Panel_Input_06-26-18.pdf

PDF 965 KB Posted

Attached to
Building 1 Circuit Breaker Replacement Federal contract opportunity
Solicitation number
NB194000-18-02008
Issued by
Department of Commerce National Institute of Standards and Technology

About this file

Panel Inputs - additional information offerors may find helpful

View the file

Other files for this federal contract opportunity

Other files attached to Building 1 Circuit Breaker Replacement, newest first.
File Type Posted
Site_Visit_Information.pdf PDF
1EW1.pdf PDF
Questions_and_Responses.docx DOCX document
1e4sp.pdf PDF
1EW1.pdf PDF
One_Lines.pdf PDF
1e0sp.pdf PDF
Attachment_IV_-_Instructions_and_Evaluation.pdf PDF
1e3sp.pdf PDF
Attachment_II-_Applicable_Provisions_and_Clauses.pdf PDF
Attachment_III_Wage_Determination.pdf PDF
1E2SP.pdf PDF
Attachment_V_Exp_Proj-Data-Sheet.doc DOC document
1EW2.pdf PDF
1e1sp.pdf PDF
Attachment_VI__NIST_Boulder_PPQ_Form.doc DOC document
Attachment_I_-_SOW_B1_Circuit_Breaker_Replacement.pdf PDF
Show all 17

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Conduit Type EMT 1-1/4

Panel.Notes Old cloth wire, old bakalite. Replace panel, breakers, wire, bus breakers

Number Of Circuits 18MLOMCB

Phase 3Amp Rating 100Voltage 208/120

Short Circuit Rating 10000

Number Of Wires 4

Ground Wire Size 8Wire Type CU

Panel Schedule Available On Dwg

Approx Age 1955

Model# C693098Manufacturer

WH

EquipName 4001

Room# 4001AFloor 4Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 1

XFMR_ID T1, T2, T3, T4

Added To Oneline

Estimated Repair Time Hr 8

Equipment Type:

MOUNTING:

FedB BUS BKR RM 4006

Feed Wire Size 3

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 4001

Isc 3P (A)mps 7823

Panel

Surface

Conduit Type EMT 1-1/4"

Panel.Notes Fed from Bus breaker same ROOM, Replace breakers in kind

Number Of Circuits 12MLOMCB

Phase 3Amp Rating 100Voltage 208/120

Short Circuit Rating 22000

Number Of Wires 4

Ground Wire Size 8Wire Type CU

Panel Schedule Available On Dwg

Approx Age 1980

Model# QOManufacturer

SQUARE D

EquipName 4006

Room# 4006Floor 4Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 2

XFMR_ID T1, T2, T3, T4

Added To Oneline

Estimated Repair Time Hr 2

Equipment Type:

MOUNTING:

FedB

Feed Wire Size 2

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 4006

Isc 3P (A)mps 13163

Recessed

Panel.Notes fed from bus breaker above panel, cloth wiring Replace panel & breakers look at replace bars and breakers may be surface 20"W x22"Hx 4 1/8" D see survey sheet

Number Of Circuits 12MLOMCB

Phase 3Amp Rating 50Voltage 208/120

Short Circuit Rating 22000

Number Of Wires 4

Ground Wire Size 10Wire Type CU

Panel Schedule Available On Dwg

Approx Age 1950

Model# C698183Manufacturer

WH

EquipName 4008

Room# 4008Floor 4Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 3

XFMR_ID T1, T2, T3, T4

Added To Oneline

Estimated Repair Time Hr 8

Equipment Type:

MOUNTING:

FedB

Feed Wire Size 6

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 4008

Isc 3P (A)mps 14207

Panel.Notes Replace panel & wire replace wire also breakers

Number Of Circuits 12MLOMCB

Phase 3Amp Rating 50Voltage 208/120

Short Circuit Rating 10000

Number Of Wires 4

Ground Wire Size 10Wire Type CU

Panel Schedule Available On Dwg

Approx Age 1950

Model#Manufacturer

WH

EquipName 4007

Room# 4007Floor 4Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 4

XFMR_ID T1, T2, T3, T4

Added To Oneline

Estimated Repair Time Hr 8

Equipment Type:

MOUNTING:

FedB RM 4008 BUS BKR

Feed Wire Size 6

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 4007

Isc 3P (A)mps 9527

Panel.Notes Replace panel, breakers, wire

Number Of Circuits 12MLOMCB

Phase 3Amp Rating 50Voltage 208/120

Short Circuit Rating 10000

Number Of Wires 4

Ground Wire Size 10Wire Type CU

Panel Schedule Available On Dwg

Approx Age 1955

Model# DNYA33764STXManufacturer

WH

EquipName 4011

Room# 4011Floor 4Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 5

XFMR_ID T1, T2, T3, T4

Added To Oneline

Estimated Repair Time Hr 8

Equipment Type:

MOUNTING:

FedB RM 4012 BUS BKR

Feed Wire Size 6

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 4011

Isc 3P (A)mps 9806

Panel.Notes Code violation, Need room in front of panel. Replace breakers and bus breakers. 2 THHN

Number Of Circuits 20MLOMCB

Phase 3Amp Rating 100Voltage 208/120

Short Circuit Rating 22000

Number Of Wires 4

Ground Wire Size NONEWire Type CU

Panel Schedule Available On Dwg

Approx Age 2005

Model# Q0C420LManufacturer

SQ D

EquipName 4012

Room# 4012Floor 4Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 6

XFMR_ID T1, T2, T3, T4

Added To Oneline

Estimated Repair Time Hr 2

Equipment Type:

MOUNTING:

FedB RM 4012 BUS BKR

Feed Wire Size 2

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 4012

Isc 3P (A)mps 17519

Panel.Notes Replace breakers only, 2hrs estimated shut down time VIDEO IS EMG4016. Fed from Panel EP3 ckt 1,3,5 - Rm 2047B

Number Of Circuits 16MLOMCB

Phase 3Amp Rating 100Voltage 208/120

Short Circuit Rating 10000

Number Of Wires 4

Ground Wire Size 4Wire Type CU

Panel Schedule Available On Dwg

Approx Age 2005

Model# QOC1603Manufacturer

SQ D

EquipName EMG4016

Room# 4016Floor 4Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 7

XFMR_ID T1, T2, T3, T4

Added To Oneline

Estimated Repair Time Hr 2

Equipment Type:

MOUNTING:

FedB RM 2047B PNL EP3

Feed Wire Size 4

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName EMG4016

Isc 3P (A)mps 1560

Panel.Notes REPLACE BREAKERS, BUS BREAKER ONLY.

Number Of Circuits 24MLOMCB

Phase 3Amp Rating 100Voltage 208/120

Short Circuit Rating 22000

Number Of Wires 4

Ground Wire Size NONEWire Type CU

Panel Schedule Available On Dwg

Approx Age 2005

Model# QOC24UManufacturer

SQ D

EquipName 4016

Room# 4016Floor 4Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 8

XFMR_ID T1, T2, T3, T4

Added To Oneline

Estimated Repair Time Hr

Equipment Type:

MOUNTING:

FedB RM 4016 BUS BREAKER

Feed Wire Size 2

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 4016

Isc 3P (A)mps 19101

Panel.Notes REPLACE BREAKERS ONLY, 3 THHN

Number Of Circuits 12MLOMCB

Phase 3Amp Rating 100Voltage 208/120

Short Circuit Rating 22000

Number Of Wires 4

Ground Wire Size NONEWire Type CU

Panel Schedule Available On Dwg

Approx Age 1990

Model# QOC412LManufacturer

SQUARE D

EquipName 4015

Room# 4015Floor 4Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 9

XFMR_ID T1, T2, T3, T4

Added To Oneline

Estimated Repair Time Hr

Equipment Type:

MOUNTING:

FedB

Feed Wire Size 3

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 4015

Isc 3P (A)mps 13708

Panel.Notes REPLACE PANEL, BRKR, WIRE, BUS BREAKER

Number Of Circuits 12MLOMCB

Phase 3Amp Rating 50Voltage 208/120

Short Circuit Rating 22000

Number Of Wires 4

Ground Wire Size 10Wire Type CU

Panel Schedule Available On Dwg

Approx Age 1955

Model# C698390Manufacturer

WH

EquipName 4020

Room# 4020Floor 4Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 10

XFMR_ID T1, T2, T3, T4

Added To Oneline

Estimated Repair Time Hr 8

Equipment Type:

MOUNTING:

FedB

Feed Wire Size 6

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 4020

Isc 3P (A)mps 15634

Panel.Notes REPLACE PANEL, BRKRS, BUS BRKR, WIRE CLOTH

Number Of Circuits 12MLOMCB

Phase 3Amp Rating 50Voltage 208/120

Short Circuit Rating 22000

Number Of Wires 4

Ground Wire Size 10Wire Type CU

Panel Schedule Available On Dwg

Approx Age 1955

Model# C698393Manufacturer

WH

EquipName 4019

Room# 4019Floor 4Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 11

XFMR_ID T1, T2, T3, T4

Added To Oneline

Estimated Repair Time Hr 8

Equipment Type:

MOUNTING:

FedB

Feed Wire Size 6

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 4019

Isc 3P (A)mps 10488

Panel.Notes JUST REPLACE BRKRS. 6 THHN

Number Of Circuits 24MLOMCB

Phase 3Amp Rating 50Voltage 208/120

Short Circuit Rating 22000

Number Of Wires 4

Ground Wire Size 6Wire Type CU

Panel Schedule Available On Dwg

Approx Age 2005

Model# QOC24USManufacturer

SQUARE D

EquipName 4021

Room# 4021Floor 4Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 12

XFMR_ID T1, T2, T3, T4

Added To Oneline

Estimated Repair Time Hr 2

Equipment Type:

MOUNTING:

FedB RM 4024 BUS BKR

Feed Wire Size 6

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 4021

Isc 3P (A)mps 10517

Panel.Notes BREAKERS, PANEL S & BUS BRKRS

Number Of Circuits 16MLOMCB

Phase 3Amp Rating 100Voltage 208/120

Short Circuit Rating 22000

Number Of Wires 4

Ground Wire Size NONEWire Type CU

Panel Schedule Available On Dwg

Approx Age 2005

Model# QOC16USManufacturer

SQUARE D

EquipName 4035

Room# 4035Floor 4Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 13

XFMR_ID T1, T2, T3, T4

Added To Oneline

Estimated Repair Time Hr 8

Equipment Type:

MOUNTING:

FedB RM 4032 BUS BKR

Feed Wire Size 3

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 4035

Isc 3P (A)mps 15151

Panel.Notes REPLACE PANEL GUTS, BRKRS, WIRES & BUS BRKR, 20"WX30"HX5-3/4"D SEE

SURVEY SHEET

Number Of Circuits 24MLOMCB

Phase 3Amp Rating 100Voltage 208/120

Short Circuit Rating 42000

Number Of Wires 4

Ground Wire Size 8Wire Type CU

Panel Schedule Available On Dwg

Approx Age 1955

Model# C692980Manufacturer

WH

EquipName 4L2

Room# 4037 HALLFloor 4Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 14

XFMR_ID T1, T2, T3, T4

Added To Oneline

Estimated Repair Time Hr 8

Equipment Type:

MOUNTING:

FedB RM 4036 BUS BKR

Feed Wire Size 3

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 4L2

Isc 3P (A)mps 26935

Panel.Notes CLOTH WIRE, BRKR, PANEL, BUS DUCT BRKR REPLACE PANEL WITH NEW WHERE

GENERATOR TIME FREQ OFF LIBRARY HAS BUS DUCT TO 4TH FLOOR PROBABLY

400A FROM 4038 TO WINGS 3& 4 THEN STOP. 3 THW. PNL EL2 CKT 38,40,42 RM 2036

Number Of Circuits 12MLOMCB

Phase 3Amp Rating 100Voltage 208/120

Short Circuit Rating 10000

Number Of Wires 4

Ground Wire Size 8Wire Type CU

Panel Schedule Available On Dwg

Approx Age 1955

Model# C697617Manufacturer

WH

EquipName EL4

Room# 4038Floor 4Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 15

XFMR_ID T1, T2, T3, T4

Added To Oneline

Estimated Repair Time Hr

Equipment Type:

MOUNTING:

FedB RM 2036 PNL EL2

Feed Wire Size 3

Feeds Another Panel EL5(4536),EL6(2548)

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName EL4

Isc 3P (A)mps 7638

Panel.Notes LOOKS LIKE LAB PANEL UPS ALL VOLTAGE 88V FED BY UPS BELOW PANEL

Number Of Circuits 24MLOMCB

Phase 1Amp Rating 125Voltage 208/120

Short Circuit Rating 42000

Number Of Wires

Ground Wire Size NONEWire Type CU

Panel Schedule Available On Dwg

Approx Age 2005

Model# QOC24USManufacturer

SQUARE D

EquipName 4042D

Room# 4044Floor 4Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 17

XFMR_ID T1, T2, T3, T4

Added To Oneline

Estimated Repair Time Hr 8

Equipment Type:

MOUNTING:

FedB RM 4044 BUS BKR

Feed Wire Size 2

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 4042D

Isc 3P (A)mps 22997

Panel.Notes REPLACE PANEL, BRKRS & BUS DUCT BKRS 20"WX36"HX 5-3/4"D SEE SURVEY SHEET

Number Of Circuits 30MLOMCB

Phase 3Amp Rating 200Voltage 208/120

Short Circuit Rating 42000

Number Of Wires 4

Ground Wire Size NONEWire Type CU

Panel Schedule Available On Dwg

Approx Age 1955

Model# C693041Manufacturer

WH

EquipName 4L3

Room# 4053 HALLFloor 4Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 19

XFMR_ID T1, T2, T3, T4

Added To Oneline

Estimated Repair Time Hr 8

Equipment Type:

MOUNTING:

FedB RM 4054 BUS BKR

Feed Wire Size 3/0

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 4L3

Isc 3P (A)mps 22056

Panel.Notes REPLACE BRKRS ONLY & BUS BRKRS * PANEL IS RATED FOR 125A BUT FED WITH

150A BB CHANGE TO 125A BB. 1THHN

Number Of Circuits 24MLOMCB

Phase 3Amp Rating 125Voltage 208/120

Short Circuit Rating 22000

Number Of Wires 4

Ground Wire Size NONEWire Type CU

Panel Schedule Available On Dwg

Approx Age 2005

Model# QOC24USManufacturer

SQUARE D

EquipName 4054

Room# 4054Floor 4Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 20

XFMR_ID T1, T2, T3, T4

Added To Oneline

Estimated Repair Time Hr 2

Equipment Type:

MOUNTING:

FedB BUS BKR RM 4054

Feed Wire Size 1

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 4054

Isc 3P (A)mps 17613

Panel.Notes REPLACE BRKR ONLY

Number Of Circuits 20MLOMCB

Phase 3Amp Rating 100Voltage 208/120

Short Circuit Rating 22000

Number Of Wires 4

Ground Wire Size NONEWire Type CU

Panel Schedule Available On Dwg

Approx Age 1980

Model# QOC 420LManufacturer

SQUARE D

EquipName 7P21

Room# 4055Floor 4Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 21

XFMR_ID T1, T2, T3, T4

Added To Oneline

Estimated Repair Time Hr 2

Equipment Type:

MOUNTING:

FedB BUS BKR RM 4054

Feed Wire Size 3

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 7P21

Isc 3P (A)mps 13449

Panel.Notes REPLACE BRKR ONLY

Number Of Circuits 20MLOMCB

Phase 3Amp Rating 100Voltage 208/120

Short Circuit Rating 22000

Number Of Wires 4

Ground Wire Size NONEWire Type CU

Panel Schedule Available On Dwg

Approx Age 1980

Model# QOC 420LManufacturer

SQUARE D

EquipName 7P21

Room# 4055Floor 4Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 21

XFMR_ID T1, T2, T3, T4

Added To Oneline

Estimated Repair Time Hr 2

Equipment Type:

MOUNTING:

FedB BUS BKR RM 4054

Feed Wire Size 3

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 7P21

Isc 3P (A)mps 20736

Panel.Notes SURFACE MOUNT REPLACE PANELS, BRKRS, REPLACE WIRE, BUS BRKR

Number Of Circuits 12MLOMCB

Phase 3Amp Rating 50Voltage 208/120

Short Circuit Rating 10000

Number Of Wires 4

Ground Wire Size 10Wire Type CU

Panel Schedule Available On Dwg

Approx Age 1955

Model# C698401Manufacturer

WH

EquipName 4061

Room# 4061Floor 4Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 22

XFMR_ID T‐13, T‐14

Added To Oneline

Estimated Repair Time Hr 2

Equipment Type:

MOUNTING:

FedB BUS BKR

Feed Wire Size 6

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 4061

Isc 3P (A)mps 3779

Conduit Type EMT 1-1/4 "

Panel.Notes BRKR AND BUS BRKR REPLACE. FED FROM 100 BUS BREAKER

Number Of Circuits 20MLOMCB

Phase 3Amp Rating 100Voltage 208/120

Short Circuit Rating 22000

Number Of Wires 4

Ground Wire Size 6Wire Type CU

Panel Schedule Available On Dwg

Approx Age 1990

Model# QOC24UManufacturer

SQUARE D

EquipName 7P26

Room# 4062Floor 4Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 23

XFMR_ID T‐13, T‐14

Added To Oneline

Estimated Repair Time Hr 2

Equipment Type:

MOUNTING:

FedB RM 4062 BUS BKR

Feed Wire Size 3

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 7P26

Isc 3P (A)mps 11458

Panel.Notes REPLACE EVERYTHING BRKRS, PANEL, BUS BRKR, WIRE, WIRE NOT RATED

CORRECTLY 2 PANELS ONE 30 ONE 12 FIELD VERIFY NOTATION. 4TW

Number Of Circuits 12MLOMCB

Phase 3Amp Rating 80Voltage 208/120

Short Circuit Rating 10000

Number Of Wires 4

Ground Wire Size 8Wire Type CU

Panel Schedule Available On Dwg

Approx Age 1970

Model#Manufacturer

ITE

EquipName 7P20

Room# 4069Floor 4Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 25

XFMR_ID T‐13, T‐14

Added To Oneline

Estimated Repair Time Hr 8

Equipment Type:

MOUNTING:

FedB RM 4066 BUS BKR

Feed Wire Size 4

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 7P20

Isc 3P (A)mps 8079

Panel.Notes REPLACE PANEL, BRKR, WIRE, RECESS, BUS BREAKER 20"WX30"HX5-3/4"D SEE

SURVEY SHEET

Number Of Circuits 24MLOMCB

Phase 3Amp Rating 100Voltage 208/120

Short Circuit Rating 22000

Number Of Wires 4

Ground Wire Size 8Wire Type CU

Panel Schedule Available On Dwg

Approx Age 1955

Model# C693082Manufacturer

WH

EquipName 4L1A

Room# 4068 HALLFloor 4Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 26

XFMR_ID T‐13, T‐14

Added To Oneline

Estimated Repair Time Hr 8

Equipment Type:

MOUNTING:

FedB

Feed Wire Size 3

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 4L1A

Isc 3P (A)mps 12390

Conduit Type EMT 2"

Panel.Notes REPLACE BRKRS ONLY, BUS BRKR

Number Of Circuits 42MLOMCB

Phase 3Amp Rating 200Voltage 208/120

Short Circuit Rating 22000

Number Of Wires 4

Ground Wire Size NONEWire Type CU

Panel Schedule Available On Dwg

Approx Age 2005

Model# NQOD4421 225CUManufacturer

SQUARE D

EquipName 4078

Room# 4078Floor 4Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 30

XFMR_ID T‐13, T‐14

Added To Oneline

Estimated Repair Time Hr 2

Equipment Type:

MOUNTING:

FedB RM 4078 BUS BKR

Feed Wire Size 3/0

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 4078

Isc 3P (A)mps 19311

Conduit Type EMT 1-14

Panel.Notes REPLACE BRKRS PANEL, BUS BRKR 20"W X 30"H X 5-3/4"D SEE YELLOW SURVEY

SHEET

Number Of Circuits 24MLOMCB

Phase 3Amp Rating 100Voltage 208/120

Short Circuit Rating 25000

Number Of Wires 4

Ground Wire Size 6Wire Type CU

Panel Schedule Available On Dwg

Approx Age 1955

Model# C692981Manufacturer

WH

EquipName 4L2A

Room# 4083 HALLFloor 4Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 31

XFMR_ID T‐13, T‐14

Added To Oneline

Estimated Repair Time Hr 8

Equipment Type:

MOUNTING:

FedB

Feed Wire Size 3

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 4L2A

Isc 3P (A)mps 21014

Panel.Notes BREAKERS ONLY REPLACE UPS BYPASS/POWER AMPLIFIER/LTS4080. 3THHN

Number Of Circuits 30MLOMCB

Phase 3Amp Rating 100Voltage 208/120

Short Circuit Rating 42000

Number Of Wires 4

Ground Wire Size 6Wire Type CU

Panel Schedule Available On Dwg

Approx Age 2005

Model# NQUD430LManufacturer

SQUARE D

EquipName 4080WP

Room# 4080Floor 4Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 32

XFMR_ID T‐13, T‐14

Added To Oneline

Estimated Repair Time Hr 2

Equipment Type:

MOUNTING:

FedB RM 4080 BUS BKR

Feed Wire Size 3

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 4080WP

Isc 3P (A)mps 23000

Panel.Notes REPLACE BREAKERS, AND PANEL. fed from 100 bus breaker, WIRE THHN

Number Of Circuits 30MLOMCB

Phase 3Amp Rating 50Voltage 208/120

Short Circuit Rating 22000

Number Of Wires 4

Ground Wire Size 8Wire Type CU

Panel Schedule Available On Dwg

Approx Age 1980

Model# QO30USManufacturer Square D

EquipName 3083

Room# 3083Floor 3Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 34

XFMR_ID

Added To Oneline

Estimated Repair Time Hr

Equipment Type:

MOUNTING:

FedB RM 3083 HALL BUS BKR

Feed Wire Size 6

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 3083

Isc 3P (A)mps 11536

Panel.Notes RECESSED, REPLACE WIRE, BKRS, PANEL BUS BKRS. 2O"W X 38"H X 5-3/4"D, SEE

SURVEY SHEET FOR DIMENSIONS

Number Of Circuits 36MLOMCB

Phase 3Amp Rating 200Voltage 208/120

Short Circuit Rating 25000

Number Of Wires 4

Ground Wire Size 4Wire Type CU

Panel Schedule Available On Dwg

Approx Age 1955

Model# C692963Manufacturer

WH

EquipName 3L2A

Room# 3082 HALLFloor 3Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 35

XFMR_ID

Added To Oneline

Estimated Repair Time Hr

Equipment Type:

MOUNTING:

FedB

Feed Wire Size 3/0

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 3L2A

Isc 3P (A)mps 19949

Panel.Notes REPLACE BKRS, BUS BKRS ONLY FED FROM 200 BUS BRKR/HAS SURGE ARRESTER

& MOUNTING KIT, ;1#250KCMIL N;1$4 GND)

Number Of Circuits 42MLOMCB

Phase 3Amp Rating 200Voltage 208/120

Short Circuit Rating 22000

Number Of Wires 4

Ground Wire Size 4Wire Type CU

Panel Schedule Available On Dwg

Approx Age 2005

Model# QOC342MSManufacturer

SQ D

EquipName 3078

Room# 3078Floor 3Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 36

XFMR_ID

Added To Oneline

Estimated Repair Time Hr

Equipment Type:

MOUNTING:

FedB RM 3078 BUS BKR

Feed Wire Size 3/0

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 3078

Isc 3P (A)mps 18963

Panel.Notes Replace BREAKERS, BUS BREAKERS only. Code violation no room in front of panel. FED

FROM 100 BUS BREAKER. 2 THHN

Number Of Circuits 24MLOMCB

Phase 3Amp Rating 100Voltage 208/120

Short Circuit Rating 22000

Number Of Wires 4

Ground Wire Size 10Wire Type CU

Panel Schedule Available On Dwg

Approx Age 2005

Model# QOC24USManufacturer

SQ D

EquipName 3082

Room# 3082Floor 3Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 37

XFMR_ID

Added To Oneline

Estimated Repair Time Hr

Equipment Type:

MOUNTING:

FedB RM 3082 BUS BKR

Feed Wire Size 2

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 3082

Isc 3P (A)mps 17356

Panel.Notes Replace BREAKERS, and bus breakers. FED FROM 100 BUS BREAKER, ;1#1/0 N

Number Of Circuits 30MLOMCB

Phase 3Amp Rating 100Voltage 208/120

Short Circuit Rating 22000

Number Of Wires 4

Ground Wire Size 6Wire Type CU

Panel Schedule Available On Dwg

Approx Age 2000

Model# QOC30USManufacturer

SQ D

EquipName 3079

Room# 3079Floor 3Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 38

XFMR_ID

Added To Oneline

Estimated Repair Time Hr

Equipment Type:

MOUNTING:

FedB RM 3078 BUS BKR

Feed Wire Size 3

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 3079

Isc 3P (A)mps 14461

Panel.Notes REPLACE BREAKERS, AND PANEL. 125 MAIN LUGS, 6 THHN

Number Of Circuits 24MLOMCB

Phase 3Amp Rating 50Voltage 208/120

Short Circuit Rating 10000

Number Of Wires 4

Ground Wire Size 8Wire Type CU

Panel Schedule Available On Dwg

Approx Age 1980

Model# QOC24USManufacturer

SQ D

EquipName 3075

Room# 3075Floor 3Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 39

XFMR_ID

Added To Oneline

Estimated Repair Time Hr

Equipment Type:

MOUNTING:

FedB RM 3074 BUS BKR

Feed Wire Size 6

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 3075

Isc 3P (A)mps 7542

Panel.Notes REPLACE PANEL, BREAKERS, BUS BREAKERS. ESTIMATED SHUT DOWN TIME 2 HR.

FED FROM 100 BUS BREAKER_KW/HR. 2 TW

Number Of Circuits 42MLOMCB

Phase 3Amp Rating 100Voltage 208/120

Short Circuit Rating 22000

Number Of Wires 4

Ground Wire Size NONEWire Type CU

Panel Schedule Available On Dwg

Approx Age 1960

Model# TL42-420S/NP245771Manufacturer

GE

EquipName 3074

Room# 3074Floor 3Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 40

XFMR_ID

Added To Oneline

Estimated Repair Time Hr

Equipment Type:

MOUNTING:

FedB RM 3074 BUS BKR

Feed Wire Size 2

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 3074

Isc 3P (A)mps 15719

Panel.Notes REPLACE BREAKER, PANEL, WIRES, BUS BREAKER

Number Of Circuits 12MLOMCB

Phase 3Amp Rating 50Voltage 208/120

Short Circuit Rating 10000

Number Of Wires 4

Ground Wire Size 8Wire Type CU

Panel Schedule Available On Dwg

Approx Age 1955

Model# C698373Manufacturer

WH

EquipName 3071

Room# 3071Floor 3Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 41

XFMR_ID

Added To Oneline

Estimated Repair Time Hr

Equipment Type:

MOUNTING:

FedB RM 3070 BUS BKR

Feed Wire Size 6

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 3071

Isc 3P (A)mps 7494

Panel.Notes REPLACE PANEL, BREAKERS, BUS BREAKER, WIRE CLOTH. ESTIMATED DOWN

TIME 8 HRS. FED FROM 100 BUS BREAKER

Number Of Circuits 12MLOMCB

Phase 3Amp Rating 50Voltage 208/120

Short Circuit Rating 22000

Number Of Wires 4

Ground Wire Size 10Wire Type CU

Panel Schedule Available On Dwg

Approx Age 1955

Model# C698369Manufacturer

WH

EquipName 3070

Room# 3070Floor 3Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 42

XFMR_ID

Added To Oneline

Estimated Repair Time Hr

Equipment Type:

MOUNTING:

FedB RM 3070 BUS BKR

Feed Wire Size 6

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 3070

Isc 3P (A)mps 10767

Panel.Notes REPLACE PANEL, BREAKERS, BUS BREAKERS, WIRE. 20 X 30 X 5-3/4 SEE SHEET FOR

DIMENSIONS

Number Of Circuits 24MLOMCB

Phase 3Amp Rating 100Voltage 208/120

Short Circuit Rating 22000

Number Of Wires 4

Ground Wire Size NONEWire Type CU

Panel Schedule Available On Dwg

Approx Age 1955

Model# C693081Manufacturer

WH

EquipName 3L1A

Room# 3068 HALLFloor 3Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 43

XFMR_ID

Added To Oneline

Estimated Repair Time Hr

Equipment Type:

MOUNTING:

FedB

Feed Wire Size 3

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 3L1A

Isc 3P (A)mps 15011

Panel.Notes REPLACE BREAKERS AND BUS BREAKERS. ESTIMATED DOWN TIME 2 HRS. FED

FROM 50 BUS BREAKER, ;1#4 N)

Number Of Circuits 24MLOMCB

Phase 3Amp Rating 50Voltage 208/120

Short Circuit Rating 22000

Number Of Wires 4

Ground Wire SizeWire Type CU

Panel Schedule Available On Dwg

Approx Age 2005

Model# QOC24US125Manufacturer

SQ D

EquipName 3065

Room# 3067Floor 3Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 45

XFMR_ID

Added To Oneline

Estimated Repair Time Hr

Equipment Type:

MOUNTING:

FedB RM 3066 BUS BKR

Feed Wire Size 8

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 3065

Isc 3P (A)mps 9773

Panel.Notes REPLACE BREAKERS, BUS BREAKERS. CODE VIOLATION, FED WITH A 150 AMP 3 PHASE BUS BREAKER NEED TO MAKE 125 AMP 3066 and 3064 are the same room. FED

FROM 100 BUS BREAKER, 2 THHN

Number Of Circuits 20MLOMCB

Phase 3Amp Rating 100Voltage 208/120

Short Circuit Rating 22000

Number Of Wires 4

Ground Wire Size NONEWire Type CU

Panel Schedule Available On Dwg

Approx Age 2013

Model# QOC24UManufacturer

SQ D

EquipName 7P25

Room# 3066Floor 3Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 46

XFMR_ID

Added To Oneline

Estimated Repair Time Hr

Equipment Type:

MOUNTING:

FedB RM 3066 BUS BKR

Feed Wire Size 2

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 7P25

Isc 3P (A)mps 13280

Panel.Notes REPLACE BREAKERS, BUS BREAKERS. CODE VIOLATION, PANEL IS BEING FED BY 150A 3 PHASE BUS BREAKER. FED FROM 100 BUS BREAKER, 3066 and 3064 are the same room

Number Of Circuits 20MLOMCB

Phase 3Amp Rating 100Voltage 208/120

Short Circuit Rating 22000

Number Of Wires 4

Ground Wire Size NONEWire Type CU

Panel Schedule Available On Dwg

Approx Age 2005

Model# QOC24UManufacturer

SQ D

EquipName 7P24

Room# 3064Floor 3Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 47

XFMR_ID

Added To Oneline

Estimated Repair Time Hr

Equipment Type:

MOUNTING:

FedB RM 3064 BUS BKR

Feed Wire Size 2

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 7P24

Isc 3P (A)mps 13155

Panel.Notes REPLACE BREAKERS, BUS BREAKERS. CODE VIOLATION, PANEL IS BEING FED BY 150A 3 PHASE BUS BREAKER. FED FROM 100 BUS BREAKER, 3066 and 3064 are the same room

Number Of Circuits 20MLOMCB

Phase 3Amp Rating 100Voltage 208/120

Short Circuit Rating 22000

Number Of Wires 4

Ground Wire Size NONEWire Type CU

Panel Schedule Available On Dwg

Approx Age 2005

Model# QOC24UManufacturer

SQ D

EquipName 7P24

Room# 3064Floor 3Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 47

XFMR_ID

Added To Oneline

Estimated Repair Time Hr

Equipment Type:

MOUNTING:

FedB RM 3064 BUS BKR

Feed Wire Size 2

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 7P24

Isc 3P (A)mps 23427

Conduit Type

Panel.Notes REPLACE PANEL, BREAKERS, WIRE, AND BUS BREAKERS. FED FROM 100 BUS

BREAKER

Number Of Circuits 24MLOMCB

Phase 3Amp Rating 100Voltage 208/120

Short Circuit Rating 22000

Number Of Wires 4

Ground Wire Size NONEWire Type CU

Panel Schedule Available On Dwg

Approx Age 1955

Model# EQB/MLA24-4LManufacturer

ITE

EquipName 3062

Room# 3062Floor 3Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 48

XFMR_ID

Added To Oneline

Estimated Repair Time Hr

Equipment Type:

MOUNTING:

FedB RM 3062 BUS BKR

Feed Wire Size 3

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 3062

Isc 3P (A)mps 12920

Panel.Notes REPLACE BREAKERS ONLY, RELABEL PANEL 3063. FED FROM 100 BUS BREAKER

Number Of Circuits 20MLOMCB

Phase 3Amp Rating 100Voltage 208/120

Short Circuit Rating 22000

Number Of Wires 4

Ground Wire Size NONEWire Type CU

Panel Schedule Available On Dwg

Approx Age 1980

Model# QOC420LManufacturer

SQ D

EquipName 7P14

Room# 3063Floor 3Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 49

XFMR_ID

Added To Oneline

Estimated Repair Time Hr

Equipment Type:

MOUNTING:

FedB RM 3062 BUS BKR

Feed Wire Size 3

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 7P14

Isc 3P (A)mps 12848

Panel.Notes REPLACE PANEL, WIRES, BREAKERS, AND BUS BREAKERS. 20 X 30 X 5-3/4, SEE

SHEET FOR DIMENSIONS. FED FROM 100 BUS BREAKER

Number Of Circuits 24MLOMCB

Phase 3Amp Rating 100Voltage 208/120

Short Circuit Rating 22000

Number Of Wires 4

Ground Wire Size NONEWire Type CU

Panel Schedule Available On Dwg

Approx Age 1955

Model# C692978Manufacturer

WH

EquipName 3L3

Room# 3053 HALLFloor 3Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 54

XFMR_ID

Added To Oneline

Estimated Repair Time Hr

Equipment Type:

MOUNTING:

FedB RM 3054 BUS BKR

Feed Wire Size 3

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 3L3

Isc 3P (A)mps 18443

Conduit Type EMT 1"

Panel.Notes REPLACE BREAKERS ONLY. CODE VIOLATION, NEED TO HAVE 36" IN FRONT OF

PANEL. FED FROM 100/50 BUS BREAKER

Number Of Circuits 12MLOMCB

Phase 3Amp Rating 50Voltage 208/120

Short Circuit Rating 10000

Number Of Wires 4

Ground Wire Size NONEWire Type CU

Panel Schedule Available On Dwg

Approx Age 1980

Model# QOC16US/QOC412LManufacturer

SQ D

EquipName 3053

Room# 3053Floor 3Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 55

XFMR_ID

Added To Oneline

Estimated Repair Time Hr

Equipment Type:

MOUNTING:

FedB RM 3050 BUS BKR

Feed Wire Size 6

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 3053

Isc 3P (A)mps 7686

Panel.Notes REPLACE PANEL, BREAKER, BUS BREAKER

Number Of Circuits 30MLOMCB

Phase 3Amp Rating 100Voltage 208/120

Short Circuit Rating 22000

Number Of Wires 4

Ground Wire Size 8Wire Type CU

Panel Schedule Available On Dwg

Approx Age 1980

Model# QOC3OUSManufacturer

SQ D

EquipName 3050

Room# 3050Floor 3Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 56

XFMR_ID

Added To Oneline

Estimated Repair Time Hr

Equipment Type:

MOUNTING:

FedB RM 3050 BUS BKR

Feed Wire Size 3

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 3050

Isc 3P (A)mps 19913

Panel.Notes REPLACE BREAKERS ONLY. FED FROM 100/50 BUS BREAKER

Number Of Circuits 12MLOMCB

Phase 3Amp Rating 50Voltage 208/120

Short Circuit Rating 10000

Number Of Wires 4

Ground Wire Size NONEWire Type CU

Panel Schedule Available On Dwg

Approx Age 1980

Model# QOC16USManufacturer

SQ D

EquipName 3047A

Room# 3049Floor 3Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 57

XFMR_ID

Added To Oneline

Estimated Repair Time Hr

Equipment Type:

MOUNTING:

FedB RM 3050A BUS BKR

Feed Wire Size 6

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 3047A

Isc 3P (A)mps 8281

Panel.Notes REPLACE PANEL, BREAKERS, BUS BREAKER. ESTIMATED DOWN TIME 8 HRS.

Number Of Circuits 24MLOMCB

Phase 3Amp Rating 100Voltage 208/120

Short Circuit Rating 42000

Number Of Wires 4

Ground Wire Size NONEWire Type CU

Panel Schedule Available On Dwg

Approx Age 1970

Model# EQ424AManufacturer

ITE

EquipName 3046

Room# 3046Floor 3Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 58

XFMR_ID

Added To Oneline

Estimated Repair Time Hr

Equipment Type:

MOUNTING:

FedB RM 3046 BUS BKR

Feed Wire Size 2

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 3046

Isc 3P (A)mps 21931

Panel.Notes REPLACE BREAKERS ONLY

Number Of Circuits 12MLOMCB

Phase 3Amp Rating 50Voltage 208/120

Short Circuit Rating 22000

Number Of Wires 4

Ground Wire Size NONEWire Type CU

Panel Schedule Available On Dwg

Approx Age 1980

Model# QO412L125Manufacturer

SQ D

EquipName 3047B

Room# 3045Floor 3Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 59

XFMR_ID

Added To Oneline

Estimated Repair Time Hr

Equipment Type:

MOUNTING:

FedB RM 3044 BUS BKR

Feed Wire Size 6

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 3047B

Isc 3P (A)mps 11329

Conduit Type

Panel.Notes REPLACE PANEL, BREAKERS, WIRE, BUS BREAKER

Number Of Circuits 12MLOMCB

Phase 3Amp Rating 100Voltage 208/120

Short Circuit Rating 10000

Number Of Wires 4

Ground Wire Size 8Wire Type CU

Panel Schedule Available On Dwg

Approx Age 1955

Model# C693018Manufacturer

WH

EquipName EL3

Room# 3038Floor 3Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 60

XFMR_ID

Added To Oneline

Estimated Repair Time Hr

Equipment Type:

MOUNTING:

FedB RM 2036 PNL EL2

Feed Wire Size 3

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName EL3

Isc 3P (A)mps 8869

Number Of Circuits 12MLOMCB

Phase 3Amp Rating 50Voltage 208/120

Short Circuit Rating 22000

Number Of Wires 4

Ground Wire Size 8Wire Type CU

Panel Schedule Available On Dwg

Approx Age 1980

Model# QOC16USManufacturer

SQ D

EquipName 3036

Room# 3036Floor 3Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 61

XFMR_ID

Added To Oneline

Estimated Repair Time Hr

Equipment Type:

MOUNTING:

FedB RM 3036 BUS BKR

Feed Wire Size 8

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 3036

Isc 3P (A)mps 15947

Panel.Notes REPLACE PANEL, BREAKERS, BUS DUCT BREAKER, WIRES. 20 X 30 X 5-3/4, SEE

SHEET FOR DIMENSIONS.

Number Of Circuits 24MLOMCB

Phase 3Amp Rating 100Voltage 208/120

Short Circuit Rating 42000

Number Of Wires 4

Ground Wire Size 8Wire Type CU

Panel Schedule Available On Dwg

Approx Age 1955

Model# C692977Manufacturer

WH

EquipName 3L2

Room# 3034 HALLFloor 3Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 62

XFMR_ID

Added To Oneline

Estimated Repair Time Hr

Equipment Type:

MOUNTING:

FedB RM 3034 BUS BKR

Feed Wire Size 3

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 3L2

Isc 3P (A)mps 26832

Panel.Notes REPLACE BREAKERS WITH 22 K BREAKERS. 200A MAIN LUGS FED FROM 100 BUS

BREAKER

Number Of Circuits 30MLOMCB

Phase 3Amp Rating 100Voltage 208/120

Short Circuit Rating 42000

Number Of Wires 4

Ground Wire Size 8Wire Type CU

Panel Schedule Available On Dwg

Approx Age 1980

Model# QOC30USManufacturer

SQ D

EquipName 3034

Room# 3034Floor 3Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 63

XFMR_ID

Added To Oneline

Estimated Repair Time Hr

Equipment Type:

MOUNTING:

FedB RM 3034 BUS BKR

Feed Wire Size 3

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 3034

Isc 3P (A)mps 28100

Panel.Notes REPLACE BREAKERS. FED FROM 100 BUS BREAKER

Number Of Circuits 24MLOMCB

Phase 3Amp Rating 150Voltage 208/120

Short Circuit Rating 42000

Number Of Wires 4

Ground Wire Size NONEWire Type CU

Panel Schedule Available On Dwg

Approx Age 1970

Model# CR-268288Manufacturer

GE

EquipName 3032

Room# 3032Floor 3Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 64

XFMR_ID

Added To Oneline

Estimated Repair Time Hr

Equipment Type:

MOUNTING:

FedB RM 3032 BUS BKR

Feed Wire Size 2/0

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 3032

Isc 3P (A)mps 30507

Panel.Notes REPLACE BREAKERS, BUS BREAKERS

Number Of Circuits 42MLOMCB

Phase 3Amp Rating 200Voltage 208/120

Short Circuit Rating 22000

Number Of Wires 4

Ground Wire Size NONEWire Type CU

Panel Schedule Available On Dwg

Approx Age 2005

Model# NQ442L2CManufacturer

SQ D

EquipName 3028A

Room# 3028AFloor 3Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 65

XFMR_ID

Added To Oneline

Estimated Repair Time Hr

Equipment Type:

MOUNTING:

FedB RM 3028 BUS BKR

Feed Wire Size 3/0

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 3028A

Isc 3P (A)mps 19630

Panel.Notes REPLACE PANEL, BREAKERS, BUS BREAKERS. CODE VIOLATION, NEED CORRECT

ACCESS, MOVE PANEL TO OTHER LOCATION AWA FROM CLOSET. RECPS 3021 WEST

VIDEO IS 0325

Number Of Circuits 12MLOMCB

Phase 3Amp Rating 50Voltage 208/120

Short Circuit Rating 10000

Number Of Wires 4

Ground Wire Size 10Wire Type CU

Panel Schedule Available On Dwg

Approx Age 1955

Model# C698259Manufacturer

WH

EquipName 3021

Room# 3021Floor 3Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 66

XFMR_ID

Added To Oneline

Estimated Repair Time Hr

Equipment Type:

MOUNTING:

FedB RM 3022 BUS BKR

Feed Wire Size 6

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 3021

Isc 3P (A)mps 7847

Conduit Type EMT 2"'

Panel.Notes REPLACE PANEL, BREAKERS, WIRE, BUS BREAKER. 20 X 44 X 5-3/4" SEE SHEET FOR

DIMENSIONS.

Number Of Circuits 42MLOMCB

Phase 3Amp Rating 200Voltage 208

Short Circuit Rating 42000

Number Of Wires 4

Ground Wire Size 6Wire Type CU

Panel Schedule Available On Dwg

Approx Age 1955

Model# C69042Manufacturer

WH

EquipName 3L1

Room# 3014 HALLFloor 3Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 67

XFMR_ID

Added To Oneline

Estimated Repair Time Hr

Equipment Type:

MOUNTING:

FedB

Feed Wire Size 3/0

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 3L1

Isc 3P (A)mps 22351

Panel.Notes CODE VIOLATION, PANEL NEEDS 3' IN FRONT PER NEC. 22 KAIC CKT BRKRS, ; 1#1/0 N

Number Of Circuits 24MLOMCB

Phase 3Amp Rating 100Voltage 208/120

Short Circuit Rating 22000

Number Of Wires 4

Ground Wire Size 8Wire Type CU

Panel Schedule Available On Dwg

Approx Age 2000

Model# QOC420LManufacturer

SQ D

EquipName 3014

Room# 3014Floor 3Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 68

XFMR_ID

Added To Oneline

Estimated Repair Time Hr

Equipment Type:

MOUNTING:

FedB RM 3014 BUS BKR

Feed Wire Size 3

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 3014

Isc 3P (A)mps 17936

Conduit Type EMT 2-1/2

Panel.Notes REPLACE BREAKERS ONLY. FED FROM 200 BUS BREAKER

Number Of Circuits 30MLOMCB

Phase 3Amp Rating 200Voltage 208/120

Short Circuit Rating 25000

Number Of Wires 4

Ground Wire Size NONEWire Type CU

Panel Schedule Available On Dwg

Approx Age 2004

Model# NQOD 430L225CUManufacturer

SQ D

EquipName 3006

Room# 3008Floor 3Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 69

XFMR_ID

Added To Oneline

Estimated Repair Time Hr

Equipment Type:

MOUNTING:

FedB RM 3008 BUS BKR

Feed Wire Size 4/0

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 3006

Isc 3P (A)mps 20336

Panel.Notes PANEL WILL REMAIN AS IT IS. SEE BOX FOR PANEL SCHEDULE. (4#3/0)

Number Of Circuits 30MLOMCB

Phase 3Amp Rating 200Voltage 208/120

Short Circuit Rating 22000

Number Of Wires 4

Ground Wire Size NONEWire Type CU

Panel Schedule Available On Dwg

Approx Age 2015

Model# NQ442L2CManufacturer

SQ D

EquipName 7P12

Room# 3001Floor 3Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 70

XFMR_ID

Added To Oneline

Estimated Repair Time Hr

Equipment Type:

MOUNTING:

FedB

Feed Wire Size 3/0

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 7P12

Isc 3P (A)mps 13372

Panel.Notes REPLACE PANEL, BREAKERS, WIRES CLOTH

Number Of Circuits 12MLOMCB

Phase 3Amp Rating 50Voltage 208/120

Short Circuit Rating 22000

Number Of Wires 4

Ground Wire Size 8Wire Type CU

Panel Schedule Available On Dwg

Approx Age 1950

Model# C698196Manufacturer Westinghouse

EquipName 2031

Room# 2031Floor 2Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1E2SP

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 71

XFMR_ID

Added To Oneline

Estimated Repair Time Hr

Equipment Type:

MOUNTING:

FedB RM 2030 BUS BKR

Feed Wire Size 6

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 2031

Isc 3P (A)mps 9811

Conduit Type EMT 1 1/4"

Panel.Notes REPLACE BREAKERS ONLY. CODE VIOLATION, WATER PIPE ABOVE PANEL, REQUIRED ACCESS SPACE IS NOT PER NEC, ADDED PANEL SCHEDLE

Number Of Circuits 20MLOMCB

Phase 3Amp Rating 100Voltage 208/120

Short Circuit Rating 22000

Number Of Wires 4

Ground Wire Size NONEWire Type CU

Panel Schedule Available On Dwg

Approx Age 1990

Model# QON42OL125/QOC4Manufacturer

SQ D

EquipName 7P21

Room# 2033Floor 2Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1E2SP

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 72

XFMR_ID

Added To Oneline

Estimated Repair Time Hr

Equipment Type:

MOUNTING:

FedB RM 2032 BUS BKR

Feed Wire Size 3

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 7P21

Isc 3P (A)mps 20736

Panel.Notes REPLACE BREAKERS ONLY. CODE VIOLATION, WATER PIPE ABOVE PANEL, REQUIRED ACCESS SPACE IS NOT PER NEC, ADDED PANEL SCHEDLE

Number Of Circuits 20MLOMCB

Phase 3Amp Rating 100Voltage 208/120

Short Circuit Rating 22000

Number Of Wires 4

Ground Wire Size NONEWire Type CU

Panel Schedule Available On Dwg

Approx Age 1990

Model# QON42OL125/QOC4Manufacturer

SQ D

EquipName 7P21

Room# 2033Floor 2Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1E2SP

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 72

XFMR_ID

Added To Oneline

Estimated Repair Time Hr

Equipment Type:

MOUNTING:

FedB RM 2032 BUS BKR

Feed Wire Size 3

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 7P21

Isc 3P (A)mps 13449

Panel.Notes REPLACE BREAKERS, BUS BREAKERS

Number Of Circuits 30MLOMCB

Phase 3Amp Rating 100Voltage 208/120

Short Circuit Rating 22000

Number Of Wires 4

Ground Wire Size NONEWire Type CU

Panel Schedule Available On Dwg

Approx Age 2005

Model# NQOD442L225Manufacturer

SQ D

EquipName 7P22

Room# 2035Floor 2Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1E2SP

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 73

XFMR_ID

Added To Oneline

Estimated Repair Time Hr

Equipment Type:

MOUNTING:

FedB RM 2034 BUS BKR

Feed Wire Size 3

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 7P22

Isc 3P (A)mps 20878

Panel.Notes REPLACE PANEL, BREAKERS, BUS BREAKER. ADDED SCHEDULE TO DRAWINGS

Number Of CircuitsMLOMCB

Phase 3Amp Rating 125Voltage 208/120

Short Circuit Rating 22000

Number Of Wires 4

Ground Wire Size NONEWire Type CU

Panel Schedule Available On Dwg

Approx Age 1980

Model# G2442ML3150Manufacturer

ITE

EquipName 2L10

Room# 2047BFloor 2Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1E2SP

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 74

XFMR_ID

Added To Oneline

Estimated Repair Time Hr

Equipment Type:

MOUNTING:

FedB

Feed Wire Size 1

Feeds Another Panel

Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr

ComponentName 2L10

Isc 3P (A)mps 16525

Conduit Type EMT 4"

Panel.Notes REPLACE BREAKERS, BUS BREAKERS/VIDEO FOR THIS PANEL WITH 76

Number Of Circuits 38MLOMCB

Phase 3Amp Rating 350Voltage 208/120

Short Circuit Rating 22000

Number Of Wires 4

Ground Wire Size NONEWire Type CU

Panel Schedule Available On Dwg

Approx Age 1990

Model# ALF3424MBManufacturer

GE

EquipName EP3

Room# 2047BFloor 2Building Section Spine

NIST ELECTRICAL PANEL SURVEY Drawing Nam 1E2SP

Main CB Rating Need To Revie Visited Not Installed

DEMOLITION

Panel INDEX 75

XFMR_ID

Added To Oneline

Estimated Repair Time Hr

Equipment Type:

MOUNTING:

FedB RM 2042 BUS BKR

Feed Wire Size 500

Feeds Another Panel EP3B(2053),EP3C(2047B),EMG40 16,EMG3527, EP3A(2047B)Cannot Find Fee DwgAddedviewPortMatchesOneline

Schedule

ReplaceBkrsOnly ReplacePanelBrkrs…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it.