Plans 26230.pdf
PDF 7 MB Posted
- Solicitation number
- RFQ 171 260000000378 1
- Issued by
- Michigan
About this file
This is a construction plan document prepared by the State of Michigan Department of Technology, Management and Budget for the Department of Corrections at Macomb Correctional Facility (MAC) in New Haven, Michigan. The project involves a Level IV Conversion of Housing Units 4 and 5 (HU-4 and HU-5), with file number 472/26230.MNB and Matrix Project Number 260482.00. The scope of work includes architectural, mechanical, and electrical modifications to convert the facility to a higher security level. Key construction elements include the installation of new security surround walls with stainless steel posts and frames, new steel security doors with electromechanical locks, new stainless steel door frames with wire mesh, modification of existing fin tube heating enclosures, relocation of exhaust grilles, installation of new exit signage, door position monitoring systems, and fire protection modifications. The work requires coordination across multiple trades including general contracting, mechanical, electrical, and fire protection services. Contractors must comply with the 2023 Michigan Electrical Code, Michigan Mechanical Code, and NFPA standards, with particular attention to tamper-proof security requirements appropriate for a correctional facility. The plans specify that all electrical outages shall not exceed two hours, with portable generator backup required for longer shutdowns coordinated at least two weeks in advance.
The project requires adherence to strict facility security protocols and MDOC standards, including the use of security screws and tamper-resistant hardware in all inmate-accessible areas. Contractors must conduct a pre-bid site walk-through to verify existing conditions before bidding, as drawings are based on existing record documents and casual field observation with discrepancies to be reported to the engineer. The specifications include detailed requirements for door hardware, hinges, closers, thresholds, gaskets, and glazing, with specific manufacturer preferences noted (such as Hager, Pemko, and Willoughby for hardware components). All demolition work must be approved by the owner/tenant prior to commencement, and contractors are responsible for removing obsolete exposed conduit and equipment not scheduled for reuse. The project requires updated panel schedules for all affected electrical panels, arc flash labels for new panelboards, and new printed circuit directories. Post-construction meetings are mandated at six-month and eleven-month intervals during the warranty period to review and address any identified issues.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| LEIN Request 26230.pdf | ||
| Advertisement 26230.pdf | ||
| Service Disabled Veteran Owned Business Info Sheet 2025.pdf | ||
| MichSpec 26230.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
34625 26 MILE RD,
NEW HAVEN, MI 48048
FILE NUMBER: 472/26230.MNB
MATRIX PROJECT NUMBER: 260482.00MECHANICAL/ELECTRICAL ENGINEER
STATE OF MICHIGAN
DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET
FOR DEPARTMENT OF CORRECTIONS
MACOMB CORRECTIONAL FACILITY (MAC) - HU 4 & 5 LEVEL IV CONVERSION
N SITE MAP
DRAWING INDEX
HU-4
HU-5
A-000
TITLE SHEET
NJB
JFS
file no.
checked by drawn by consultant issue date funding code contract order no.
consultant job no.
260482.00
M a t r ix
472/26230.MNB
07/02/2026 BID SET
sheet description
D
EP
A R
TM
EN
T O
F
TE
C H
N O
LO
G
Y , M
A N
A G
EM
EN
T A
N D
B U
D G
ET
ST
A
TE
O F
M
IC
H
IG
A N
A D
A M
P . L
A C
H , R
A , D
IR
EC
TO
R
ST
A
TE
F
A C
IL
IT
IE
S
A D
M
IN
IS
TR
A
TI
O N
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
M a t r ix
A-101
CLARKSTON, MI
7300 DIXIE HWY.
PHONE
FAX
PHONE
248.605.2030 248.605.2030
48346 #600
WEB DSARCHITECTS.COM
ARCHITECTS
ST
A
TE
O
F M
IC
H
IG
A
N D
EP
A
R
TM
EN
T
O F
TE
C
H N
O
LO
G Y
, M A
N A
G
EM
EN
T
A N
D B
U D
G
ET
A D
A M
P . L
A C
H , R
A , D
IR
EC
TO
R
ST
A
TE
F
A C
IL
IT
IE
S
A D
M
IN
IS
TR
A
TI
O N
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
AutoCAD SHX Text %%uFLOOR PLAN
AutoCAD SHX Text 1/2" = 1'-0"
AutoCAD SHX Text
HOUSING UNIT 4&5 - ACTIVITY ROOM
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
%%UDEMOLITION PLAN
AutoCAD SHX Text 1/2" = 1'-0"
AutoCAD SHX Text
HOUSING UNIT 4&5 - SHOWER A
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
HOUSING UNIT 4&5 - SHOWER B
AutoCAD SHX Text
DEMOLITION NOTES
AutoCAD SHX Text
AutoCAD SHX Text
DEMOLITION NOTES
AutoCAD SHX Text
CONSTRUCTION NOTES
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text REMOVE AND DISPOSE OF A PORTION OF EXISTING BRICK VENEER, CMU BLOCK WALL AND INSULATION FOR FUTURE DOOR AND LINTELS. PROVIDE NEW TEMPORARY SHORING AS REQUIRED.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
REFER TO MECHANICAL DRAWINGS FOR HEATER WORK.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text REMOVE AND RELOCATE WALL MOUNTED BULLETIN CASES, VERIFY WITH OWNER EXACT LOCATIONS OF REINSTALL.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text REMOVE AND DISPOSE OF INDICATED EXISTING STAINLESS STEEL TABLE FOR HOUSING UNIT #4 ONLY.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text PROVIDE NEW 8" SINGLE COURSE MASONRY LINTEL WITH (2) #5 BARS ABOVE DOOR OPENING AND 8" BEARING EACH END. GROUT CORES SOLID BELOW BEARING EACH END. PROVIDE NEW L4" X 4" X 3/8" STEEL ANGLE BRICK LINTEL ABOVE DOOR OPENING.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text PROVIDE NEW BRICK WEEPS HOLES TO MATCH EXISTING ABOVE DOOR OPENING WITH NEW METAL FLASHING AND DRAINAGE MATERIAL ABOVE DOOR OPENING.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text PROVIDE NEW 8" BULLNOSE CMU END BLOCKS AND TOOTH INTO EXISTING. PROVIDE NEW PAINT FINISH TO MATCH EXISTING ON NEW CMU AS RESULT OF NEW DOOR INSTALLATION.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
401 - HU#4
AutoCAD SHX Text PROVIDE NEW VCT FLOORING FINISH TO MATCH EXISTING IN DOOR OPENING AS RESULT OF DEMOLITION AND NEW DOOR INSTALLATION.
AutoCAD SHX Text file no.
AutoCAD SHX Text checked by
AutoCAD SHX Text drawn by
AutoCAD SHX Text consultant
AutoCAD SHX Text issue date
AutoCAD SHX Text index no.
AutoCAD SHX Text contract order no.
AutoCAD SHX Text consultant job no.
AutoCAD SHX Text 24233.00
AutoCAD SHX Text sheet title
AutoCAD SHX Text
CONSULTING ENGINEERS, INC
AutoCAD SHX Text
FAX: 517.487.2544
AutoCAD SHX Text
PHONE: 517.487.2511
AutoCAD SHX Text
LANSING, MI 48917
AutoCAD SHX Text
544 CHERBOURG DRIVE
AutoCAD SHX Text
MATRIX PROJECT:
AutoCAD SHX Text WEB: www.matrixceinc.com
AutoCAD SHX Text
MACOMB CORRECTIONAL FACILITY
AutoCAD SHX Text
NEW HAVEN, MICHIGAN
AutoCAD SHX Text 24233.00
AutoCAD SHX Text
472/24052.JGH
AutoCAD SHX Text
SHEET NUMBER
AutoCAD SHX Text
STATEWIDE PERIMETER
AutoCAD SHX Text
REPAIR/ REPLACEMENT
AutoCAD SHX Text
KJM
AutoCAD SHX Text
DJS
AutoCAD SHX Text
HOUSING UNIT #4 PLANS
AutoCAD SHX Text
AutoCAD SHX Text A-501
AutoCAD SHX Text
501 - HU#5
AutoCAD SHX Text %%uFLOOR PLAN
AutoCAD SHX Text 1/2" = 1'-0"
AutoCAD SHX Text
HOUSING UNIT 4&5 - SHOWER A
AutoCAD SHX Text
NORTH
AutoCAD SHX Text %%uFLOOR PLAN
AutoCAD SHX Text 1/2" = 1'-0"
AutoCAD SHX Text
HOUSING UNIT 4&5 - SHOWER B
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
CONSTRUCTION NOTES
AutoCAD SHX Text
AutoCAD SHX Text
CONSTRUCTION NOTES
AutoCAD SHX Text PROVIDE AND INSTALL NEW SECURITY SURROUND WALL, STEEL POSTS, METAL DOOR FRAME, CUFF SLOTS AND SLAM LOCKS AS REQUIRED. REFER TO DETAILS NO. 2 AND NO. 3 ON SHEET A-501 FOR MORE INFORMATION.
AutoCAD SHX Text
AutoCAD SHX Text PROVIDE NEW METAL DIVIDER FRAME. SEE DETAIL NO. 4 ON SHEET A-501 FOR MORE INFORMATION.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A-501
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A-501
AutoCAD SHX Text A-501
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A-501
AutoCAD SHX Text
%%UTYP.
AutoCAD SHX Text
%%UBELOW
AutoCAD SHX Text
AutoCAD SHX Text A-501
AutoCAD SHX Text
%%UTYP.
AutoCAD SHX Text
%%UABOVE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A-501
AutoCAD SHX Text
%%UBELOW
AutoCAD SHX Text
AutoCAD SHX Text A-501
AutoCAD SHX Text
%%UABOVE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
%%UREFLECTED CEILING PLAN
AutoCAD SHX Text 1/2" = 1'-0"
AutoCAD SHX Text
HOUSING UNIT 4&5 - SHOWER A
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
HOUSING UNIT 4&5 - SHOWER B
AutoCAD SHX Text
AutoCAD SHX Text
REFLECTED CEILING NOTES
AutoCAD SHX Text
REFLECTED CEILING NOTES
AutoCAD SHX Text
%%UDEMOLITION PLAN
AutoCAD SHX Text 1/2" = 1'-0"
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
%%UREFLECTED CEILING PLAN
AutoCAD SHX Text 1/2" = 1'-0"
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text SHADED AREA INDICATES TO REMOVE AND DISPOSE OF EXISTING PORTION OF GYPSUM BOARD CEILING TO ALLOW INSTALLATION OF NEW STEEL POSTS TO BOTTOM OF EXISTING CONCRETE DECK ABOVE.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text REMOVE AND DISPOSE OF DAMAGED WALL TILES AFTER SECURITY DOOR AND FRAME BRACKET REMOVAL, APPROX. (6) BRACKETS PER SHOWER.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text REMOVE AND SALVAGE OF EXISTING EXHAUST GRILLE AND TEMPORARY MOVE EXHAUST VENTING AS NEEDED FOR CLEARANCE TO INSTALL STEEL POSTS.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EXISTING TILED CURVED SHOWER TRANSITION FLOOR TO REMAIN.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EXISTING FLOOR DRAINS TO REMAIN, TYP.
AutoCAD SHX Text
AutoCAD SHX Text
EXISTING WALL MOUNTED HVAC HEATER TO REMAIN.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text NEW 3" X 3" X 3/16" STAINLESS STEEL POST. REFER TO DETAIL NO. 5 AND NO. 6 ON SHEET A-501 FOR POST BASE CONNECTION AND POST CAP CONNECTION, TYP.
AutoCAD SHX Text
AutoCAD SHX Text NEW 6" X 3" X 3/16" STAINLESS STEEL POST. REFER TO DETAIL NO. 7 AND NO. 8 ON SHEET A-501 FOR POST BASE CONNECTION AND POST CAP CONNECTION, TYP.
AutoCAD SHX Text PROVIDE NEW CONCRETE INFILL AT EXISTING BRICK LEDGE, TOP OF NEW CONCRETE INFILL TO ALIGN WITH TOP OF ADJACENT CONCRETE SLAB AND PROVIDE A PROPER AND PLUM SURFACE FOR NEW DOOR THRESHOLD.
AutoCAD SHX Text SHADED AREA INDICATES TO PROVIDE NEW MOLD RESISTANT GYPSUM BOARD CEILING TO MATCH EXISTING THICKNESS AS RESULT OF DEMOLITION OF EXISTING TO INSTALL POST, TYP.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
REINSTALL EXHAUST GRILLE AND REATTACH EXISTING EXHAUST VENTILATION.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EXISTING LIGHT FIXTURE TO REMAIN.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EXISTING SPRINKLER HEAD TO REMAIN.
AutoCAD SHX Text
AutoCAD SHX Text
EXISTING CEILING ACCESS HATCH TO REMAIN.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
PROVIDE NEW TAMPER RESISTANT CAULK AROUND PERIMETER OF POST.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text REMOVE AND DISPOSE OF EXISTING STEEL SECURITY DOOR, FRAME AND HARDWARE IN HOUSING UNIT #5 ONLY, NO SECURITY DOORS IN HOUSING UNIT #4.
AutoCAD SHX Text
AutoCAD SHX Text SHADED AREA INDICATES TO REMOVE AND DISPOSE OF EXISTING PORTION OF GYPSUM BOARD CEILING TO ALLOW INSTALLATION OF NEW STEEL POSTS TO BOTTOM OF EXISTING CONCRETE DECK ABOVE.
AutoCAD SHX Text
AutoCAD SHX Text REMOVE AND DISPOSE OF DAMAGED WALL TILES AFTER SECURITY DOOR AND FRAME BRACKET REMOVAL, APPROX. (6) BRACKETS PER SHOWER.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text REMOVE AND SALVAGE OF EXISTING EXHAUST GRILLE AND TEMPORARY MOVE EXHAUST VENTING AS NEEDED FOR CLEARANCE TO INSTALL STEEL POSTS.
AutoCAD SHX Text
AutoCAD SHX Text
EXISTING TILED CURVED SHOWER TRANSITION FLOOR TO REMAIN.
AutoCAD SHX Text
AutoCAD SHX Text
EXISTING FLOOR DRAINS TO REMAIN, TYP.
AutoCAD SHX Text
AutoCAD SHX Text
EXISTING WALL MOUNTED HVAC HEATER TO REMAIN.
AutoCAD SHX Text
EXISTING CLOTHES HOOKS TO REMAIN, TYP.
AutoCAD SHX Text REMOVE AND DISPOSE OF EXISTING STEEL SECURITY DOOR, FRAME AND HARDWARE IN HOUSING UNIT #5 ONLY, NO SECURITY DOORS IN HOUSING UNIT #4.
AutoCAD SHX Text
AutoCAD SHX Text INSTALL FACILITY PROVIDED WALL TILE TO MATCH EXISTING AS RESULT OF HOLES FROM THE SECURITY DOORS BRACKETS IN HOUSING UNIT #5 ONLY. PROVIDE NEW GROUT TO MATCH EXISTING.
AutoCAD SHX Text
REMOVE AND DISPOSE OF INDICATED CLOTHES HOOKS ONLY.
AutoCAD SHX Text
AutoCAD SHX Text PROVIDE AND INSTALL NEW SECURITY SURROUND WALL, STEEL POSTS, METAL DOOR FRAME, CUFF SLOTS AND SLAM LOCKS AS REQUIRED. REFER TO DETAILS NO. 2 AND NO. 3 ON SHEET A-501 FOR MORE INFORMATION.
AutoCAD SHX Text
AutoCAD SHX Text PROVIDE NEW METAL DIVIDER FRAME. SEE DETAIL NO. 4 ON SHEET A-501 FOR MORE INFORMATION.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A-501
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A-501
AutoCAD SHX Text A-501
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A-501
AutoCAD SHX Text
%%UTYP.
AutoCAD SHX Text
%%UBELOW
AutoCAD SHX Text
AutoCAD SHX Text A-501
AutoCAD SHX Text
%%UTYP.
AutoCAD SHX Text
%%UABOVE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A-501
AutoCAD SHX Text
%%UBELOW
AutoCAD SHX Text
AutoCAD SHX Text A-501
AutoCAD SHX Text
%%UABOVE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text NEW 3" X 3" X 3/16" STAINLESS STEEL POST. REFER TO DETAIL NO. 5 AND NO. 6 ON SHEET A-501 FOR POST BASE CONNECTION AND POST CAP CONNECTION, TYP.
AutoCAD SHX Text
AutoCAD SHX Text NEW 6" X 3" X 3/16" STAINLESS STEEL POST. REFER TO DETAIL NO. 7 AND NO. 8 ON SHEET A-501 FOR POST BASE CONNECTION AND POST CAP CONNECTION, TYP.
AutoCAD SHX Text
AutoCAD SHX Text
PROVIDE NEW TAMPER RESISTANT CAULK AROUND PERIMETER OF POST.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text SHADED AREA INDICATES TO PROVIDE NEW MOLD RESISTANT GYPSUM BOARD CEILING TO MATCH EXISTING THICKNESS AS RESULT OF DEMOLITION OF EXISTING TO INSTALL POST, TYP.
AutoCAD SHX Text
AutoCAD SHX Text
REINSTALL EXHAUST GRILLE AND REATTACH EXISTING EXHAUST VENTILATION.
AutoCAD SHX Text
AutoCAD SHX Text
EXISTING LIGHT FIXTURE TO REMAIN.
AutoCAD SHX Text
AutoCAD SHX Text
EXISTING SPRINKLER HEAD TO REMAIN.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text PROVIDE NEW PAINT FINISH TO MATCH EXISTING ACROSS THE ENTIRE CEILING IN SHOWER A.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text PROVIDE NEW PAINT FINISH TO MATCH EXISTING ACROSS THE ENTIRE CEILING IN SHOWER B.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
INDICATED EXISTING CLOTHES HOOKS TO REMAIN.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text EXISTING METAL PLATE TO REMAIN IN HOUSING UNIT #5B AND IS ONLY LOCATED IN HOUSING UNIT #5B.
AutoCAD SHX Text
AutoCAD SHX Text P
AutoCAD SHX Text L
AutoCAD SHX Text U
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text B
AutoCAD SHX Text U
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text U
AutoCAD SHX Text N
AutoCAD SHX Text U
AutoCAD SHX Text M
AutoCAD SHX Text C
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text U
AutoCAD SHX Text M
AutoCAD SHX Text S
AutoCAD SHX Text P
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text Q
AutoCAD SHX Text U
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text P
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text U
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text INSTALL FACILITY PROVIDED WALL TILE TO MATCH EXISTING AS RESULT OF HOLES FROM THE SECURITY DOORS BRACKETS IN HOUSING UNIT #5 ONLY. PROVIDE NEW GROUT TO MATCH EXISTING.
AutoCAD SHX Text
BID 7-2-267-2-26
AutoCAD SHX Text
AutoCAD SHX Text
DOOR CONTROL SHALL BE TIED INTO LOCAL CONTROL CENTER IN HOUSING UNIT 4 OR 5.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text NEW DOOR POSITION ALARM SENSOR SHALL BE TIED INTO LOCAL CONTROL CENTER IN HOUSING UNIT 4 OR 5 AND BACK TO CONTROL CENTER IN ADMINISTRATION BUILDING.
AutoCAD SHX Text
M a t r ix
ST
A
TE
O
F M
IC
H
IG
A
N
A-501
CLARKSTON, MI
7300 DIXIE HWY.
PHONE
FAX
PHONE
248.605.2030 248.605.2030
48346 #600
WEB DSARCHITECTS.COM
ARCHITECTS
D
EP
A R
TM
EN
T O
F
TE
C H
N O
LO
G
Y , M
A N
A G
EM
EN
T A
N D
B U
D G
ET
A D
A M
P . L
A C
H , R
A , D
IR
EC
TO
R
ST
A
TE
F
A C
IL
IT
IE
S
A D
M
IN
IS
TR
A
TI
O N
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
AutoCAD SHX Text C1
AutoCAD SHX Text PARALLEL CLOSER - PUSH SIDE - NO HOLD OPEN PROVIDE NEW 'LCN' CLOSER #4210 SERIES. PARALLEL (PUSH SIDE) MOUNTING. FINISH 689 ALUMINUM. PROVIDE 4210-3077EDA, EXTRA HEAVY DUTY ARM.
AutoCAD SHX Text H1
AutoCAD SHX Text BALL BEARING- NON REMOVABLE PIN PROVIDE NEW HINGES, 2 PAIR PER LEAF, 4 1/2" X 4 1/2", WITH BALL BALL BALL BEARINGS, NON-REMOVABLE PIN, BB1199 BY 'HAGER' OR EQUAL. FINISH US32D.
AutoCAD SHX Text F1
AutoCAD SHX Text ALUM THRESHOLD PROVIDE NEW HEAVY DUTY LATCHING PANIC EXIT SADDLE THRESHOLD BY 'PEMKO' 1700 SERIES OR EQUAL. FINISH 'A'. VERIFY IN FIELD EXACT WIDTH, LENGTH AND MATCH DEPTH OF FRAME.
AutoCAD SHX Text
GS1
AutoCAD SHX Text WEATHERSTRIP THERMAL SEAL - NOT FIRE RATED PROVIDE NEW FIRE RATED ADHESIVE GASKETING FOR FIRE AND SMOKE BY 'PEMKO' MODEL #PK33_ OR EQUAL. FINISH 'BL' BLACK.
AutoCAD SHX Text
DOOR
AutoCAD SHX Text
HINGES
AutoCAD SHX Text
CLOSERS
AutoCAD SHX Text
THRESHOLD
AutoCAD SHX Text
GASKETS AND SEALS
AutoCAD SHX Text
DOOR SCHEDULE
AutoCAD SHX Text
AutoCAD SHX Text
DOOR
AutoCAD SHX Text
NO.
AutoCAD SHX Text
OPEN. SIZE
AutoCAD SHX Text
DOOR
AutoCAD SHX Text
TYPE
AutoCAD SHX Text
DOOR
AutoCAD SHX Text
TYPE
AutoCAD SHX Text
FRAME
AutoCAD SHX Text
CLOSER
AutoCAD SHX Text
FRAME
AutoCAD SHX Text
LATCH
AutoCAD SHX Text
HINGES
AutoCAD SHX Text G1.
AutoCAD SHX Text ALL DOOR SIZE DIMENSIONS GIVEN ARE APPROXIMATE. DOOR SUPPLIER SHALL FIELD VERIFY EXACT REQUIREMENTS.
AutoCAD SHX Text
FRAME
AutoCAD SHX Text T1
AutoCAD SHX Text
THRESHOLD
AutoCAD SHX Text
GASKETS
AutoCAD SHX Text
GENERAL NOTES
AutoCAD SHX Text
GLAZING
AutoCAD SHX Text
GL1.
AutoCAD SHX Text EXTERIOR - INSIDE SECURED AREA - 1 1/4" PATRIOT ARMOR LOW-E INSULATED GLAZING WITH U-VALUE OF 0.25 (R-4).
AutoCAD SHX Text
GLAZING
AutoCAD SHX Text D1
AutoCAD SHX Text F1
AutoCAD SHX Text
LS1
AutoCAD SHX Text H1
AutoCAD SHX Text STEEL FRAME - 10 GA PROVIDE NEW 'AMERICAN STEEL PRODUCTS' DOOR FRAME. FRAME TO BE AN, 10 GAUGE GALVANNEALED DOUBLE RABBET WITH WELDED CORNERS. PROVIDE FRAME BACK COATING AND GROUT FRAME SOLID. PRIME FINISH. FIELD PAINT TO MATCH EXISTING. PROVIDE 4" HEADER AND 2" JAMBS.
AutoCAD SHX Text C1
AutoCAD SHX Text T1
AutoCAD SHX Text
GS1
AutoCAD SHX Text
LS1
AutoCAD SHX Text
LOCKSET
AutoCAD SHX Text 3'-0" X 7'-0"
AutoCAD SHX Text
STEEL
AutoCAD SHX Text
STEEL
AutoCAD SHX Text
GL1
AutoCAD SHX Text
AutoCAD SHX Text D1
AutoCAD SHX Text F1
AutoCAD SHX Text
LS1
AutoCAD SHX Text H1
AutoCAD SHX Text C1
AutoCAD SHX Text T1
AutoCAD SHX Text
GS1
AutoCAD SHX Text 3'-0" X 7'-0"
AutoCAD SHX Text
STEEL
AutoCAD SHX Text
STEEL
AutoCAD SHX Text
GL1
AutoCAD SHX Text STEEL - INSULATED - HALF LITE PROVIDE NEW 'CECO' RESTRICTDOR SERIES STEEL STIFFENED DOOR WITH FIBERGLASS INSULATION. EXTERIOR TO BE 14 GAUGE GALVANNEALED STEEL WITH SEAMLESS WELDED EDGE CONSTRUCTION LEVEL 4. PROVIDE LOW PROFILE LITE KIT L-FRA100-SP GALVANNEAL - A40 STEEL BY 'NATIONAL GUARD PRODUCTS, INC.' LITE TO BE 2'-11 1/2"H X 2'-0 1/2"W CENTERED IN DOOR ABOVE EXIT DEVICE. PROVIDE TORX SECURITY SCREWS. PRIME FINISH. FIELD PAINT TO MATCH EXISTING.
AutoCAD SHX Text D1
AutoCAD SHX Text ELECTRICAL - DEADLATCH - KEYED BOTH SIDES PROVIDE NEW ELECTROMECHANICAL LOCK BY 'WILLOUGHBY LOCKING SYSTEMS' WLS-1300, MOTORIZED, DEADLOCKING, LATCH, WITH KEY CYLINDER, SOLENOID, KEYED BOTH SIDES. STAINLESS STEEL FINISH. DOOR CONTROL SHALL BE TIED INTO LOCAL CONTROL CENTER IN HOUSING UNIT 4 OR 5.
AutoCAD SHX Text
HA1
AutoCAD SHX Text HORIZONTAL TUBE PULL PROVIDE NEW STAINLESS STEEL HORIZONTAL TUBE PULL BY 'HAGER' MODEL #136S OR EQUAL. 1-1/4" PULL DIAMETER. FINISH US32D.
AutoCAD SHX Text
HA2
AutoCAD SHX Text VERTICAL TUBE PULL PROVIDE NEW 18" STAINLESS STEEL VERTICAL TUBE PULL BY 'HAGER' MODEL #10 OR EQUAL. 1-1/4" PULL DIAMETER. FINISH US32D.
AutoCAD SHX Text
HANDLES
AutoCAD SHX Text
HANDLES
AutoCAD SHX Text
HA1,2
AutoCAD SHX Text
HA1,2
AutoCAD SHX Text PROTECTION PLATE - 33" - 36" +/- PROVIDE NEW STAINLESS STEEL HEAVY DUTY KICK PLATE BY 'ROCKWOOD' MODEL #K1062 OR EQUAL. 0.0.62 THICKNESS. FINISH US32D. FASTEN WITH 'TORX' SECURITY TORX SCREWS. PLATE TO BE 33" TO 36" HIGH X 33" TO 36" WIDE.
AutoCAD SHX Text
KICK PLATE
AutoCAD SHX Text K1
AutoCAD SHX Text
KICK PLATE
AutoCAD SHX Text K1
AutoCAD SHX Text K1
AutoCAD SHX Text A-101
AutoCAD SHX Text
AutoCAD SHX Text 3/4" = 1'-0"
AutoCAD SHX Text
WALL SECTION AT DOOR OPENING
AutoCAD SHX Text
EXISTING CONCRETE FOOTING TO REMAIN
AutoCAD SHX Text
TOP OF NEW CONCRETE INFILL AND EXISTING SLAB ON GRADE
AutoCAD SHX Text 100'-0"
AutoCAD SHX Text
TOP OF NEW DOOR ROUGH OPENING
AutoCAD SHX Text 107'-4"
AutoCAD SHX Text
NEW STEEL DOOR AND STEEL DOOR FRAME, REFER TO DOOR SCHEDULE FOR MORE INFORMATION
AutoCAD SHX Text NEW SINGLE COURSE 8" MASONRY LINTEL WITH (2) #5 BARS WITH 8" BEARING ON EACH END AND GROUT SOLID CORES BELOW BEARING ENDS
AutoCAD SHX Text
NEW 4" X 4" X 3/8" L STEEL ANGLE BRICK LINTEL
AutoCAD SHX Text
NEW METAL FLASHING WITH DRAINAGE MATERIAL
AutoCAD SHX Text
NEW WEEPS TO MATCH EXISTING
AutoCAD SHX Text NEW PAINT FINISH TO MATCH EXISTING ON EXISTING CMU AS RESULT OF NEW DOOR INSTALLATION
AutoCAD SHX Text
NEW VCT FLOORING FINISH TO MATCH EXISTING AS RESULT OF NEW DOOR INSTALLATION
AutoCAD SHX Text NEW CONCRETE INFILL AT EXISTING BRICK LEDGE, ALIGN NEW INFILL WITH TOP OF ADJACENT EXISTING SLAB ON GRADE
AutoCAD SHX Text
EXISTING SLAB ON GRADE
AutoCAD SHX Text file no.
AutoCAD SHX Text checked by
AutoCAD SHX Text drawn by
AutoCAD SHX Text consultant
AutoCAD SHX Text issue date
AutoCAD SHX Text index no.
AutoCAD SHX Text contract order no.
AutoCAD SHX Text consultant job no.
AutoCAD SHX Text 24233.00
AutoCAD SHX Text sheet title
AutoCAD SHX Text
CONSULTING ENGINEERS, INC
AutoCAD SHX Text
FAX: 517.487.2544
AutoCAD SHX Text
PHONE: 517.487.2511
AutoCAD SHX Text
LANSING, MI 48917
AutoCAD SHX Text
544 CHERBOURG DRIVE
AutoCAD SHX Text
MATRIX PROJECT:
AutoCAD SHX Text WEB: www.matrixceinc.com
AutoCAD SHX Text
MACOMB CORRECTIONAL FACILITY
AutoCAD SHX Text
NEW HAVEN, MICHIGAN
AutoCAD SHX Text 24233.00
AutoCAD SHX Text
472/24052.JGH
AutoCAD SHX Text
SHEET NUMBER
AutoCAD SHX Text
STATEWIDE PERIMETER
AutoCAD SHX Text
REPAIR/ REPLACEMENT
AutoCAD SHX Text
KJM
AutoCAD SHX Text
DJS
AutoCAD SHX Text
DETAILS
AutoCAD SHX Text A-101
AutoCAD SHX Text
AutoCAD SHX Text 3/4" = 1'-0"
AutoCAD SHX Text
DOOR ELEVATION
AutoCAD SHX Text A-101
AutoCAD SHX Text
AutoCAD SHX Text 1 1/2" = 1'-0"
AutoCAD SHX Text
DOOR SECTION
AutoCAD SHX Text A-101
AutoCAD SHX Text
AutoCAD SHX Text 3/4" = 1'-0"
AutoCAD SHX Text
DIVIDER ELEVATION
AutoCAD SHX Text A-101
AutoCAD SHX Text
AutoCAD SHX Text 3" = 1'-0"
AutoCAD SHX Text
3" POST BASE CONNECTION
AutoCAD SHX Text A-101
AutoCAD SHX Text
AutoCAD SHX Text 3" = 1'-0"
AutoCAD SHX Text
3" POST CAP CONNECTION
AutoCAD SHX Text
AutoCAD SHX Text A-501
AutoCAD SHX Text
AutoCAD SHX Text A-501
AutoCAD SHX Text
AutoCAD SHX Text A-501
AutoCAD SHX Text
AutoCAD SHX Text A-501
AutoCAD SHX Text
AutoCAD SHX Text A-501
AutoCAD SHX Text
%%USIM.
AutoCAD SHX Text
%%USIM.
AutoCAD SHX Text
AutoCAD SHX Text A-501
AutoCAD SHX Text
AutoCAD SHX Text A-501
AutoCAD SHX Text
EXISTING TILE FLOOR
AutoCAD SHX Text NEW 3"X3"X3/16" STAINLESS STEEL POST WITH 3/4"X5/8" CONT. STAINLESS STEEL DOOR STOP ALONG PERIMETER OF DOOR OPENING ONLY
AutoCAD SHX Text NEW 2"X2"X3/16" STAINLESS STEEL DOOR FRAME WELDED TOGETHER WITH 2"X2"X1/4" STAINLESS STEEL WIRE MESH WITH WOVEN LOCK CRIMP WEAVE, NEW DOOR IS 2'-8" X 6'-6" OVERALL. NEW HINGES, 2 PAIR PER LEAF, 4 1/2" X 4 1/2", WITH NEW HINGES, 2 PAIR PER LEAF, 4 1/2" X 4 1/2", WITH BALL BEARINGS, NON-REMOVABLE PIN, BB1199 BY 'HAGER' OR EQUAL. FINISH US32D. PROVIDE 15"X4 1/2" CUFF SLOT IN DOOR. PROVIDE NEW SURFACE MOUNTED SLAM LOCK AND SURFACE MOUNTED STRIKE BY 'WILLOUGHBY' OR EQUAL. INSURE THAT MECHANISM HAS LOCKING LATCH POSITION IN A WAY TO CLOSE SHUT BY SLAMMING. PROVIDE 4"X2"X3/16" STAINLESS STEEL FRAME FOR SLAM LOCK TO MOUNT TO AND SUPPORT CUFF SLOT FRAME.
AutoCAD SHX Text NEW 6"X3"X3/16" STAINLESS STEEL POST WITH 3/4"X5/8" CONT. STAINLESS STEEL DOOR STOP ALONG PERIMETER OF DOOR OPENING ONLY
AutoCAD SHX Text NEW 3"X3"X3/16" STAINLESS STEEL HEADER WITH 3/4"X5/8" CONT. STAINLESS STEEL DOOR STOP ALONG PERIMETER OF DOOR OPENING ONLY. FIELD WELD TO VERTICAL 3" AND 6" POST
AutoCAD SHX Text
NEW 3"X3"X3/16" STAINLESS STEEL HEADER, FIELD WELDED TO VERTICAL 3" AND 6" POST
AutoCAD SHX Text PROVIDE NEW MOLD RESISTANT GYPSUM BOARD CEILING AS DEMOLITION FOR NEW POST INSTALLATION, THICKNESS TO MATCH EXISTING, PROVIDE NEW PAINT FINISH ACROSS ENTIRE SHOWER CEILING TO MATCH EXISTING
AutoCAD SHX Text
EXISTING DECKING ABOVE
AutoCAD SHX Text EXISTING WALL TILE TO REMAIN AND INSTALL NEW WALL TILES IN HOUSING UNIT #5 AS RESULT OF DEMOLITION
AutoCAD SHX Text
EXISTING TILE FLOOR
AutoCAD SHX Text
NEW 6"X3"X3/16" STAINLESS STEEL POST AT CENTER OF SURROUND WALL
AutoCAD SHX Text
NEW 3"X3"X3/16" STAINLESS STEEL HEADER, FIELD WELD TO VERTICAL 3" AND 6" POST
AutoCAD SHX Text PROVIDE NEW MOLD RESISTANT GYPSUM BOARD CEILING AS DEMOLITION FOR NEW POST INSTALLATION, THICKNESS TO MATCH EXISTING, PROVIDE NEW PAINT FINISH TO MATCH EXISTING
AutoCAD SHX Text
EXISTING DECKING ABOVE
AutoCAD SHX Text
NEW 2"X2"X1/4" STAINLESS STEEL WIRE MESH WITH WOVEN LOCK CRIMP WEAVE, TYP.
AutoCAD SHX Text
NEW 2"X2"X1/4" STAINLESS STEEL WIRE MESH WITH WOVEN LOCK CRIMP WEAVE, TYP.
AutoCAD SHX Text
NEW 2"X2"X3/16" STAINLESS STEEL DOOR FRAME WELDED TOGETHER, TYP.
AutoCAD SHX Text
NEW 2"X2"X3/16" STAINLESS STEEL DOOR FRAME WELDED TOGETHER, TYP.
AutoCAD SHX Text
EXISTING TILE FLOOR
AutoCAD SHX Text NEW MOLD RESISTANT GYPSUM BOARD CEILING AS DEMOLITION FOR NEW POST INSTALLATION, THICKNESS TO MATCH EXISTING, PROVIDE NEW PAINT FINISH TO MATCH EXISTING
AutoCAD SHX Text
EXISTING DECKING ABOVE
AutoCAD SHX Text NEW 2"X2"X3/16"X2" LONG STAINLESS STEEL CLIP ANGLE WITH NEW 1/4" DIA. TAMPER RESISTANT THRU BOLTS, NUTS, AND WASHERS, TYP.
AutoCAD SHX Text
NEW 3"X3"X3/16" STAINLESS STEEL POST
AutoCAD SHX Text
NEW 3"X3"X3/16" STAINLESS STEEL STIFFENER, FIELD WELD TO VERTICAL 3" AND 6" POST
AutoCAD SHX Text
NEW 3"X3"X3/16" STAINLESS STEEL STIFFENER, FIELD WELD TO VERTICAL 3" AND 6" POST
AutoCAD SHX Text
NEW 3"X3"X3/16" STAINLESS STEEL STIFFENER, FIELD WELD TO VERTICAL 3" AND 6" POST
AutoCAD SHX Text
NEW 2"X2"X1/4" STAINLESS STEEL WIRE MESH WITH WOVEN LOCK CRIMP WEAVE, TYP.
AutoCAD SHX Text
NEW 6"X3"X3/16" STAINLESS STEEL POST AT CENTER OF SURROUND WALL
AutoCAD SHX Text
REFER TO DETAIL NO. 2 AND NO. 3 FOR DOOR CONSTRUCTION, TYP.
AutoCAD SHX Text
EXISTING WALL TILE TO REMAIN, TYP.
AutoCAD SHX Text
EXISTING WALL TILE TO REMAIN, TYP.
AutoCAD SHX Text
EXISTING WALL TILE TO REMAIN, TYP.
AutoCAD SHX Text NEW 2"X2"X3/16"X2" LONG STAINLESS STEEL CLIPANGLE WITH NEW 1/4" DIA. STAINLESS STEEL TAMPER RESISTANT THRU BOLTS, NUTS, AND WASHERS, TYP.
AutoCAD SHX Text
NEW 2"X2"X1/4" STAINLESS STEEL WIRE MESH WITH WOVEN LOCK CRIMP WEAVE, TYP.
AutoCAD SHX Text
NEW 2"X2"X3/16" STAINLESS STEEL DOOR FRAME WELDED TOGETHER, TYP.
AutoCAD SHX Text NEW 3/4"X5/8" CONT. STAINLESS STEEL DOOR STOP ALONG PERIMETER OF DOOR OPENING ONLY
AutoCAD SHX Text
NEW 3"X3"X3/16" STAINLESS STEEL POST
AutoCAD SHX Text NEW 2"X2"X3/16"X2" LONG STAINLESS STEEL CLIPANGLE WITH NEW 1/4" DIA. STAINLESS STEEL TAMPER RESISTANT THRU BOLTS, NUTS, AND WASHERS, TYP.
AutoCAD SHX Text
NEW 2"X2"X1/4" STAINLESS STEEL WIRE MESH WITH WOVEN LOCK CRIMP WEAVE, TYP.
AutoCAD SHX Text
NEW 3"X3"X3/16" STAINLESS STEEL POST
AutoCAD SHX Text
NEW 3"X3"X3/16" STAINLESS STEEL HEADER, FIELD WELD TO VERTICAL 3" AND 6" POST
AutoCAD SHX Text
NEW TAMPER RESISTANT CAULK ALONG PERIMETER OF POST BASE, TYP.
AutoCAD SHX Text
NEW TAMPER RESISTANT CAULK ALONG PERIMETER OF POST BASE, TYP.
AutoCAD SHX Text
NEW TAMPER RESISTANT CAULK ALONG PERIMETER OF POST BASE, TYP.
AutoCAD SHX Text
NEW 2"X2"X3/16" STAINLESS STEEL DOOR FRAME WELDED TOGETHER, TYP.
AutoCAD SHX Text
NEW 2"X2"X1/4" STAINLESS STEEL WIRE MESH WITH WOVEN LOCK CRIMP WEAVE, TYP.
AutoCAD SHX Text
NEW 2"X2"X3/16" STAINLESS STEEL DOOR FRAME WELDED TOGETHER, TYP.
AutoCAD SHX Text
NEW 2"X2"X3/16" STAINLESS STEEL DOOR FRAME WELDED TOGETHER, TYP.
AutoCAD SHX Text
NEW CUFF SLOT
AutoCAD SHX Text
NEW 6"X3"X3/16" STAINLESS STEEL POST AT CENTER OF SURROUND WALL
AutoCAD SHX Text NEW 3/4"X5/8" CONT. STAINLESS STEEL DOOR STOP ALONG PERIMETER OF DOOR OPENING ONLY
AutoCAD SHX Text NEW 3/4"X5/8" CONT. STAINLESS STEEL DOOR STOP ALONG PERIMETER OF DOOR OPENING ONLY
AutoCAD SHX Text A-101
AutoCAD SHX Text
AutoCAD SHX Text 3" = 1'-0"
AutoCAD SHX Text
6" POST BASE CONNECTION
AutoCAD SHX Text A-101
AutoCAD SHX Text
AutoCAD SHX Text 3" = 1'-0"
AutoCAD SHX Text
6" POST CAP CONNECTION
AutoCAD SHX Text NEW 2"X2"X3/16"X2" LONG STAINLESS STEEL CLIPANGLE WITH NEW 1/4" DIA. STAINLESS STEEL TAMPER RESISTANT THRU BOLTS, NUTS, AND WASHERS, TYP.
AutoCAD SHX Text
NEW 2"X2"X1/4" STAINLESS STEEL WIRE MESH WITH WOVEN LOCK CRIMP WEAVE, TYP.
AutoCAD SHX Text
NEW 2"X2"X3/16" STAINLESS STEEL DOORFRAME WELDED TOGETHER, TYP.
AutoCAD SHX Text NEW 3/4"X5/8" CONT. STAINLESS STEEL DOOR STOP ALONG PERIMETER OF DOOR OPENING ONLY
AutoCAD SHX Text
NEW 6"X3"X3/16" STAINLESS STEEL POST
AutoCAD SHX Text NEW 2"X2"X3/16"X2" LONG STAINLESS STEEL CLIP ANGLE WITH NEW 1/4" DIA. STAINLESS STEEL TAMPER RESISTANT THRU BOLTS, NUTS, AND WASHERS, TYP.
AutoCAD SHX Text
NEW TAMPER RESISTANT CAULK ALONG PERIMETER OF POST BASE, TYP.
AutoCAD SHX Text
NEW DOOR HINGE
AutoCAD SHX Text
NEW 2"X2"X1/4" STAINLESS STEEL WIRE MESH WITH WOVEN LOCK CRIMP WEAVE, TYP.
AutoCAD SHX Text
NEW 6"X3"X3/16" STAINLESS STEEL POST
AutoCAD SHX Text
NEW 3"X3"X3/16" STAINLESS STEEL HEADER, FIELD WELD TO VERTICAL 3" AND 6" POST
AutoCAD SHX Text REPLACE CUT CMU BLOCK WITH NEW 8" BULLNOSE EDGE CMU BLOCK AND TOOTH INTO EXISTING AROUND NEW ROUGH OPENING AND GROUT SOLID AS RESULT OF CMU LINTEL BEARING ABOVE, PAINT NEW BLOCK TO MATCH EXISTING
AutoCAD SHX Text
NEW 3"X3"X3/16" STAINLESS STEEL HEADER, FIELD WELD TO VERTICAL 3" AND 6" POST
AutoCAD SHX Text NEW 2"X2"X3/16"X2" LONG STAINLESS STEEL CLIP ANGLE WITH NEW 1/4" DIA. TAMPER RESISTANT THRU BOLTS, NUTS, AND WASHERS, TYP.
AutoCAD SHX Text A1.
AutoCAD SHX Text ELECT - DOOR POSITION SWITCH PROVIDE NEW DOOR POSITION INDICATOR SWITCH BY SENTRY SECURITY FASTENERS, IN. SS-701665 200MRS-TB MAGNETIC DOOR POSITION SWITCH, ADJUSTABLE WITH TRIPLE BIAS, NON-HANDED. NEW DOOR POSITION ALARM SENSOR SHALL BE TIED INTO LOCAL CONTROL CENTER HOUSING UNIT 4 OR 5 AND BACK TO CONTROL CENTER IN ADMINISTRATION BUILDING.
AutoCAD SHX Text
ALARM
AutoCAD SHX Text
ALARM
AutoCAD SHX Text A1
AutoCAD SHX Text A1
AutoCAD SHX Text N1.
AutoCAD SHX Text NEW DOOR POSITION ALARM SENSOR SHALL BE TIED INTO LOCAL CONTROL CENTER IN HOUSING UNIT 4 OR 5 AND BACK TO CONTROL CENTER IN ADMINISTRATION BUILDING.
AutoCAD SHX Text
NOTES
AutoCAD SHX Text
NOTES
AutoCAD SHX Text N1
AutoCAD SHX Text N1
AutoCAD SHX Text P
AutoCAD SHX Text L
AutoCAD SHX Text U
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text B
AutoCAD SHX Text U
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text U
AutoCAD SHX Text N
AutoCAD SHX Text U
AutoCAD SHX Text M
AutoCAD SHX Text C
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text U
AutoCAD SHX Text M
AutoCAD SHX Text S
AutoCAD SHX Text P
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text Q
AutoCAD SHX Text U
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text P
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text U
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text
BID 7-2-267-2-26
FCPS
V
M C
VI
AV
B
C
DC
M
B
KP
SSCP
CR
SS
AS
TS
G
NCC
M P
E
A L B1 B2
S
SRS
X
X
X
CB
EMERGENCY PUSH STATION
CODE BLUE STATION
TVSS
VFD
TRANSIENT VOLTAGE SURGE SUPPRESSION
VARIABLE FREQUENCY DRIVE
GLASS BREAK
DS
DUPLEX RECEPTACLE
TEACHER STATION
ADMINISTRATION STATION
STUDENT STATION
CARD READER CO CARBON MONOXIDE DETECTOR
H
DOCK LIGHT FIXTURE
CONTROL MODULE
S
TELEPHONE / DATA OUTLET
DUTY STATION
STAFF STATION
STAFF REGISTER STATION
DOME LIGHT
DUAL BED STATION
SINGLE BED STATION
BED / LIGHT INTERFACE
PENDENT INTERFACE
EMERGENCY PULL STATION
MASTER STATION
NURSE CALL CONTROLLER
NURSE CALL
ADDENDUM NOTE
PLAN NOTE
DEMOLITION NOTE
THREE PHASE MOTOR
BELL
AUDIO / VIDEO INPUT
VIDEO INPUT
WALL MOUNTED SPEAKER / CLOCK COMBO
WALL MOUNTED SPEAKERS
DUAL FACE CLOCK
CCTV CONTROL PANELCCTV
SECURITY SYSTEM CONTROL PANEL
KEY PAD
BEAM DETECTOR
MOTION DETECTOR
DOOR CONTACT
CAMERA
MONITOR MODULE
FIRE CONTROL POWER SUPPLY
VISUAL ONLY UNIT
ELECTRICAL SYMBOLS LEGEND
DH
V
S
C
M
I
J
SINGLE RECEPTACLE (120 VOLT)
EMERGENCY RECEPTACLE
DOUBLE DUPLEX RECEPTACLE
SINGLE FACE CLOCK
FLUSH FLOOR BOX
SURFACE FLOOR BOX
SPECIAL EQUIPMENT RECEPTACLE
TELEPHONE OUTLET
DATA OUTLET
POWER POLE
JUNCTION BOX
WALL JUNCTION BOX
PULL (JUNCTION) BOX
UNDERFLOOR JUNCTION BOX
OUTLETS
LIGHT FIXTURE
STRIP FIXTURE
IN-GRADE LIGHT FIXTURE
SPOTLIGHT (number of heads shown) EXIT SIGN (face & direction as shown)
WALL MOUNT LIGHT FIXTURE
CEILING LIGHT FIXTURE
TRACK & FIXTURE
STREET TYPE POLE FIXTURE
POLE MOUNTED LIGHT FIXTURE
EXTERIOR WALL MOUNT LIGHT FIXTURE
WALLPACK LIGHT FIXTURE
SPECIAL PURPOSE LIGHT FIXTURE
HIGH BAY LIGHT FIXTURE
EMERGENCY EGRESS LIGHT FIXTURE
(number of heads shown)
EMERGENCY LIGHT FIXTURE
FIXTURES
SWITCHES
SINGLE-POLE SWITCH
DIMMER SWITCH
TIME SWITCH
KEY SWITCH
MANUAL MOTOR SWITCH
THERMAL OVERLOAD SWITCH
SWITCH WITH PILOT LIGHT
FOUR-WAY SWITCH
THREE-WAY SWITCH
CIRCUITRY and RACEWAYS
UNDERFLOOR DUCT
BUS DUCT
PLUGMOLD AS SPECIFIED
WIREMOLD AS SPECIFIED
FLEXIBLE PIGTAILS/CONNECTIONS
"CONDUIT RUN CONTINUES" INDICATION
END OF CONDUIT RUN, CAP AND STAKE
END OF CONDUIT RUN
HOME RUN (with circuit numbers)
CONDUIT STUB DOWN
CONDUIT STUB UP
CONDUIT INSTALLED
CONDUIT INSTALLED
MECHANICAL
ELECTRIC WATER HEATER
ELECTRIC UNIT HEATER
PIPE TRACE HEATER
RESISTANCE HEATER, KW SHOWN
SINGLE PHASE MOTOR
SOUND and SIGNAL
INTERCOM OUTLET
MICROPHONE OUTLET
TELEVISION OUTLET
CHIME
BUZZER
VOLUME CONTROL
SPEAKER
SERVICE and EQUIPMENT
THERMOSTAT
CAPACITOR
ENCLOSED CIRCUIT BREAKER
TRANSFER SWITCH
WIREWAY
GROUND CONNECTION PER N.E.C.
TELEPHONE TERMINAL BOARD
GENERATOR, KW SHOWN
CURRENT TRANSFORMERS
UTILITY METER, AS REQUIRED
WEATHERHEAD
PANELBOARD, FLUSH MOUNTED
PANELBOARD, SURFACE MOUNTED
COMB. STARTER
MAGNETIC STARTER
FUSED DISCONNECT SWITCH
TRANSFORMER
CONTROL
xxVA connection by x/C) IRRIGATION CONTROLLER (120 volt
LIGHTING CONTACTOR
CONTROL TRANSFORMER
buttons indicated) PUSHBUTTON STATION (number of TIME CLOCK (24 hour U.O.N.)
PHOTOCELL (voltage as required)
HUMIDISTAT
FIRE ALARM
TAMPER SWITCH (furnished by FP/C) FLOW SWITCH (furnished by FP/C)
FIREFIGHTER COMMUNICATION JACK
MAGNETIC DOOR HOLDER
REMOTE INDICATING LIGHT, CLG. MTD.
REMOTE INDICATING LIGHT, WALL MTD.
END OF LINE DEVICE
ANNUNCIATOR PANEL
FIRE ALARM CONTROL PANEL
PULL STATION
SPEAKER & LIGHT
SPEAKER
HORN
DUCT SMOKE DETECTOR
HEAT DETECTOR
SMOKE DETECTOR
HORN & LIGHT
DESIGNATIONS
(by E.C.)
(by others)
TT
FACP
ANN
EOL
G
WW
PC
CT
TS
T
H
TC
IC
F
FC
F
T
1,3
OR
PM
WM
BD
UFD
B
F S
J
J
D
WH
PP
J
SWITCH STYLE OCCUPANCY SENSOROC
DIGITAL TIME SWITCH
POWER PACK
DUAL TECHNOLOGY SENSOR - 360° - 500 SQ FT
DUAL TECHNOLOGY SENSOR - 360° - 1000 SQ FT
ULTRASONIC SENSOR - 360° - 2 CIRCUIT
OCCUPANCY SENSOR / PHOTOCELL
WALL MOUNT DUAL TECHNOLOGY SENSOR
OS5
OS4
T
OS2
OS3
OS1
PP
DUCT SMOKE DETECTORF/S
CEILING MOUNTED WIFI
DIGITAL EQUIPMENT METER, AS REQUIRED
POLE
PUMP
PANEL
P
PNL
PVC
PRV-
P-
PB
POLY VINYL CLORIDE
POWER ROOF VENTILATOR
PULL BOX
GENERAL CONTRACTOR
GROUND
HUMIDIFIERH-
GND
GFI
GC
GROUND FAULT INTERRUPTER
ABBREVIATIONS LEGEND
POWER
SWITCH
RECEPT
SF-
SWBD
TCC
SPEC
SW
RGC
RTU-
PWR
VOLTS
WATTS
UF
V
W
UL
VL
UNO
UH-
TS
TYP
TR
ROOF TOP UNIT
RECEPTACLE
SWITCHBOARD
UNDER FLOOR
SPECIFICATIONS
RIGID GALVANIZED STEEL CONDUIT
UNLESS NOTED OTHERWISE
UNDERWRITERS' LABORATORIES, INC.
TAMPER PROOF RECEPTACLE
TAMPER PROOF SWITCH
TEMPERATURE CONTROL CONTRACTOR
VERIFY LOCATION WITH OWNER
TYPICAL
UNIT HEATER
SUPPLY FAN
WITH
WITHOUT
W/
XFMR
W/O
WP
TRANSFORMER
WEATHER PROOF
HOUR
LIGHT
JUNCTION BOX
LIGHT CONTROL
ISOLATED GROUND
HORSEPOWER
MINIMUM
MOUNT
MAKE-UP AIR UNIT
MOTOR CONTROL CENTER
MAIN LUG ONLY
MOUNTED
MOUNTING
MAXIMUM
LIGHTING
LT FLEX
MTD
MUAU-
MTG
MLO
MIN
MT
MC
MAX
MCC
LTG
IG
LC
LT
IMC
JB
HR
HVAC
HOA
HP
NORMALLY CLOSED
NOT IN CONTRACT
NORMALLY OPEN
NOT TO SCALE
NIGHT LIGHTNL
NTS
NO
NIC
NC
HAND-OFF-AUTO SELECTOR SWITCH
HEATING/VENTILATING/AIR CONDITIONING
INTERMEDIATE METAL CONDUIT
LIQUID TIGHT FLEXIBLE METAL CONDUIT
MECHANICAL CONTRACTOR
HID HIGH INTENSITY DISCHARGE
A
AC
AFF
ACU-
AHJ
AHU-
AS
B-
BC
AIC
ATS
BLDG
CHLR-
CND (C)
CKT BKR
CKT
CUH-
CU-
DISC
DFU-
EF-
EC
DWH-
EBB-
DWG
CT-
EXIST./EX.
EWC
FLEX
FLA
FLR
FSES
FLUOR
EMT
ABOVE FINISHED FLOOR
AIR CONDITIONING UNIT
AMPS
ABOVE COUNTER
AIR HANDLING UNIT
AUTOMATIC TRANSFER SWITCH
AMPS INTERRUPTING CAPACITY
AUTHORITY HAVING JURISDICTION
ABOVE SHELF
BOILER
BUILDING
BELOW COUNTER
CHILLER
DOMESTIC WATER HEATER
CABINET UNIT HEATER
CIRCUIT
CIRCUIT BREAKER
CONDUIT
CONDENSING UNIT
COOLING TOWER
DUCT FURNACE
DRAWING
DISCONNECT
FOOD SERVICE EQUIP. SUPPLIER
ELECTRIC WATER COOLER
ELECTRICAL CONTRACTOR
ELECTRIC BASEBOARD
ELECTRICAL METALLIC TUBING
EXISTING
EXHAUST FAN
FLOOR
FLUORESCENT
FLEXIBLE CONDUIT
FULL LOAD AMPS
EM EMERGENCY
F/S FIRE/SMOKE
FU- FURNACE
GENERAL ELECTRICAL NOTES
1. ALL WORK SHALL BE IN COMPLIANCE WITH THE 2023 MICHIGAN
ELECTRICAL CODE AND MDOC STANDARDS.
2. ALL NON-FIRE RATED WALLS ARE TO BE PATCHED WITH LIKE
MATERIAL TO MAINTAIN ORIGINAL RATING.
3. ALL WALL AND FLOOR PENETRATIONS THROUGH FIRE RATED WALLS
ARE TO BE SEALED WITH FIRE CAULK TO MAINTAIN ORIGINAL
RATING. EXISTING PENETRATIONS IN THE AREA OF WORK THAT ARE
NOT PROPERLY SEALED ARE TO BE SEALED TO MATCH THE RATING
OF THE WALL.
4. ALL CONDUITS SHALL BE FIELD ROUTED ALONG EXISTING PIPING
AND STRUCTURAL STEEL. CONDUITS SHALL BE INSTALLED
STRAIGHT, LEVEL, AND PARALLEL OR PERPENDICULAR TO THE
BUILDING LINES.
5. CONTRACTORS SHALL VISIT THE PROJECT SITE DURING PRE-BID
WALK THROUGH TO DETERMINE THE EXACT EXTENT OF THE WORK
REQUIRED BEFORE BIDDING THE PROJECT.
6. REMOVE ALL EXISTING OBSOLETE EXPOSED CONDUIT, WIRE, AND
EQUIPMENT NOT TO BE RE-USED WHERE WORK IS BEING DONE
EXCEPT ITEMS NOTED OTHERWISE.
7. WHERE BUILDING SURFACES ARE DAMAGED BY THE REMOVAL OF
OLD WORK, SURFACES SHALL BE PATCHED AND PAINTED TO MATCH
ADJACENT.
8. ISTING WORK, WHICH IS PRESENTLY CONCEALED, WHICH WILL
REMAIN CONCEALED, AND DOES NOT INTERFERE WITH ANY NEW
WORK OF ANY TRADE NEED NOT BE REMOVED. HOWEVER, ALL
CONDUIT SHALL BE CAPPED BELOW FINISH SURFACE AND THEN
PATCHED AND PAINTED TO MATCH, OR AS NOTED.
9. STING OPENINGS, WHICH ARE TO BE REUSED, SHALL BE MODIFIED
OR ENLARGED TO SUIT THE NEW SYSTEMS AS REQUIRED. PROVIDE
ALL REQUIRED CUTTING AND PATCHING.
10. RACTOR SHALL BE RESPONSIBLE FOR PATCHING THE EXISTING
WALLS TO MATCH THE ADJACENT SURFACES BEHIND ALL SURFACE
MOUNTED EQUIPMENT.
11. RACTOR SHALL FIELD VERIFY ALL EQUIPMENT AND LOADS PRIOR TO
INSTALLING SERVICE TO EQUIPMENT.
12. INGS ARE BASED ON EXISTING RECORD DOCUMENTS AND CASUAL
FIELD OBSERVATION. REPORT ANY DISCREPANCIES TO ENGINEER
FOR CLARIFICATION.
1. CONDUITS AND BOXES:
1.1. 3/4" MINIMUM TRADE SIZE.
1.2. EMT TYPE CONDUIT IS APPROVED WITH COMPRESSION
FITTINGS.
1.3. NO PVC ALLOWED INSIDE OF BUILDINGS.
1.4. CONDUITS SHALL BE ATTACHED WITH TWO-HOLE STRAPS.
SINGLE HOLE STRAPS ARE NOT PERMITTED.
1.5. NO SET SCREWS ARE ALLOWED.
1.6. TAMPER-PROOF SCREWS REQUIRED FOR EXPOSED CONDUIT
AND BOXES MOUNTED BELOW TEN FEET.
1.7. DRIVE PIN ANCHORS USED ON MASONARY OR CONCRETE
WALLS/CEILINGS.
2. MINIMUM RACEWAY SIZE; 3/4" TRADE SIZE. ALL FLEXIBLE CONDUIT
RACEWAYS SHALL BE LIQUID TITE, MAXIMUM 72" LENGTH AND MUST
BE APPROVED BY PSC AND MDOC PROJECT MANAGER. REFER TO
SPECIFICATION 260533 - RACEWAY AND BOXES FOR ELECTRICAL
SYSTEMS.
3. INSTALLATION OF ANY NEW OR REWORKED CONDUIT, FITTINGS, AND
STRAPS SHALL FOLLOW CURRENT NEC AND MDOC STANDARDS.
4. CONDUIT, CONDUIT INSTALLATION, AND BOXES BEING REUSED
SHALL BE BROUGHT UP TO CURRENT MDOC STANDARDS.
5. ALL CONDUIT AND BOXES ABOVE 10 FOOT OR IN
MECHANICAL/ELECTRICAL ROOMS, SHALL MEET THE FOLLOWING
REQUIREMENTS:
5.1. STRAP DISTANCE: 5 FEET.
5.2. FASTENERS: 2 HOLE.
5.3. CONDUIT” INTERIOR EMT, EXTERIOR EXPOSED/CONCEALED-
GRC.
5.4. FITTINGS: COMPRESSION.
5.5. BOXES: STANDARD BOXES FOR ENVIORNMENT INSTALLED TO
MEET N.E.C.
5.6. SECURE CONDUIT WITHIN 12 INCHES OF BOXES AND
ENCLOSURES.
6. ALL CONDUIT AND BOXES 10 FOOT AND BELOW SHALL MEET THE
FOLLOWING REQUIREMENTS:
6.1. STRAP DISTANCE: 3 FEET.
6.2. FASTENERS: 2 HOLE WITH SECURITY SCREWS.
6.3. SECURITY HARDWARE:
6.3. SECURITY HARDWARE:
6.3.1. TORX T-25 WITH CENTER REJECTION PIN.
6.3.2. HEX HEAD CONCRETE SCREWS WITH NO SCREWDRIVER
SLOT.
6.3.3. EXPANSION POUND-IN ANCHORSWITH NO SCREWDRIVER
SLOT THAT DO NOT REQUIRE TO BE EXPLOSIVELY DRIVEN.
6.3.4. PRE-APPROVED HARDWARE.
6.4. CONDUIT: INTERIOR EMT, EXTERIOR EXPOSED/ CONCEALED -
GRC.
6.5. FITTINGS: COMPRESSION
6.6. BOXES:
6.6.1. SURFACE MOUNTED:
6.6.1.1. BELL BOX: FS TYPE, WITH SQUARE HEAD KO SEAL.
6.6.1.2. NO KNOCKOUTS - DRILL AS REQUIRED.
6.7. SECURE CONDUIT WITHIN 12 INCHES OF BOXES AND
ENCLOSURES.
7. ALL EXPOSED WIRING SHALL BE IN CONDUIT.
8. ALL WALLS THAT ARE ACCESSIBLE SHALL BE FISHED AND DEVICE
CUT INTO WALL.
9. ALL LOCATIONS WHERE THE WALLS CAN NOT BE FISHED SHALL BE
SURFACE MOUNTED CONDUIT FOLLOWING NOTES 14 THROUGH 15
ABOVE.
10. ALL EXTERIOR CONCEALED CONDUIT UNDERGROUND SHALL BE
RNC/HDPE SCHEDULE 80. ALL EXTERIOR ABOVE GROUND CONDUIT
SHALL BE RGC UP TO 10 FEET ABOVE GRADE. PROVIDE UL LISTED
#12 COPPER TRACER WIRE TO ALL UNDERGROUND CONDUITS
INSTALLED FOR LOW VOLTAGE.
11. ALL ELECTRICAL OUTAGES SHALL NOT LAST OVER 2-HOURS. IF A
WINDOW OF GREATER THAN 2 HOURS FOR AN ELECTRICAL SHUT
DOWN OR CUT OVER IS REQUIRED, THEN A PORTABLE GENERATOR
SHALL BE USED TO REPLACE POWER TO ALL PERIMETER DETCTION,
VIDEO MANAGEMENT, LINE SAFTEY, AND ANY OTHER ELECTRICAL
SERVICE REQUIRED. ALL OUTAGES AND CUT OVERS SHALL BE
COORDINATED A MINIMUM OF 2-WEEKS PRIOR TO WORK, INCLUDING
AN HOUR BY HOUR SCHEDULE, MUST BE SUBMITTED TO MDOC
LEADERSHIP AND THE FACILITY FOR REVIEW.
12. WHEN RELOCATING ANY ELECTRICAL DEVICE, CONTRACTOR SHALL
COMPLETE THE RELOCATION IN ONE DAY AND VERIFY THAT ALL
DEVICES RELOCATED ARE WORKING PROPERLY PRIOR TO LEAVING
THE SITE.
13. CONTRACTOR SHALL PROVIDE AND INSTALL ALL REQUIRED
COMPONENTS, RACEWAYS, WIRE, AND HARDWARE, AS INDICATED
ON DRAWINGS.
14. CONTRACTOR SHALL PROVIDE UPDATED PANEL SCHEDULES FOR
ALL PANELS AFFECTED BY THIS PROJECT. UPDATED SCHEDULES
SHALL BE PRINTED AND INSTALLED ON THE INSIDE COVER OF THE
PANEL.
15. ALL WORK COMPLETED WITHOUT APPROVED SHOP DRAWINGS IS AT
CONTRACTOR'S RISK.
16. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR INSTALLATION OF
ALL 24V CONTROL WIRING AS REQUIRED TO LOCALLY CONTROL ALL
HVAC & PLUMBING IN ACCORDANCE WITH THE SEQUENCE OF
OPERATIONS. REFER TO THE MECHANICAL DRAWINGS FOR ALL
LOCAL THERMOSTAT LOCATIONS AND MECHANICAL SPECIFICATIONS
FOR INSTALLATION REQUIREMENTS. COORDINATE IN FIELD WITH
MECHANICAL CONTRACTOR AS REQUIRED. ELECTRICAL
CONTRACTOR SHALL PROVIDE AND INSTALL ALL CONDUIT, WIRE,
AND HARDWARE AS REQUIRED IN ACCORDANCE WITH ELECTRICAL
SPECIFICATIONS. REFER TO SHEET E-100 DETAIL 1 FOR ADDITIONAL
INFORMATION.
17. CONTRACTOR SHALL NOTIFY PSC OF ANY EXISTING INSTALLATIONS
NOT MEETING THESE STANDARDS PRIOR TO STARTING WORK IN THE
AREA.
18. UPON RELOCATING LIGHTS AND CAMERAS CONTRACTORS SHALL
VERIFY THAT THE LIGHTS AND CAMERAS ARE WORKING PROPERLY
PRIOR TO LEAVING THE SITE.
19. CONTRACTOR SHALL USE MDOC APPROVED POLES AND FIXTURES,
NO ALTERNATES WILL BE ALLOWED. ALL OTHER STATE OF MICHIGAN
AGENCY SPECIFICATIONS DO NOT APPLY.
20. CONTRACTOR SHALL NOT ADD MORE THAN 20% CAPACITY TO ANY
PANEL.
21. ARC FLASH LABELS TO BE PROVIDED FOR ALL NEW PANELBOARDS.
22. NEW PRINTED CIRCUIT DIRECTORIES SHALL BE PROVIDED FOR ALL
NEW AND REVISED PANELBOARDS.
23. CONTRACTOR SHALL SUBMIT AN RFI FOR ANY NON-CODE
COMPLIANT ELECTRICAL EQUIPMENT OR ELECTRICAL INSTALLATION.
AN RFI RESPONSE WILL BE PROVIDED GIVING DIRECTION ON HOW
TO PROCEED.
GENERAL HVAC NOTES
1. ALL WORK SHALL CONFORM TO MICHIGAN MECHANICAL CODE,
LATEST APPLICABLE EDITION.
2. INSTALL ALL EQUIPMENT, MATERIALS, AND ACCESSORIES PER
MANUFACTURERS WRITTEN INSTRUCTIONS.
3. ALL EXISTING SYSTEMS (INCLUDING EXHAUST FANS, FIN TUBE)
THAT SERVES AREAS BEING RENOVATED SHALL BE REBALANCED
AS REQUIRED.
4. NOTIFY OWNER OF ANY PIPING OR DUCTWORK DEMOLITION THAT
MAY AFFECT NORMAL OPERATION OF OTHER AREAS.
5. FIELD VERIFY LOCATIONS OF EXISTING PIPING THAT MAY CONFLICT
WITH NEW CONSTRUCTION AND RELOCATE AS NEEDED.
6. CONTRACTOR SHALL COORDINATE ALL WORK WITH OTHER
DISCIPLINES PRIOR TO CONSTRUCTION TO AVOID CONFLICTS.
7. PROVIDE MANUAL AIR VENTS WITH 3/4" HOSE CONNECTION AT ALL
HIGH POINTS.
8. OFFSET PIPING TO ACCOMMODATE LARGE DUCTWORK.
9. THE CONTRACTOR SHALL FIELD VERIFY THE SIZES, LOCATION,
ELEVATIONS, AND DETAILS OF ALL EXISTING CONDITIONS THAT MAY
AFFECT THE WORK.
10. THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING THE
INTEGRITY OF ALL EQUIPMENT AND MATERIALS IN A "NEW"
CONDITION DURING CONSTRUCTION.
11. ALL WORK SHALL BE PERFORMED BY LICENSED CONTRACTORS
AND SUBCONTRACTORS AS REQUIRED BY LAW.
12. IF THERE IS CONFLICTING INFORMATION IN THE PLANS OR
SPECIFICATIONS THE MORE STRINGENT AND GREATER COST ITEM
SHALL BE USED.
13. DRAWINGS INDICATE REQUIRED SIZES AND POINTS OF
TERMINATION OF PIPES AND DUCTS AND SUGGESTED ROUTES. IT
IS NOT INTENTION OF DRAWINGS TO INDICATE ALL NECESSARY
OFFSETS. INSTALL WORK IN MANNER TO CONFORM TO
STRUCTURE, AVOID OBSTRUCTIONS, PRESERVE HEADROOM AND
KEEP OPENINGS AND PASSAGEWAYS CLEAR. DO NOT SCALE FROM
DRAWINGS.
14. PERFORM WORK IN ACCORDANCE WITH THE LATEST EDITIONS,
REVISIONS, AMENDMENTS, OR SUPPLEMENTS OF APPLICABLE
STATUTES, ORDINANCES, CODES OR REGULATIONS OF FEDERAL,
STATE, AND LOCAL AUTHORITIES HAVING JURISDICTION IN EFFECT
ON THE DATE BIDS ARE RECEIVED.
15. WHERE APPROVED STANDARDS HAVE BEEN ESTABLISHED BY OSHA,
UNDERWRITERS, LABORATORIES, AMERICAN CODES, ASA, ASHRAE,
ARI, NEC, STATE FIRE INSURANCE REGULATION BODY, NFPA OR
OTHERS, THESE STANDARDS SHALL BE FOLLOWED WHETHER OR
NOT INDICATED ON THE DRAWING AND SPECIFICATIONS.
16. DUCT/PIPING LAYOUT IS SCHEMATIC. EXACT LOCATION OF
DUCT/PIPING AND EQUIPMENT SHALL BE COORDINATED WITH
BUILDING STRUCTURE, EQUIPMENT FURNISHED, ARCHITECTURAL
DRAWINGS, AND ALL OTHER TRADES PRIOR TO INSTALLATION. ANY
CONTRACTOR INSTALLING WORK WITHOUT PRIOR COORDINATION
SHALL RELOCATE HIS WORK AT HIS EXPENSE TO ALLOW PROPER
INSTALLATION OF ANY AND ALL TRADES WORK.
17. UNLESS OTHERWISE NOTED, ALL DUCT/PIPING SHALL BE
CONCEALED WHEREVER POSSIBLE. PROVIDE CHROME
ESCUTCHEON OR ALUMINUM DUCT COLLAR AT EACH PENETRATION
OF A FINISHED SURFACE.
18. DUCT/PIPING SHALL NOT BE RUN ABOVE ELECTRICAL GEAR IN THE
SERVICE SPACE REQUIRED BY THE NATIONAL ELECTRICAL CODE.
19. ANY ADDITIONAL LOW VOLTAGE CONTROL WIRING THAT IS
REQUIRED SHALL BE PROVIDED BY THE HVAC CONTRACTOR.
CONTROL WIRING SHALL BE RUN IN CONDUIT IF REQUIRED BY
LOCAL CODES OR THE SPECIFICATIONS. POWER SHALL BE
PROVIDED BY THE ELECTRICAL CONTRACTOR.
20. ALL PIPING SHALL BE CONCEALED ABOVE THE CEILING SPACE, IN
NEW METAL CHASES, OR WITHIN THE EXISTING FIN TUBE
ENCLOSURES.
21. CONTRACTOR TO TRACK AND PROVIDE PAPERWORK TO OWNER OF
THE AMOUNT OF MATERIAL BEING RECYCLED THROUGHOUT THE
PROJECT.
22. CONTRACTOR TO PATCH, PRIME, AND PAINT EXISTING
WALLS/CEILINGS AS NEEDED TO MATCH EXISTING WHERE
DEMOLITION AND/OR NEW WORK IS COMPLETED.
23. ALL FASTENERS USED IN AREAS EXPOSED TO INMATES SHALL USE
TAMPERPROOF SCREWS.
24. CONTRACTOR TO REFER TO ALL ELECTRICAL CONSTRUCTION
DOCUMENTS AND DIVISION 26 SPECIFICATIONS FOR CONTROL
WIRING RACEWAYS. ALL CONTROL WIRING RACEWAYS ARE TO
MEET MDOC REQUIREMENTS.
25. CONTRACTOR WILL HAVE 1 ESCORT TO WORK WITH THROUGH AT
THE PROJECT.
26. CONTRACTOR TO NOTIFY THE FACILITY AT LEAST 1 DAY IN
ADVANCE FOR ANY HOT WORK TO ALLOW THE OWNER TO DISABLE
THE FIRE ALARM.
27. CONTRACTOR TO ATTEND A 6 MONTH AND AN 11 MONTH POST
CONSTRUCTION MEETING WITH THE ENGINEER AND OWNER TO
REVIEW AND FIX ISSUES DURING THE WARRANTY PERIOD.
MECHANICAL SYMBOLS LEGEND
HVAC PIPING SYMBOLSHVAC PIPING
HVAC DUCTWORK
F/S F/S s s
TEMPERATURE CONTROL SYMBOLS
MISCELLANEOUS NOTES
HVAC DUCTWORK SYMBOLS HVAC DUCTWORK & DIFFUSER TAGS HVAC PIPING VALVES
MECHANICAL ABBREVIATIONS
AFF ABOVE FINISH FLOOR
AC AIR COMPRESSOR
AHU AIR HANDLING UNIT
AS AIR SEPARATOR
A.T.C. ARCHITECTURAL TRADES CONTRACTOR
B BOILER
B.A.S. BUILDING AUTOMATION SYSTEM
CAF COMBUSTION AIR FAN
CC COOLING COIL
CFM CUBIC FEET PER MINUTE
CHLR CHILLER
CHP CONSOLE HEAT PUMP
CONV CONVECTOR
CT COOLING TOWER
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
CV CONTROL VALVE
CWP CHILLED WATER PUMP
DB DRY BULB
DFU DUCT FURNACE
DIA DIAMETER
DN DOWN
DPR DAMPER
DS DUCT SILENCER
EAT ENTERING AIR TEMPERATURE
EF EXHAUST FAN
EG EXHAUST GRILLE
E.T.C. ELECTRICAL TRADES CONTRACTOR
EVR EVAPORATOR
EWT ENTERING WATER TEMPERATURE
EXH EXHAUST
EXIST EXISTING
FF FINISH FLOOR
FPM FEET PER MINUTE
FT FEET
FTR FINNED TUBE RADIATION
FU FURNACE
GAL GALLON
GFRH GAS FIRED RADIANT HEATER
GR GRILLE
H HUMIDIFIER
HC HEATING COIL
HD HEAD (FT)
HP HORSE POWER
HHP HORIZONTAL HEAT PUMP
HTG HEATING
HVAC HEATING, VENTILATION, & AIR CONDITIONING
HWP HEATING WATER PUMP
HX HEAT EXCHANGER
ID INSIDE DIAMETER
I.E. INVERT ELEVATION
IAH INTAKE HOOD
LAT LEAVING AIR TEMPERATURE
LH LATENT HEAT (MBH)
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MBH BTU PER HOUR (THOUSAND)
MIN MINIMUM
M.T.C. MECHANICAL TRADES CONTRACTOR
N.C. NOISE CRITERIA
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NTS NOT TO SCALE
P PUMP
PCR PUMPED CONDENSATE RETURN
PD PRESSURE DROP
RCP RADIANT CEILING PANEL
REQ'D REQUIRED
RG RETURN GRILLE
RH RELATIVE HUMIDITY
RLH RELIEF HOOD
RTU ROOF TOP UNIT
SD SUPPLY DIFFUSER
SF SUPPLY FAN
SG SUPPLY GRILLE
SH SENSIBLE HEAT (MBH)
SM SHEET METAL
SQ. FT. SQUARE FEET
SST SATURATED SUCTION TEMPERATURE
STR STRAINER
TC TOTAL COOLING (MBH)
TCL TEMPERATURE CONTROL
T&P TEMPERATURE & PRESSURE RELIEF VALVE
TYP TYPICAL
UH UNIT HEATER
VAV VARIABLE AIR VOLUME BOX
VRH VARIABLE AIR VOLUME REHEAT BOX
FPVAV FAN POWERED VARIABLE AIR VOLUME BOX
V.F.D VARIABLE FREQUENCY DRIVE
ZD ZONE DAMPER
X-SA EXISTING ITEM (EXISTING SUPPLY AIR DUCT)
ITEM
EXISTING
CHILLED WATER SUPPLY
CHILLED WATER RETURN
CONDENSATE DRAIN
CONDENSER WATER SUPPLY
CONDENSER WATER RETURN
COOLING TOWER WATER SUPPLY
COOLING TOWER WATER RETURN
DIRECT EXPANSION
HEAT PUMP WATER SUPPLY
HEAT PUMP WATER RETURN
HEATING WATER SUPPLY
HEATING WATER RETURN
SUCTION (REFRIGERANT)
LIQUID (REFRIGERANT)
SUCTION (DIRECT EXPANSION)
LIQUID (DIRECT EXPANSION)
LOW PRESSURE STEAM (0-20 LBS.)
MEDIUM PRESSURE STEAM (21-75 LBS.)
HIGH PRESSURE STEAM (76 LBS. & ABV.)
STEAM CONDENSATE (GRAVITY)
PUMPED STEAM CONDENSATE
STEAM CONDENSATE BOILER FEED
GATE VALVE
GAS COCK
CHECK VALVE
BALANCE COCK
CIRCUIT SETTER
TWO-WAY CONTROL VALVE
THREE-WAY CONTROL VALVE
GLOBE VALVE
BALL VALVE
SOLENOID VALVE
EXPANSION VALVE WITH
THERMOSTATIC BULB
PLUG VALVE
BUTTERFLY VALVE
RELIEF VALVE
HOSE & DRAIN END VALVE
PRESSURE RELIEF VALVE
PRESSURE REDUCING VALVE
TRIPLE DUTY VALVE
GAS PRESSURE REGULATOR
STRAINER (BLOW-OFF)
FLOW DIRECTION
PIPING DROP
PIPING RISE
INLINE PIPING DROP
INLINE PIPING RISE
PIPING TEE
PIPING ELBOW
THERMOMETER
PUMP
UNION
PIPE ANCHOR
PIPE GUIDE
BACK FLOW PREVENTER
PIPE CAP
PIPE BREAK
THERMOMETER WELL
EXPANSION LOOP
EXPANSION COMPENSATOR
THERMOSTAT
PROGRAMMABLE THERMOSTAT
THERMOSTAT (W/ NIGHT SETBACK)
ROOM SENSOR
HUMIDISTAT
PRESSURE GAUGE
DAMPER (ELECTRIC OPERATION)
DAMPER (PNEUMATIC OPERATION)
DAMPER BLADES
SUPPLY AIR DUCT
EXIST SUPPLY AIR DUCT
RETURN AIR DUCT
EXIST RETURN AIR DUCT
OUTSIDE AIR DUCT
EXIST OUTSIDE AIR DUCT
EXHAUST AIR DUCT
EXIST EXHAUST AIR DUCT
SUPPLY AIR DUCT RISER
RETURN AIR DUCT RISER
OUTSIDE AIR DUCT RISER (AS NOTED)
EXHAUST AIR DUCT
INSULATED DUCTWORK (AS NOTED)
SUPPLY AIR DIFFUSER (SQUARE)
SUPPLY AIR DIFFUSER (INLINE)
TURNING VANES
SURFACE MTD. GRILLE
SUPPLY AIR DIFFUSER (ROUND)
90° TEE W/45° APPROACH
CONICAL TAKE-OFF
CONICAL TAKE-OFF W/ DAMPER
BALANCE DAMPER
RETURN AIR DUCT BOOT
ECCENTRIC REDUCER
CONCENTRIC REDUCER
VERTICAL FIRE DAMPER
EXISTING VERTICAL FIRE DAMPER
HORIZONTAL FIRE DAMPER
EXISTING HORIZONTAL FIRE DAMPER
VERTICAL SMOKE DAMPER
HORIZONTAL SMOKE DAMPER
VERTICAL FIRE / SMOKE DAMPER
HORIZONTAL FIRE / SMOKE DAMPER
DUCT SMOKE DETECTOR, INSTALLED BY M.T.C.,
PROVIDED & WIRED BY E.T.C.
UNIT HEATER
CEILING EXHAUST FAN
ROOF MOUNTED EXHAUST FAN
DEMOLITION
POINT OF CONNECTION BETWEEN NEW AND
EXISTING
POINT OF EXISTING TO REMAIN AND EXISTING
TO BE REMOVED
INDICATES PLAN NOTE
INDICATES DEMOLITION NOTE
DETAIL BUBBLE
DETAIL NUMBER
PAGE LOCATION INDICATES
DIRECTION OF DETAIL SECTION
X
X
XX
XXXX
XX
XXXX
SA
OA
X-OA
X-EA
EA
X-SA
X-RA
RA
SCP
SC
DXS
DXL
HR
CR
CD
CS
DX
CTR
HPR
HS
HPS
CTS
CWR
CWS
S
L
LPS
MPS
HPS
SC (BF)
TAG CFM
NECK REMARKS
SIZE
SD-1 250
8"ø ---
P
H
S
T
T P
T N
M
M
SD
1. SEE ARCHITECTURAL DRAWINGS FOR ADDITIONAL INFORMATION.
2. EXISTING EQUIPMENT LAYOUT IS SCHEMATIC. EXACT LOCATION OF EXISTING
DUCT/PIPING AND EQUIPMENT SHALL BE COORDINATED WITH BUILDING
STRUCTURE, EQUIPMENT FURNISHED, ARCHITECTURAL DRAWINGS AND ALL
OTHER TRADES PRIOR TO DEMOLITION.
3. PERFORM WORK IN ACCORDANCE WITH THE LATEST EDITIONS, REVISIONS,
AMENDMENTS, OR SUPPLEMENTS OF APPLICABLE STATUTES, ORDINANCES,
CODES OR REGULATIONS OF FEDERAL, STATE, AND LOCAL AUTHORITIES
HAVING JURISDICTION IN EFFECT ON THE DATE BIDS ARE RECEIVED.
4. WHERE APPROVED STANDARDS HAVE BEEN ESTABLISHED BY OSHA,
UNDERWRITERS LABORATORIES, AMERICAN CODES, ASA, ASHRAE, ARI, NEC,
STATE FIRE INSURANCE REGULATION BODY, NFPA OR OTHERS. THESE
STANDARDS SHALL BE FOLLOWED WHETHER OR NOT INDICATED ON THE
DRAWING AND SPECIFICATIONS.
5. COORDINATE CUTTING AND PATCHING WITH GENERAL CONTRACTOR.
6. ALL BOLD DASHED LINES INDICATE ITEMS TO BE REMOVED UNLESS NOTED BY
KEYNOTE. ALL OTHER…