PreBid 100pct Drawings - Attachment 2 (Part 2).pdf

PDF 10 MB Posted

Attached to
Combat Integration & Identification Systems (CI&IDS) Lab Revitalization Project
Solicitation number
N00421-20-S-0116
Issued by

About this file

This sources sought notice provides details for a construction project to build a single story office building at the Naval Air Warfare Center - Aircraft Division in Patuxent River, Maryland. The project is estimated between $5 million to $10 million with a 365 calendar day performance period. Interested parties must be registered in SAM and capable of bonding for similar construction projects. Responses are due by August 10th and should include company information, interest in bidding, and descriptions of at least three similar past projects with values and durations. The notice is seeking information from all business sizes but may be set aside for small businesses including 8(a), HUBZone, SDVOSB, or woman-owned small businesses given eligible responses. The Naval Air Systems Command and Naval Air Warfare Center are the agencies involved.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REF.REF.

C

D

S-2

WATER METER

ASSEMBLY IN THE

VERTICAL.

2" DOMESTIC WATER

SERVICE, SEE CIVIL

FOR CONTINUATION.

H-1

1 1/2" DCW

1" DCW

DWH-1

STORAGE

MECH

MOTHER'S

BREAK

JAN

WOMEN

MEN

CORRIDOR

ELEC

TR

3/4" DCW

1 1/4" DHW

WHD-1

2" DCW

1" DCW

1 1/4" DCW

3/4" DHC

BALANCING

VALVE (1 GPM)

BALANCING

VALVE (1 GPM)

DHWP-1

DET-1

SPACE RESERVED FOR

INCOMING FIRE PROTECTION

SERVICE TO BUILDING, SEE

FIRE PROTECTION SHEETS.

PROVIDE A MINIMUM 3FT

CLEARANCE IN FRONT OF

ALL COMPONENTS.

1" DCW

MIXING VALVE

1 1/4" DHW

1 1/4" DCW

DDC PANELS

PROVIDE ISOLATION

VALVE IN 1" DCW

PROVIDE LEAD FREE

DUAL CHECK VALVE

1/2" DCW TO

VB-1 SERVING

COFFEE MAKER

1/2" DCW TO

VB-1 SERVING

REFRIGERATOR

1 1/2" DCW

1/2" DHC1/2" DHC

3/4" DHW

WC-1A WC-1A

WC-1 WC-1

WC-1U-1A

S-1

1 1/4" DCW

1" DCW

3/4" DCW

1/2" DHW

1 1/4" DCW

1" DCW

3/4" DCW

1" DHW

1/2" DHW

1/2" DCW

3/4" DCW

1/2" DCW

MS-1

EWC-1

L-1 (TYP 3)

L-1 (TYP 3)

PROVIDE PRESSURE

ACTIVATED TRAP PRIMER

ON DCW LINE IN CHASE.

C

D

FD-1

S-2

FD-1

DWH-1

4" SAN DROP

BELOW GRADE

3" VTR

STORAGE

MECH

MOTHER'S

BREAK

JAN

WOMEN

MEN

CORRIDOR

ELEC

TR

WCO

FD-1

FD-1

2" V

FCO

SPACE RESERVED FOR

INCOMING FIRE PROTECTION

SERVICE TO BUILDING, SEE

FIRE PROTECTION SHEETS.

PROVIDE A MINIMUM 3FT

CLEARANCE IN FRONT OF

ALL COMPONENTS.

6" CONCRETE PAD

DET-1

3" SAN

3" SAN

2" V

4" SAN

4" SAN

3" SAN

4" SAN

DDC PANELS

FCO

2" SAN

2" V

4" SAN

HUMIDIFIER. SEE

MECHANICAL

WC-1A

WC-1A

WC-1

WC-1

WC-1U-1A

L-1 (TYP 3)L-1 (TYP 3)

2" V

FD-1

MS-1

EWC-1

S-1

3" SAN

3" SAN

3" SAN

1 1/2" V

2" V

3" V3" V

1 1/2" V

2" V

2" V

1 1/2" V

3" SAN

3" SANWCO

2" V

2" V

4" SAN DROP

BELOW GRADE

3" SAN

N O

T F

O R

C O

N S

T R

U C

T

IO

N

P R

E L

IM

IN

A

R Y

SATISFACTORY TO

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

W

A S

H

IN

G T

O N

P A

T U

X E

N T

R

IV

E R

M

D

AS NOTED

2850 EISENHOWER AVENUE

SUITE 200

ALEXANDRIA, VA 22314

N A

V F

A C

L R

P F

A C

IL

IT

Y I D

S

.1

.2

W E

B S

T E

R F

IE

L D

N A

V A

L S

T A

T

IO

N P

A T

U X

E N

T R

IV

E

R

PRE-BID FINAL

(100%) DESIGN

SUBMITTAL

07/02/20

R E

V D

A T

E

F

IL

E N

A M

E

U N

C

LA

S S

IF

IE

D

DRAWFORM REVISION: 12 APRIL 2018

CHIEF ENG/ARCH

IPT TECH. BRANCH HEAD

PROJECT MANAGER

A/E INFO

APPROVED

/2

/2

:1

:2

P M

C U s e rs \z a b a lo s \D o c u m e n ts \2

R

M

C

E N

ID

S b im m e c h

.r v t

P-401

FI

R

S T

FL

O

O R

E N

LA

R

G E

D P

LU

M

B

IN

G P

LA

N

S

AEBSWL ZMA

1/4" = 1'-0" A1

FIRST FLOOR ENLARGED DOMESTIC WATER PIPING PLAN

1/4" = 1'-0"

A4

FIRST FLOOR ENLARGED SANITARY PIPING PLAN

2' 4' 8'0'2' 4' 8'0'

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

SEAL

2850 EISENHOWER AVENUE

SUITE 200

ALEXANDRIA, VA 22314

PRE-FINAL

100% DESIGN

SUBMITTAL

06 / 03 / 20

PRE - BID

07 / 02 / 20

WATER HAMMER ARRESTOR

INSTALLATION DETAIL

WATER HAMMER ARRESTOR DETAIL ELECTRIC WATER HEATER DETAIL

TRAP SEAL PRIMER DETAIL

SECURE

SIDE

NON-SECURE

SIDE

HOSE

NO SCALE

3" P-TRAP

HOSE

30" LONG

AND PAILHOOK

SPOUT WITH HOSE END

VACUUM BREAKER

SERVICE FAUCET WITH

SPOUT BRACE

BRACKET

TRAP PRIMER CONNECTION

NO SCALE

NO SCALE

NO SCALE

NO SCALE

C1 C4

A2

MOP SINK DETAIL

DCW BUILDING ENTRY DETAIL

SECURE PIPE PENETRATION DETAIL

PIPE SLEEVE THRU INTERIOR WALL DETAIL

DOMESTIC HOT WATER PUMP DETAIL

H C

A5

C2

PIPE

PIPE CLAMP

NO. 4 WIRE

PROVIDE ACOUSTICAL

SEALANT AT ALL GYPSUM

BOARD PENETRATIONS

PIPE INSULATION

AS SPECIFIED

GROUND PIPE WITHIN

6" OF PERIMETER

CONNECT TO

BUILDING GROUND

A3

NOTES:

1. PREFERRED INSTALL WATER HAMMER

ARRESTORS AT THE END OF BRANCH LINE

BETWEEN THE LAST TWO FIXTURES SERVED.

2. ONE WATER HAMMER ARRESTOR PER 20' LINE,

AND ANOTHER FOR BRANCHES OVER 20' IN

LENGTH.

3. THE SUM OF FIXTURE UNIT RATING OF UNITS OVER

20' IN LENGTH SHALL BE EQUAL TO OR GREATER

THAN THE DEMAND OF THE BRANCHES.

WATER HAMMER ARRESTOR

SCHEDULE

PDI SYMBOL A B C D E F

FIXTURE UNIT

RATING

1-11 12-32 33-60 61-113 114-154 155-330

WATER HAMMER

ARRESTOR

TYPICAL BRANCH LINE

SUPPLY RISER

PDI "A"

PDI

SYMBOL

SCALE: NONE

BUILDING

DCW SUPPLY

WATER METER ASSEMBLY

DCW SUPPLY

TO BUILDING

CONNECT TO REMOTE REGISTER

ON EXTERIOR AND BAS

STRAINER

SET SLEEVE IN WALL

AND ANCHOR DURING

WALL CONSTRUCTION

PACK WITH FIBERGLASS

AND SEAL BOTH SIDES

PIPE

INSULATION ESCUTCHEON PLATES

( BOTH SIDES WHERE

EXPOSED )

PIPE SLEEVE

WALL

B2

SUPPORT PIPING ON

BOTH SIDES OF

WATER METER

ASSEMBLY

4" HOUSEKEEPING PAD

PIPE TO

6" AFF

COMBINATION

TEMPERATURE AND

PRESSURE RELIEF

(T&P) VALVE

SCALE: NONE

WATER SHALL BE

STORED AT 140

DEG F

TANK DRAIN VALVE

DI-ELECTRIC UNION, TYPICAL

EXPANSION

TANK

COLD WATER

SUPPLY

VACUUM RELIEF VALVE TYP

HOT WATER

SUPPLY

THERMOMETER (TYPICAL)

CHECK VALVE

(TYPICAL)

ISOLATION VALVE

(TYP)

THERMOSTATIC VALVE SET

TO DELIVER 120°F WATER

3/4" UNLESS NOTED

OTHERWISE

4. CONCENTRIC REDUCER

1. IN-LINE CIRCULATOR PUMP

3. BALL VALVE

2. MOTOR

5. BALANCING VALVE

6. SPRING CHECK VALVE

7. PRESSURE GAUGES

NOTE:

1. EXTERNAL GAGE TAPS ON PIPES SHALL NOT BE REQUIRED

WHEN PUMP IS PROVIDED WITH FLANGE GAGE CONNECTOR.

A1

HOT WATER RETURN

STRAP-ON AQUASTAT

IN LINE RE-CIRCULATING PUMP.

SEE DETAIL THIS SHEET

FLOOR DRAIN

FLOOR SLAB

AVAILABLE FOR

1/2" TRAP PRIMER SUPPLY

1/2" TRAP PRIMER LINE

TRAP PRIMER VALVE

SLEEVE THRU

SLAB

TO MAIN BUILDING

WASTE DRAIN

DOMESTIC COLD WATER

WATERPROOF

SEALANT

MATERIAL

BACKING

SEALANT

DISTRIBUTION UNIT

5 ADDITIONAL LINES)

(DCW) LINE

SCALE: NONE

BALL VALVE

SCALE: NONE

10 DIA. MIN.

CLEARANCE

5 DIA. MIN.

CLEARANCE

1\4" PIPE OR TUBING

1\4" PET COCK (TYP)

N O

T F

O R

C O

N S

T R

U C

T

IO

N

P R

E L

IM

IN

A

R Y

SATISFACTORY TO

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

W

A S

H

IN

G T

O N

P A

T U

X E

N T

R

IV

E R

M

D

AS NOTED

2850 EISENHOWER AVENUE

SUITE 200

ALEXANDRIA, VA 22314

N A

V F

A C

L R

P F

A C

IL

IT

Y I D

S

.1

.2

W E

B S

T E

R F

IE

L D

N A

V A

L S

T A

T

IO

N P

A T

U X

E N

T R

IV

E

R

PRE-BID FINAL

(100%) DESIGN

SUBMITTAL

07/02/20

R E

V D

A T

E

F

IL

E N

A M

E

U N

C

LA

S S

IF

IE

D

DRAWFORM REVISION: 12 APRIL 2018

CHIEF ENG/ARCH

IPT TECH. BRANCH HEAD

PROJECT MANAGER

A/E INFO

APPROVED

/2

/2

:1

:2

P M

C U s e rs \z a b a lo s \D o c u m e n ts \2

R

M

C

E N

ID

S b im m e c h

.r v t

P-501

D E

TA

IL

S

AEBSWL ZMA

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

SEAL

2850 EISENHOWER AVENUE

SUITE 200

ALEXANDRIA, VA 22314

PRE-FINAL

100% DESIGN

SUBMITTAL

06 / 03 / 20

PLUMBING FIXTURES

DESIGNATION FIXTURE ACCESSIBILITY MATERIAL

FLUSH

VALVE

SUPPLY

FITTINGS AND

STOPS

TRAP CARRIER

CONNECTION SIZES

NOTES

WASTE VENT HOT COLD

WC-1 WATER CLOSET - - VITREOUS CHINA

1" SUPPLY,

1.28 GPF

1 1/2" TOP

SPUD ANGLE

STOP

INTEGRAL WALL 4" 2" - - 1"

LOW FLOW 1.28 GPF WATER CLOSET WITH

MANUAL FLUSH VALVE

WC-1A WATER CLOSET ADA VITREOUS CHINA

1" SUPPLY,

1.28 GPF

1 1/2" TOP

SPUD ANGLE

STOP

INTEGRAL WALL 4" 2" - - 1"

LOW FLOW 1.28 GPF WATER CLOSET WITH

MANUAL FLUSH VALVE. RIM HEIGHT AT 17"

AFF.

U-1A URINAL ADA VITREOUS CHINA

3/4"

SUPPLY,

0.125 GPF

3/4" TOP

SPUD ANGLE

STOP

INTEGRAL WALL 2" 1 1/2" - - 3/4"

LOW FLOW 0.125 GPF URINAL WITH MANUAL

FLUSH VALVE. RIM HEIGHT AT 17" AFF.

MS-1 MOP SINK - -

STAINLESS

STEEL

- - - - 3" FLOOR 3" 1 1/2" 1/2" 1/2"

STAINLESS STEEL 36x30x12 MINIMUM BOWL

SIZE WITH STAINLESS STEEL GUARDS TO

PROTECT THE SURROUNDING WALLS,

STRAINER GRATE. PROVIDE TRAP PRIMER

CONNECTION ON P-TRAP.

L-1 LAVATORY ADA VITREOUS CHINA - - ANGLE STOPS 1 1/2" UNDERMOUNT 1 1/2" 1 1/2" 1/2" 1/2"

MAXIMUM 0.5 GPM FAUCET WITH MANUAL

CONTROL. PROVIDE ASSE 1070 VALVE TO

LIMIT WATER 110 DEG F.

S-1

BREAK ROOM

SINK

STAINLESS

STEEL

- - ANGLE STOPS 1 1/2" UNDERMOUNT 1 1/2" 1 1/2" 1/2" 1/2"

28" X 18" X 9" SS BOWL WITH REAR CENTER

DRAIN. KITCHEN FAUCET WITH BRUSHED

NICKEL FINISH, SINGLE LEVEL CONTROL ON

SIDE, AND PULL DOWN 2 PATTERN SPRAY

HEAD. PROVIDE ASSE 1070 VALVE TO LIMIT

WATER TO 110 DEG F.

S-2

MOTHERS ROOM

SINK

STAINLESS

STEEL

- - ANGLE STOPS 1 1/2" UNDERMOUNT 1 1/2" 1 1/2" 1/2" 1/2"

20" X 18" X 9" SS BOWL WITH REAR CENTER

DRAIN. KITCHEN FAUCET WITH BRUSHED

NICKEL FINISH, SINGLE LEVER CONTROL ON

SIDE, AND PULL DOWN 2 PATTERN SPRAY

HEAD. PROVIDE ASSE 1070 VALVE TO LIMIT

WATER TO 110 DEG F.

EWC-1

BI-LEVEL

ELECTRIC

WATER COOLER

ADA

STAINLESS

STEEL

- - ANGLE STOPS 1 1/4"

WALL

MOUNTED

1 1/2" 1 1/2" - - 1/2"

BI-LEVEL, BUBBLER STYLE, AIR-COOLED

CONDENSING UNIT WITH PORTABLE BOTTLE

REFILL STATION.

VB-1 VALVE BOX - - ABS PLASTIC - -

QUARTER

TURN

WALL

MOUNTED

- - - - - - 1/2"

VALVE BOX WITH INTEGRAL WATER

HAMMER ARRESTOR.

WALL HYDRANT

DESIGNATION FIXTURE TYPE CONNECTION SIZE (IN) DESCRIPTION

WHD-1

ENCASED WALL

HYDRANT

3/4"

ENCASED, ANTI-SIPHON, AUTOMATIC DRAINING WALL

HYDRANT WITH 3/4" HOSE CONNECTION, FLUSH

INSTALLATION, NON-FREEZE TYPE INTEGRAL BACKFLOW

PREVENTER

FLOOR DRAIN

DESIGNATION

AREA

SERVED

TYPE DESCRIPTION

FD-1 VARIOUS FLOOR DRAIN

3" CAST IRON FLOOR DRAIN, NO HUB CONNECTION, NICKEL

BRONZE TOP. PROVIDE P-TRAP WITH TRAP PRIMER

CONNECTION.

FD-2

LAB

SPACES

FLOOR DRAIN

3" CAST IRON FLOOR DRAIN, NO HUB CONNECTION, NICKEL

BRONZE TOP. PROVIDE RIM EXTENSION OR FUNNEL TO

ELEVATION OF TOP OF RAISED FLOOR. COORDINATE WITH

RAISED FLOOR MANUFACTURER. PROVIDE P-TRAP WITH

TRAP PRIMER CONNECTION.

WATER HEATER

DESIGNATION DWH-1

TYPE ELECTRIC

LOCATION MECHANICAL

STORAGE (GAL) 80

STORAGE TEMPERATURE (F) 140

INPUT (kW) 4.5

GPH AT 90 DEG F RISE 20

ELECTRICAL DATA - -

VOLTS 120

PHASE 1

HZ 60

REMARKS 1

REMARKS LEGEND:

1. RECOVERY RATE FOR NON-SIMULTANEOUS ELEMENT

OPERATION.

DW EXPANSION TANK

DESIGNATION DET-1

SERVICE DOMESTIC HOT WATER

LOCATION MECHANICAL

TYPE DIAPHRAGM

FILL PRESSURE (PSI) 50

RELIEF VALVE PRESSURE SETTING (PSI) 80

MINIMUM ACCEPTANCE VOLUME (GAL) 3.2

DOMESTIC HOT WATER

RECIRCULATION PUMP

DESIGNATION DHWP-1

FLOW RATE (GPM) 2

HEAD (FT-H2O) 15

TYPE IN-LINE CENTRIFUGAL

RPM 1,800

VOLTS 120

PHASE 1

FREQUENCY (Hz) 60

REMARKS 1

REMARKS LEGEND:

1. SEE SHEET MECHANICAL FOR PUMP CONTROLS

N O

T F

O R

C O

N S

T R

U C

T

IO

N

P R

E L

IM

IN

A

R Y

SATISFACTORY TO

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

W

A S

H

IN

G T

O N

P A

T U

X E

N T

R

IV

E R

M

D

AS NOTED

2850 EISENHOWER AVENUE

SUITE 200

ALEXANDRIA, VA 22314

N A

V F

A C

L R

P F

A C

IL

IT

Y I D

S

.1

.2

W E

B S

T E

R F

IE

L D

N A

V A

L S

T A

T

IO

N P

A T

U X

E N

T R

IV

E

R

PRE-BID FINAL

(100%) DESIGN

SUBMITTAL

07/02/20

R E

V D

A T

E

F

IL

E N

A M

E

U N

C

LA

S S

IF

IE

D

DRAWFORM REVISION: 12 APRIL 2018

CHIEF ENG/ARCH

IPT TECH. BRANCH HEAD

PROJECT MANAGER

A/E INFO

APPROVED

/2

/2

:1

:2

P M

C U s e rs \z a b a lo s \D o c u m e n ts \2

R

M

C

E N

ID

S b im m e c h

.r v t

P-601

S C

H E

D U

LE

S

AEBSWL ZMA

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

SEAL

2850 EISENHOWER AVENUE

SUITE 200

ALEXANDRIA, VA 22314

PRE-FINAL

100% DESIGN

SUBMITTAL

06 / 03 / 20

FCO

FD-1

FD-1

FD-1

FD-1

FD-2

FD-2

WC-1A

WC-1A

U-1A

WC-1

MS-1

EWC-1

FD-1

S-1

S-2

4" SAN WITH INVERT AT 3'-6"

BELOW FINISHED FLOOR. SEE

CIVIL FOR CONTINUATION.

3" SAN

3" SAN

2" VTR

3" SAN

FCO

2" V

2" V

4" SAN

WCO

4" SAN

3" SAN

3" SAN

2" SAN 3" SAN

FCO

WC-1

WCO

L-1

L-1

L-1

1 1/2" SAN

2" SAN

4" SAN

L-1 L-1

L-1

1 1/2" SAN

WC-1

2" SAN

4" SAN

FD-1

4" SAN

3" SAN

3" SAN

FCO

2" V

3" V

2" V 1 1/2" V

1 1/2" V

2" V

1 1/2" V

2" V 1 1/2" V

1 1/2" V 2" V

2" V

1 1/2" V

2" V

1 1/2" V

2" V

3" V

3" VTR

2" SAN

3" SAN

3" SAN

4" SAN

4" SAN

1 1/2" V

1 1/2" V

2" V

2" V

2" V

3" SAN

N O

T F

O R

C O

N S

T R

U C

T

IO

N

P R

E L

IM

IN

A

R Y

SATISFACTORY TO

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

W

A S

H

IN

G T

O N

P A

T U

X E

N T

R

IV

E R

M

D

AS NOTED

2850 EISENHOWER AVENUE

SUITE 200

ALEXANDRIA, VA 22314

N A

V F

A C

L R

P F

A C

IL

IT

Y I D

S

.1

.2

W E

B S

T E

R F

IE

L D

N A

V A

L S

T A

T

IO

N P

A T

U X

E N

T R

IV

E

R

PRE-BID FINAL

(100%) DESIGN

SUBMITTAL

07/02/20

R E

V D

A T

E

F

IL

E N

A M

E

U N

C

LA

S S

IF

IE

D

DRAWFORM REVISION: 12 APRIL 2018

CHIEF ENG/ARCH

IPT TECH. BRANCH HEAD

PROJECT MANAGER

A/E INFO

APPROVED

/2

/2

:1

:2

P M

C U s e rs \z a b a lo s \D o c u m e n ts \2

R

M

C

E N

ID

S b im m e c h

.r v t

P-801

S A

N

IT

A R

Y P

IP

IN

G R

IS

E

R

AEBSWL ZMA

A1

SANITARY PIPING RISER DIAGRAM

SCALE: NONE

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

SEAL

2850 EISENHOWER AVENUE

SUITE 200

ALEXANDRIA, VA 22314

PRE-FINAL

100% DESIGN

SUBMITTAL

06 / 03 / 20

1" DCW

TO H-1

U-1A

WC-1

L-1

L-1

WC-1A

S-1

S-2

MS-1

EWC-1

2" DOMESTIC WATER

SERVICE, SEE CIVIL

FOR CONTINUATION

WHD-1

WHD-1

WHD-1

WHD-1

3/4" DCW

3/4" DCW

1 1/4" DHW

2" DCW

1" DCW

1/2" DCW TO HUMIDIFIER.

SEE MECHANICAL PLANS.

1/2" DCW TO HUMIDIFIER.

SEE MECHANICAL PLANS.

TO DHW-1

1" DCW

BALANCING

VALVE (1 GPM)

BALANCING

VALVE (1 GPM)

DHWP-1

TO DET-1

TO MIXING VALVE

FROM MIXING VALVE

1" DCW

ISOLATION

VALVE

3/4" DHC

1 1/4" DCW

1/2" DCW TO VB-1 SERVING

REFRIGERATOR 1/2" DCW TO VB-1

SERVING COFFEE

MAKER

3/4" DCW

WATER METER

WC-1A

WC-1

L-1

L-1

WC-1

L-1

L-1

1 1/2" DCW

1 1/4" DCW

1" DCW

3/4" DCW

3/4" DCW

3/4" DHW

1/2" DHW

1/2" DHC

1 1/2" DCW

1 1/4" DCW

1" DCW

3/4" DCW

1/2" DHW

1/2" DCW

3/4" DCW

1/2" DCW

N O

T F

O R

C O

N S

T R

U C

T

IO

N

P R

E L

IM

IN

A

R Y

SATISFACTORY TO

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

W

A S

H

IN

G T

O N

P A

T U

X E

N T

R

IV

E R

M

D

AS NOTED

2850 EISENHOWER AVENUE

SUITE 200

ALEXANDRIA, VA 22314

N A

V F

A C

L R

P F

A C

IL

IT

Y I D

S

.1

.2

W E

B S

T E

R F

IE

L D

N A

V A

L S

T A

T

IO

N P

A T

U X

E N

T R

IV

E

R

PRE-BID FINAL

(100%) DESIGN

SUBMITTAL

07/02/20

R E

V D

A T

E

F

IL

E N

A M

E

U N

C

LA

S S

IF

IE

D

DRAWFORM REVISION: 12 APRIL 2018

CHIEF ENG/ARCH

IPT TECH. BRANCH HEAD

PROJECT MANAGER

A/E INFO

APPROVED

/2

/2

:1

:2

P M

C U s e rs \z a b a lo s \D o c u m e n ts \2

R

M

C

E N

ID

S b im m e c h

.r v t

P-802

D O

M E

S

TI

C W

A

TE

R P

IP

IN

G R

IS

E

R

AEBSWL ZMA

A1

DOMESTIC PIPING RISER DIAGRAM

SCALE: NONE

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

SEAL

2850 EISENHOWER AVENUE

SUITE 200

ALEXANDRIA, VA 22314

PRE-FINAL

100% DESIGN

SUBMITTAL

06 / 03 / 20

MECHANICAL GENERAL NOTES

INTENT

1. THESE DRAWINGS ARE SCHEMATIC IN NATURE AND INDICATE THE GENERAL AND APPROXIMATE LOCATION OF EQUIPMENT, PIPING AND DUCTWORK. THEY ARE

NOT INTENDED TO SHOW ALL POSSIBLE CONDITIONS. IT IS INTENDED THAT A COMPLETE HEATING, VENTILATING AND AIR CONDITIONING SYSTEM (HVAC) BE PROVIDED WITH ALL NECESSARY EQUIPMENT, APPURTENANCES AND CONTROLS. THE CONTRACTOR SHALL CAREFULLY REVIEW ALL THE CONTRACT DOCUMENTS AND COORDINATE BETWEEN ALL TRADES PRIOR TO SUBMITTING SHOP DRAWINGS. THE CONTRACTOR SHALL VERIFY ALL SIZES, MATERIALS, TEMPERATURE AND PRESSURE RATINGS BEFORE ORDERING OR INSTALLING ANY MATERIALS OR EQUIPMENT. THE CONTRACTOR SHALL PREPARE INSTALLATION INSTRUCTIONS AND

FABRICATION DRAWINGS PRIOR TO ACTUAL INSTALLATION.

2. REFER TO EACH DRAWING FOR NOTES SPECIFIC TO THAT DRAWING SHEET.

3. DO NOT SCALE FOR DUCT, PIPE OR EQUIPMENT LOCATIONS.

WORK SAFETY AND QUALITY

1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE SAFETY OF CONTRACTOR'S PERSONNEL EMPLOYED ON THIS PROJECT AND IN PARTICULAR, WHEN WORKING

IN CONFINED SPACES. THE CONTRACTOR SHALL COMPLY WITH ALL OCCUPATIONAL SAFETY HEALTH ADMINISTRATION (OSHA) REQUIREMENTS.

2. ALL MISCELLANEOUS MATERIAL REQUIRED TO ENSURE PROPER INSTALLATION AND IS SHOWN IN DETAILS FOR PIPING, DUCTS, AND EQUIPMENT (UNLESS

OTHERWISE NOTED) SHALL BE FURNISHED AND INSTALLED BY THE MECHANICAL CONTRACTOR.

3. ALL MECHANICAL EQUIPMENT AND SYSTEMS SHALL BE INSTALLED IN A MANNER WHICH MINIMIZES NOISE AND VIBRATION.

COORDINATION WITH OTHER TRADES

1. THE CONTRACTOR SHALL COORDINATE THE INSTALLATION OF WORK WITH THE WORK OF OTHER TRADES. MINOR DEVIATIONS FROM THE PLANS MAY BE MADE TO

AVOID CONFLICTS.

2. COORDINATE DUCTWORK AND PIPING WITH ELECTRICAL, STRUCTURE, AND PLUMBING. MAKE OFFSETS AND TRANSITIONS TO COORDINATE WITH OTHER TRADES

WITHOUT ADDITIONAL EXPENSE TO THE OWNER.

3. COORDINATE MECHANICAL EQUIPMENT AND MATERIAL LOCATIONS WITH ELECTRICAL, PLUMBING, FIRE PROTECTION, STRUCTURAL AND ARCHITECTURAL PLANS

TO AVOID CONFLICTS.

4. COORDINATE THE VOLTAGE AND PHASE OF EACH PIECE OF EQUIPMENT WITH DIVISION 26 (ELECTRICAL CONTRACT DOCUMENTS) PRIOR TO ORDERING. PROVIDE WRITTEN VERIFICATION OF COORDINATION WITH DIVISION 26 PRIOR TO INSTALLATION OF EQUIPMENT.

5. REFER TO THE ARCHITECTURAL PLANS FOR EXACT LOCATION OF ALL LOUVERS, VENTS, DUCTS, AND PIPING THAT PENETRATE EXTERIOR WALLS.

6. PROVIDE OPENINGS IN BUILDING CONSTRUCTION FOR PASSAGE OF PIPING AND DUCTWORK. DO NOT PENETRATE STRUCTURAL MEMBERS WITHOUT PRIOR

APPROVAL.

7. ALL NECESSARY ALLOWANCES AND PROVISIONS SHALL BE MADE BY THIS CONTRACTOR FOR BEAMS, COLUMNS, TRUSSES OR OTHER OBSTRUCTIONS OF THE BUILDING OR THE WORK OF OTHER CONTRACTORS, WHETHER OR NOT SAME IS INDICATED. WHERE NECESSARY TO AVOID OBSTRUCTIONS, THE DUCTS SHALL BE TRANSFORMED, DIVIDED, OFFSET, RAISED OR LOWERED WITH THE REQUIRED FREE AREA BEING MAINTAINED.

DUCTWORK

1. DUCT SIZES ARE SHOWN AS INSIDE CLEAR DIMENSIONS. WHERE INTERNAL INSULATION IS CALLED FOR, DIMENSIONS SHALL BE INCREASED FOR THE THICKNESS

OF THE INSULATION. SEE SPECIFICATION FOR THICKNESS.

2. ALL BRANCH DUCTWORK SHALL BE SIZED TO MATCH THE TERMINAL CONNECTION SERVED UNLESS NOTED OTHERWISE. FLEXIBLE DUCT TO DIFFUSERS SHALL BE INSTALLED FREE OF KINKS AND SAGS. MAXIMUM LENGTH OF FLEXIBLE DUCT SHALL BE 6'-0". ALL RUNOUT AND BRANCH DUCTS SHALL CONTAIN A MANUAL

VOLUME DAMPER FOR BALANCING.

3. ALL DUCT TRANSITIONS FROM SQUARE TO ROUND SHALL BE SMOOTH SQUARE TO ROUND TRANSITIONS.

4. ALL DIFFUSERS SHALL HAVE FOUR-WAY BLOW UNLESS NOTED OTHERWISE.

5. SEE REFLECTED CEILING PLANS FOR EXACT LOCATION OF AIR DEVICES.

6. ALL DAMPERS, DAMPER OPERATORS, AND FANS SHALL BE ACCESSIBLE. LOCATE ALL EQUIPMENT OR APPURTENANCES IN AREAS WITH ACCESSIBLE CEILINGS.

THE CONTRACTOR MAY UTILIZE ACCESS PANELS FOR THOSE AREAS NOT EASILY ACCESSIBLE. ALL ACCESS PANEL LOCATIONS SHALL BE COORDINATED WITH THE CONTRACT DOCUMENTS AND APPROVED BY THE OWNER PRIOR TO INSTALLATION OF EQUIPMENT.

7. ALL OPEN ENDED DUCTS SHALL BE REINFORCED WITH STEEL ANGLES (1-1/2" X 1-1/2" X 1/8") BOLTED OR RIVETED 6" ON CENTER (MAXIMUM) ALL AROUND THE

PERIMETER OF THE DUCT MINIMUM 2 PER SIDE.

8. ALL DUCTWORK SHALL BE SLEEVED THROUGH WALL PENETRATIONS.

9. PROVIDE AIR TURNING DEVICES IN DUCTWORK AT ANY CHANGES IN DIRECTION OF GREATER THAN 60 DEGREES.

10. PROVIDE CONICAL TEES FOR ROUND AND FLAT OVAL DUCT TAKE-OFFS.

PIPING

1. SLOPE CONDENSATE DRAINS AT 1/8 INCHES FALL PER FOOT MINIMUM IN THE DIRECTION OF FLOW.

2. ALL PIPING SHALL BE SLEEVED THROUGH WALL PENETRATIONS.

3. SIZE AND ROUTE REFRIGERANT PIPING PER EQUIPMENT MANUFACTURER'S RECOMMENDATIONS.

EQUIPMENT

1. INSTALL ALL MECHANICAL EQUIPMENT AND APPURTENANCES IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS, CONTRACT DOCUMENTS, AND

APPLICABLE CODES AND REGULATIONS.

2. ALL MECHANICAL EQUIPMENT SHALL BE INSTALLED IN SUCH A MANNER SO THAT ALL FILTERS, VALVES, MOTORS, DAMPERS, ETC., ARE COMPLETELY ACCESSIBLE

AND SERVICEABLE, INCLUDING ACCESS DOORS IF REQUIRED.

3. COMPLETE AND PROPER INSTALLATION OF THERMOSTATS AND ALL OTHER NECESSARY FIELD MOUNTED CONTROL COMPONENTS SHALL BE THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR. THE EQUIPMENT MANUFACTURERS SHALL FURNISH COMPLETE WIRING CONTROLS.

4. PROVIDE FLEXIBLE CONNECTIONS BETWEEN HVAC EQUIPMENT AND SHEET METAL DUCTWORK.

CONTROLS

1. PROVIDE THERMOSTATS OR HUMIDISTATS WHERE SHOWN ON THE DRAWINGS.

HVAC AND MECHANICAL PIPING LEGEND

PHASES

EXISTING TO REMAIN

DEMOLITION WORK

TEMPORARY WORK

NEW WORK

DUCT SYSTEM - SUPPLY

AIR

DUCT SYSTEMS

DUCT SYSTEM - RETURN AIR

DUCT SYSTEM - EXHAUST AIR

AIR TERMINALS

CEILING DIFFUSER - SUPPLY AIR

CEILING GRILLE - RETURN AIR

CEILING GRILLE - EXHAUST AIR

AIR TERMINAL TAGS

S2C S=SUPPLY,R=RETURN,E=EXHAUST

NUMBER = UNIT DESIGNATION

A=6", B=8", C=10"

NUMBER = AIRFLOW

R-1

WxH

S2C

S=SUPPLY,R=RETURN,E=EXHAUST

NUMBER = UNIT DESIGNATION

SIZE: WIDTH x HEIGHT

NUMBER = AIRFLOW

SS

FSFS

MM

DUCT ACCESSORIES & FITTINGS

DAMPER, MANUAL BALANCING

DAMPER, MOTORIZED CONTROL

DAMPER, SMOKE

DAMPER, FIRE

DAMPER, COMBINATION

FIRE & SMOKE

DAMPER, BACKDRAFT

DUCT ELBOW, RECTANGULAR,

MITERED WITH TURNING VANES

DUCT ELBOW,

ROUND / RECTANGULAR,

RADIUS BEND.

DUCT ELBOW, FLAT OVAL,

GORED / MITERED BEND.

FLEXIBLE DUCT,

ROUND / RECTANGULAR

RECTANGLE OVAL

ROUND

DUCT TRANSITIONS: RECTANGLE TO

RECTANGLE; RECTANGLE TO ROUND;

ROUND TO OVAL.

T

H

S

CO

CO2

SENSORS

SENSOR - TEMPERATURE

SENSOR - HUMIDITY

SENSOR - SMOKE

SENSOR - CARBON MONOXIDE

SENSOR - CARBON DIOXIDE

POINT OF DISCONNECTION

POINT OF CONNECTION

PIPE SYSTEM - CHILLED WATER RETURN

PIPING SYSTEMS

PIPE ACCESSORIES & FITTINGS

CHR

CHS

CD

CWR

CWS

FOR

FOS

HWR

HWS

NG

RBP

RL

RS

DCR

WCR

HPS

LPS

MPS

PIPE SYSTEM - CHILLED WATER SUPPLY

PIPE SYSTEM - CONDENSATE DRAIN

PIPE SYSTEM - CONDENSER WATER RETURN

PIPE SYSTEM - CONDENSER WATER SUPPLY

PIPE SYSTEM - FUEL OIL RETURN

PIPE SYSTEM - FUEL OIL SUPPLY

PIPE SYSTEM - HOT WATER RETURN

PIPE SYSTEM - HOT WATER SUPPLY

PIPE SYSTEM - NATURAL GAS

PIPE SYSTEM - REFRIGERATION, BYPASS

PIPE SYSTEM - REFRIGERATION, LIQUID

PIPE SYSTEM - REFRIGERATION, SUCTION

PIPE SYSTEM - STEAM CONDENSATE RETURN, DRY

PIPE SYSTEM - STEAM CONDENSATE RETURN, WET

PIPE SYSTEM - HIGH PRESSURE STEAM

PIPE SYSTEM - LOW PRESSURE STEAM

PIPE SYSTEM - MEDIUM PRESSURE STEAM

HWC PIPE SYSTEM - HOT WATER RECIRCULATION

CHECK VALVE

BALL VALVE

GLOBE VALVE

Y STRAINER

GATE VALVE

BUTTERFLY VALVE

CONTROL VALVE, THREE WAY

MOTORIZED CONTROL VALVE

BALANCING VALVE

PLUG VALVE

PIPE TURN UP

PIPE TURN DOWN

PIPE CONCENTRIC REDUCER

PIPE FLANGE & UNION

N O

T F

O R

C O

N S

T R

U C

T

IO

N

P R

E L

IM

IN

A

R Y

SATISFACTORY TO

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

W

A S

H

IN

G T

O N

P A

T U

X E

N T

R

IV

E R

M

D

AS NOTED

2850 EISENHOWER AVENUE

SUITE 200

ALEXANDRIA, VA 22314

N A

V F

A C

L R

P F

A C

IL

IT

Y I D

S

.1

.2

W E

B S

T E

R F

IE

L D

N A

V A

L S

T A

T

IO

N P

A T

U X

E N

T R

IV

E

R

PRE-BID FINAL

(100%) DESIGN

SUBMITTAL

07/02/20

R E

V D

A T

E

F

IL

E N

A M

E

U N

C

LA

S S

IF

IE

D

DRAWFORM REVISION: 12 APRIL 2018

CHIEF ENG/ARCH

IPT TECH. BRANCH HEAD

PROJECT MANAGER

A/E INFO

APPROVED

/2

/2

:0

:4

P M

C U s e rs \z a b a lo s \D o c u m e n ts \2

R

M

C

E N

ID

S b im m e c h

.r v t

M-001

LE

G

E N

D , A

B B

R E

V

IA

TI

O

N S

G

E N

E R

A L

N O

TE

S

AEBSWL ZMA

MECHANICAL ABBREVIATIONS

(E) EXISTING ELEMENT TO REMAIN

ACC AIR COOLED CHILLER

ACU AIR CONDITIONING UNIT

AD ACCESS DOOR

AFF ABOVE FINISHED FLOOR

AFMS AIR FLOW MEASUREMENT STATION

AHU AIR HANDLING UNIT

AI ANALOG INPUT

AO ANALOG OUTPUT

APD AIR PRESSURE DROP

APPROX APPROXIMATELY

ARCH ARCHITECTURE

BEL BELLMOUTH FITTING

BT BUFFER TANK

CD CONDENSATE DRAIN

CDW CONDENSER WATER

CFH CUBIC FEET PER HOUR

CFM CUBIC FEET PER MINUTE

CHP CHILLED WATER PUMP

CHR CHILLED WATER RETURN

CHS CHILLED WATER SUPPLY

CLG COOLING OR CEILING

CO CLEANOUT

COND CONDENSATE OR CONDENSER

CT COOLING TOWER

CWR CONDENSER WATER RETURN

CWS CONDENSER WATER SUPPLY

DDC DIRECT DIGITAL CONTROL

DEG DEGREES

DI DIGITAL INPUT

DN DOWN

DO DIGITAL OUTPUT

DOAS DEDICATED OUTDOOR AIR SYSTEM

DP DIFFERENTIAL PRESSURE

EA EXHAUST AIR OR EACH

EF EXHAUST FAN

EL OR ELEV ELEVATION

EXH EXHAUST

F OR °F DEGREES FARENHEIT

FCU FAN COIL UNIT

FD FIRE DAMPER

FPM FEET PER MINUTE

FS FLOW SWITCH

FT FOOT OR FEET

FZ FREEZESTAT

GA GAUGE

GAL GALLON (U.S.)

GALV GALVANIZED

HGI HOODED GRAVITY INTAKE

HGR HOODED GRAVITY RELIEF

HWB HOT WATER BOILER

HWP HOT WATER PUMP

HWR HEATING HOT WATER RETURN

HWS HEATING HOT WATER SUPPLY

L LOUVER

NC NOISE CRITERIA OR NORMALLY CLOSED

NO NUMBER OR NORMALLY OPEN

NPSH NET POSITIVE SUCTION HEAD

NTS NOT TO SCALE

OA OUTSIDE AIR

PSI POUNDS PER SQUARE INCH

QTY QUANTITY

RA RETURN AIR

RH RELATIVE HUMIDITY

RLF RELIEF AIR

SA SUPPLY AIR

SD SMOKE DAMPER

SF SQUARE FEET

SFD COMBINATION FIRE & SMOKE DAMPER

STD STANDARD

STL STEEL

TB TERMINAL BOX

TSTAT THERMOSTAT

TUC TERMINAL UNIT CONTROLLER

TYP TYPICAL

UH UNIT HEATER

VAV VARIABLE AIR VOLUME

VFD VARIABLE FREQUENCY DRIVE

VLV VALVE

W/ WITH

W/O WITHOUT

WG WATER GAUGE

XFER TRANSFER

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

SEAL

2850 EISENHOWER AVENUE

SUITE 200

ALEXANDRIA, VA 22314

PRE-FINAL

100% DESIGN

SUBMITTAL

06 / 03 / 20

M

M

M

M

M

M

M

M M

M

M

18 7 6 5 4 3 2

A

B

C

D

E

CONFERENCE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

MOTHER'S

STORAGE

OFFICE

S3D

(TYP 8)

ACCU-1

OFFICE

LAB (TOP

SEC)

LAB

(SECRET)

SZVAV-1

SZVAV-2

S3D

S3E

SZVAV-1

SZVAV-2

R3

36"x16"

R3

36"x16"

28"x18"

28"x18"

28"x18"

28"x18"

A1

M-401

A1

M-402

24"x16"

T

T

H-2

H-3

S3E

S3E

S3E

S3E

S3E

28"x18" 22"x16"

R3

36"x16"

(TYP 2)

TR

ELEC

MECH

WOMEN

MEN

VEST

CORRIDOR

JAN

BREAK

ENGINEERING

28"x18"

"ø

"ø

"ø

"ø 14

"ø

"ø

"x

"ø6

N O

T F

O R

C O

N S

T R

U C

T

IO

N

P R

E L

IM

IN

A

R Y

SATISFACTORY TO

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

W

A S

H

IN

G T

O N

P A

T U

X E

N T

R

IV

E R

M

D

AS NOTED

2850 EISENHOWER AVENUE

SUITE 200

ALEXANDRIA, VA 22314

N A

V F

A C

L R

P F

A C

IL

IT

Y I D

S

.1

.2

W E

B S

T E

R F

IE

L D

N A

V A

L S

T A

T

IO

N P

A T

U X

E N

T R

IV

E

R

PRE-BID FINAL

(100%) DESIGN

SUBMITTAL

07/02/20

R E

V D

A T

E

F

IL

E N

A M

E

U N

C

LA

S S

IF

IE

D

DRAWFORM REVISION: 12 APRIL 2018

CHIEF ENG/ARCH

IPT TECH. BRANCH HEAD

PROJECT MANAGER

A/E INFO

APPROVED

/2

/2

:0

:5

P M

C U s e rs \z a b a lo s \D o c u m e n ts \2

R

M

C

E N

ID

S b im m e c h

.r v t

M-101

FI

R

S T

FL

O

O R

M E

C H

A N

IC

A

L P

LA

N

AEBSWL ZMA

1/8" = 1'-0" A1

FIRST FLOOR MECHANICAL PLAN

PLAN

NORTH

4' 8' 16'0'

WORK NOTES

1 PROVIDE SECURE DUCT PENETRATION. SEE DETAIL B3/A-504.

2 ROUTE OUTSIDE AIR INTAKE DUCT UP ALONG WALL AND PROVIDE

28X28 WEATHER HOOD BIRD SCREEN FACING AWAY FROM

BUILDING. BOTTOM OF OPENING MUST BE AT LEAST 10' ABOVE

GRADE. ROUTE SUPPLY AND RETURN AIR DUCTS UP ALONG WALL

AND PENETRATE WALL HIGH ENOUGH TO MAINTAIN 10' CLEAR IN

LAB. SEE DETAIL C4/M-502.

3 6" CONCRETE PAD.

4 EQUIPMENT CLEARANCE (TYPICAL)

5 PROVIDE ATFP CONTROL DAMPER.

6 DIFFUSERS SHALL BE AT LEAST 10' AFF. MAINTAIN A CLEAR HEIGHT

OF 10' AFF IN LAB SPACE.

7 ROUTE DUCT UNDER BEAM.

8 ROUTE CONDENSATE TO DRYWELL. SEE DETAIL C1/M-502.

GENERAL MECHANICAL NOTES

1 THE LOCATION OF ALL DUCT, PIPING, AND EQUIPMENT SHALL BE

ADJUSTED TO ACCOMMODATE ANTICIPATED OR ENCOUNTERED

INTERFERENCES.

2 PROVIDE BALANCING DAMPER FOR EACH SUPPLY, RETURN, AND

EXHAUST RUNOUT.

3 ALL RUNOUTS TO TERMINALS ARE NECK SIZE UNLESS OTHERWISE

NOTED.

4 MAINTAIN MANUFACTURER RECOMMENDED CLEARANCE AROUND

ALL EQUIPMENT.

5 DUCT SIZES SHOWN REFER TO AIR SIZE.

6 ALL DUCT TAPS SHALL HAVE 45 DEGREE DUCT HEELS.

7 DUCT SIZES SHOWN AS XX"/XX" REFER TO OVAL DUCT. ALL MEDIUM

PRESSURE DUCTWORK MUST BE EITHER ROUND OR OVAL.

8 A MINIMUM OF 6 DUCT DIAMETERS OF STRAIGHT DUCT DIRECTLY

UPSTREAM OF VAV CONNECTION IS REQUIRED.

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

SEAL

2850 EISENHOWER AVENUE

SUITE 200

ALEXANDRIA, VA 22314

PRE-FINAL

100% DESIGN

SUBMITTAL

06 / 03 / 20

18 7 6 5 4 3 2

A

B

C

D

E

HGR-1

HGI-1

N O

T F

O R

C O

N S

T R

U C

T

IO

N

P R

E L

IM

IN

A

R Y

SATISFACTORY TO

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

W

A S

H

IN

G T

O N

P A

T U

X E

N T

R

IV

E R

M

D

AS NOTED

2850 EISENHOWER AVENUE

SUITE 200

ALEXANDRIA, VA 22314

N A

V F

A C

L R

P F

A C

IL

IT

Y I D

S

.1

.2

W E

B S

T E

R F

IE

L D

N A

V A

L S

T A

T

IO

N P

A T

U X

E N

T R

IV

E

R

PRE-BID FINAL

(100%) DESIGN

SUBMITTAL

07/02/20

R E

V D

A T

E

F

IL

E N

A M

E

U N

C

LA

S S

IF

IE

D

DRAWFORM REVISION: 12 APRIL 2018

CHIEF ENG/ARCH

IPT TECH. BRANCH HEAD

PROJECT MANAGER

A/E INFO

APPROVED

/2

/2

:0

:5

P M

C U s e rs \z a b a lo s \D o c u m e n ts \2

R

M

C

E N

ID

S b im m e c h

.r v t

M-102

R O

O F

M E

C H

A N

IC

A

L P

LA

N

AEBSWL ZMA

PLAN

NORTH

4' 8' 16'0' 1/8" = 1'-0"

A1

ROOF MECHANICAL PLAN

WORK NOTES

GENERAL MECHANICAL NOTES

1 MAINTAIN MANUFACTURER RECOMMENDED CLEARANCE AROUND

ALL EQUIPMENT.

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

SEAL

2850 EISENHOWER AVENUE

SUITE 200

ALEXANDRIA, VA 22314

PRE-FINAL

100% DESIGN

SUBMITTAL

06 / 03 / 20

FIRST FLOOR

0' - 0"

FIRST FLOOR

0' - 0"

EAVE HT

13' - 6"

EAVE HT

13' - 6"

AHU-1

REFRIGERANT PIPING

TO DX COIL

L-1

28"x30" RA

DH-1

6" CONCRETE PAD

30"x60" EXH

30"x60" OA

22"x38" OA

30"x28" EXH

40"x40" OA

HGI-1

UH-1

18"x24" OA

10"x10" EXH

MECH

STORAGE

26"/22" SA

28"x30" RA

26"x30" RA

6"ø

26"/22" SA

30"x28" EXH

22"x38" OA

MOTORIZED

DAMPER

ROOF CURB

N O

T F

O R

C O

N S

T R

U C

T

IO

N

P R

E L

IM

IN

A

R Y

SATISFACTORY TO

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

W

A S

H

IN

G T

O N

P A

T U

X E

N T

R

IV

E R

M

D

AS NOTED

2850 EISENHOWER AVENUE

SUITE 200

ALEXANDRIA, VA 22314

N A

V F

A C

L R

P F

A C

IL

IT

Y I D

S

.1

.2

W E

B S

T E

R F

IE

L D

N A

V A

L S

T A

T

IO

N P

A T

U X

E N

T R

IV

E

R

PRE-BID FINAL

(100%) DESIGN

SUBMITTAL

07/02/20

R E

V D

A T

E

F

IL

E N

A M

E

U N

C

LA

S S

IF

IE

D

DRAWFORM REVISION: 12 APRIL 2018

CHIEF ENG/ARCH

IPT TECH. BRANCH HEAD

PROJECT MANAGER

A/E INFO

APPROVED

/2

/2

:0

:5

P M

C U s e rs \z a b a lo s \D o c u m e n ts \2

R

M

C

E N

ID

S b im m e c h

.r v t

M-301

M E

C H

A N

IC

A

L R

O O

M S

E C

TI

O

N

AEBSWL ZMA

1/2" = 1'-0" A2

MECHANICAL ROOM SECTION

1' 2' 4'0'

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

SEAL

2850 EISENHOWER AVENUE

SUITE 200

ALEXANDRIA, VA 22314

PRE-FINAL

100% DESIGN

SUBMITTAL

06 / 03 / 20

M

M

M

M M

16 5 4 3 2

C

D

E

A2

M-301

TR

MECH

MEN

WOMEN

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

BREAK

MOTHER'S

STORAGE

OFFICE

VAV-03

VAV-02

VAV-01

T

T

T VAV-03

TT

VAV-01

VAV-02

OFFICE

A1

M-403

R1

R2

R1

R1

R2

R1

R2

R2

S1B

S1B

S1B

S1B

8"ø

R2

R1

R2

R1

R1

R2

R1

R2

S1B

S1B

S1B

S1B

8"x8" 8"x8"

8"ø

8"x8"8"x8"

8"x8"

14"x14"

R2

"ø

S1B

S1B

S1B

S1B

S1B

S1B

S1B

S1B

S1B

S1B

R1

22"x16"16"x10" 105

S1A 10"x10"

10"x8"

30"x28"

6"x6"

E1

E1

10"x6"

8"x8"

18"x18"

ENGINEERING

12"ø

14"ø 10"x10"

10"x10"10"x10"

8"x8" 8"x10" 10"x10" 12"x12"

8" x8

8" x8

8" x8

8" x8

8" x8

8" x8

8"x8"

12"x10"12"x10"

10"x10"10"x10"8"x8"

8" x8

8" x8

"x

"x

18"ø

"ø

16"ø

"x

6"ø

12"x10"

6"ø

12"ø

10"ø

10"ø

R1

20"x20"

"x

"x

"x

"x

10"ø12"x10"

20"x20"

22"/26"

30"x26"

ELEC

T T

T

VAV-01 VAV-01

VAV-01

T VAV-02TVAV-02

TVAV-02

H

N O

T F

O R

C O

N S

T R

U C

T

IO

N

P R

E L

IM

IN

A

R Y

SATISFACTORY TO

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

W

A S

H

IN

G T

O N

P A

T U

X E

N T

R

IV

E R

M

D

AS NOTED

2850 EISENHOWER AVENUE

SUITE 200

ALEXANDRIA, VA 22314

N A

V F

A C

L R

P F

A C

IL

IT

Y I D

S

.1

.2

W E

B S

T E

R F

IE

L D

N A

V A

L S

T A

T

IO

N P

A T

U X

E N

T R

IV

E

R

PRE-BID FINAL

(100%) DESIGN

SUBMITTAL

07/02/20

R E

V D

A T

E

F

IL

E N

A M

E

U N

C

LA

S S

IF

IE

D

DRAWFORM REVISION: 12 APRIL 2018

CHIEF ENG/ARCH

IPT TECH. BRANCH HEAD

PROJECT MANAGER

A/E INFO

APPROVED

/2

/2

:0

:5

P M

C U s e rs \z a b a lo s \D o c u m e n ts \2

R

M

C

E N

ID

S b im m e c h

.r v t

M-401

FI

R

S T

FL

O

O R

M E

C H

A N

IC

A

L P

LA

N

N

O R

TH

AEBSWL ZMA

3/16" = 1'-0" A1

FIRST FLOOR MECHANICAL PLAN - NORTH

WORK NOTES

GENERAL MECHANICAL NOTES

1 THE LOCATION OF ALL DUCT, PIPING, AND EQUIPMENT SHALL BE

ADJUSTED TO ACCOMMODATE ANTICIPATED OR ENCOUNTERED

INTERFERENCES.

2 PROVIDE BALANCING DAMPER FOR EACH SUPPLY, RETURN, AND

EXHAUST RUNOUT.

3 ALL RUNOUTS TO TERMINALS ARE NECK SIZE UNLESS OTHERWISE

NOTED.

4 MAINTAIN MANUFACTURER RECOMMENDED CLEARANCE AROUND

ALL EQUIPMENT.

5 DUCT SIZES SHOWN REFER TO AIR SIZE.

6 ALL DUCT TAPS SHALL HAVE 45 DEGREE DUCT HEELS.

7 DUCT SIZES SHOWN AS XX"/XX" REFER TO OVAL DUCT. ALL MEDIUM

PRESSURE DUCTWORK MUST BE EITHER ROUND OR OVAL.

8 A MINIMUM OF 6 DUCT DIAMETERS OF STRAIGHT DUCT DIRECTLY

UPSTREAM OF VAV CONNECTION IS REQUIRED.

PLAN

NORTH

0' 4' 8' 12'

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

SEAL

2850 EISENHOWER AVENUE

SUITE 200

ALEXANDRIA, VA 22314

PRE-FINAL

100% DESIGN

SUBMITTAL

06 / 03 / 20

16 5 4 3 2

A

B

C

CONFERENCE

WOMEN

OFFICE

JA

N

VAV-04

VAV-05

TT

T

T VAV-09

T

AV

110A

S2B

R1

OFFICE

VAV-06

VAV-09

CUH-1

R2 18"x18"

24"x24"

"ø

20"x20"

18"x18"

R2

20"ø

S1B

S1B

S1B

S1B

S1B

S1B

S1B

S1B

S1B

20"x14"

R1

T VAV-08

R1

R2

S1B

R1 420

R2

S1A

S1A

S1A

S1A

S1A

S1A

R1

R2

R1

S1A

S2B

8"x8"

10"x10"

12"x10"

E2

30"x28"

MEN

CORRIDOR

VEST

BREAK

S4

S4

S4

S4

S4

S4

S4

S4

S4

S4

"x

"ø

14"ø

"ø

12"ø

14"ø14"ø

"ø

12"ø

8"ø

10"ø 8"ø

10"x10" 16"x10"

"ø

8"ø

20"x16" 20"x20"

16"ø14"ø

12"ø

"ø

22"ø

"ø6" ø

8"x8"

8"ø

8" ø

"x

8"

"ø

6"ø

8" x8

"x

10"x10"

6"ø 10"x10"

14"x12"

VAV-08

14"x10"

8" ø

R1

18"x16"

"x

14"x14"

14"x14"

R1

20"x20"

6"x6"

10"x10"

10"x10"

12"x12"

S4

S4

VAV-07

ENGINEERING

12"x10"14"x10"

20"x20"

12"ø

6"x6"

VAV-04

N O

T F

O R

C O

N S

T R

U C

T

IO

N

P R

E L

IM

IN

A

R Y

SATISFACTORY TO

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

W

A S

H

IN

G T

O N

P A

T U

X E

N T

R

IV

E R

M

D

AS NOTED

2850 EISENHOWER AVENUE

SUITE 200

ALEXANDRIA, VA 22314

N A

V F

A C

L R

P F

A C

IL

IT

Y I D

S

.1

.2

W E

B S

T E

R F

IE

L D

N A

V A

L S

T A

T

IO

N P

A T

U X

E N

T R

IV

E

R

PRE-BID FINAL

(100%) DESIGN

SUBMITTAL

07/02/20

R E

V D

A T

E

F

IL

E N

A M

E

U N

C

LA

S S

IF

IE

D

DRAWFORM REVISION: 12 APRIL 2018

CHIEF ENG/ARCH

IPT TECH. BRANCH HEAD

PROJECT MANAGER

A/E INFO

APPROVED

/2

/2

:0

:5

P M

C U s e rs \z a b a lo s \D o c u m e n ts \2

R

M

C

E N

ID

S b im m e c h

.r v t

M-402

FI

R

S T

FL

O

O R

M E

C H

A N

IC

A

L P

LA

N

S

O U

TH

AEBSWL ZMA

3/16" = 1'-0" A1

FIRST FLOOR MECHANICAL PLAN - SOUTH

WORK NOTES

1 40"X40" EXHAUST DUCT UP TO HGR-1.

2 ATFP EMERGENCY SHUTDOWN SWITCH LOCATION. PROVIDE ATFP

SWITCH WITH COVER.

3 DUCT STATIC PRESSURE SENSOR LOCATION.

GENERAL MECHANICAL NOTES

1 THE LOCATION OF ALL DUCT, PIPING, AND EQUIPMENT SHALL BE

ADJUSTED TO ACCOMMODATE ANTICIPATED OR ENCOUNTERED

INTERFERENCES.

2 PROVIDE BALANCING DAMPER FOR EACH SUPPLY, RETURN, AND

EXHAUST RUNOUT.

3 ALL RUNOUTS TO TERMINALS ARE NECK SIZE UNLESS OTHERWISE

NOTED.

4 MAINTAIN MANUFACTURER RECOMMENDED CLEARANCE AROUND

ALL EQUIPMENT.

5 DUCT SIZES SHOWN REFER TO AIR SIZE.

6 ALL DUCT TAPS SHALL HAVE 45 DEGREE DUCT HEELS.

7 DUCT SIZES SHOWN AS XX"/XX" REFER TO OVAL DUCT. ALL MEDIUM

PRESSURE DUCTWORK MUST BE EITHER ROUND OR OVAL.

8 A MINIMUM OF 6 DUCT DIAMETERS OF STRAIGHT DUCT DIRECTLY

UPSTREAM OF VAV CONNECTION IS REQUIRED.

PLAN

NORTH

0' 4' 8' 12'

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

SEAL

2850 EISENHOWER AVENUE

SUITE 200

ALEXANDRIA, VA 22314

PRE-FINAL

100% DESIGN

SUBMITTAL

06 / 03 / 20

M

M

M

M

M

D

E

A2

M-301

L-1

BEL

H-1

AHU-1

EF-2

DDC PANELS

MECH

DH-1

TUH-1

L-3

20"x18" EXH

12"x10" EXH

L-2

DSS-1A

DSS-1

TR

ELEC

UH-2

24"x18" EXH

EF-3

BEL

14"x12" EXH 12"x12" EXH

30"x28" EXH

24"x18" OA

30"x28" RA

38"x22" OA

60"x30" EXH

60"x30" OA

L-4

EF-1

S1A

S1A

R2

DWH-1

PIPING TO DH-1

MOTHER'S

STORAGE

3/4" CD

6"x6" RA

14"x14" RA

22"/26" SA

R2

REFRIGERANT

PIPING

6"x6" RA

T

10"x10" EXH

T

30"x26" RA

12"x12"

36"x18"

"x

"x

"x

6"ø

AHU CLEARANCE

N O

T F

O R

C O

N S

T R

U C

T

IO

N

P R

E L

IM

IN

A

R Y

SATISFACTORY TO

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

W

A S

H

IN

G T

O N

P A

T U

X E

N T

R

IV

E R

M

D

AS NOTED

2850 EISENHOWER AVENUE

SUITE 200

ALEXANDRIA, VA 22314

N A

V F

A C

L R

P F

A C

IL

IT

Y I D

S

.1

.2

W E

B S

T E

R F

IE

L D

N A

V A

L S

T A

T

IO

N P

A T

U X

E N

T R

IV

E

R

PRE-BID FINAL

(100%) DESIGN

SUBMITTAL

07/02/20

R E

V D

A T

E

F

IL

E N

A M

E

U N

C

LA

S S

IF

IE

D

DRAWFORM REVISION: 12 APRIL 2018

CHIEF ENG/ARCH

IPT TECH. BRANCH HEAD

PROJECT MANAGER

A/E INFO

APPROVED

/2

/2

:0

:5

P M

C U s e rs \z a b a lo s \D o c u m e n ts \2

R

M

C

E N

ID

S b im m e c h

.r v t

M-403

M E

C H

A N

IC

A

L R

O O

M E

N

LA

R G

E D

P

LA

N

AEBSWL ZMA

1/2" = 1'-0" A1

MECHANICAL ROOM ENLARGED PLAN

WORK NOTES

1 PROVIDE BELLMOUTH FITTING AND BIRDSCREEN AT INLET.

2 6" CONCRETE PAD.

3 SPACE RESERVED FOR INCOMING FIRE PROTECTION SERVICE TO

BUILDING, SEE FIRE PROTECTION. MAINTAIN CLEAR SPACE ABOVE

AS SHOWN. PROVIDE A MINIMUM 3FT CLEARANCE IN FRONT OF ALL

COMPONENTS.

4 40"X40" OUTSIDE AIR DUCT UP TO HGI-1.

5 PROVIDE CONCRETE PAD FOR CONDENSING UNIT. COORDINATE

EXACT LOCATION WITH CIVIL. SEE STRUCTURAL FOR DETAIL.

6 REFRIGERANT PIPING. SIZE PER MANUFACTURER'S

RECOMMENDATIONS. PROVIDE ALUMINUM JACKET FOR OUTDOOR

EXPOSED PIPING INSULATION.

7 ROUTE CONDENSATE TO SPLASHBLOCK AWAY FROM OUTDOOR

UNIT.

8 PROVIDE ATFP CONTROL DAMPER.

1' 2' 4'0'

GENERAL MECHANICAL NOTES

1 THE LOCATION OF ALL DUCT, PIPING, AND EQUIPMENT SHALL BE

ADJUSTED TO ACCOMMODATE ANTICIPATED OR ENCOUNTERED

INTERFERENCES.

2 PROVIDE BALANCING DAMPER FOR EACH SUPPLY, RETURN, AND

EXHAUST RUNOUT.

3 ALL RUNOUTS TO TERMINALS ARE NECK SIZE UNLESS OTHERWISE

NOTED.

4 MAINTAIN MANUFACTURER RECOMMENDED CLEARANCE AROUND

ALL EQUIPMENT.

5 DUCT SIZES SHOWN REFER TO AIR SIZE.

6 ALL DUCT TAPS SHALL HAVE 45 DEGREE DUCT HEELS.

7 DUCT SIZES SHOWN AS XX"/XX" REFER TO OVAL DUCT. ALL MEDIUM

PRESSURE DUCTWORK MUST BE EITHER ROUND OR OVAL.

8 A MINIMUM OF 6 DUCT DIAMETERS OF STRAIGHT DUCT DIRECTLY

UPSTREAM OF VAV CONNECTION IS REQUIRED.

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

SEAL

2850 EISENHOWER AVENUE

SUITE 200

ALEXANDRIA, VA 22314

PRE-FINAL

100% DESIGN

SUBMITTAL

06 / 03 / 20

TYPICAL CEILING SUPPLY

DIFFUSER CONNECTION

DUCTLESS SPLIT SYSTEM DETAIL

SERIES FAN-POWERED VAV TERMINAL

WITH ELECTRIC REHEAT

CEILING RETURN GRILLE WITH FILTER

CEILING RETURN/EXHAUST GRILLE

WITHOUT FILTER

ELECTRIC HEATING COIL

CONNECTIONS SHALL BE LEFT

OR RIGHT HAND AS SPACE

REQUIREMENTS DICTATE

(MIN. 4" EXTENSION ALL SIDES)

4" THICK CONCRETE PAD

OUTDOOR UNIT

FURNISHED BY FCU MFGR.

WALL SLEEVE WITH CAPS

TO INDOOR UNIT

VOLTAGE CONTROL

POWER & HIGH

RL REFRIGERANT

INSULATED RS,

AIRFLOW

LINES

AIRFLOW

TO THERMOSTAT

CONNECTION CABLE

INDOOR UNIT

FURNISHED BY FCU MFGR.

WALL MOUNTING BRACKET

CABLE

SEE PLANS FOR ROUTING

3/4"∅ DRAIN LINE

THERMISTOR

SECURE TO CONCRETE PAD

SA

C1

C3

C1

A4

A1

SCALE: NONE

INSULATION

ACOUSTICAL CEILING TILE

SUPPLY AIR DUCT

VOLUME DAMPER

DIAMETER = "A"

INSULATED ACOUSTIC FLEX DUCT - LENGTH MINIMUM 3

FEET, NOT TO EXCEED 5 FEET. LIMIT ANY OFFSET, SAG,

AND MISALIGNMENT TO 4" IN ANY DIRECTION. DO NOT USE

FLEX DUCT FOR OFFSETS GREATER THAN 45 DEGREES

OR CONNECTION TO DIFFUSERS GREATER THAN 45

DEGREES.

SCALE: NONE

EXTERNALLY INSULATED

RIGID DUCT AND TOP OF

DIFFUSER

R = 1.5A

"A"

45° ENTRY SQUARE TO ROUND.

45° ENTRY

24x24 LAY IN GRILLE

RETURN OR EXHAUST DUCT

(SEE PLANS FOR SIZES)

VOLUME DAMPER

RETURN OR EXHAUST DUCT

2"

TRANSITION IF REQUIRED

SCALE: NONE

DISCHARGE DUCT

ELECTRIC HEATING COIL

ATTACH TO STRUCTURE

SCALE: NONE

PROVIDE 6 DIA OF

STRAIGHT NECK-SIZE DUCT

NOTES:

1. SEE AT/FP CONSTRAINT DETAILS ON SHEET M-503. FIXTURES WEIGHING 31 LBS OR MORE SHALL BE

BRACED TO RESIST FORCES OF 0.5 TIMES THE EQUIPMENT WEIGHT IN ANY HORIZONTAL DIRECTION

AND 1.5 TIMES THE EQUIPMENT WEIGHT IN THE DOWNWARD DIRECTION.

VOLUME DAMPER

MEDIUM PRESSURE SUPPLY

SEE PLANS FOR SIZES

RETURN CONNECTION.

SEE PLANS FOR ROUTING.

FURNISH TERMINAL UNIT

WITH SINGLE POINT

ELECTRICAL CONNECTION

AND FACTORY MOUNTED

FUSED DISCONNECT.

EXTERNALLY INSULATE

INLET COLLAR AND

SECURE TO TERMINAL

WITH METAL FOIL TAPETYPICAL TERMINAL

HANGER CONNECTION

CONTROLS SHALL BE

EITHER RIGHT OR LEFT

HAND AS SPACE REQUIRE-

MENTS DICTATE

PROVIDE RUBBER

ISOLATION GROMMET (TYP)

LONG RADIUS RIGID

90 DEG ELBOW

SUPPLY DIFFUSER WITH NECK

TRANSITION AS REQUIRED

SCALE: NONE

45 DEG HEEL

RETURN DUCT (SEE

PLANS FOR SIZES)

VOLUME DAMPER

RETURN DUCT

VARIOUS

24x24 FILTER GRILLE WITH 20x20

FILTER AND DUCT CONNECTION

20x20 PLENUM

WITH END CAP

45 DEG HEEL

CEILING

N O

T F

O R

C O

N S

T R

U C

T

IO

N

P R

E L

IM

IN

A

R Y

SATISFACTORY TO

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

W

A S

H

IN

G T

O N

P A

T U

X E

N T

R

IV

E R

M

D

AS NOTED

2850 EISENHOWER AVENUE

SUITE 200

ALEXANDRIA, VA 22314

N A

V F

A C

L R

P F

A C

IL

IT

Y I D

S

.1

.2

W E

B S

T E

R F

IE

L D

N A

V A

L S

T A

T

IO

N P

A T

U X

E N

T R

IV

E

R

PRE-BID FINAL

(100%) DESIGN

SUBMITTAL

07/02/20

R E

V D

A T

E

F

IL

E N

A M

E

U N

C

LA

S S

IF

IE

D

DRAWFORM REVISION: 12 APRIL 2018

CHIEF ENG/ARCH

IPT TECH. BRANCH HEAD

PROJECT MANAGER

A/E INFO

APPROVED

/2

/2

:0

:5

P M

C U s e rs \z a b a lo s \D o c u m e n ts \2

R

M

C

E N

ID

S b im m e c h

.r v t

M-501

D E

TA

IL

S

AEBSWL ZMA

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

SEAL

2850 EISENHOWER AVENUE

SUITE 200

ALEXANDRIA, VA 22314

PRE-FINAL

100% DESIGN

SUBMITTAL

06 / 03 / 20

SECURE

SIDE

NON-SECURE

SIDE

SECURE PIPE PENETRATION DETAIL

INLINE EXHAUST FAN DETAIL

AIR HANDLING UNIT DRAIN FOR

NEGATIVE PRESSURE DRAIN PAN

BELLMOUTH FITTING DETAIL

GRADE MOUNTED AIR CONDITIONER UNIT

DRAIN FOR NEGATIVE PRESSURE DRAIN PAN

PLAN VIEW SIDE ELEVEATION

EXTERIOR WALL DUCT RISER SUPPORT DETAIL

B3

A3

A1

A4

C1 C4

PIPE

PIPE CLAMP

NO. 4 WIRE

PROVIDE ACOUSTICAL

SEALANT AT ALL GYPSUM

BOARD PENETRATIONS

PIPE INSULATION

AS SPECIFIED

GROUND PIPE WITHIN

6" OF PERIMETER

CONNECT TO

BUILDING GROUND

SCALE: NONE

1.

SEE PLANS FOR

DUCT SIZE

PROVIDE DOUBLE NUT

ARRANGEMENT BELOW

SUPPORT BRACKET

(TYPICAL)

SUPPORT BRACKET

NOTES:

SUPPORT FAN PER MANUFACTURER'S RECOMMENDATIONS.

SCALE: NONE

FLEXIBLE CONNECTION

(TYPICAL)

SEE PLANS FOR

DUCT SIZE

SUPPORT RODS

(TYPICAL)INLINE

EXHAUST

FAN

VIBRATION ISOLATORS

NOTE: CONDENSATE DRAIN PIPE SIZE SHALL BE UNIT

DRAIN CONNECTION SIZE (MINUMUM 1").

"A" = SYSTEM STATIC PRESSURE IN INCHES, AT DRAIN POINT + 1"

SCALE: NONE

MOP SINK OR FLOOR DRAIN

2" AIR GAP

45 DEGREE CUT

UNIT DRAIN CONNECTION

ON FAN INLET

UNIT DRAIN PAN

(0.5 x A)in

A

SQUARE HEAD PLUGS

SLOPE MINIMUM 1/8" PER

FOOT DOWN TOWARD DRAIN

INSULATE WITH

VAPOR BARRIER

6"

DUCT WIDTH

6"

DUCT HEIGHT

HEIGHT + 12"

WIDTH + 12"

6"

6"

DUCT DIAMETER

DIAMETER + 12"

R6"

SCALE: NONE

PROVIDE

BIRDSCREEN

PROVIDE

BIRDSCREEN

UNIT DRAIN PAN

UNIT DRAIN CONNECTION

"A" = SYSTEM STATIC PRESSURE IN INCHES, AT DRAIN POINT (1.5" MIN).

(0.5 x A)in

A SLOPE 1/8" PER FOOT

NOTES:

1. CONDENSATE DRAIN PIPE SIZE SHALL BE UNIT DRAIN CONNECTION

SIZE (MINIMUM 3/4")

2. THIS DETAIL IS PROVIDED FOR REFERENCE. INSTALL PER

MANUFACTURER INSTALLATION INSTRUCTIONS.

THREADED CAP

CONCRETE PIPE

12" DIA. x 24" LONG

PEA GRAVEL

CLEAN LOOSE

DRY WELL NEXT TO EQUIPMENT PAD

SCALE: NONE

SCALE: NONE

SECURE METAL BUILDING

WALL, TYP. 4 PLACES.

COORDINATE WITH METAL

BUILDING MANUFACTURER

2"x2"x1/4" ANGLE

CLIP WITH BOLTS

& HEX NUTS

DUCT RISER WITH

INSULATION. SEE

PLANS FOR SIZES

1-1/2"x1-1/2"x1/4"

(TYP.)

TO SUIT

STANDARD DUCT

RISER SUPPORT

W/BOLTS AND

HEX NUTS

THRU BOLT STANDARD

RISER SUPPORT TO ANGLE

CLIP, TYP.

VARIES

1/4"

TYP.

1-1/2"x1-1/2"x1/4" ALL

WELDED CONSTRUCTION

TO SUIT

DUCT RISER WITH

INSULATION. SEE

PLANS FOR SIZES

STANDARD DUCT

RISER SUPPORT

W/BOLTS AND HEX

NUTS

SECURE METAL BUILDING

WALL, TYP. 4 PLACES.

COORDINATE WITH METAL

BUILDING MANUFACTURER

N O

T F

O R

C O

N S

T R

U C

T

IO

N

P R

E L

IM

IN

A

R Y

SATISFACTORY TO

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

W

A S

H

IN

G T

O N

P A

T U

X E

N T

R

IV

E R

M

D

AS NOTED

2850 EISENHOWER AVENUE

SUITE 200

ALEXANDRIA, VA 22314

N A

V F

A C

L R

P F

A C

IL

IT

Y I D

S

.1

.2

W E

B S

T E

R F

IE

L D

N A

V A

L S

T A

T

IO

N P

A T

U X

E N

T R

IV

E

R

PRE-BID FINAL

(100%) DESIGN

SUBMITTAL

07/02/20

R E

V D

A T

E

F

IL

E N

A M

E

U N

C

LA

S S

IF

IE

D

DRAWFORM REVISION: 12 APRIL 2018

CHIEF ENG/ARCH

IPT TECH. BRANCH HEAD

PROJECT MANAGER

A/E INFO

APPROVED

/2

/2

:0

:5

P M

C U s e rs \z a b a lo s \D o c u m e n ts \2

R

M

C

E N

ID

S b im m e c h

.r v t

M-502

D E

TA

IL

S

AEBSWL ZMA

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

SEAL

2850 EISENHOWER AVENUE

SUITE 200

ALEXANDRIA, VA 22314

PRE-FINAL

100% DESIGN

SUBMITTAL

06 / 03 / 20

ATFP BRACING DETAIL FOR SUSPENDED

MECHANICAL EQUIPMENT WITH EXTERNAL

VIBRATION ISOLATORS

ATFP BRACING DETAIL FOR SUSPENDED

MECHANICAL EQUIPMENT WITH INTERNAL

VIBRATION ISOLATORS

PLAN VIEW

HANGER ROD

EQUIPMENT

MECHANICAL

(TYP)

VIBRATION ISOLATION

45°

TRANSVERSE AND

LONGITUDINAL

(TYP.)

CABLE BRACE

WITH 1/2" SLACK

CABLES INSTALLED

ON BOTH SIDES

30° TO 90°

ELEVATION

30° TO 90°

SUPPORT

TYP.

45°

MEMBER

PLAN VIEW

ELEVATION

WITH 1/2" SLACK

CABLES INSTALLED

ON BOTH SIDES

SUPPORT ANGLE

DOUBLE NUT (TYP)

SEE ATFP CABLE

ASSEMBLY DETAIL

SUSPENDED

MECHANICAL

EQUIPMENT

SUPPORT ANGLE

DOUBLE NUT (TYP)

ASSEMBLY DETAIL

SEE ATFP CABLE

CABLES INSTALLED

TIGHT (TYP.)

(TYP.)

(TYP.)

CABLE BRACE

LONGITUDINAL

TRANSVERSE AND

HANGER ROD (TYP)

SUSPENDED

MECHANICAL

EQUIPMENT

SUSPENDED

SUSPENDED

MECHANICAL

EQUIPMENT

> 31 LBS

> 31 LBS

> 31 LBS

> 31 LBS

HANGER ROD (TYP)

B2

B3

SCALE: NONE

N O

T F

O R

C O

N S

T R

U C

T

IO

N

P R

E L

IM

IN

A

R Y

SATISFACTORY TO

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

W

A S

H

IN

G T

O N

P A

T U

X E

N T

R

IV

E R

M

D

AS NOTED

2850 EISENHOWER AVENUE

SUITE 200

ALEXANDRIA, VA 22314

N A

V F

A C

L R

P F

A C

IL

IT

Y I D

S

.1

.2

W E

B S

T E

R F

IE

L D

N A

V A

L S

T A

T

IO

N P

A T

U X

E N

T R

IV

E

R

PRE-BID FINAL

(100%) DESIGN

SUBMITTAL

07/02/20

R E

V D

A T

E

F

IL

E N

A M

E

U N

C

LA

S S

IF

IE

D

DRAWFORM REVISION: 12 APRIL 2018

CHIEF ENG/ARCH

IPT TECH. BRANCH HEAD

PROJECT MANAGER

A/E INFO

APPROVED

/2

/2

:0

:5

P M

C U s e rs \z a b a lo s \D o c u m e n ts \2

R

M

C

E N

ID

S b im m e c h

.r v t

M-503

D E

TA

IL

S

AEBSWL ZMA

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

SEAL

2850 EISENHOWER AVENUE

SUITE 200

ALEXANDRIA, VA 22314

PRE-FINAL

100% DESIGN

SUBMITTAL

06 / 03 / 20

DUCTLESS SPLIT SYSTEM SCHEDULE

OUTDOOR UNIT DESIGNATION DSS-1

INDOOR UNIT DESIGNATION DSS-1A

ROOM SERVED TR-202

IN

D

O O

R U

N

IT EVAPORATOR

AIRFLOW (H/L) 500/400

RATED TOTAL COOLING CAPACITY (MBH) 18

ELECTRICAL

VOLTAGE (V) 208

PHASE 1

FREQUENCY (Hz) 60

REFRIGERANT R-410A

O U

T D

O O

R U

N

IT

ELECTRICAL

AMBIENT DESIGN TEMPERATURE (DEG F) 95

RATED TOTAL COOLING CAPACITY (MBH) 18

MINIMUM CIRCUIT AMPACITY (A) 16.5

RECOMMENDED FUSE SIZE (A) 20

VOLTAGE (V) 208

PHASE 1

FREQUENCY (Hz) 60

REMARKS 1, 2, 3, & 4

REMARKS LEGEND:

1. POWER FROM OUTDOOR UNIT, OUTDOOR UNIT POWER INCLUDES EVAPORATOR POWER.

INSTALL PER MANUFACTURER'S INSTRUCTIONS, ADJUST CHARGE AS NEEDED FOR

REFRIGERANT PIPE LENGTH.

2. PROVIDE 3/4" CONDUIT BETWEEN INDOOR AND OUTDOOR UNIT.

3. PROVIDE LOW AMBIENT OPERATION DOWN TO 0 DEG F OUTSIDE AIR.

4. PROVIDE CORROSION RESISTANT COATING ON CONDENSER COIL.

AIR COOLED CONDENSING UNIT

SCHEDULE

DESIGNATION ACCU-1

MINIMUM COOLING CAPACITY (MBH) 345

EER AT AHRI (CONDENSER ONLY) 11.4

DESIGN COOLING OUTDOOR TEMP DB (DEG F) 95

COMPRESSOR

TYPE SCROLL

QUANTITY 2

ELECTRICAL

VOLTAGE (V) 480

PHASE 3

FREQUENCY (Hz) 60

TOTAL POWER (Kw) 33.8

MINIMUM CIRCUIT AMPACITY (A) 63

MAXIMUM OVERCURRENT PROTECTION 80

REMARKS 1 & 2

REMARKS LEGEND:

1. PROVIDE A DIGITAL SCROLL COMPRESSOR. UNIT MUST BE CAPABLE OF

REDUCING CAPACITY TO 10% OF TOTAL CAPACITY WITH THE ABILITY TO

MODULATAE CAPACITY UP TO FULL LOAD.

2. PROVIDE LOW AMBIENT CONTROL.

VAV AIR HANDLING UNIT SCHEDULE

DESIGNATION AHU-1

LOCATION 200 - MECH

AREA SERVED VARIOUS

MINIMUM OUTSIDE AIR (CFM) 1,600

S

U P

P L Y

F A

N

MAXIMUM FAN AIRFLOW (CFM) 7,000

MINIMUM FAN AIRFLOW (CFM) 2,400

CONTROL TYPE VFD

EXTERNAL STATIC PRESSURE (IN. WG) 2

MOTOR (HP) 10

SUPPLY FAN MOTOR SPEED (RPM) 1,800

DRIVE TYPE DIRECT

R E

T U

R N

F A

N

MAXIMUM FAN AIRFLOW (CFM) 7,000

MINIMUM FAN AIRFLOW (CFM) 2,400

CONTROL TYPE VFD

EXTERNAL STATIC PRESSURE (IN. WG) 1

MOTOR (HP) 5

RETURN FAN MOTOR SPEED (RPM) 1,800

DRIVE TYPE DIRECT

C O

O L

IN

G

C O

IL

COIL TYPE DX

AIR FLOW (CFM) 7,000

ENTERING AIR TEMPERATURE DB / WB (DEG F) 79.1 / 68.1

LEAVING AIR TEMPERATURE DB / WB (DEG F) 53.0 / 52.0

TOTAL CAPACITY (MBH) 345

SENSIBLE CAPACITY (MBH) 200

FACE VELOCITY (FPM) 521

AIR PRESSURE DROP (IN W.G.) 0.544

REFRIGERANT TYPE R410A

H E

A T

IN

G

C O

IL

HEATING TYPE ELECTRIC

HEATING AIRFLOW (CFM) 2,400

TOTAL CAPACITY (kW) 17

ENTERING AIR TEMPERATURE DB (DEG F) 35.7

LEAVING AIR TEMPERATURE DB (DEG F) 58.0

AIR PRESSURE DROP (IN W.G.) 0.147

FILTERS PRE-FILTER / FINAL FILTER (MERV) 8 / 13

ELECTRICAL

CIRCUIT 1

VOLTS / PH / HZ 480 / 3 / 60

FLA (A) 22.85

MCA (A) 26.35

MAX FUSE SIZE (A) 40

ELECTRICAL

CIRCUIT 2

(ELEC HEAT)

VOLTS / PH / HZ 480 / 3 / 60

FLA (A) 21.56

MCA (A) 26.89

MAX FUSE SIZE (A) 30

REMARKS 1 & 2

REMARKS LEGEND:

1. PROVIDE SINGLE POINT POWER CONNECTION FOR CIRCUIT 1 AND A SEPARATE

POWER CONNECTION FOR CIRCUIT 2 FOR ELECTRIC HEATER.

2. EXTERNAL STATIC PRESSURES SHOWN DO NOT INCLUDE DIRTY FILTER LOSS.

ASSUME MEDIUM LOADED FILTER.

FAN POWERED BOX SCHEDULE

UNIT DESIGNATION VAV-01 VAV-02 VAV-03 VAV-04 VAV-05 VAV-06 VAV-07 VAV-08 VAV-09

TYPE SERIES SERIES SERIES SERIES SERIES SERIES SERIES SERIES SERIES

INLET DIAMETER (IN) 8 8 14 4 6 4 8 14 12

PRIMARY

AIRFLOW

(CFM)

MAX 460 460 2,100 100 415 90 440 2,150 1,670

MIN 140 140 630 40 170 40 130 650 500

UNIT FAN

CFM 460 460 2,100 190 415 190 440 2,150 1,670

ESP (IN-WC) 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4

REHEAT TYPE ELECTRIC ELECTRIC ELECTRIC ELECTRIC ELECTRIC ELECTRIC ELECTRIC ELECTRIC ELECTRIC

REHEAT CAPACITY (KW) 2.5 2.5 9.5 1.0 2.5 1.0 2.5 11.0 7.5

EAT (DEG F) 64.0 64.0 64.1 65.3 62.7 65.3 64.2 64.1 64.1

LAT (DEG F) 81.2 81.2 79.1 81.8 81.6 81.8 81.2 80.2 78.2

ELECTRICAL

MOTOR QUANTITY 1 1 1 1 1 1 1 1 1

MOTOR POWER (HP) 1/3 1/3 1/2 1/8 1/3 1/8 1/3 1/2 1/2

VOLTAGE 277 277 277 277 277 277 277 277 277

PHASE 1 1 1 1 1 1 1 1 1

FREQUENCE (Hz) 60 60 60 60 60 60 60 60 60

FLA 11.43 11.43 41.2 4.31 11.43 4.31 11.43 44.81 32.18

MCA 14.28 14.28 51.5 5.39 14.28 5.39 14.28 56.01 40.22

MSCP 15 15 50 15 15 15 15 60 40

MAX RATED SOUND PWL (NC) 31 31 46 29 31 29 31 46 42

MAX DISCHARGE SOUND PWL (NC) 19 19 32 22 19 22 19 34 30

REMARKS 1, 2, 3, 4, 6, & 7 1, 2, 3, 4, 6, & 7 1, 2, 3, 4, 6, & 7 1, 2, 3, 5, 6, & 7 1, 2, 3, 4, 6, & 7 1, 2, 3, 5, 6, & 7 1, 2, 3, 4, 6, & 7 1, 2, 3, 4, 6, & 7 1, 2, 3, 4, 6, & 7

REMARKS LEGEND:

1. PROVIDE FILTER IN RETURN GRILLE. ESP LISTED INCLUDES FILTER PRESSURE DROP.

2. PROVIDE 0.5 INCH NON FIBEROUS INSULATION LINER.

3. PROVIDE INTEGRAL DISCONNECT.

4. PROVIDE ELECTRONICALLY COMMUTATED MOTOR.

5. PROVIDE PSC MOTOR WITH SCR CONTROL.

6. PROVIDE 24V CONTROL POWER TRANSFORMER AS REQUIRED.

7. PROVIDE ELECTRIC REHEAT WITH SCR CONTROL.

N O

T F

O R

C O

N S

T R

U C

T

IO

N

P R

E L

IM

IN

A

R Y

SATISFACTORY TO

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

W

A S

H

IN

G T

O N

P A

T U

X E

N T

R

IV

E R

M

D

AS NOTED

2850 EISENHOWER AVENUE

SUITE 200

ALEXANDRIA, VA 22314

N A

V F

A C

L R

P F

A C

IL

IT

Y I D

S

.1

.2

W E

B S

T E

R F

IE

L D

N A

V A

L S

T A

T

IO

N P

A T

U X

E N

T R

IV

E

R

PRE-BID FINAL

(100%) DESIGN

SUBMITTAL

07/02/20

R E

V D

A T

E

F

IL

E N

A M

E

U N

C

LA

S S

IF

IE

D

DRAWFORM REVISION: 12 APRIL 2018

CHIEF ENG/ARCH

IPT TECH. BRANCH HEAD

PROJECT MANAGER

A/E INFO

APPROVED

/2

/2

:0

:5

P M

C U s e rs \z a b a lo s \D o c u m e n ts \2

R

M

C

E N

ID

S b im m e c h

.r v t

M-601

S C

H E

D U

LE

S

AEBSWL ZMA

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

SEAL

2850 EISENHOWER AVENUE

SUITE 200

ALEXANDRIA, VA 22314

PRE-FINAL

100% DESIGN

SUBMITTAL

06 / 03 / 20

HUMIDIFIER SCHEDULE

UNIT NUMBER H-1 H-2 H-3

UNIT TYPE

ELECTRIC STEAM

WITH DUCT

MOUNTED

JACKETED TUBES

ELECTRIC STEAM

WITH BLOWER

PACK

ELECTRIC STEAM

WITH BLOWER

PACK

ASSOCIATED EQUIPMENT DH-1 - - - -

NOMINAL CAPACITY (LB/H) 20 10 10

RATED CAPACITY (LB/H) 22 11 11

FILL RATE (GPM) 0.2 0.2 0.2

DRAIN RATE (GPM) 1.60 1.60 1.60

TYPE ELECTRODE ELECTRODE ELECTRODE

MAXIMUM WATER PRESSURE

(PSIG)

80 80 80

MINIMUM WATER PRESSURE

(PSIG)

30 30 30

DRAIN WATER OD (IN) 1.18 1.18 1.18

E L E

C T

R

IC

A L

VOLTS (V) 480 277 277

PHASE 3 1 1

HERTZ 60 60 60

RATED POWER (KW) 7.5 3.9 3.9

MCA (A) 9.0 14.0 14.0

MOCP (A) 15 20 20

REMARKS 1, 3, 4, & 5 2, 3, 4, & 5 2, 3, 4, & 5

REMARKS LEGEND:

1. PROVIDE DUCT-MOUNTED STEAM DISTRIBUTOR IN 26"x20" OVAL SUPPLY DUCTWORK

WHERE SHOWN ON PLANS. ABSORPTION DISTANCE SHALL BE NO MORE THAN 1-FT.

2. PROVIDE UNIT MOUNTED BLOWER PACK FOR ROOM DIRECT HUMIDIFICATION.

3. PROVIDE WALL MOUNTING BRACKET.

4. PROVIDE DRAIN COOLER TO LIMIT DRAIN WATER TO 135 F BEFORE IT IS DISCHARGED TO

THE DRAIN.

5. PROVIDE BACNET COMMUNICATION TIE-IN.

FAN SCHEDULE

DESIGNATION EF-1 EF-2 EF-3

USAGE EXHAUST EXHAUST EXHAUST

SERVES ROOM(S)

MEN, WOMEN,

JAN

MECH ELEC

DESCRIPTION INLINE INLINE INLINE

FAN DATA - - - - - -

AIRFLOW (SCFM) 350 500 800

TOTAL SP (IN-H2O) 0.25 0.25 0.25

RPM 1,517 1,452 1,659

DRIVE TYPE DIRECT DIRECT DIRECT

MOTOR DATA - - - - - -

HORSEPOWER 1/10 1/10 1/6

RPM 1,725 1,725 1,725

VOLTS 115 115 115

PHASE 1 1 1

HERTZ 60 60 60

MAXIMUM dBA AT 5 FEET 50 52 56

REMARKS 1 & 2 1 & 2 1 & 2

REMARKS LEGEND:

1. PROVIDE FAN WITH UNIT MOUNTED DISCONNECT.

2. PROVIDE ELECTRONICALLY COMMUTATED MOTOR FOR BALANCING.

SINGLE ZONE VARIABLE AIR VOLUME UNIT

SCHEDULE

DESIGNATION SZVAV-1 SZVAV-2

AREA SERVED

134 - LAB

(SECRET)

135 - LAB (TOP

SECRET)

LOCATION

OUTSIDE ON

GRADE

OUTSIDE ON

GRADE

S U

P P

L Y

F A

N

SUPPLY FAN AIRFLOW (CFM) 3,800 3,800

MINIMUM SUPPLY…