Panel_Input_06-26-18.pdf
PDF 965 KB Posted
- Attached to
- Building 1 Circuit Breaker Replacement Federal contract opportunity
- Solicitation number
- NB194000-18-02008
About this file
Panel Inputs - additional information offerors may find helpful
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Site_Visit_Information.pdf | ||
| 1EW1.pdf | ||
| Questions_and_Responses.docx | DOCX document | |
| 1e4sp.pdf | ||
| 1EW1.pdf | ||
| One_Lines.pdf | ||
| 1e0sp.pdf | ||
| Attachment_IV_-_Instructions_and_Evaluation.pdf | ||
| 1e3sp.pdf | ||
| Attachment_II-_Applicable_Provisions_and_Clauses.pdf | ||
| Attachment_III_Wage_Determination.pdf | ||
| 1E2SP.pdf | ||
| Attachment_V_Exp_Proj-Data-Sheet.doc | DOC document | |
| 1EW2.pdf | ||
| 1e1sp.pdf | ||
| Attachment_VI__NIST_Boulder_PPQ_Form.doc | DOC document | |
| Attachment_I_-_SOW_B1_Circuit_Breaker_Replacement.pdf |
Show all 17
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Conduit Type EMT 1-1/4
Panel.Notes Old cloth wire, old bakalite. Replace panel, breakers, wire, bus breakers
Number Of Circuits 18MLOMCB
Phase 3Amp Rating 100Voltage 208/120
Short Circuit Rating 10000
Number Of Wires 4
Ground Wire Size 8Wire Type CU
Panel Schedule Available On Dwg
Approx Age 1955
Model# C693098Manufacturer
WH
EquipName 4001
Room# 4001AFloor 4Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 1
XFMR_ID T1, T2, T3, T4
Added To Oneline
Estimated Repair Time Hr 8
Equipment Type:
MOUNTING:
FedB BUS BKR RM 4006
Feed Wire Size 3
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 4001
Isc 3P (A)mps 7823
Panel
Surface
Conduit Type EMT 1-1/4"
Panel.Notes Fed from Bus breaker same ROOM, Replace breakers in kind
Number Of Circuits 12MLOMCB
Phase 3Amp Rating 100Voltage 208/120
Short Circuit Rating 22000
Number Of Wires 4
Ground Wire Size 8Wire Type CU
Panel Schedule Available On Dwg
Approx Age 1980
Model# QOManufacturer
SQUARE D
EquipName 4006
Room# 4006Floor 4Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 2
XFMR_ID T1, T2, T3, T4
Added To Oneline
Estimated Repair Time Hr 2
Equipment Type:
MOUNTING:
FedB
Feed Wire Size 2
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 4006
Isc 3P (A)mps 13163
Recessed
Panel.Notes fed from bus breaker above panel, cloth wiring Replace panel & breakers look at replace bars and breakers may be surface 20"W x22"Hx 4 1/8" D see survey sheet
Number Of Circuits 12MLOMCB
Phase 3Amp Rating 50Voltage 208/120
Short Circuit Rating 22000
Number Of Wires 4
Ground Wire Size 10Wire Type CU
Panel Schedule Available On Dwg
Approx Age 1950
Model# C698183Manufacturer
WH
EquipName 4008
Room# 4008Floor 4Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 3
XFMR_ID T1, T2, T3, T4
Added To Oneline
Estimated Repair Time Hr 8
Equipment Type:
MOUNTING:
FedB
Feed Wire Size 6
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 4008
Isc 3P (A)mps 14207
Panel.Notes Replace panel & wire replace wire also breakers
Number Of Circuits 12MLOMCB
Phase 3Amp Rating 50Voltage 208/120
Short Circuit Rating 10000
Number Of Wires 4
Ground Wire Size 10Wire Type CU
Panel Schedule Available On Dwg
Approx Age 1950
Model#Manufacturer
WH
EquipName 4007
Room# 4007Floor 4Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 4
XFMR_ID T1, T2, T3, T4
Added To Oneline
Estimated Repair Time Hr 8
Equipment Type:
MOUNTING:
FedB RM 4008 BUS BKR
Feed Wire Size 6
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 4007
Isc 3P (A)mps 9527
Panel.Notes Replace panel, breakers, wire
Number Of Circuits 12MLOMCB
Phase 3Amp Rating 50Voltage 208/120
Short Circuit Rating 10000
Number Of Wires 4
Ground Wire Size 10Wire Type CU
Panel Schedule Available On Dwg
Approx Age 1955
Model# DNYA33764STXManufacturer
WH
EquipName 4011
Room# 4011Floor 4Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 5
XFMR_ID T1, T2, T3, T4
Added To Oneline
Estimated Repair Time Hr 8
Equipment Type:
MOUNTING:
FedB RM 4012 BUS BKR
Feed Wire Size 6
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 4011
Isc 3P (A)mps 9806
Panel.Notes Code violation, Need room in front of panel. Replace breakers and bus breakers. 2 THHN
Number Of Circuits 20MLOMCB
Phase 3Amp Rating 100Voltage 208/120
Short Circuit Rating 22000
Number Of Wires 4
Ground Wire Size NONEWire Type CU
Panel Schedule Available On Dwg
Approx Age 2005
Model# Q0C420LManufacturer
SQ D
EquipName 4012
Room# 4012Floor 4Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 6
XFMR_ID T1, T2, T3, T4
Added To Oneline
Estimated Repair Time Hr 2
Equipment Type:
MOUNTING:
FedB RM 4012 BUS BKR
Feed Wire Size 2
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 4012
Isc 3P (A)mps 17519
Panel.Notes Replace breakers only, 2hrs estimated shut down time VIDEO IS EMG4016. Fed from Panel EP3 ckt 1,3,5 - Rm 2047B
Number Of Circuits 16MLOMCB
Phase 3Amp Rating 100Voltage 208/120
Short Circuit Rating 10000
Number Of Wires 4
Ground Wire Size 4Wire Type CU
Panel Schedule Available On Dwg
Approx Age 2005
Model# QOC1603Manufacturer
SQ D
EquipName EMG4016
Room# 4016Floor 4Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 7
XFMR_ID T1, T2, T3, T4
Added To Oneline
Estimated Repair Time Hr 2
Equipment Type:
MOUNTING:
FedB RM 2047B PNL EP3
Feed Wire Size 4
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName EMG4016
Isc 3P (A)mps 1560
Panel.Notes REPLACE BREAKERS, BUS BREAKER ONLY.
Number Of Circuits 24MLOMCB
Phase 3Amp Rating 100Voltage 208/120
Short Circuit Rating 22000
Number Of Wires 4
Ground Wire Size NONEWire Type CU
Panel Schedule Available On Dwg
Approx Age 2005
Model# QOC24UManufacturer
SQ D
EquipName 4016
Room# 4016Floor 4Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 8
XFMR_ID T1, T2, T3, T4
Added To Oneline
Estimated Repair Time Hr
Equipment Type:
MOUNTING:
FedB RM 4016 BUS BREAKER
Feed Wire Size 2
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 4016
Isc 3P (A)mps 19101
Panel.Notes REPLACE BREAKERS ONLY, 3 THHN
Number Of Circuits 12MLOMCB
Phase 3Amp Rating 100Voltage 208/120
Short Circuit Rating 22000
Number Of Wires 4
Ground Wire Size NONEWire Type CU
Panel Schedule Available On Dwg
Approx Age 1990
Model# QOC412LManufacturer
SQUARE D
EquipName 4015
Room# 4015Floor 4Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 9
XFMR_ID T1, T2, T3, T4
Added To Oneline
Estimated Repair Time Hr
Equipment Type:
MOUNTING:
FedB
Feed Wire Size 3
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 4015
Isc 3P (A)mps 13708
Panel.Notes REPLACE PANEL, BRKR, WIRE, BUS BREAKER
Number Of Circuits 12MLOMCB
Phase 3Amp Rating 50Voltage 208/120
Short Circuit Rating 22000
Number Of Wires 4
Ground Wire Size 10Wire Type CU
Panel Schedule Available On Dwg
Approx Age 1955
Model# C698390Manufacturer
WH
EquipName 4020
Room# 4020Floor 4Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 10
XFMR_ID T1, T2, T3, T4
Added To Oneline
Estimated Repair Time Hr 8
Equipment Type:
MOUNTING:
FedB
Feed Wire Size 6
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 4020
Isc 3P (A)mps 15634
Panel.Notes REPLACE PANEL, BRKRS, BUS BRKR, WIRE CLOTH
Number Of Circuits 12MLOMCB
Phase 3Amp Rating 50Voltage 208/120
Short Circuit Rating 22000
Number Of Wires 4
Ground Wire Size 10Wire Type CU
Panel Schedule Available On Dwg
Approx Age 1955
Model# C698393Manufacturer
WH
EquipName 4019
Room# 4019Floor 4Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 11
XFMR_ID T1, T2, T3, T4
Added To Oneline
Estimated Repair Time Hr 8
Equipment Type:
MOUNTING:
FedB
Feed Wire Size 6
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 4019
Isc 3P (A)mps 10488
Panel.Notes JUST REPLACE BRKRS. 6 THHN
Number Of Circuits 24MLOMCB
Phase 3Amp Rating 50Voltage 208/120
Short Circuit Rating 22000
Number Of Wires 4
Ground Wire Size 6Wire Type CU
Panel Schedule Available On Dwg
Approx Age 2005
Model# QOC24USManufacturer
SQUARE D
EquipName 4021
Room# 4021Floor 4Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 12
XFMR_ID T1, T2, T3, T4
Added To Oneline
Estimated Repair Time Hr 2
Equipment Type:
MOUNTING:
FedB RM 4024 BUS BKR
Feed Wire Size 6
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 4021
Isc 3P (A)mps 10517
Panel.Notes BREAKERS, PANEL S & BUS BRKRS
Number Of Circuits 16MLOMCB
Phase 3Amp Rating 100Voltage 208/120
Short Circuit Rating 22000
Number Of Wires 4
Ground Wire Size NONEWire Type CU
Panel Schedule Available On Dwg
Approx Age 2005
Model# QOC16USManufacturer
SQUARE D
EquipName 4035
Room# 4035Floor 4Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 13
XFMR_ID T1, T2, T3, T4
Added To Oneline
Estimated Repair Time Hr 8
Equipment Type:
MOUNTING:
FedB RM 4032 BUS BKR
Feed Wire Size 3
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 4035
Isc 3P (A)mps 15151
Panel.Notes REPLACE PANEL GUTS, BRKRS, WIRES & BUS BRKR, 20"WX30"HX5-3/4"D SEE
SURVEY SHEET
Number Of Circuits 24MLOMCB
Phase 3Amp Rating 100Voltage 208/120
Short Circuit Rating 42000
Number Of Wires 4
Ground Wire Size 8Wire Type CU
Panel Schedule Available On Dwg
Approx Age 1955
Model# C692980Manufacturer
WH
EquipName 4L2
Room# 4037 HALLFloor 4Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 14
XFMR_ID T1, T2, T3, T4
Added To Oneline
Estimated Repair Time Hr 8
Equipment Type:
MOUNTING:
FedB RM 4036 BUS BKR
Feed Wire Size 3
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 4L2
Isc 3P (A)mps 26935
Panel.Notes CLOTH WIRE, BRKR, PANEL, BUS DUCT BRKR REPLACE PANEL WITH NEW WHERE
GENERATOR TIME FREQ OFF LIBRARY HAS BUS DUCT TO 4TH FLOOR PROBABLY
400A FROM 4038 TO WINGS 3& 4 THEN STOP. 3 THW. PNL EL2 CKT 38,40,42 RM 2036
Number Of Circuits 12MLOMCB
Phase 3Amp Rating 100Voltage 208/120
Short Circuit Rating 10000
Number Of Wires 4
Ground Wire Size 8Wire Type CU
Panel Schedule Available On Dwg
Approx Age 1955
Model# C697617Manufacturer
WH
EquipName EL4
Room# 4038Floor 4Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 15
XFMR_ID T1, T2, T3, T4
Added To Oneline
Estimated Repair Time Hr
Equipment Type:
MOUNTING:
FedB RM 2036 PNL EL2
Feed Wire Size 3
Feeds Another Panel EL5(4536),EL6(2548)
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName EL4
Isc 3P (A)mps 7638
Panel.Notes LOOKS LIKE LAB PANEL UPS ALL VOLTAGE 88V FED BY UPS BELOW PANEL
Number Of Circuits 24MLOMCB
Phase 1Amp Rating 125Voltage 208/120
Short Circuit Rating 42000
Number Of Wires
Ground Wire Size NONEWire Type CU
Panel Schedule Available On Dwg
Approx Age 2005
Model# QOC24USManufacturer
SQUARE D
EquipName 4042D
Room# 4044Floor 4Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 17
XFMR_ID T1, T2, T3, T4
Added To Oneline
Estimated Repair Time Hr 8
Equipment Type:
MOUNTING:
FedB RM 4044 BUS BKR
Feed Wire Size 2
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 4042D
Isc 3P (A)mps 22997
Panel.Notes REPLACE PANEL, BRKRS & BUS DUCT BKRS 20"WX36"HX 5-3/4"D SEE SURVEY SHEET
Number Of Circuits 30MLOMCB
Phase 3Amp Rating 200Voltage 208/120
Short Circuit Rating 42000
Number Of Wires 4
Ground Wire Size NONEWire Type CU
Panel Schedule Available On Dwg
Approx Age 1955
Model# C693041Manufacturer
WH
EquipName 4L3
Room# 4053 HALLFloor 4Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 19
XFMR_ID T1, T2, T3, T4
Added To Oneline
Estimated Repair Time Hr 8
Equipment Type:
MOUNTING:
FedB RM 4054 BUS BKR
Feed Wire Size 3/0
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 4L3
Isc 3P (A)mps 22056
Panel.Notes REPLACE BRKRS ONLY & BUS BRKRS * PANEL IS RATED FOR 125A BUT FED WITH
150A BB CHANGE TO 125A BB. 1THHN
Number Of Circuits 24MLOMCB
Phase 3Amp Rating 125Voltage 208/120
Short Circuit Rating 22000
Number Of Wires 4
Ground Wire Size NONEWire Type CU
Panel Schedule Available On Dwg
Approx Age 2005
Model# QOC24USManufacturer
SQUARE D
EquipName 4054
Room# 4054Floor 4Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 20
XFMR_ID T1, T2, T3, T4
Added To Oneline
Estimated Repair Time Hr 2
Equipment Type:
MOUNTING:
FedB BUS BKR RM 4054
Feed Wire Size 1
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 4054
Isc 3P (A)mps 17613
Panel.Notes REPLACE BRKR ONLY
Number Of Circuits 20MLOMCB
Phase 3Amp Rating 100Voltage 208/120
Short Circuit Rating 22000
Number Of Wires 4
Ground Wire Size NONEWire Type CU
Panel Schedule Available On Dwg
Approx Age 1980
Model# QOC 420LManufacturer
SQUARE D
EquipName 7P21
Room# 4055Floor 4Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 21
XFMR_ID T1, T2, T3, T4
Added To Oneline
Estimated Repair Time Hr 2
Equipment Type:
MOUNTING:
FedB BUS BKR RM 4054
Feed Wire Size 3
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 7P21
Isc 3P (A)mps 13449
Panel.Notes REPLACE BRKR ONLY
Number Of Circuits 20MLOMCB
Phase 3Amp Rating 100Voltage 208/120
Short Circuit Rating 22000
Number Of Wires 4
Ground Wire Size NONEWire Type CU
Panel Schedule Available On Dwg
Approx Age 1980
Model# QOC 420LManufacturer
SQUARE D
EquipName 7P21
Room# 4055Floor 4Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 21
XFMR_ID T1, T2, T3, T4
Added To Oneline
Estimated Repair Time Hr 2
Equipment Type:
MOUNTING:
FedB BUS BKR RM 4054
Feed Wire Size 3
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 7P21
Isc 3P (A)mps 20736
Panel.Notes SURFACE MOUNT REPLACE PANELS, BRKRS, REPLACE WIRE, BUS BRKR
Number Of Circuits 12MLOMCB
Phase 3Amp Rating 50Voltage 208/120
Short Circuit Rating 10000
Number Of Wires 4
Ground Wire Size 10Wire Type CU
Panel Schedule Available On Dwg
Approx Age 1955
Model# C698401Manufacturer
WH
EquipName 4061
Room# 4061Floor 4Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 22
XFMR_ID T‐13, T‐14
Added To Oneline
Estimated Repair Time Hr 2
Equipment Type:
MOUNTING:
FedB BUS BKR
Feed Wire Size 6
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 4061
Isc 3P (A)mps 3779
Conduit Type EMT 1-1/4 "
Panel.Notes BRKR AND BUS BRKR REPLACE. FED FROM 100 BUS BREAKER
Number Of Circuits 20MLOMCB
Phase 3Amp Rating 100Voltage 208/120
Short Circuit Rating 22000
Number Of Wires 4
Ground Wire Size 6Wire Type CU
Panel Schedule Available On Dwg
Approx Age 1990
Model# QOC24UManufacturer
SQUARE D
EquipName 7P26
Room# 4062Floor 4Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 23
XFMR_ID T‐13, T‐14
Added To Oneline
Estimated Repair Time Hr 2
Equipment Type:
MOUNTING:
FedB RM 4062 BUS BKR
Feed Wire Size 3
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 7P26
Isc 3P (A)mps 11458
Panel.Notes REPLACE EVERYTHING BRKRS, PANEL, BUS BRKR, WIRE, WIRE NOT RATED
CORRECTLY 2 PANELS ONE 30 ONE 12 FIELD VERIFY NOTATION. 4TW
Number Of Circuits 12MLOMCB
Phase 3Amp Rating 80Voltage 208/120
Short Circuit Rating 10000
Number Of Wires 4
Ground Wire Size 8Wire Type CU
Panel Schedule Available On Dwg
Approx Age 1970
Model#Manufacturer
ITE
EquipName 7P20
Room# 4069Floor 4Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 25
XFMR_ID T‐13, T‐14
Added To Oneline
Estimated Repair Time Hr 8
Equipment Type:
MOUNTING:
FedB RM 4066 BUS BKR
Feed Wire Size 4
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 7P20
Isc 3P (A)mps 8079
Panel.Notes REPLACE PANEL, BRKR, WIRE, RECESS, BUS BREAKER 20"WX30"HX5-3/4"D SEE
SURVEY SHEET
Number Of Circuits 24MLOMCB
Phase 3Amp Rating 100Voltage 208/120
Short Circuit Rating 22000
Number Of Wires 4
Ground Wire Size 8Wire Type CU
Panel Schedule Available On Dwg
Approx Age 1955
Model# C693082Manufacturer
WH
EquipName 4L1A
Room# 4068 HALLFloor 4Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 26
XFMR_ID T‐13, T‐14
Added To Oneline
Estimated Repair Time Hr 8
Equipment Type:
MOUNTING:
FedB
Feed Wire Size 3
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 4L1A
Isc 3P (A)mps 12390
Conduit Type EMT 2"
Panel.Notes REPLACE BRKRS ONLY, BUS BRKR
Number Of Circuits 42MLOMCB
Phase 3Amp Rating 200Voltage 208/120
Short Circuit Rating 22000
Number Of Wires 4
Ground Wire Size NONEWire Type CU
Panel Schedule Available On Dwg
Approx Age 2005
Model# NQOD4421 225CUManufacturer
SQUARE D
EquipName 4078
Room# 4078Floor 4Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 30
XFMR_ID T‐13, T‐14
Added To Oneline
Estimated Repair Time Hr 2
Equipment Type:
MOUNTING:
FedB RM 4078 BUS BKR
Feed Wire Size 3/0
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 4078
Isc 3P (A)mps 19311
Conduit Type EMT 1-14
Panel.Notes REPLACE BRKRS PANEL, BUS BRKR 20"W X 30"H X 5-3/4"D SEE YELLOW SURVEY
SHEET
Number Of Circuits 24MLOMCB
Phase 3Amp Rating 100Voltage 208/120
Short Circuit Rating 25000
Number Of Wires 4
Ground Wire Size 6Wire Type CU
Panel Schedule Available On Dwg
Approx Age 1955
Model# C692981Manufacturer
WH
EquipName 4L2A
Room# 4083 HALLFloor 4Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 31
XFMR_ID T‐13, T‐14
Added To Oneline
Estimated Repair Time Hr 8
Equipment Type:
MOUNTING:
FedB
Feed Wire Size 3
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 4L2A
Isc 3P (A)mps 21014
Panel.Notes BREAKERS ONLY REPLACE UPS BYPASS/POWER AMPLIFIER/LTS4080. 3THHN
Number Of Circuits 30MLOMCB
Phase 3Amp Rating 100Voltage 208/120
Short Circuit Rating 42000
Number Of Wires 4
Ground Wire Size 6Wire Type CU
Panel Schedule Available On Dwg
Approx Age 2005
Model# NQUD430LManufacturer
SQUARE D
EquipName 4080WP
Room# 4080Floor 4Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e4sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 32
XFMR_ID T‐13, T‐14
Added To Oneline
Estimated Repair Time Hr 2
Equipment Type:
MOUNTING:
FedB RM 4080 BUS BKR
Feed Wire Size 3
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 4080WP
Isc 3P (A)mps 23000
Panel.Notes REPLACE BREAKERS, AND PANEL. fed from 100 bus breaker, WIRE THHN
Number Of Circuits 30MLOMCB
Phase 3Amp Rating 50Voltage 208/120
Short Circuit Rating 22000
Number Of Wires 4
Ground Wire Size 8Wire Type CU
Panel Schedule Available On Dwg
Approx Age 1980
Model# QO30USManufacturer Square D
EquipName 3083
Room# 3083Floor 3Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 34
XFMR_ID
Added To Oneline
Estimated Repair Time Hr
Equipment Type:
MOUNTING:
FedB RM 3083 HALL BUS BKR
Feed Wire Size 6
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 3083
Isc 3P (A)mps 11536
Panel.Notes RECESSED, REPLACE WIRE, BKRS, PANEL BUS BKRS. 2O"W X 38"H X 5-3/4"D, SEE
SURVEY SHEET FOR DIMENSIONS
Number Of Circuits 36MLOMCB
Phase 3Amp Rating 200Voltage 208/120
Short Circuit Rating 25000
Number Of Wires 4
Ground Wire Size 4Wire Type CU
Panel Schedule Available On Dwg
Approx Age 1955
Model# C692963Manufacturer
WH
EquipName 3L2A
Room# 3082 HALLFloor 3Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 35
XFMR_ID
Added To Oneline
Estimated Repair Time Hr
Equipment Type:
MOUNTING:
FedB
Feed Wire Size 3/0
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 3L2A
Isc 3P (A)mps 19949
Panel.Notes REPLACE BKRS, BUS BKRS ONLY FED FROM 200 BUS BRKR/HAS SURGE ARRESTER
& MOUNTING KIT, ;1#250KCMIL N;1$4 GND)
Number Of Circuits 42MLOMCB
Phase 3Amp Rating 200Voltage 208/120
Short Circuit Rating 22000
Number Of Wires 4
Ground Wire Size 4Wire Type CU
Panel Schedule Available On Dwg
Approx Age 2005
Model# QOC342MSManufacturer
SQ D
EquipName 3078
Room# 3078Floor 3Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 36
XFMR_ID
Added To Oneline
Estimated Repair Time Hr
Equipment Type:
MOUNTING:
FedB RM 3078 BUS BKR
Feed Wire Size 3/0
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 3078
Isc 3P (A)mps 18963
Panel.Notes Replace BREAKERS, BUS BREAKERS only. Code violation no room in front of panel. FED
FROM 100 BUS BREAKER. 2 THHN
Number Of Circuits 24MLOMCB
Phase 3Amp Rating 100Voltage 208/120
Short Circuit Rating 22000
Number Of Wires 4
Ground Wire Size 10Wire Type CU
Panel Schedule Available On Dwg
Approx Age 2005
Model# QOC24USManufacturer
SQ D
EquipName 3082
Room# 3082Floor 3Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 37
XFMR_ID
Added To Oneline
Estimated Repair Time Hr
Equipment Type:
MOUNTING:
FedB RM 3082 BUS BKR
Feed Wire Size 2
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 3082
Isc 3P (A)mps 17356
Panel.Notes Replace BREAKERS, and bus breakers. FED FROM 100 BUS BREAKER, ;1#1/0 N
Number Of Circuits 30MLOMCB
Phase 3Amp Rating 100Voltage 208/120
Short Circuit Rating 22000
Number Of Wires 4
Ground Wire Size 6Wire Type CU
Panel Schedule Available On Dwg
Approx Age 2000
Model# QOC30USManufacturer
SQ D
EquipName 3079
Room# 3079Floor 3Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 38
XFMR_ID
Added To Oneline
Estimated Repair Time Hr
Equipment Type:
MOUNTING:
FedB RM 3078 BUS BKR
Feed Wire Size 3
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 3079
Isc 3P (A)mps 14461
Panel.Notes REPLACE BREAKERS, AND PANEL. 125 MAIN LUGS, 6 THHN
Number Of Circuits 24MLOMCB
Phase 3Amp Rating 50Voltage 208/120
Short Circuit Rating 10000
Number Of Wires 4
Ground Wire Size 8Wire Type CU
Panel Schedule Available On Dwg
Approx Age 1980
Model# QOC24USManufacturer
SQ D
EquipName 3075
Room# 3075Floor 3Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 39
XFMR_ID
Added To Oneline
Estimated Repair Time Hr
Equipment Type:
MOUNTING:
FedB RM 3074 BUS BKR
Feed Wire Size 6
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 3075
Isc 3P (A)mps 7542
Panel.Notes REPLACE PANEL, BREAKERS, BUS BREAKERS. ESTIMATED SHUT DOWN TIME 2 HR.
FED FROM 100 BUS BREAKER_KW/HR. 2 TW
Number Of Circuits 42MLOMCB
Phase 3Amp Rating 100Voltage 208/120
Short Circuit Rating 22000
Number Of Wires 4
Ground Wire Size NONEWire Type CU
Panel Schedule Available On Dwg
Approx Age 1960
Model# TL42-420S/NP245771Manufacturer
GE
EquipName 3074
Room# 3074Floor 3Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 40
XFMR_ID
Added To Oneline
Estimated Repair Time Hr
Equipment Type:
MOUNTING:
FedB RM 3074 BUS BKR
Feed Wire Size 2
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 3074
Isc 3P (A)mps 15719
Panel.Notes REPLACE BREAKER, PANEL, WIRES, BUS BREAKER
Number Of Circuits 12MLOMCB
Phase 3Amp Rating 50Voltage 208/120
Short Circuit Rating 10000
Number Of Wires 4
Ground Wire Size 8Wire Type CU
Panel Schedule Available On Dwg
Approx Age 1955
Model# C698373Manufacturer
WH
EquipName 3071
Room# 3071Floor 3Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 41
XFMR_ID
Added To Oneline
Estimated Repair Time Hr
Equipment Type:
MOUNTING:
FedB RM 3070 BUS BKR
Feed Wire Size 6
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 3071
Isc 3P (A)mps 7494
Panel.Notes REPLACE PANEL, BREAKERS, BUS BREAKER, WIRE CLOTH. ESTIMATED DOWN
TIME 8 HRS. FED FROM 100 BUS BREAKER
Number Of Circuits 12MLOMCB
Phase 3Amp Rating 50Voltage 208/120
Short Circuit Rating 22000
Number Of Wires 4
Ground Wire Size 10Wire Type CU
Panel Schedule Available On Dwg
Approx Age 1955
Model# C698369Manufacturer
WH
EquipName 3070
Room# 3070Floor 3Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 42
XFMR_ID
Added To Oneline
Estimated Repair Time Hr
Equipment Type:
MOUNTING:
FedB RM 3070 BUS BKR
Feed Wire Size 6
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 3070
Isc 3P (A)mps 10767
Panel.Notes REPLACE PANEL, BREAKERS, BUS BREAKERS, WIRE. 20 X 30 X 5-3/4 SEE SHEET FOR
DIMENSIONS
Number Of Circuits 24MLOMCB
Phase 3Amp Rating 100Voltage 208/120
Short Circuit Rating 22000
Number Of Wires 4
Ground Wire Size NONEWire Type CU
Panel Schedule Available On Dwg
Approx Age 1955
Model# C693081Manufacturer
WH
EquipName 3L1A
Room# 3068 HALLFloor 3Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 43
XFMR_ID
Added To Oneline
Estimated Repair Time Hr
Equipment Type:
MOUNTING:
FedB
Feed Wire Size 3
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 3L1A
Isc 3P (A)mps 15011
Panel.Notes REPLACE BREAKERS AND BUS BREAKERS. ESTIMATED DOWN TIME 2 HRS. FED
FROM 50 BUS BREAKER, ;1#4 N)
Number Of Circuits 24MLOMCB
Phase 3Amp Rating 50Voltage 208/120
Short Circuit Rating 22000
Number Of Wires 4
Ground Wire SizeWire Type CU
Panel Schedule Available On Dwg
Approx Age 2005
Model# QOC24US125Manufacturer
SQ D
EquipName 3065
Room# 3067Floor 3Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 45
XFMR_ID
Added To Oneline
Estimated Repair Time Hr
Equipment Type:
MOUNTING:
FedB RM 3066 BUS BKR
Feed Wire Size 8
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 3065
Isc 3P (A)mps 9773
Panel.Notes REPLACE BREAKERS, BUS BREAKERS. CODE VIOLATION, FED WITH A 150 AMP 3 PHASE BUS BREAKER NEED TO MAKE 125 AMP 3066 and 3064 are the same room. FED
FROM 100 BUS BREAKER, 2 THHN
Number Of Circuits 20MLOMCB
Phase 3Amp Rating 100Voltage 208/120
Short Circuit Rating 22000
Number Of Wires 4
Ground Wire Size NONEWire Type CU
Panel Schedule Available On Dwg
Approx Age 2013
Model# QOC24UManufacturer
SQ D
EquipName 7P25
Room# 3066Floor 3Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 46
XFMR_ID
Added To Oneline
Estimated Repair Time Hr
Equipment Type:
MOUNTING:
FedB RM 3066 BUS BKR
Feed Wire Size 2
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 7P25
Isc 3P (A)mps 13280
Panel.Notes REPLACE BREAKERS, BUS BREAKERS. CODE VIOLATION, PANEL IS BEING FED BY 150A 3 PHASE BUS BREAKER. FED FROM 100 BUS BREAKER, 3066 and 3064 are the same room
Number Of Circuits 20MLOMCB
Phase 3Amp Rating 100Voltage 208/120
Short Circuit Rating 22000
Number Of Wires 4
Ground Wire Size NONEWire Type CU
Panel Schedule Available On Dwg
Approx Age 2005
Model# QOC24UManufacturer
SQ D
EquipName 7P24
Room# 3064Floor 3Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 47
XFMR_ID
Added To Oneline
Estimated Repair Time Hr
Equipment Type:
MOUNTING:
FedB RM 3064 BUS BKR
Feed Wire Size 2
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 7P24
Isc 3P (A)mps 13155
Panel.Notes REPLACE BREAKERS, BUS BREAKERS. CODE VIOLATION, PANEL IS BEING FED BY 150A 3 PHASE BUS BREAKER. FED FROM 100 BUS BREAKER, 3066 and 3064 are the same room
Number Of Circuits 20MLOMCB
Phase 3Amp Rating 100Voltage 208/120
Short Circuit Rating 22000
Number Of Wires 4
Ground Wire Size NONEWire Type CU
Panel Schedule Available On Dwg
Approx Age 2005
Model# QOC24UManufacturer
SQ D
EquipName 7P24
Room# 3064Floor 3Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 47
XFMR_ID
Added To Oneline
Estimated Repair Time Hr
Equipment Type:
MOUNTING:
FedB RM 3064 BUS BKR
Feed Wire Size 2
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 7P24
Isc 3P (A)mps 23427
Conduit Type
Panel.Notes REPLACE PANEL, BREAKERS, WIRE, AND BUS BREAKERS. FED FROM 100 BUS
BREAKER
Number Of Circuits 24MLOMCB
Phase 3Amp Rating 100Voltage 208/120
Short Circuit Rating 22000
Number Of Wires 4
Ground Wire Size NONEWire Type CU
Panel Schedule Available On Dwg
Approx Age 1955
Model# EQB/MLA24-4LManufacturer
ITE
EquipName 3062
Room# 3062Floor 3Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 48
XFMR_ID
Added To Oneline
Estimated Repair Time Hr
Equipment Type:
MOUNTING:
FedB RM 3062 BUS BKR
Feed Wire Size 3
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 3062
Isc 3P (A)mps 12920
Panel.Notes REPLACE BREAKERS ONLY, RELABEL PANEL 3063. FED FROM 100 BUS BREAKER
Number Of Circuits 20MLOMCB
Phase 3Amp Rating 100Voltage 208/120
Short Circuit Rating 22000
Number Of Wires 4
Ground Wire Size NONEWire Type CU
Panel Schedule Available On Dwg
Approx Age 1980
Model# QOC420LManufacturer
SQ D
EquipName 7P14
Room# 3063Floor 3Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 49
XFMR_ID
Added To Oneline
Estimated Repair Time Hr
Equipment Type:
MOUNTING:
FedB RM 3062 BUS BKR
Feed Wire Size 3
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 7P14
Isc 3P (A)mps 12848
Panel.Notes REPLACE PANEL, WIRES, BREAKERS, AND BUS BREAKERS. 20 X 30 X 5-3/4, SEE
SHEET FOR DIMENSIONS. FED FROM 100 BUS BREAKER
Number Of Circuits 24MLOMCB
Phase 3Amp Rating 100Voltage 208/120
Short Circuit Rating 22000
Number Of Wires 4
Ground Wire Size NONEWire Type CU
Panel Schedule Available On Dwg
Approx Age 1955
Model# C692978Manufacturer
WH
EquipName 3L3
Room# 3053 HALLFloor 3Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 54
XFMR_ID
Added To Oneline
Estimated Repair Time Hr
Equipment Type:
MOUNTING:
FedB RM 3054 BUS BKR
Feed Wire Size 3
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 3L3
Isc 3P (A)mps 18443
Conduit Type EMT 1"
Panel.Notes REPLACE BREAKERS ONLY. CODE VIOLATION, NEED TO HAVE 36" IN FRONT OF
PANEL. FED FROM 100/50 BUS BREAKER
Number Of Circuits 12MLOMCB
Phase 3Amp Rating 50Voltage 208/120
Short Circuit Rating 10000
Number Of Wires 4
Ground Wire Size NONEWire Type CU
Panel Schedule Available On Dwg
Approx Age 1980
Model# QOC16US/QOC412LManufacturer
SQ D
EquipName 3053
Room# 3053Floor 3Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 55
XFMR_ID
Added To Oneline
Estimated Repair Time Hr
Equipment Type:
MOUNTING:
FedB RM 3050 BUS BKR
Feed Wire Size 6
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 3053
Isc 3P (A)mps 7686
Panel.Notes REPLACE PANEL, BREAKER, BUS BREAKER
Number Of Circuits 30MLOMCB
Phase 3Amp Rating 100Voltage 208/120
Short Circuit Rating 22000
Number Of Wires 4
Ground Wire Size 8Wire Type CU
Panel Schedule Available On Dwg
Approx Age 1980
Model# QOC3OUSManufacturer
SQ D
EquipName 3050
Room# 3050Floor 3Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 56
XFMR_ID
Added To Oneline
Estimated Repair Time Hr
Equipment Type:
MOUNTING:
FedB RM 3050 BUS BKR
Feed Wire Size 3
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 3050
Isc 3P (A)mps 19913
Panel.Notes REPLACE BREAKERS ONLY. FED FROM 100/50 BUS BREAKER
Number Of Circuits 12MLOMCB
Phase 3Amp Rating 50Voltage 208/120
Short Circuit Rating 10000
Number Of Wires 4
Ground Wire Size NONEWire Type CU
Panel Schedule Available On Dwg
Approx Age 1980
Model# QOC16USManufacturer
SQ D
EquipName 3047A
Room# 3049Floor 3Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 57
XFMR_ID
Added To Oneline
Estimated Repair Time Hr
Equipment Type:
MOUNTING:
FedB RM 3050A BUS BKR
Feed Wire Size 6
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 3047A
Isc 3P (A)mps 8281
Panel.Notes REPLACE PANEL, BREAKERS, BUS BREAKER. ESTIMATED DOWN TIME 8 HRS.
Number Of Circuits 24MLOMCB
Phase 3Amp Rating 100Voltage 208/120
Short Circuit Rating 42000
Number Of Wires 4
Ground Wire Size NONEWire Type CU
Panel Schedule Available On Dwg
Approx Age 1970
Model# EQ424AManufacturer
ITE
EquipName 3046
Room# 3046Floor 3Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 58
XFMR_ID
Added To Oneline
Estimated Repair Time Hr
Equipment Type:
MOUNTING:
FedB RM 3046 BUS BKR
Feed Wire Size 2
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 3046
Isc 3P (A)mps 21931
Panel.Notes REPLACE BREAKERS ONLY
Number Of Circuits 12MLOMCB
Phase 3Amp Rating 50Voltage 208/120
Short Circuit Rating 22000
Number Of Wires 4
Ground Wire Size NONEWire Type CU
Panel Schedule Available On Dwg
Approx Age 1980
Model# QO412L125Manufacturer
SQ D
EquipName 3047B
Room# 3045Floor 3Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 59
XFMR_ID
Added To Oneline
Estimated Repair Time Hr
Equipment Type:
MOUNTING:
FedB RM 3044 BUS BKR
Feed Wire Size 6
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 3047B
Isc 3P (A)mps 11329
Conduit Type
Panel.Notes REPLACE PANEL, BREAKERS, WIRE, BUS BREAKER
Number Of Circuits 12MLOMCB
Phase 3Amp Rating 100Voltage 208/120
Short Circuit Rating 10000
Number Of Wires 4
Ground Wire Size 8Wire Type CU
Panel Schedule Available On Dwg
Approx Age 1955
Model# C693018Manufacturer
WH
EquipName EL3
Room# 3038Floor 3Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 60
XFMR_ID
Added To Oneline
Estimated Repair Time Hr
Equipment Type:
MOUNTING:
FedB RM 2036 PNL EL2
Feed Wire Size 3
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName EL3
Isc 3P (A)mps 8869
Number Of Circuits 12MLOMCB
Phase 3Amp Rating 50Voltage 208/120
Short Circuit Rating 22000
Number Of Wires 4
Ground Wire Size 8Wire Type CU
Panel Schedule Available On Dwg
Approx Age 1980
Model# QOC16USManufacturer
SQ D
EquipName 3036
Room# 3036Floor 3Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 61
XFMR_ID
Added To Oneline
Estimated Repair Time Hr
Equipment Type:
MOUNTING:
FedB RM 3036 BUS BKR
Feed Wire Size 8
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 3036
Isc 3P (A)mps 15947
Panel.Notes REPLACE PANEL, BREAKERS, BUS DUCT BREAKER, WIRES. 20 X 30 X 5-3/4, SEE
SHEET FOR DIMENSIONS.
Number Of Circuits 24MLOMCB
Phase 3Amp Rating 100Voltage 208/120
Short Circuit Rating 42000
Number Of Wires 4
Ground Wire Size 8Wire Type CU
Panel Schedule Available On Dwg
Approx Age 1955
Model# C692977Manufacturer
WH
EquipName 3L2
Room# 3034 HALLFloor 3Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 62
XFMR_ID
Added To Oneline
Estimated Repair Time Hr
Equipment Type:
MOUNTING:
FedB RM 3034 BUS BKR
Feed Wire Size 3
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 3L2
Isc 3P (A)mps 26832
Panel.Notes REPLACE BREAKERS WITH 22 K BREAKERS. 200A MAIN LUGS FED FROM 100 BUS
BREAKER
Number Of Circuits 30MLOMCB
Phase 3Amp Rating 100Voltage 208/120
Short Circuit Rating 42000
Number Of Wires 4
Ground Wire Size 8Wire Type CU
Panel Schedule Available On Dwg
Approx Age 1980
Model# QOC30USManufacturer
SQ D
EquipName 3034
Room# 3034Floor 3Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 63
XFMR_ID
Added To Oneline
Estimated Repair Time Hr
Equipment Type:
MOUNTING:
FedB RM 3034 BUS BKR
Feed Wire Size 3
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 3034
Isc 3P (A)mps 28100
Panel.Notes REPLACE BREAKERS. FED FROM 100 BUS BREAKER
Number Of Circuits 24MLOMCB
Phase 3Amp Rating 150Voltage 208/120
Short Circuit Rating 42000
Number Of Wires 4
Ground Wire Size NONEWire Type CU
Panel Schedule Available On Dwg
Approx Age 1970
Model# CR-268288Manufacturer
GE
EquipName 3032
Room# 3032Floor 3Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 64
XFMR_ID
Added To Oneline
Estimated Repair Time Hr
Equipment Type:
MOUNTING:
FedB RM 3032 BUS BKR
Feed Wire Size 2/0
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 3032
Isc 3P (A)mps 30507
Panel.Notes REPLACE BREAKERS, BUS BREAKERS
Number Of Circuits 42MLOMCB
Phase 3Amp Rating 200Voltage 208/120
Short Circuit Rating 22000
Number Of Wires 4
Ground Wire Size NONEWire Type CU
Panel Schedule Available On Dwg
Approx Age 2005
Model# NQ442L2CManufacturer
SQ D
EquipName 3028A
Room# 3028AFloor 3Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 65
XFMR_ID
Added To Oneline
Estimated Repair Time Hr
Equipment Type:
MOUNTING:
FedB RM 3028 BUS BKR
Feed Wire Size 3/0
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 3028A
Isc 3P (A)mps 19630
Panel.Notes REPLACE PANEL, BREAKERS, BUS BREAKERS. CODE VIOLATION, NEED CORRECT
ACCESS, MOVE PANEL TO OTHER LOCATION AWA FROM CLOSET. RECPS 3021 WEST
VIDEO IS 0325
Number Of Circuits 12MLOMCB
Phase 3Amp Rating 50Voltage 208/120
Short Circuit Rating 10000
Number Of Wires 4
Ground Wire Size 10Wire Type CU
Panel Schedule Available On Dwg
Approx Age 1955
Model# C698259Manufacturer
WH
EquipName 3021
Room# 3021Floor 3Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 66
XFMR_ID
Added To Oneline
Estimated Repair Time Hr
Equipment Type:
MOUNTING:
FedB RM 3022 BUS BKR
Feed Wire Size 6
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 3021
Isc 3P (A)mps 7847
Conduit Type EMT 2"'
Panel.Notes REPLACE PANEL, BREAKERS, WIRE, BUS BREAKER. 20 X 44 X 5-3/4" SEE SHEET FOR
DIMENSIONS.
Number Of Circuits 42MLOMCB
Phase 3Amp Rating 200Voltage 208
Short Circuit Rating 42000
Number Of Wires 4
Ground Wire Size 6Wire Type CU
Panel Schedule Available On Dwg
Approx Age 1955
Model# C69042Manufacturer
WH
EquipName 3L1
Room# 3014 HALLFloor 3Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 67
XFMR_ID
Added To Oneline
Estimated Repair Time Hr
Equipment Type:
MOUNTING:
FedB
Feed Wire Size 3/0
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 3L1
Isc 3P (A)mps 22351
Panel.Notes CODE VIOLATION, PANEL NEEDS 3' IN FRONT PER NEC. 22 KAIC CKT BRKRS, ; 1#1/0 N
Number Of Circuits 24MLOMCB
Phase 3Amp Rating 100Voltage 208/120
Short Circuit Rating 22000
Number Of Wires 4
Ground Wire Size 8Wire Type CU
Panel Schedule Available On Dwg
Approx Age 2000
Model# QOC420LManufacturer
SQ D
EquipName 3014
Room# 3014Floor 3Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 68
XFMR_ID
Added To Oneline
Estimated Repair Time Hr
Equipment Type:
MOUNTING:
FedB RM 3014 BUS BKR
Feed Wire Size 3
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 3014
Isc 3P (A)mps 17936
Conduit Type EMT 2-1/2
Panel.Notes REPLACE BREAKERS ONLY. FED FROM 200 BUS BREAKER
Number Of Circuits 30MLOMCB
Phase 3Amp Rating 200Voltage 208/120
Short Circuit Rating 25000
Number Of Wires 4
Ground Wire Size NONEWire Type CU
Panel Schedule Available On Dwg
Approx Age 2004
Model# NQOD 430L225CUManufacturer
SQ D
EquipName 3006
Room# 3008Floor 3Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 69
XFMR_ID
Added To Oneline
Estimated Repair Time Hr
Equipment Type:
MOUNTING:
FedB RM 3008 BUS BKR
Feed Wire Size 4/0
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 3006
Isc 3P (A)mps 20336
Panel.Notes PANEL WILL REMAIN AS IT IS. SEE BOX FOR PANEL SCHEDULE. (4#3/0)
Number Of Circuits 30MLOMCB
Phase 3Amp Rating 200Voltage 208/120
Short Circuit Rating 22000
Number Of Wires 4
Ground Wire Size NONEWire Type CU
Panel Schedule Available On Dwg
Approx Age 2015
Model# NQ442L2CManufacturer
SQ D
EquipName 7P12
Room# 3001Floor 3Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1e3sp
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 70
XFMR_ID
Added To Oneline
Estimated Repair Time Hr
Equipment Type:
MOUNTING:
FedB
Feed Wire Size 3/0
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 7P12
Isc 3P (A)mps 13372
Panel.Notes REPLACE PANEL, BREAKERS, WIRES CLOTH
Number Of Circuits 12MLOMCB
Phase 3Amp Rating 50Voltage 208/120
Short Circuit Rating 22000
Number Of Wires 4
Ground Wire Size 8Wire Type CU
Panel Schedule Available On Dwg
Approx Age 1950
Model# C698196Manufacturer Westinghouse
EquipName 2031
Room# 2031Floor 2Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1E2SP
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 71
XFMR_ID
Added To Oneline
Estimated Repair Time Hr
Equipment Type:
MOUNTING:
FedB RM 2030 BUS BKR
Feed Wire Size 6
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 2031
Isc 3P (A)mps 9811
Conduit Type EMT 1 1/4"
Panel.Notes REPLACE BREAKERS ONLY. CODE VIOLATION, WATER PIPE ABOVE PANEL, REQUIRED ACCESS SPACE IS NOT PER NEC, ADDED PANEL SCHEDLE
Number Of Circuits 20MLOMCB
Phase 3Amp Rating 100Voltage 208/120
Short Circuit Rating 22000
Number Of Wires 4
Ground Wire Size NONEWire Type CU
Panel Schedule Available On Dwg
Approx Age 1990
Model# QON42OL125/QOC4Manufacturer
SQ D
EquipName 7P21
Room# 2033Floor 2Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1E2SP
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 72
XFMR_ID
Added To Oneline
Estimated Repair Time Hr
Equipment Type:
MOUNTING:
FedB RM 2032 BUS BKR
Feed Wire Size 3
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 7P21
Isc 3P (A)mps 20736
Panel.Notes REPLACE BREAKERS ONLY. CODE VIOLATION, WATER PIPE ABOVE PANEL, REQUIRED ACCESS SPACE IS NOT PER NEC, ADDED PANEL SCHEDLE
Number Of Circuits 20MLOMCB
Phase 3Amp Rating 100Voltage 208/120
Short Circuit Rating 22000
Number Of Wires 4
Ground Wire Size NONEWire Type CU
Panel Schedule Available On Dwg
Approx Age 1990
Model# QON42OL125/QOC4Manufacturer
SQ D
EquipName 7P21
Room# 2033Floor 2Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1E2SP
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 72
XFMR_ID
Added To Oneline
Estimated Repair Time Hr
Equipment Type:
MOUNTING:
FedB RM 2032 BUS BKR
Feed Wire Size 3
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 7P21
Isc 3P (A)mps 13449
Panel.Notes REPLACE BREAKERS, BUS BREAKERS
Number Of Circuits 30MLOMCB
Phase 3Amp Rating 100Voltage 208/120
Short Circuit Rating 22000
Number Of Wires 4
Ground Wire Size NONEWire Type CU
Panel Schedule Available On Dwg
Approx Age 2005
Model# NQOD442L225Manufacturer
SQ D
EquipName 7P22
Room# 2035Floor 2Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1E2SP
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 73
XFMR_ID
Added To Oneline
Estimated Repair Time Hr
Equipment Type:
MOUNTING:
FedB RM 2034 BUS BKR
Feed Wire Size 3
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 7P22
Isc 3P (A)mps 20878
Panel.Notes REPLACE PANEL, BREAKERS, BUS BREAKER. ADDED SCHEDULE TO DRAWINGS
Number Of CircuitsMLOMCB
Phase 3Amp Rating 125Voltage 208/120
Short Circuit Rating 22000
Number Of Wires 4
Ground Wire Size NONEWire Type CU
Panel Schedule Available On Dwg
Approx Age 1980
Model# G2442ML3150Manufacturer
ITE
EquipName 2L10
Room# 2047BFloor 2Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1E2SP
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 74
XFMR_ID
Added To Oneline
Estimated Repair Time Hr
Equipment Type:
MOUNTING:
FedB
Feed Wire Size 1
Feeds Another Panel
Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs ReplaceWire ReplaceBusBrkr
ComponentName 2L10
Isc 3P (A)mps 16525
Conduit Type EMT 4"
Panel.Notes REPLACE BREAKERS, BUS BREAKERS/VIDEO FOR THIS PANEL WITH 76
Number Of Circuits 38MLOMCB
Phase 3Amp Rating 350Voltage 208/120
Short Circuit Rating 22000
Number Of Wires 4
Ground Wire Size NONEWire Type CU
Panel Schedule Available On Dwg
Approx Age 1990
Model# ALF3424MBManufacturer
GE
EquipName EP3
Room# 2047BFloor 2Building Section Spine
NIST ELECTRICAL PANEL SURVEY Drawing Nam 1E2SP
Main CB Rating Need To Revie Visited Not Installed
DEMOLITION
Panel INDEX 75
XFMR_ID
Added To Oneline
Estimated Repair Time Hr
Equipment Type:
MOUNTING:
FedB RM 2042 BUS BKR
Feed Wire Size 500
Feeds Another Panel EP3B(2053),EP3C(2047B),EMG40 16,EMG3527, EP3A(2047B)Cannot Find Fee DwgAddedviewPortMatchesOneline
Schedule
ReplaceBkrsOnly ReplacePanelBrkrs…
This is the start of the file's text. The full file is on GovTribe.