17-T-0138_Attachment_2.pdf
PDF 1 MB Posted
- Attached to
- Diesel Generator Maintenance Federal contract opportunity
- Solicitation number
- N39040-17-T-0138
About this file
RFQ Attachment 2
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| N39040-17-T-0138-0002.pdf | ||
| Att_10_QandA.pdf | ||
| N3904017T0138_Amendment_0001.pdf | ||
| 17-T-0138_Attachment_1_-_REV1.pdf | ||
| 17-T-0138_Attachment_3.pdf | ||
| 17-T-0138_Attachment_1.pdf | ||
| 17-T-0138_Attachment_6_QASP_Matrix_-_Diesel_Generators_-_rev2.pdf | ||
| 17-T-0138_Attachment_8_Wage_Determination.pdf | ||
| N39040-17-T-0138.pdf | ||
| 17-T-0138_Attachment_5_QASP_-_Diesel_Generators_-_rev2.pdf | ||
| 17-T-0138_Attachment_4_HazControl.pdf | ||
| 17-T-0138_Attachment_7__Contract_Administration_Plan_(CAP).pdf |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
APPENDIX 2
Appendix 2 - Page 1 of 4
LOAD HOUSE DIESEL GENERATOR INVENTORY:
Manufacturer Model# Serial Number KW Location
Cummings DMT300C 380461 300 Dry Dock #1
Caterpillar SR-4 6BA01975 300 Dry Dock #2
Cummings DMT300C 860462 300 Dry Dock #3
Detroit 71237000 J2185/2 250 Conex Box
A-1. PREVENTIVE MAINTENANCE (PM) (Scheduled).
Perform maintenance on the above generators per the criteria listen below. PMs will be performed each calendar quarter (eg. 1st quarter: 1 Jan – 31 Mar) as scheduled by the contract POC. Four PMs will be performed during the year (three Minor PMs and 1 Major PM). Complete appropriate minor or major preventative maintenance checklist the day that the work is performed and provide checklist and any other relevant documentation to Shipyard POC.
The minor (quarterly) checks shall consist of checking the diesel generator as noted below.
1. Service/clean air filters
2. Perform air inlet restriction test
3. Check coolant level
4. Check ground connection
5. Check/adjust engine oil level
6. Check block heater operation
7. Check/adjust governor linkage/controls
8. Check/correct anti-freeze concentration
9. Check radiator for air restriction and dirt
10. Check engine gauges and metering for proper operation
11. Inspect exhaust system for leakage and deterioration
12. Inspect/adjust all accessible hoses, belts, and linkages
13. Inspect accessible fuel lines for leakage or deterioration
14. Check battery electrolyte levels and specific gravity
15. Clean battery terminals and check tightness of cables
16. Ensure battery charger is operating properly and record battery charging voltage
17. Adjust output voltage (450VAC) and frequency (60Hz) if required
18. Operate the diesel generator under load (200 kW) for a minimum of 30 minutes and check for proper operation. Running the diesel loaded must be coordinated with the Shipyard POC for the load bank. Shipyard will provide and operate the load bank. Check for fuel or coolant leaks, check and record voltage and frequency output, engine oil pressure, engine operating temperature, and check for unusual engine vibration.
christina.ellis Typewritten Text N39040-17-T-0138 Attachment 2
Appendix 2 - Page 2 of 4
The major (yearly) checks shall consist of checking the diesel generator as noted below.
1. Clean engine
2. Clean crankcase breather
3. Change air filter
4. Change fuel filters
5. Change engine oil and oil filter
6. Perform air inlet restriction test
7. Perform coolant system pressure test
8. Perform back pressure reading on exhaust system
9. Inspect main generator windings
10. Inspect fan hub, drive pulley and water pump
11. Inspect exhaust system for leakage and deterioration
12. Inspect/adjust all accessible hoses, belts, and linkages
13. Inspect accessible fuel lines for leakage or deterioration
14. Check and adjust valves
15. Check ground connection
16. Check block heater operation
17. Check/adjust governor linkage/controls
18. Check radiator for air restriction and dirt
19. Check engine gauges and metering for proper operation
20. Check tightness of mounting bolts and vibration isolators
21. Check engine and generator shutdown and alarm systems for proper operation
22. Flush cooling system
23. Grease main generator bearing
24. Remove, clean, and adjust magnetic pickup
25. Test fuel for water and algae/bacteria growth
26. Measure and record generator winding resistance
27. Vacuum/blow dust out of main generator (30psi max.)
28. Adjust output voltage (450VAC) and frequency (60Hz) if required
29. Change batteries (every 2 years—next replacement in 2018)
30. Check battery electrolyte levels and specific gravity
31. Clean battery terminals and check tightness of cables
32. Ensure battery charger is operating properly and record battery charging voltage
33. Operate the diesel generator under load (200 kW) for a minimum of 30 minutes and check for proper operation. Running the diesel loaded must be coordinated with the Shipyard POC for the load bank. Shipyard will provide and operate the load bank. Check for fuel or coolant leaks, check and record voltage and frequency output, engine oil pressure, engine operating temperature, and check for unusual engine vibration
(Check One)
Generator Hours (Pre-Start)
Generator Hours (Completion)
Date
CUMMINS DMT300C 300KW S/N: 380461 (DRY DOCK #1)
CATERPILLAR SP-4 300KW S/N: 6840197B (DRY DOCK #2)
CUMMINS DMT300C 300KW S/N: 860462 (DRY DOCK #3)
DETROIT 71237000 250KW S/N: J2185/2 (CONEX BOX)
Appendix 2 - Page 3 of 4
DIESEL GENERATOR MINOR PREVENTATIVE MAINTENANCE CHECKLIST (QUARTERLY)
MAINTENANCE SAT UNSAT
Operate the Generator Under Load (200kW) for a Minimum of 30 Minutes and Check for Proper Operation as follows:
SAT UNSAT
Service/clean air filters Check for Coolant or Fuel Leaks
Perform air inlet restriction test Output voltage ______VAC
Check coolant level Output Frequency ________Hz
Check ground connection Engine Oil Pressure ________PSI
Check/adjust engine oil level Engine Operating Temperature _______ F
Check block heater operation Check for Unusual Vibration or Noise
Check/adjust governor linkage/controls Comments:
Check/correct anti-freeze concentration
Check radiator for air restriction and dirt
Check engine gauges and metering for proper operation
Inspect exhaust system for leakage and deterioration
Inspect/adjust all accessible hoses, belts, and linkages
Inspect accessible fuel lines for leakage or deterioration
Check battery electrolyte levels and specific gravity
Clean battery terminals and check tightness of cables
Ensure battery charger is operating properly and record battery charging voltage
Voltage: ________________
Adjust output voltage (450VAC) and frequency (60Hz) if required
(Check One)
Generator Hours (Pre-Start)
Generator Hours (Completion)
Date
CUMMINS DMT300C 300KW S/N: 380461 (DRY DOCK #1)
CATERPILLAR SP-4 300KW S/N: 6840197B (DRY DOCK #2)
CUMMINS DMT300C 300KW S/N: 860462 (DRY DOCK #3)
DETROIT 71237000 250KW S/N: J2185/2 (CONEX BOX)
Appendix 2 - Page 4 of 4
DIESEL GENERATOR MAJOR PREVENTATIVE MAINTENANCE CHECKLIST (YEARLY)
MAINTENANCE ITEMS SAT UNSAT MAINTENANCE ITEMS SAT UNSAT
Clean engine Check/adjust governor linkage/controls
Clean crankcase breather Check radiator for air restriction and dirt
Change air filter Check engine gauges and metering for proper operation
Change fuel filters Check tightness of mounting bolts and vibration isolators
Change engine oil and oil filter Check engine and generator shutdown and alarm systems for proper operation
Perform air inlet restriction test Flush cooling system
Perform coolant system pressure test Grease main generator bearing
Perform back pressure reading on exhaust system Remove, clean, and adjust magnetic pickup
Inspect main generator windings Test fuel for water and algae/bacteria growth
Inspect fan hub, drive pulley and water pump Vacuum/blow dust out of main generator (30psi max.)
Inspect exhaust system for leakage and deterioration Adjust output voltage (450VAC) and frequency (60Hz) if required
Inspect/adjust all accessible hoses, belts, and linkages Change batteries (every 2 years)
Inspect accessible fuel lines for leakage or deterioration Check battery electrolyte levels and specific gravity
Check and adjust valves Clean battery terminals and check tightness of cables
Check ground connection Ensure battery charger is operating properly and record battery charging voltage Voltage: _______________
Check block heater operation Measure and record the generator winding resistance
Winding Resistance:
Operate the Generator Under Load (200kW) for a Minimum of 30 Minutes and Check for Proper Operation as follows: SAT UNSAT
Check for Coolant or Fuel Leaks
Output voltage ______VAC
Output Frequency ________Hz
Engine Oil Pressure ________PSI
Engine Operating Temperature _______ F
Check for Unusual Vibration or Noise
Comments: