Amendment 0003 B121 Specification for Overhead Coiling Door.pdf
PDF 744 KB Posted
- Attached to
- Bldg 121 Repair Overhead Doors
- Solicitation number
- N400856908311
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Amendment 0003 SOW 6908311.pdf | ||
| Amendment 0003.pdf | ||
| Amendment 0002.pdf | ||
| B121 Specification for Overhead Coiling Door.pdf | ||
| Amendment 0001.pdf | ||
| SOW 6908311.pdf | ||
| RFP 6908311.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SECTION 08 36 13
SECTIONAL OVERHEAD DOORS
08/11
PART 1 GENERAL
REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by the basic designation only.
ALUMINUM ASSOCIATION (AA)
AA DAF45 (2003; Reaffirmed 2009) Designation System for Aluminum Finishes
ASTM INTERNATIONAL (ASTM)
ASTM A36/A36M (2014) Standard Specification for Carbon Structural Steel
ASTM A123/A123M (2017) Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products
ASTM A227/A227M (2017) Standard Specification for Steel Wire, Cold-Drawn for Mechanical Springs
ASTM A229/A229M (2017) Standard Specification for Steel Wire, Quenched and Tempered for Mechanical Springs
ASTM A653/A653M (2019) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM B209 (2014) Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate
ASTM B209M (2014) Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate (Metric)
ASTM B221 (2014) Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes
ASTM B221M (2013) Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes (Metric)
ASTM E330/E330M (2014) Structural Performance of Exterior Windows, Doors, Skylights and Curtain Walls by Uniform Static Air Pressure
Amendment 0003
Difference
DOOR AND ACCESS SYSTEM MANUFACTURERS ASSOCIATION (DASMA)
ANSI/DASMA 102 (2011) Specifications for Sectional Overhead-Type Doors
ANSI/DASMA 108 (2012) Standard Method for Testing Sectional Garage Doors and Rolling Doors:
Determination of Structural Performance Under Uniform Static Air Pressure Difference
NATIONAL ASSOCIATION OF ARCHITECTURAL METAL MANUFACTURERS (NAAMM)
NAAMM AMP 500 (2006) Metal Finishes Manual
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
NEMA ICS 1 (2000; R 2015) Standard for Industrial Control and Systems: General Requirements
NEMA ICS 2 (2000; R 2005; Errata 2008) Industrial Control and Systems Controllers, Contactors, and Overload Relays Rated 600 V
NEMA ICS 6 (1993; R 2016) Industrial Control and Systems: Enclosures
NEMA MG 1 (2018) Motors and Generators
NEMA ST 20 (2014) Dry-Type Transformers for General Applications
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2017; ERTA 1-2 2017; TIA 17-1; TIA 17-2;
TIA 17-3; TIA 17-4; TIA 17-5; TIA 17-6;
TIA 17-7; TIA 17-8; TIA 17-9; TIA 17-10;
TIA 17-11; TIA 17-12; TIA 17-13; TIA
17-14; TIA 17-15; TIA 17-16; TIA 17-17 )
National Electrical Code
UNDERWRITERS LABORATORIES (UL)
UL 325 (2017) UL Standard for Safety Door, Drapery, Gate, Louver, and Window Operators and Systems
SUBMITTALS
Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance to Section 01 33 29 SUSTAINABILITY REPORTING. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES.
SD-02 Shop Drawings
Doors; G
Not in Use
SD-03 Product Data
Doors; Replacement doors, door panels, door hardware, installation shall be like in kind or better to existing doors. Electrically-operated doors, include supporting brackets for motors, location, type, and ratings of motors, switches, and safety devices shall be like in kind or better to existing doors.
Electric operators;
Replacemnt openers shall be like in kind or better to existing openers. For electrically motor-operated doors, submit manufacturer's wiring diagrams for motor and controls.
SD-08 Manufacturer's Instructions
Doors shall be like in kind or better to existing doors.
SD-10 Operation and Maintenance Data
Doors; Shall be like in kind or better to existing doors.
Submit Data Package 2 in accordance with Section 01 78 23
OPERATION AND MAINTENANCE DATA.
DELIVERY, STORAGE, AND HANDLING
Protect doors and accessories from damage during delivery, storage, and handling. Clearly mark manufacturer's brand name. Store doors in dry locations with adequate ventilation, free from dust and water. Remove damaged items and provide new. Provide easy access for inspection and handling of overhead doors prior to installation.
PART 2 PRODUCTS
MATERIALS
Hard-Drawn Springwire
ASTM A227/A227M.
Oil-Tempered Springwire
ASTM A229/A229M.
Steel Sheet
ASTM A653/A653M.
Steel Shapes
ASTM A36/A36M.
Aluminum Extrusions
ASTM B221, Alloy 6063-T5.
Aluminum Sheets and Strips
ASTM B209, alloy and temper best suited for the purpose.
Glass
Fully tempered, clear glass 1/8 inch thick.
DOORS
Doors shall comply with ANSI/DASMA 102. Metal doors to have horizontal sections hinged together which operate in a system of tracks to completely close the door opening in the closed position and make the full width and height of the door opening available for use in the open position. Provide a permanent label on the door indicating the name and address of the manufacturer. Provide doors with standard lift type designed to slide up and back into a horizontal overhead position and requiring a maximum of 16 inch of headroom for 2 inch tracks and 21 inch of headroom for 3 inch tracks, low headroom type designed to slide up and back into a horizontal overhead position and requiring a maximum of 10 inch of headroom for 2 inch tracks and 12 inch of headroom for 3 inch tracks, high lift type designed to slide up and back into a combination vertical and horizontal position, by hand chain with gear or sprocket reduction, by electric power with auxiliary hand chain operation.
DESIGN REQUIREMENTS
Design wind load shall conform to the design wind load for the building door area without damage. Doors shall be tested in accordance with either ASTM E330/E330M or ANSI/DASMA 108 and shall meet the acceptance criteria of
ANSI/DASMA 108.
FABRICATION
Steel Overhead Doors
Form door sections of hot-dipped galvanized steel not lighter than 20 gage with longitudinal integral reinforcing ribs or 24 gage with longitudinal integral reinforcing ribs and flat bottom V-grooves. Install sections not less than 2 inch in thickness. Meeting rails to have interlocking joints to ensure a weathertight closure and alignment for full width of the door.
Provide sections of the height indicated or the manufacturer's standard.
Do not exceed thick 24 inch height for intermediate sections. Bottom sections may be varied to suit door height. Do not exceed 30 inch height for bottom section. Provide glass panels and install panels using manufacturer's standard for rubber gaskets.
Insulated Sections
Not in use
Aluminum Sections
At the Contractor's option, door sections may be constructed of aluminum in lieu of steel. Provide the same structural and thermal properties for aluminum sections as specified for steel sections.
Aluminum Panel Overhead Doors
Provide door panel construction with extruded aluminum stiles and rails with aluminum and glass panels. Stiles and rails has a minimum wall thickness of 0.060 inch. Meeting rails shall have interlocking joints to ensure a weathertight closure and alignment for full width of door.
Provide sections to the height indicated or the manufacturer's standard, but the height of an intermediate section not to exceed 24 inch. Bottom sections may be varied to suit door height, but to not exceed 30 inch in height. Provide aluminum panels not less than 0.040 inch in thickness.
Install panel using a continuous vinyl gasket and snap-in type of aluminum or vinyl glazing bead. Install glass panels as specified for aluminum panels.
Tracks
Provide galvanized steel tracks not lighter than 14 gage thick for 2 inch tracks and not lighter than 12 gage thick for 3 inch tracks. Provide galvanized steel vertical tracks with continuous galvanized steel angle not lighter than 13 gage for installation to walls. Incline vertical track through use of adjustable brackets to obtain a weathertight closure at jambs. Reinforce horizontal track with galvanized steel angle; support from track ceiling construction with galvanized steel angle and cross bracing to provide a rigid installation.
Hardware
Provide hinges, brackets, rollers, locking devices, and other hardware required for complete installation. Install roller brackets and hinges with 14 gage galvanized steel. Provide rollers with ball bearings and case-hardened races. Provide reinforcing on doors where roller hinges are connected. Provide a positive locking device and cylinder lock with two keys on manually operated doors.
Counterbalancing
Counterbalance doors with an oil-tempered, helical-wound torsional spring mounted on a steel shaft. Provide adjustable spring tension, connect spring to doors with cable through cable drums. Provide cable safety factor of at least 5 to 1.
MANUAL OPERATORS
Pushup Operators
Not in Use
Chain Hoist Operators
Provide a galvanized, endless chain operating over a sprocket. Extend chain to within 4 feet of the floor and mount on inside of building. Obtain reduction by use of roller chain and sprocket drive or gearing. Provide chain cleat and pin for securing operator chain. Allow for future installation of power operators to chain hoist operator. Do not exceed the maximum lifting force of 35 pounds required to operate the door.
ELECTRIC OPERATORS
Operator Features
Operators shall be labeled and listed to the requirements of UL 325.
Provide operators of the drawbar type or side mount (jack shaft) type as recommended by the manufacturer. Include operators with electric motor, machine-cut reduction gears, steel chain and sprockets, magnetic brake, brackets, pushbutton controls, limit switches, magnetic reversing contactor, a manual chain hoist operator for emergency use, and other accessories necessary for operation. Design electric operator so motor may be removed without disturbing the limit switch timing and without affecting the manual operator. Provide the operator with slipping clutch coupling to prevent stalling the motor. Provide a clutch controlled emergency manual operator so that it may be engaged and disengaged from the floor; do not affect limit switch timing by operation. The manual operator is not required if door can be manual-pushup operated with a force not to exceed 25 pounds. Provide an electrical or mechanical device that disconnects the motor from the operating mechanism when the manual operator is engaged.
Motors
NEMA MG 1, high-starting torque, reversible type with sufficient horsepower and torque output to move the door in either direction from any position.
Provide a motor to produce a door travel speed of not less than 8 inch or more than one foot per second without exceeding the rated capacity. Motors shall be operate on current of the characteristics indicated at not more than 3600 rpm. Single-phase motors shall not have commutation or more than one starting contact. Provide motor enclosures with drip-proof type or NEMA TENV type.
Controls
Provide a motor for each door with an enclosed, across-the-line type, magnetic reversing contactor, thermal overload and undervoltage protection, solenoid-operated brake, limit switches, and control switches. Locate control switches at least 5 feet above the floor so the operator will have complete visibility of the door at all times. Provide control equipment to conform to NEMA ICS 1 and NEMA ICS 2. Provide control enclosures with NEMA ICS 6, Type 12 or Type 4, except that contactor enclosures may be Type
1. Provide a three-button type control switch stations with buttons marked "OPEN," "CLOSE," and "STOP." The "OPEN" and "STOP" buttons shall require only momentary pressure to operate. The "CLOSE" button shall require constant pressure to maintain the closing motion of the door. If the door is in motion and the "STOP" button is pressed or the "CLOSE" button released, the door shall stop instantly and remain in the stop position;
from the stop position, the door may be operated in either direction by the "OPEN" or "CLOSE" button. Pushbuttons shall be full-guarded to prevent accidental operation. Provide limit switches to automatically stop doors at the fully open and closed positions. Limit switch positions shall be readily adjustable.
Entrapment Protection Devices
Entrapment protection devicesshall be provided for electrically-operated doors in accordance with UL 325. These devices shall immediately stop and reverse the door in its closing travel upon sensing an obstruction in the door opening or upon failure of the device or any component of the control system. Any momentary door-closing circuit shall be automatically locked out and the door shall be operable manually or with constant pressure controls until the failure or damage has been corrected. No entrapment protection device shall be used as a limit switch, unless its function is specifically intended to do so.
Control Transformers
NEMA ST 20. Provide transformers in power circuits as necessary to reduce the voltage on the control circuits to 120 volts or less.
Electrical Components
NFPA 70. Furnish manual or automatic control and safety devices, including extra flexible Type SO cable and spring-loaded automatic takeup reel or equivalent device, for operation of the doors. Conduit wiring and mounting of controls are specified in the corresponding electrical specification section.
Hazardous Locations
Not In Use
]WEATHER SEALS [AND SENSING EDGES]
Provide exterior doors with weatherproof joints between sections by means of tongue-and-groove joints, rabbetted joints, shiplap joints, or wool pile, vinyl or rubber weatherstripping; a rubber, or vinyl adjustable weatherstrip at the top and jambs; and a compressible neoprene or rubber weather seal attached to the bottom of the door. On exterior doors that are electrically operated, where a sensing edge is employed, the bottom seal shall be combination compressible weather seal and sensing edge for stopping and reversing door movement.
FINISHES
Hot-dip galvanize concealed metal surfaces and tracks in accordance with ASTM A123/A123M. Hot-dip galvanized and other ferrous metal surfaces, except rollers and lock components, which are galvanized or plated shop primed.
Galvanized and Shop Primed
Provide a zinc coating on specified surfaces, a phosphate treatment, and a shop prime coat of rust-inhibitive paint. Conform to ASTM A653/A653M for galvanized coating, coating designation G60, for steel sheets, and ASTM A123/A123M for assembled steel products. The weight of coatings for assembled products shall be as designated in Table I of ASTM A123/A123M for the class of material to be coated. Provide a prime coat especially developed for materials treated by phosphates and adapted to application by dipping or spraying. Repair damaged zinc-coated surfaces with galvanizing repair paint and spot prime. At the Contractor's option, a two-part system including bonderizing, baked-on epoxy primer, and baked-on enamel topcoat may be applied in lieu of prime coat specified.
Aluminum
Provide a clear anodized finish to aluminum surfaces in accordance with AA-M10-C22-A41 contained in AA DAF45 and NAAMM AMP 500. Pretreat exposed surfaces and apply a white baked-on enamel finish in accordance with manufacturer's standard.
PART 3 EXECUTION
INSTALLATION
NFPA 70. Install doors in accordance manufacturer's written installation instructions. Lubricate and adjust doors to operate freely.
Provide a weathertight installation and free from warp, twist, or distortion. Adjust and lubricate doors to operate freely.
Provide all items and accessories for a complete installation in every respect.
ELECTRICAL WORK
NFPA 70. Conduit, wiring, and mounting of controls, shall be installed accordance manufacturer's written installation instructions.
TESTING
After installation is complete, operate doors to demonstrate installation and function of operators, safety features, and controls. Correct deficiencies.
-- End of Section --
File details come from the government source that posted it. Updated .