New Weight Room_Cheer Gym BluePrints.pdf
PDF 250 KB Posted
- Attached to
- District Security Cameras - See Attached
- Solicitation number
- RFP-CSP-250000001411-1
- Issued by
- Kent County, Cheboygan City, Michigan
About this file
This is an electrical blueprint and specifications document for a Weight Room & Cheer Addition project at Cedar Springs Public Schools in Cedar Springs, Michigan. The document shows detailed electrical plans for power and communications systems in various rooms including a weight room (J103), cheer room (J104), entry area (J101), and storage room (J102). The plans include specifications for electrical installations such as receptacles, lighting controls, access control systems, cameras, and networking equipment. Key features include three batting cages with dedicated switches, motorized window shades (listed as an alternate), overhead doors with card readers, and protective wire guards for devices in the cheer room.
The technical specifications detail requirements for tamper-resistant receptacles, smoke damper power supplies, dedicated circuits for electronic door hardware, and specific mounting heights for monitors (7'-0" AFF) and access points (10'-0" AFF). The document includes electrical keynotes describing special requirements like surface-mounted conduit installations, exterior camera data drops with 10-foot service loops, and card reader controls for overhead doors. Electrical feeds are specified to run from panels 'LC' and 'HC' to new panels 'LC5' and 'H2C' located in the new mezzanine area, with requirements for painting conduits to match mounting surfaces.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
T
1/4 1/4
F
F
F
AV
AV
AV
1/2
S5
S5
S5
S5
C
C
C
SC
SC
AV
1/2
EL
EL
DC
DC
CR
CR
EL EL
DC DC
1/2
SC
SC
K K K
SC
SC
SC
SC
1/2
FB1 FB1 FB1
FB1
FB1
FB1FB1FB1
1/2
EL
DC
CR
DC
ES
CR
CR CRDC
ES
DC
ES
DC
EL
CR
S
S
R
S5
S5
S5
C F
AV
AV
CR CR
CR CR
1053 DD
DD
F
AV
1/2
1/3
F
F1/3
1.
2.
3.
4.
A.
B.
C.
D.
E.
5.
6.
7.
REFER TO ELECTRICAL GENERAL NOTES ON SHEET E0.01.
REFER TO CODE COMPLIANCE PLAN FOR LOCATIONS AND RATINGS OF
VERTICAL AND HORIZONTAL BUILDING ASSEMBLIES. PROVIDE APPROPRIATE
FIRESTOPPING SYSTEMS PER SPECIFICATIONS TO MEET ALL APPLICABLE
CODES.
ALL GENERAL-USE 15- AND 20-AMPERE, 125- AND 250-VOLT NON-LOCKING
RECEPTACLES SHALL BE TAMPER-RESISTANT TYPE; REFER TO NEC 406.12 AND
SPECIFICATION SECTION 26 27 26.
PROVIDE 120VAC POWER FOR ALL SMOKE DAMPERS AND COMBINATION
FIRE/SMOKE DAMPERS.
REFER TO MECHANICAL/HVAC DRAWINGS FOR LOCATIONS AND QUANTITIES
OF DAMPERS.
CONNECT TO DEDICATED 20A BRANCH CIRCUIT (WITH BREAKER LOCK-ON
ACCESSORY) IN LOCAL PANELBOARD FOR DAMPER(S) IN EACH AREA
(DAMPERS MAY BE GROUPED ON EACH CIRCUIT).
TERMINATE W/ BOX-COVER FUSIBLE DISCONNECT SWITCH AT EACH
DAMPER.
PROVIDE FIRE ALARM DUCT SMOKE DETECTOR WITHIN 5 FEET OF EACH
DAMPER (UNLESS COVERED BY ANOTHER DUCT DETECTOR WITHIN 5 FEET).
PROVIDE FIRE ALARM ADDRESSABLE RELAY(S) FOR INTERLOCKING
DAMPER W/ CORRESPONDING HVAC UNIT(S) PER CODE REQUIREMENTS.
PROVIDE BOX-COVER FUSIBLE DISCONNECT SWITCH (ON BUILDING INTERIOR IN
ACCESSIBLE LOCATION) FOR EACH SMALL (< 1/2 HP) MECHANICAL AND/OR
PLUMBING EQUIPMENT MOTOR LOAD WHERE MORE THAN ONE UNIT IS
CONNECTED TO A COMMON BRANCH CIRCUIT. TYPICAL EQUIPMENT TYPES
INCLUDE BUT ARE NOT LIMITED TO CABINET HEATERS, DAMPERS, EXHAUST
FANS, FAN COIL UNITS, PUMPS, UNIT HEATERS, VAV BOXES, ETC.
DESIGNATED CABLING PATHWAYS (CONDUITS, CABLE TRAYS, PENETRATION
SLEEVES, ETC.) SHALL BE RESERVED FOR DIV. 27 COMMUNICATIONS CABLING
AND DIV. 28 SAFETY/SECURITY CABLING ONLY. OTHER CABLING TYPES, SUCH
AS DIV. 23 CONTROLS, DIV. 26 CONTROLS, AND ARCHITECTURAL EQUIPMENT
CABLING SHALL BE SUPPORTED AND SLEEVED BY OTHER INDEPENDENT
PATHWAYS, HANGERS, AND SUPPORTS.
CONSOLIDATE ALL POWER SUPPLIES REQUIRED FOR ELECTRONIC DOOR
HARDWARE (REF. SECTION 08 71 00) TO CENTRAL LOCATION(S) ADJACENT TO
DESIGNATED ACCESS CONTROL EQUIPMENT LOCATION(S). CONNECT ALL
POWER SUPPLIES TO DEDICATED [LOCAL] [STANDBY POWER SYSTEM] BRANCH
CIRCUIT(S) AS DESIGNATED [FOR CONTINUED OPERATION UNDER LOSS OF
UTILITY POWER].
POWER & COMMUNICATION GENERAL NOTES
WEIGHT ROOM
J103
CHEER ROOM
J104
ENTRY
J101
J101G
J101F
J104A
S-1A
EX. VESTIBULE
A101
EX. STORAGE
B102
EX PANEL 'H1C'
EX PANEL 'HC'
EX. XFMR 'T-LC1'
EX PANEL 'LC'
EX PANEL 'L1C'
WL
GFCI
WL
GFCI
WL
GFCI
44"
GFCI
44"
2D 44"
J103B
J103E
J103A
SOUND SYSTEM
BATTING
CAGE #1
BATTING
CAGE #2
BATTING
CAGE #3
OVERHEAD
DOOR
OVERHEAD
DOOR
1D
1D
MOTORIZED
SHADES (CKT LC5-34)
(ALTERNATE)
MOTORIZED
SHADES (CKT LC5-25)
(ALTERNATE A1)
44"
STAIR
S-1
STORAGE
J102
MONITOR
7'-0" AFF
7'-0" AFF
1D
MONITOR
7'-0" AFF
7'-0" AFF
1D
2D
WG/PC
EWC
GFCI
BRKR
SOUND SYSTEM
E7.01
E7.01
44"
44"
MOTORIZED
SHADES (CKT LC5-25)
(ALTERNATE A1)
1D AP
10'-0" AFF
1D AP
10'-0" AFF
1D AP
10'-0" AFF
1D AP
10'-0" AFF
LC5-9
WL
GFCI
LC5-13
LC5-15
LC5-14
LC5-16
LC5-17
10'-6" AFF SOUND
SYSTEM SPEAKER
10'-6" AFF SOUND
SYSTEM SPEAKER
18'-0"
AFF
1D
18'-0"
AFF
1D
18'-0"
AFF
MONITOR
7'-0" AFF 7'-0" AFF
1D
LC5-12
BATTING CAGE
SWITCHES
LC5-19 LC5-20
LC5-21
8'-0" 1D
8'-0" 1D
18'-0"
AFF
8'-0" 1D
8'-0" 1D
LC5-18
LC5-22
LC5-23
LC5-24
P03
INTO MEZZANINE
FEEDER FROM EX. PANEL 'LC'
AND PANEL 'HC' TO NEW PANELS
'LC5' AND 'H2C'
P04
P04
OVERHEAD
DOOR
LC5-26
LC5-27
LC5-27
LC5-12
LC5-28
OVERHEAD
DOOR
J104D
LC5-11
ROLLING
FIRE DOOR
LC5-29
P05
P05
10'-6"
LC5-30
LC5-31
LC5-32
LC5-33
LC5-38
ILLUMINATED ENTRY
BUILDING SIGN TIE
TO LC RELAY PANEL
LC5-10
J103D J103C
P07
P07
CHEER ROOM
J104
MECHANICAL MEZZANINE
J201
AHU-25.1
AHU-25.2
EF
HUH-1
ENTRY
J101
STAIR
S-1
EX. GYMNASIUM
B101
VFD-3 VFD-2
VFD-1
H2C-1,3,5
H2C-2,4,6H2C-7,9,11
VFD-4
PANEL 'LC5'
PANEL 'H2C' H2C-8,10,12
NEW IDF #4
LC5-36
LC5-37
HUH-2
5-30R
LC5-36
LC5-39 LC5-40
UNIT A
UNIT B
UNIT C
UNIT D
UNIT E
UNIT F
UNIT G
UNIT
H
U N
IT
J
PROJECT NO.
DRAWN
REVIEWED
NO PART OF THIS DRAWING MAY BE
USED OR REPRODUCED IN ANY FORM
OR BY ANY MEANS, OR STORED IN A
DATA BASE OR RETRIEVAL SYSTEM,
WITHOUT PRIOR WRITTEN
PERMISSION OF
ALL RIGHTS RESERVED
c
KEYPLAN
ISSUANCES
GMB COPYRIGHT
Au to de sk
D oc s:
//5
-5
C ed ar
S pr in gs
H ig h Sc ho ol
W re st lin g
C he er A dd iti on /5
-5
9E
2.
rv t
1/
/2
1:
:2
PM
E2.1J
5-5319
UNIT 'J' POWER &
COMMUNICATIONS PLANS
NAM
AAM
H
IG
H S
C H
O O
L W
E
IG
H T
R O
O M
C
H E
E R
A D
D
IT
IO
N
C E D A R S P R
IN
G S P U B
LI
C S C H O O
LS
C E
D A
R S
P R
IN
G
S
M
IC
H
IG
A N
ELECTRICAL KEYNOTES
P03 ALL CLOCKS, PA, FIRE ALARM AND AP WALL MOUNTED DEVICES IN THE CHEER
ROOM SHALL HAVE WIRE GUARDS/PROTECTIVE COVERS. TYPICAL.
P04 E.C. TO FURNISH AND INSTALL NEW ELECTRICAL FEEDS WITH RACEWAYS
FROM PANEL 'LC' AND PANEL 'HC' TO NEW PANELS 'LC5' AND 'H2C' LOCATED IN
THE NEW MEZZANINE IN THE BUILDING ADDITION. E.C. TO RUN THESE FEEDS
OUT OF THIS ROOM AND SURFACE MOUNT UP TO THE BOTTOM OF THE JOIST
AROUND THE PERIMETER OF THE GYM. PAINT CONDUITS TO MATCH THE
SURFACES THAT THE CONDUITS ARE TO BE MOUNTED ON.
P05 TYPICAL EXTERIOR CAMERA WILL HAVE A (1) DATA DROP. CONTRACTOR TO
INSTALL A 10'-0" SERVICE LOOP INTO THE CEILING AREA IN THE STRUCTURE
AT THE CAMERA LOCATION TO PROVIDE FLIEXIBILITY FOR THE INSTALL TO
PENETRATE WALL AT THE DESIRED LOCATION. THIS IS TYPICAL.
P07 PROVIDE CARD READER FOR EACH OVERHEAD DOOR. CARD READER TO
LOCK-OUT MANUAL DOOR CONTROLS PREVENTING OPERATION OF DOOR BY
UNAUTHORIZED USER.
1/8" = 1'-0"
UNIT 'J' FIRST FLOOR POWER & COMMUNICATIONS PLAN
1/8" = 1'-0"
UNIT 'J' SECOND FLOOR POWER & COMMUNICATIONS PLAN
09.23.2024 BIDS &
CONSTRUCTION
10.08.2024 ADDENDUM 001
01.16.2025 BULLETIN 003
https://app.procore.com/2968002/project/drawing_areas/2446072/drawing_log/314390787 https://app.procore.com/2968002/project/drawing_areas/2446072/drawing_log/314390787 https://app.procore.com/2968002/project/drawing_areas/2446072/drawing_log/309931283
File details come from the government source that posted it. Updated .