDED PRACTICE FOR MEASURING, MIXING, TRANSPORTING, AND PLACING CONCRETE".
H. REINFORCING STEEL: fy = 60,000 PSI.
I. BOTTOM OF FOOTING TO BE MINIMUM 3'-6" BELOW GRADE.
4' - 0"3' - 0"
4' - 0"
3' - 0"
#4 @ 12" O.C. TYP
#4 @ 12" O.C. TYP
C L
MANUAL SWING GATE
GALVANIZED PIPE SLEEVE
ONE SIZE GREATER THAN
EXISTING CONDUIT
#4 BAR X 2" LONG
WELDED TO SLEEVE
ON FOUR SIDES
CONCRETE WALL
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /S a g in a w V
A
B u ild in g
U
S T
/F F
E S a g in a w
B u ild in g
U
S T
B rv t
/1
/2
:1
:4
P
M
S101
FOUNDATION PLAN AND DETAILS
03/14/2023 PM CL
REMOVAL OF UST AND
REPLACEMENT WITH AST FOR
GENERATOR IN BUILDING 19
655-22-202
1500 WEISS ST. SAGINAW, MI 48602
BID DOCUMENTS
SAGINAW VA
MEDICAL
CENTER Approved: Veteran's Affairs Medical Center
N
1/4" = 1'-0"
FOUNDATION PLAN
3/4" = 1'-0"
A
SECTION - TANK FOUNDATION
3/4" = 1'-0" B
SECTION - WALL FOUNDATION
1/4" = 1'-0"
C
SECTION
No. Revisions: Date:
BID DOCUMENTS 03/14/2023
1/4" = 1'-0"
SWING GATE FOUNDATION DETAIL
3/4" = 1'-0"
PIPE SLEEVE DETAIL
5/A401
BUILDING 19
6' - 0" 31' - 4"
BUILDING 1
BUILDING 22
4' - 0"
EQ EQ
A401
5 5
11 1112 12 12
18 18
G E N E R A L N O T E S
A. REFER TO SHEET GI000 FOR GENERAL NEW WORK NOTES.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /S a g in a w V
A
B u ild in g
U
S T
/F F
E S a g in a w
B u ild in g
U
S T
B rv t
/1
/2
:1
:2
P
M
A101
FLOOR PLAN
03/14/2023 PQ TD
REMOVAL OF UST AND
REPLACEMENT WITH AST FOR
GENERATOR IN BUILDING 19
655-22-202
1500 WEISS ST. SAGINAW, MI 48602
BID DOCUMENTS
SAGINAW VA
MEDICAL
CENTER Approved: Veteran's Affairs Medical Center
N
1/4" = 1'-0"
FIRST FLOOR PLAN
D R A W I N G N O T E S :
1 4" CONCRETE PAD - SEE STRUCTURAL DRAWINGS.
2 8-IN CMU WITH 4-IN BRICK VENEER - ONE LAYER OF NO. 5 BARS AT 32-IN OC, ONLY CELLS WITH REINFORCED BARS NEED TO BE GROUTED, HORIZONTAL REINFORCEMENT NOT NEEDED FOR BLAST. SEE SECTIONS AND ELEVATIONS ON SHEET
AE401.
3 8-IN CMU WITH 4-IN BRICK VENEER, 2000 PSI MASONRY WITH TWO LAYERS OF VERTICAL BARS (NO. 4 OR 5) AT 8-IN OC, HORIZONTAL REINFORCING NOT REQUIRED FOR BLAST - SEE SECTIONS AND ELEVATIONS ON SHEET AE401.
4 8-IN CMU WITH 4-IN BRICK VENEER, 2000 PSI MASONRY WITH TWO LAYERS OF VERTICAL BARS (NO. 4 OR 5) AT 8-IN OC, AND WIRE MESH HORIZONTAL REINFORCEMENT AT EVERY COURSE - SEE SECTIONS AND ELEVATIONS ON SHEET AE401.
5 BRICK WALL TO REMAIN - NOT REQUIRED TO BE BLAST RESISTANT.
6 TRELLISING SYSTEM - SEE DETAILS ON SHEET AE401.
7 MANUAL SWING GATE ARM BARRIER - 20'-0" LONG ARM - SEE STRUCTURAL FOR FOOTING DETAIL.
8 INSTALL A NEW 6000 GALLON ABOVEGROUND STORAGE TANK - SEE MECHANICAL DRAWINGS.
9 INSTALL A NEW 100 GALLON DAY TANK - SEE MECHANICAL DRAWINGS.
10 EXTERIOR LIGHT FIXTURE - SEE ELECTRICAL DRAWINGS.
11 GRAVEL TO REMAIN.
12 RADIATORS TO REMAIN.
13 MANHOLE TO REMAIN - TYP.
14 RELOCATE "WRONG DIRECTION" SIGN.
15 STOP SIGN TO REMAIN.
16 LIGHT POST TO REMAIN.
17 ELECTRICAL TRANSFORMER TO REMAIN.
18 CONTROL JOINT BETWEEN EXISTING AND NEW WALL.
No. Revisions: Date:
BID DOCUMENTS 03/14/2023
C L
CL
12"
4" CONCRETE PAD
8" CMU - REINFORCED
AND GROUTED SOLID
4" BRICK - RUNNING BOND
4" BRICK - SOLDIER COURSE RUNNING BOND
STAINLESS STEEL COPING
PAINTED WHITE
REINFORCEMENT -
SEE STRUCTURAL
DETAILS.
CONCRETE FOOTING -
SEE STRUCTURAL
DETAILS.
REINFORCEMENT -
SEE STRUCTURAL
DETAILS.
/8
/8
2"X12" - CONTINUOUS
PRESSURE TREATED
BLOCKING
1/2" EXPANSION JOINT MATERIAL
COLLAR JOINT
TYP.
4' - 0"
T Y
P
TRELLISING SYSTEM
(DEDUCT ITEM)
BRICK -
SOLDIER COURSE
CONCRETE COPING
BRICK - RUNNING BOND
1' - 8"
609' - 0"
617' - 4"
T/O FOUNDATION
T/O RUNNING BOND
T/O WALL
L 3" X 3" X 3/8" STEEL LINTEL WITH
8" MINIMAL BEARING
HOLLOW METAL MASONRY FRAME
BRICK VENEER
8" BOND BEAM
COLLAR JOINT
1' - 0"
5 3/4"
CONTINUOUS SEALANT EACH SIDE
SEALANT EACH SIDE
HOLLOW METAL MASONRY FRAME
GROUTED SOLID
BRICK VENEER
8" CMU
1' - 0"
5 3/4"
COLLAR JOINT
2" SEE SCHEDULE 2"
S E
E S
C H
E D
U L E
SEE SCHEDULE
S E
E S
C H
E D
U L E
F TYPE 1
FLUSH
3" TRELLIS PANEL
3" SLED W/ 1-1/2"
SLOT FOR ADJUSTABILITY
MASONRY WALL
MOUNTING CLIP, TYP.
W/ BENT STEEL GUSSET, TYP.
EXPANSION ANCHOR BY OTHERS -
MIN. 480 LBS. PULL OUT. CLIP SIZED
FOR 3/8" DIA. FASTENER, TYP.
SPACER - 1/2" x 1-1/2" DIA., TYP.
3" 4 1/4" 1/2"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /S a g in a w V
A
B u ild in g
U
S T
/F F
E S a g in a w
B u ild in g
U
S T
B rv t
/1
/2
:1
:2
P
M
A401
ENLARGED SECTIONS,
ELEVATIONS, AND DETAILS
03/14/2023 PQ TD
REMOVAL OF UST AND
REPLACEMENT WITH AST FOR
GENERATOR IN BUILDING 19
655-22-202
1500 WEISS ST. SAGINAW, MI 48602
BID DOCUMENTS
SAGINAW VA
MEDICAL
CENTER Approved: Veteran's Affairs Medical Center
1" = 1'-0"
TYPICAL WALL SECTION
1/2" = 1'-0"
TRELLIS SYSTEM - ELEVATION
3" = 1'-0"
DOOR HEAD DETAIL
3" = 1'-0"
DOOR JAMB DETAIL
DOOR SCHEDULE
MARK WIDTH HEIGHT
DOOR
PANELS THICKNESS
FRAME
MATERIAL
DOOR
MATERIAL HARDWARE
001 6' - 0" 7' - 0" 2 1 3/4" HM HM 01
No. Revisions: Date:
BID DOCUMENTS 03/14/2023
1. DOOR DOES NOT NEED BLAST PROTECTION
2. FLUSH DOOR PANEL AND FRAME
3. REMOVABLE ASTRAGAL
DOOR SCHEDULE NOTES:
1/2" = 1'-0"
DOOR PANEL AND FRAME ELEVATION
3" = 1'-0"
TRELLIS WALL MOUNT DETAIL
A/E ARCHITECT / ENGINEER
AFF ABOVE FINISHED FLOOR
AMP AMPERE
ASHRAE AMERICAN SOCIETY OF HEATING
REFRIGERATION AIR CONDITIONING ENGINEERS
ASME AMERICAN SOCIETY OF MECHANICAL
ENGINEERS
BFP BACKFLOW PREVENTER
BHP BRAKE HORSEPOWER
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
C CENTIGRADE (CELSIUS)
CFT CUBIC FEET
CI CAST IRON
Db DRY-BULB TEMPERATURE
DB DECIBELS
DCW DOMESTIC COLD WATER
DDC DIRECT DIGITAL CONTROLS
DEG DEGREE
DIA DIAMETER
EA EXHAUST AIR
ECC ENGINEERING CONTROL CENTER
EF EXHAUST FAN
EJ EXPANSION JOINT
ENT ENTERING
ESP EXTERNAL STATIC PRESSURE
EX EXISTING
F FAHRENHEIT
FM FLOW METER
FOP FUEL OIL PUMP
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FOT FUEL OIL TANK
FOHX FUEL OIL HEAT EXCHANGER
FS FLOW SWITCH
FT FEET
FT WC FEET OF WATER COLUMN
GA GAUGE
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
HOA HAND/OFF/AUTOMATIC
HP HORSEPOWER
HZ HERTZ
I/O INPUT/OUTPUT
ID INSIDE DIAMETER
IN INCHES
IN HG INCHES OF MERCURY
IN WC INCH WATER COLUMN
IN WG INCH WATER GAUGE
KW KILOWATT
KWH KILOWATT HOUR
LF LINEAR FOOT (FEET)
MAX MAXIMUM
MBH 1,000 BTUH
MIN MINIMUM
NA NOT APPLICABLE
NC NOISE CRITERIA
NC NORMALLY CLOSED
NO NORMALLY OPEN
NPSH NET POSITIVE SUCTION HEAD
NPSHA NET POSITIVE SUCTION HEAD AVAILABLE
NPSHR NET POSITIVE SUCTION HEAD REQUIRED
NTS NOT TO SCALE
OD OUTSIDE DIAMETER
OFM OIL FLOWMETER
P PUMP
PG PRESSURE GAGE
PPM PARTS PER MILLION
PRV PRESSURE REGULATING VALVE
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH – ABSOLUTE
PSIG POUNDS PER SQUARE INCH – GAGE
PSV PRESSURE SAFETY VALVE
RLA RUN LOAD AMPERE
RPM REVOLUTIONS PER MINUTE
RV RELIEF VALVE
SP STATIC PRESSURE
SP GR SPECIFIC GRAVITY
SQ FT SQUARE FOOT (FEET)
TAB TESTING, ADJUSTING, BALANCE
TDH TOTAL DYNAMIC HEAD
TF TANK FILL PIPING
TFOT TEMPORARY FUEL OIL TANK
TSTAT THERMOSTAT
UH UNIT HEATER
U UNDERWRITERS LABORATORY
V VALVE
VFD VARIABLE FREQUENCY DRIVE
VHA VETERANS HEALTH ADMINISTRATION
VSD VARIABLE SPEED DRIVE
W WATTS
WEF WALL EXHAUST FAN
YR YEAR
ABBREVIATIONS
M
H4
H7
A
COLD WATER (CITY WATER)
HOT WATER
QUICK-COUPLE HOSE CONNECTOR
PLUG VALVE
CONTROL VALVE (CV) - FLOAT-OPERATED
PRESSURE REDUCING VALVE (PRV)
WYE STRAINER WITH VALVED DRAIN AND QUICK-COUPLE
HOSE CONNECTOR
FLOW METER
DRAWING SYMBOLS
26-SF 3
26-TU-I-I
DETAIL NUMBER
DRAWING NUMBER WHERE SHOWN
SECTION LETTER
TYPICAL UNIT NO.
BUILDING NO. WHERE EQUIPMENT IS LOCATED.
SUPPLY FAN NO. 3 IN BUILDING NO. 26
EQUIPMENT ABBREVIATION (SUPPLY FAN)
ITEM NUMBER (TERMINAL UNIT NO. 1)
ITEM (TERMINAL UNIT SHOWN)
SERVED BY AIR HANDLER UNIT NO. 1
DRAWING NUMBER WHERE DRAWN
BUILDING NO. WHERE EQUIPMENT IS LOCATED
LIMIT OF DEMOLITION
CONNECT NEW TO EXISTING
PIPING SYMBOLS
VENT LINE
DRAIN LINE
V
D
HW
CW
GENERAL PIPING SYMBOLS
ANCHOR
REDUCER OR INCREASER
DIRECTION OF FLOW
SIDE CONNECTION
ECCENTRIC REDUCER
BOTTOM CONNECTION, 45° OR 90°
TOP CONNECTION, 45° OR 90°
DIRECTION OF PIPE PITCH (DOWN)
UNION
RISE OR DROP IN PIPE
CAPPED OUTLET
PRESSURE GAGE
THERMOMETER
FLOW ELEMENTFE
PIPE UP
PIPE DOWN
REFRIGERANT SIGHT GLASS
TEST PLUG (PRESSURE/TEMPERATURE)
AUTOMATIC AIR VENT
AV
MANUAL AIR VENTMV
VALVE SYMBOLS
BALL VALVE
GATE VALVE WITH 3/4" HOSE ADAPTER
CHECK VALVE
ANGLE GLOBE VALVE
BUTTERFLY VALVE
MODULATING CONTROL VALVE
TWO POSITION CONTROL VALVE
THREE-WAY MODULATING CONTROL VALVE
AUTOMATIC BALANCING CONTROL VALVE
PRESSURE SAFETY VALVE
GATE VALVE - THREADED/FLANGED
GLOBE VALVE - THREADED/FLANGED
PRESSURE REGULATING VALVE
THREE-WAY TWO POSITION CONTROL VALVE
WYE STRAINER (WITH BALL VALVE & HOSE CONNECTION)
WATER BALANCE DEVICE
MODULATING CONTROL BUTTERFLY VALVE
CIRCUIT SETTER VALVE
CONTROLS SYMBOLS
T ROOM THERMOSTAT/TRANSMITTER - WALL MOUNT
TT TEMPERATURE TRANSMITTER
M ROOM HUMIDISTAT (MOISTURE)/TRANSMITTER - WALL MOUNT
MT MOISTURE (HUMIDITY) TRANSMITTER
PT PRESSURE TRANSMITTER
TT TEMPERATURE TRANSMITTER, AVERAGING ELEMENT
FT FLOW TRANSMITTER
IT CURRENT TRANSMITTER
SPS STATIC PRESSURE SENSOR
SD SMOKE DETECTOR
PDT PRESSURE DIFFERENTIAL TRANSMITTER
MG MAGNEHLIC PRESSURE GAUGE
PDS PRESSURE DIFFERENTIAL SWITCH
A
TEMPERATURE SENSING ELEMENT FOR
TRANSMITTING TEMPERATURE TO EMCS
(PROVIDE 12 INCHES [200mm] MINIMUM
LENGTH IN DUCT WHEN SPACE PERMITS.)
SENSOR WITH AVERAGING ELEMENT TO TRANSMIT
TEMPERATURE TO EMCS
MOTOR STARTER
M ELECTRIC OPERATED CONTROL DAMPER/OR VALVE
T
ES END SWITCH
(FC) FAIL CLOSED
(FO) FAIL OPEN
(FLP) FAIL LAST POSITION
T STEAM TRAP
CP CONDENSATE PUMP
HS HAND SWITCH (HAND-OFF-AUTO SWITCH)
NOTE:
ALL SYMBOLS AND ABBREVIATIONS ARE
SUBJECT TO MODIFICATIONS ON OTHER
DRAWINGS. ALL SYMBOLS OR ABBREVIATIONS
MIGHT NOT NECESSARILY BE USED ON THIS
PROJECT.
FUEL OIL RETURN
FUEL OIL SUPPLYFOS
FOR
GENERAL
A. THE FOLLOWING NOTES APPLY EQUALLY TO THE FULL SET OF DOCUMENTS
B. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO INSTALL COMPLETE AND OPERABLE MECHANICAL SYSTEMS AS INDICATED ON THE
DRAWINGS, AS SPECIFIED, AND AS REQUIRED BY CODE.
C. CONTRACT DOCUMENT DRAWINGS FOR MECHANICAL WORK ARE DIAGRAMMATIC AND ARE INTENDED TO CONVEY SCOPE AND GENERAL ARRANGEMENT ONLY.
D. INSTALL ALL MECHANICAL EQUIPMENT AND APPURTENANCES IN ACCORDANCE WITH MANUFACTURERS’ RECOMMENDATIONS, CONTRACT DOCUMENTS, AND APPLICABLE
CODES AND REGULATIONS.
E. PROVIDE VIBRATION ISOLATION FOR ALL MECHANICAL EQUIPMENT TO PREVENT TRANSMISSION OF VIBRATION TO BUILDING STRUCTURE.
F. COORDINATE CONSTRUCTION OF ALL MECHANICAL WORK WITH ARCHITECTURAL, STRUCTURAL, CIVIL, ELECTRICAL WORK, ETC., SHOWN ON OTHER CONTRACT
DOCUMENT DRAWINGS.
G. ALL TESTS SHALL BE COMPLETED BEFORE ANY MECHANICAL EQUIPMENT OR PIPING INSULATION IS APPLIED.
H. WHERE TWO OR MORE ITEMS OF THE SAME TYPE OF EQUIPMENT ARE REQUIRED, THE PRODUCT OF ONE MANUFACTURER SHALL BE USED.
I. COORDINATE ALL EQUIPMENT CONNECTIONS WITH MANUFACTURERS' CERTIFIED DRAWINGS.
J. COORDINATE AND PROVIDE ALL PIPING TRANSITIONS REQUIRED FOR FINAL EQUIPMENT CONNECTIONS TO FURNISHED EQUIPMENT. FIELD VERIFY AND COORDINATE ALL
PIPING DIMENSIONS BEFORE FABRICATION.
K. THE LOCATIONS OF ALL ITEMS SHOWN ON THE DRAWINGS OR CALLED FOR IN THE SPECIFICATIONS THAT ARE NOT DEFINITELY FIXED BY DIMENSIONS ARE APPROXIMATE ONLY. THE EXACT LOCATIONS NECESSARY TO SECURE THE BEST CONDITIONS AND RESULTS MUST BE DETERMINED BY THE PROJECT SITE CONDITIONS AND SHALL HAVE THE APPROVAL OF THE ENGINEER BEFORE BEING INSTALLED. DO NOT SCALE DRAWINGS.
L. ALL MISCELLANEOUS STEEL REQUIRED TO ENSURE PROPER INSTALLATION AND AS SHOWN IN DETAILS FOR PIPING AND EQUIPMENT (UNLESS OTHERWISE NOTED)
SHALL BE FURNISHED AND INSTALLED BY THE MECHANICAL CONTRACTOR.
M. ALL EQUIPMENT, PIPING, DUCTWORK. ETC., SHALL BE SUPPORTED AS SPECIFIED AND REQUIRED TO PROVIDE A VIBRATION-FREE INSTALLATION.
N. LOCATIONS AND SIZES OF ALL FLOOR, WALL, AND ROOF OPENINGS SHALL BE COORDINATED WITH ALL OTHER TRADES INVOLVED.
O. ALL OPENINGS IN FIRE WALLS DUE TO DUCTWORK, PIPING, CONDUIT, ETC., SHALL BE FIRE STOPPED PER SPECIFICATIONS.
DEMOLITION
A. WORK MUST BE COORDINATED WITH OWNER TO MAINTAIN OPERATION OF THE FACILITY. PROVIDE AT LEAST 14 DAYS ADVANCE NOTICE TO THE COR FOR ANY UTILITY
SHUT DOWN.
B. SEAL ANY FLOOR OR WALL PENETRATIONS WHERE DUCT OR PIPES ARE REMOVED. HOLES IN WALLS AND FLOORS CREATED OR EXPOSED DURING DEMOLITION SHALL
BE REPAIRED TO MATCH EXISTING FINISHES.
C. PIPING ADJACENT TO DEMOLITION SCOPE SHALL BE LEFT IN OPERATIONAL CONDITION. REPAIR INSULATION AND VERIFY SUPPORTS REMAIN AS REQUIRED.
PIPING
A. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO INSTALL COMPLETE AND OPERABLE PIPING SYSTEMS AS INDICATED ON THE
DRAWINGS, AS SPECIFIED, AND AS REQUIRED BY CODE.
B. INSTALL PIPING SO ALL VALVES, STRAINERS, UNIONS, TRAPS, FLANGES, AND OTHER APPURTENANCES REQUIRING ACCESS ARE ACCESSIBLE.
C. ALL VALVES SHALL BE INSTALLED SO THAT THE VALVE REMAINS IN SERVICE WHEN EQUIPMENT OR PIPING ON THE EQUIPMENT SIDE OF THE VALVE IS REMOVED.
D. ALL VALVES (EXCEPT CONTROL VALVES) AND STRAINERS SHALL BE THE FULL SIZE OF THE PIPE BEFORE REDUCING IN SIZE TO MAKE CONNECTIONS TO EQUIPMENT
AND CONTROLS.
E. UNIONS AND/OR FLANGES SHALL BE INSTALLED AT EACH PIECE OF EQUIPMENT, IN BYPASSES, AND IN LONG PIPING RUNS (100 FT. OR MORE) TO PERMIT DISASSEMBLY
FOR ALTERATION AND REPAIRS.
F. INSTALL ALL PIPING WITHOUT FORCING OR SPRINGING.
G. ALL PIPING SHALL CLEAR DOORS AND WINDOWS.
H. ALL VALVES SHALL BE ADJUSTED FOR SMOOTH AND EASY OPERATION.
I. ALL PIPING WORK SHALL BE COORDINATED WITH ALL TRADES INVOLVED. OFFSETS IN PIPING AROUND OBSTRUCTIONS SHALL BE PROVIDED AT NO ADDITIONAL COST TO
THE OWNER.
J. PROVIDE FLEXIBLE CONNECTIONS IN ALL PIPING SYSTEMS CONNECTED TO PUMPS AND OTHER EQUIPMENT WHICH REQUIRE VIBRATION ISOLATION. FLEXIBLE CONNECTIONS SHALL BE PROVIDED AS CLOSE TO THE EQUIPMENT AS POSSIBLE OR AS INDICATED ON THE DRAWINGS.
K. PROVIDE A LINE SIZE STRAINER UPSTREAM OF EACH AUTOMATIC VALVE. PROVIDE A SHUTOFF VALVE ON EACH SIDE OF THE STRAINER.
EQUIPMENT CONTROLS
A. REVIEW ALL DRAWINGS AND SPECIFICATIONS FOR CONTROLS AND BMS INTEGRATION REQUIREMENTS.
B. THE POINTS LISTED ON DRAWINGS SHALL BE THE MINIMUM REQUIRED TO BE INTEGRATED WITH THE CAMPUS BUILDING AUTOMATION SYSTEM. IT IS NOT THE INTENT TO SHOW ALL REQUIRED POINTS. IF OR WHEN ADDITIONAL POINTS ARE REQUIRED TO ACCOMPLISH THE SEQUENCES OF CONTROL OR MONITORING SPECIFIED, THOSE
POINTS SHALL ALSO BE PROVIDED.
FUEL SYSTEMS
A. DO NOT WELD ON THE TANK, MODIFY OR PENETRATE THE TANK STRUCTURE IN ANY WAY WITHOUT THE EXPRESS WRITTEN PERMISSION OF THE TANK MANUFACTURER
B. PIPE SUPPORTS, PLATFORMS, AND OTHER EQUIPMENT TO BE ATTACHED TO TANK MUST BE COORDINATED WITH THE TANK MANUFACTURER.
C. ALL UNUSED TANK OPENINGS MUST BE PROPERLY SEALED AND TESTED TO BE LIQUID AND VAPOR TIGHT PRIOR TO PUTTING THE TANK INTO SERVICE.
D. CONTRACTOR SHALL COORDINATE ANY REQUIRED HAZARDOUS WASTE DISPOSAL WITH THE VA.
E. DO NOT USE METALLIC FITTINGS FURNISHED BY THE PIPING MANUFACTURER TO PROTECT PRE-CUT PIPE THREADS DURING SHIPPING TO COMPLETE A PIPING
INSTALLATION.
F. ALL PIPING COMPONENTS, INCLUDING FLANGE GASKETS, PIPE DOPE/COMPOUND, AND THE PIPING ITSELF, MUST BE FULLY COMPATIBLE WITH THE PRODUCTS (FUEL
TYPE) STORED.
G. WRAP RIBBON DOPE WITH THE THREADS TO AVOID BUNCHING DURING TIGHTENING.
H. INSPECT ALL PIPING MATERIALS PRIOR TO INSTALLATION TO DETECT DAMAGE CAUSED BY SHIPPING AND HANDLING AND TO CONFIRM COMPLIANCE WITH SPECIFICATIONS. HANDLE PIPING CAREFULLY TO AVOID DAMAGE TO PIPING MATERIALS OR COATINGS DURING INSTALLATION, TESTING AND BACKFILLING. KEEP PIPE AND FITTING INTERIORS AND THREADS FREE FROM DIRT, CORROSION, MOISTURE AND DEBRIS.
I. HIGH AND LOW POINTS IN PIPING SHALL BE KEPT TO THE MINIMUM REQUIRED TO ACCOMPLISH THE ROUTING SHOWN ON PLANS. MINIMIZE USE OF FITTINGS.
J. EXERCISE CARE TO MEASURE AND CUT PIPE ACCURATELY TO AVOID THE FAILURE THAT CAN OCCUR WHEN PIPE FITTINGS ARE INSTALLED UNDER STRESS. REAM AND
DE-BURR PIPE ENDS AFTER CUTTING. DO NOT BEND STEEL PIPE.
K. ALL EQUIPMENT SHALL CONSTRUCTED AND LISTED IN ACCORDANCE WITH FEDERAL AND LOCAL REGULATIONS.
L. SYSTEM SHALL BE HAND PRIMED AND BLED OF ALL AIR BEFORE OPERATION OF FUEL HANDLING EQUIPMENT. THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL
VENTS OR EQUIPMENT REQUIRED FOR PRIMING.
M. ALL PIPING, FILL STATIONS, AND RELATED EQUIPMENT SHALL BE IDENTIFIED FOR THE PRODUCT WHICH IT USED BY ANSI/ASME A13.1 STANDARD. IDENTIFICATION SHALL BE SUITABLE FOR OUTDOOR INSTALLATION. IDENTIFICATIONS SHALL BE CONSPICUOUSLY LOCATED. ALSO REFERENCE SPECIFICATION 09 91 00 PAINTING.
N. PIPING SHALL BY PRESSURE TESTED AS REQUIRED PER NFPA 30.
O. CONTRACTOR SHALL PROVIDE WARNING SIGNAGE AND EMERGENCY INSTRUCTIONS IN ACCORDANCE WITH NFPA STANDARDS.
P. FILLING PROCECURE SHALL BE POSTED AT THE REMOTE FILL STATIONS BY THE OWNER.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s
/S a g in a w
V A
B u ild in g
U
S T
/F F
E
S a g in a w
B u ild in g
U
S T
B
M E
P rv t
/1
/2
:0
:0
P
M
M001
MECHANICAL LEGEND
03/14/2023 PDP JV
REMOVAL OF UST AND
REPLACEMENT WITH AST FOR
GENERATOR IN BUILDING 19
655-22-202
1500 WEISS ST, SAGINAW, MI 48602
BID DOCUMENTS
SAGINAW VA
MEDICAL
CENTER Approved: Owner
No. Revisions: Date:
AGU
X
E
ELEC
MH
ELEC
MH
X
FMH
FMH
FMH
FMH FMH
F M H
FMH
F
(E
G
E N
E R
A T
O R
(E
G E
N E
R A
T O
R
(E
G E
N E
R A
T O
R
(E) RADIATOR (E) RADIATOR (E) RADIATOR
TYP.
(E) TANK-5
(E) DAY TANK
(E) DAY TANK
(E) DAY TANK
(E) ELECTRICAL EQUIPMENT
P1
1. CONTRACTOR SHALL PROVIDE TEMPORARY FUELING STATION WITH 6,000 GALLON CAPACITY
FOR MANUAL DISPENSING TO GENERATOR DAY TANKS DURING CONSTRUCTION.
2. INSTALL THE TEMPORARY FUEL OIL TANK. INSTALLATION LOCATION IDENTFIEID IS SLOPED.
LEVEL TANK BEFORE FILLING.
3. TEMPORARY FUELING SHALL BE AVAILABLE FOR FULL DURATION THAT THE PERMANENT FUEL
TANKS ARE OUT OF SERVICE, INCLUDING DURING PERMITTING. NO INTERRUPTION OF FUEL
AVAILABILITY TO OWNER IS ALLOWABLE.
4. TEMPORARY FUEL SHALL MEET ALL APPLICABLE LOCAL AND NATIONAL CODES FOR FUEL
STORAGE AND DISPENSING. CONTRACTOR SHALL ALLOW FOR REGULATORY INSPECTION IF
REQUIRED.
5. TEMPORARY STORAGE AND DISPENSING EQUIPMENT SHALL BE STATIONARY (NOT TRAILER
MOUNTED). CONTRACTOR SHALL PROVIDE POWER FOR DISPENSERS. FUEL IS SUPPLIED BY
OWNER.
PHASING NOTES:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s
/S a g in a w
V A
B u ild in g
U
S T
/F F
E
S a g in a w
B u ild in g
U
S T
B
M E
P rv t
/1
/2
:1
:1
P
M
MD100
MECHANICAL DEMOLITION PLAN
03/14/2023 PDP JV
REMOVAL OF UST AND
REPLACEMENT WITH AST FOR
GENERATOR IN BUILDING 19
655-22-202
1500 WEISS ST, SAGINAW, MI 48602
BID DOCUMENTS
SAGINAW VA
MEDICAL
CENTER Approved: Owner
N
1/4" = 1'-0"
MECHANICAL DEMOLITION PLAN
D R A W I N G N O T E S :
1 EXCAVATE EXISTING UNDERGROUND STORAGE TANK. PROVIDE SHORING AROUND EXISTING ELECTRICAL EQUIPMENT AND MANHOLES. DISCONNECT ALL PIPING AND ALL TANK ACCESSORIES. SEE SPECIFICATION 02 65 00 UNDERGROUND
STORAGE TANK REMOVAL.
2 REMOVE EXISTING TANK MONITORING SYSTEM AND ALL ASSOCIATED POWER AND SENSOR TUBING TO UNDERGROUND
STORAGE TANK.
3 TEMPORARY FUEL OIL TANK PROVIDED BY CONTRACTOR.
4 DEMOLISH EXISTING FUEL PIPING.
5 REPAIR AND SEAL OPENINGS WHERE PIPING OR CONDUIT IS REMOVED AND NOT RE-USED FOR NEW PIPING. CONSIDER
WALL AS FIRE RATED WHEN SEALING PENETRATIONS.
6 PROVIDE A SPILL KIT AND SORBENT MATS AT FILLING AND DISPENSING POINTS OF TEMPORARY FUEL STORAGE.
No. Revisions: Date:
BID DOCUMENTS 03/14/2023
NTS
EXISTING PROJECT AREA
AGU
X
E
ELEC
MH
ELEC
MH
X
3/4"ø FOS 3/4"ø FOS
2FOT-1
(E
G E
N E
R A
T O
R
(E
G E
N E
R A
T O
R
(E
G E
N E
R A
T O
R
TYP.
(E) RADIATOR (E) RADIATOR (E) RADIATOR
(E) DAY TANK
(E) DAY TANK
(E) DAY TANK
FOT-2
1"ø FOR
3/4"ø FOS 1"ø FOS
1"ø FOR
FOHX-1
2"ø TF
TYP. TYP.
(E) ELECTRICAL EQUIPMENT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s
/S a g in a w
V A
B u ild in g
U
S T
/F F
E
S a g in a w
B u ild in g
U
S T
B
M E
P rv t
/1
/2
:0
:1
P
M
MH100
MECHANICAL NEW WORK PLAN
03/14/2023 PDP JV
REMOVAL OF UST AND
REPLACEMENT WITH AST FOR
GENERATOR IN BUILDING 19
655-22-202
1500 WEISS ST, SAGINAW, MI 48602
BID DOCUMENTS
SAGINAW VA
MEDICAL
CENTER Approved: Owner
N
1/4" = 1'-0"
MECHANICAL NEW WORK PLAN
D R A W I N G N O T E S :
1 INSTALL NEW PIPING. CONNECT TO EXISTING WHERE APPLICABLE.
2 INSTALL NEW ABOVEGROUND STORAGE TANK.
3 CONNECT ALARMS FROM NEW TANK MONITORING SYSTEM TO THE EXISTING BUILDING AUTOMATION SYSTEM. PROVIDE
NEW SUPERVISORY CONTROLLER TO ACCOMMODATE ADDITIONAL INPUTS.
4 INSTALL NEW OVERFLOW TANK WITH DUPLEX RETURN PUMPS. PIPE ALL VENTS TO BUILDING EXTERIOR.
5 PROVIDE INSULATION AND HEAT TRACE ON ALL EXTERIOR FUEL OIL PIPING. EXTEND INSULATION THROUGH WALL
PENETRATIONS.
6 ALIGN NEW PIPING THROUGH EXISTING WALL PENETRATION WHERE POSSIBLE (TYP).
7 NEW TANK LEVEL AND LEAK DETECTION MONITORING SYSTEM.
8 NEW FUEL OIL HEAT EXCHANGER PLACED IN MECHANICAL ROOM.
9 SLOPE OVERFLOW PIPING TO OVERFLOW TANK AT 1/4" PER FOOT. MATCH PIPE SIZE TO TANK CONNECTION SIZE.
10 INSTALL NEW ISOLATION VALVES IN THE EXISTING PIPING BETWEEN DAY TANK AND GENERATOR.
11 TANK MOUNTED FILL BOX.
12 SUPPORT ALL FUEL PIPING AND CONDUIT NOT LESS THAN 18" ABOVE GROUND. USE STRUT CHANNEL TYPE METAL
FRAMING.
FUEL TANK SCHEDULE
MARK LOCATION
SYSTEM AND/OR
SERVICE
FUEL OIL
TYPE NO
NOM CAPACITY
TYPE CONSTRUCTION DIMENSIONS PUMPS REMARKS
GAL [L]
FOT-1
OUTDOOR ABOVE
GROUND
GENERATOR BULK
FUEL STORAGE
# 2 6,000 [ 23000 ]
HORIZONTAL
CYLINDRICAL
UL-2085 (INSULATED)
DOUBLE WALL
8' (DIA) x 16' (L) N/A 1
FOT-2
GENERATOR
ROOM
GENERATOR DAY
TANK OVERFLOW
# 2 40 [ 150 ]
RECTANGULAR W/
RUPTURE BASIN
UL-142
34" x 18" x 34"
(L x W x H)
FOP-1,
FOP-2
1,2
REMARKS:
1. SEE SPECIFICATIONS AND DRAWINGS FOR ADDITIONAL REQUIREMENTS.
2. PUMPS, CONTROLS, AND ALARMS TO BE FACTORY INSTALLED AND TESTED. COORDINATE WITH DRAWINGS AND SPECIFICATIONS.
EMERGENCY GENERATOR - FUEL OIL PUMP SCHEDULE
MARK LOCATION
SYSTEM
AND/OR
SERVICE
TYPE
CAPACITY GPM
[L/s]
DISCHARGE
PRESSURE OIL
GRADE
OIL TEMP
VISCOSITY
RANGE (SSU)
SUCTION LIFT MOTOR
REMARKS
GPM [L/s] PSIG [kPa] °F [°C] IN HG [mm] HP [W] PHASE VOLT
FOP-1, FOP-2
GENERATOR
ROOM
EMERGENCY
GENERATOR
DUPLEX
RETURN
8 0.5 30 [ 210 ] #2 40 [ 21.1 ] 50 9.57 242.9 1/3 [ 250 ] 1 115 ---
FOP-3, FOP-4
GENERATOR
ROOM
EMERGENCY
GENERATOR
DUPLEX
RECIRULATION
1.6
(MINIMUM)
0.01 BY MANUF BY MANUF #2 40 [ 4.4 ] 50 N/A N/A 1/3 [ 250 ] 1 115 ---
EMERGENCY GENERATOR - FUEL OIL HEATER SCHEDULE
MARK LOCATION
SERVICE
AND/OR
SYSTEM
OIL TYPE #
OIL TEMP
OIL FLOW HEATING CAPCITY
PUMPS REMARKS∆T
°F [°C] GPH [L/s] BTU [kWh]
FOHX-1 GENERATOR ROOM
GENERATOR BULK
FUEL STORAGE
#2 40.00 [ 4 ] 99.00 [ .10 ] 17000 [ 5 ] FOP-3, FOP-4
NOTES
1. FUEL HEATING SHALL HAVE DEDICATED NOZZLES AND DROP TUBES IN THE BULK STORAGE TANK, SEPARATE FROM DAY TANK SUPPLY AND RETURN.
2. ALL EQUIPMENT SHALL COME FACTORY SKID MOUNTED. SEE SPECIFICATION FOR REQUIREMENTS.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s
/S a g in a w
V A
B u ild in g
U
S T
/F F
E
S a g in a w
B u ild in g
U
S T
B
M E
P rv t
/1
/2
:2
:2
P
M
M600
MECHANICAL SCHEDULES