AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
1. CONTRACT ID CODE
J
PAGE OF PAGES
1 8
2. AMENDMENT/MODIFICATION NO.
3. EFFECTIVE DATE
28-Jul-2020
4. REQUISITION/PURCHASE REQ. NO. 5. PROJECT NO.(If applicable)
6. ISSUED BY CODE N33191 7. ADMINISTERED BY (If other than item 6) CODE
NAVY PUBLIC WORKS DEPARTMENT, DJIBOUTI
(N-4) BLDG 211
CAMP LEMONNIER, DJIBOUTI
PSC 831 BOX 0043
FPO AE 09363-0043
See Item 6
8. NAME AND ADDRESS OF CONT RACT OR (No., Street, County, State and Zip Code) X 9A. AMENDMENT OF SOLICITATION NO.
N33191-20-R-0664
X 9B. DATED (SEE ITEM 11)
18-Jun-2020
10A. MOD. OF CONT RACT /ORDER NO.
10B. DAT ED (SEE ITEM 13)
CODE FACILIT Y CODE
11. THIS ITEM ONLY APPLIES TO AMENDMENT S OF SOLICITATIONS
X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer X is extended, is not extended.
Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:
(a) By completing Items 8 and 15, and returning copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT
TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN
REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegramor letter, provided each telegramor letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNT ING AND APPROPRIAT ION DAT A (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICAT IONS OF CONT RACTS/ORDERS.
IT MODIFIES THE CONT RACT /ORDER NO. AS DESCRIBED IN ITEM 14.
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE
CONT RACT ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONT RACT /ORDER IS MODIFIED TO REFLECT THE ADMINIST RAT IVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORT ANT: Contractor is not, is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
SOLICITATION N3319120R0664- REPLACE ROWPU STORAGE TANKS, CAMP LEMMONIER, DJIBOUTI
The closing date for this solicitation has been extended until 17 AUG 2020. All proposals must be received by 17 AUG 2020 @ 1400 Eastern Africa Time.
SEE CONTINUATION SHEETS
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print) 16A. NAME AND TITLE OF CONT RACTING OFFICER (Type or print)
TEL: EMAIL:
15B. CONT RACT OR/OFFEROR
(Signature of person authorized to sign)
15C. DATE SIGNED 16B. UNIT ED ST AT ES OF AMERICA
BY
(Signature of Contracting Officer)
16C. DATE SIGNED
14-Aug-2020
EXCEPTION TO SF 30
30-105-04
ST ANDARD FORM 30 (Rev. 10-83) APPROVED BY OIRM 11-84 Prescribed by GSA
FAR (48 CFR) 53.243
N33191-20-R-0664
The following have been added by full text:
AMENDMENT 0002
SOLICITATION N33191-20-R-1748 - REPLACE SWITCHGEAR PP2-B, CAMP LEMMONIER, DJIBOUTI
1. The purpose of the amendment is to
a. Revise the Request for Proposal with changes noted
i. Remove Option 01, page 2 of the RFP
ii. Revise the Basis of Award on page 2 of the RFP
iii. Remove Clause 52.217-4 from the RFP
iv. Remove Clause 52.217-5 from the RFP
v. Remove Clause 52.217-7 from the RFP
vi. Revise the Price Proposal Form
vii. Remove Proposal Note (6) on the last page of the RFP
b. Incorporate Pre-Proposal Inquiries and Government Responses received in response to this solicitation (PPI Log – 1 below)
PPI Log-1 28 JUL 2020
Question 1
Giving the complexity of this solicitation for which we must prepare a concept design to be able to properly evaluate the costs, we ask that the solicitation due date be extended by 2 weeks. In fact, to be able to provide a more precise cost estimate of the new water storage tanks and for the systems that require minimum sizing, as well as a structural analysis, several days to analyze the situation are needed.
Answer 1
Per issuance of this amendment, the proposal due date has been extended
Question 2
Considering that a design phase must be completed over a 10-month time period, approximately 6 months are required for fabricating and delivering the Storage Tanks from USA to Djibouti, additional months are needed to remove and install the tanks and then subsequent testing and commissioning activities must be executed, 392 days is not considered to be a sufficient amount of time to properly execute this contract. Therefore, it is requested that the current POP be extended to 24 months for a total of 720 days.
Answer 2
The period of performance remains unchanged
Question 3
On provided layout (see below), point no. 4 of NEW WORK KEYNOTES, it is mentioned the Provision of new VALVES, FITTINGS & APPURTENANCES.
To our consideration is not clear the scope of provision as we cannot understand what to provide in means of equipment (type, size, quantities, etc.)
Please provide a detailed breakdown of the equipment mentioned under point no.4
Answer 3
This is a design build project. The contractor (KTR) is responsible for the investigation and verification of pipe size, length, material type, valves, fittings, and other appurtenances. The KTR must conduct a site visit and investigation prior to submitting a bid proposal in order to assess the site, existing conditions, extend of work involved, and associated complexities.
Question 4
Under NEW WORK KEYNOTES is mentioned to be provided from the Contractor: “PROVIDE TESTING AND
COMMISSIONING TO THE COMPLETE WATER DITRIBUTION SYSTEM”. Please make clear the battery limits of the equipment to be TESTED & COMMISSIONED. “COMPLETE” means all the new equipment? or in conjunction with the existing one? and up to which level?
Answer 4
The Author of the RFP implies testing and commissioning to all provided equipment/tanks, pipes, valves, and fittings.
Test and commission in accordance with ANSI/AWWA D103-97 and UFC 3-230-01 Water Storage, Distribution, and
Transmission; whichever is more stringent.
Question 5
On page 2 paragraph 2.1 it is mentioned: “Provide two new and complete water storage tanks from a qualified manufacturer with a minimum of five years in manufacturing experience of steel storage tanks” Please clarify which references has the manufacturer to have.
Answer 5
Refer to ANSI/AWWA D103-97 and UFC 3-230-01 Water Storage, Distribution, and Transmission, whichever is more stringent.
Question 6
Is an Internal Cathodic Protection required for the two new tanks? If yes please provide us the related specs describing exactly the type of the system required.
Answer 6
The Author of the RFP required to design in accordance with ANSI/AWWA D103-97 and UFC 3-230-01 Water
Storage, Distribution, and Transmission, whichever is more stringent. Kindly refer the design base on these standards and guidelines.
Question 7
Is lightning Protection required for the two new tanks? If yes please provide us the related specs describing exactly the type of the system required.
Answer 7
No lightning protection required.
Question 8
Is Obstruction Lighting required for the two new tanks? If yes please provide us the related specs.
Answer 8
No obstruction lighting is required.
Question 9
Is remote level indication required for the new two tanks? If yes please specify if also cabling is required to be terminated to an existing (or not) marshalling cabinet with existing (or not) I/O Cards and if existing (or not) SCADA has to be updated.
Answer 9
Each existing tank has a mechanical level gauge visible externally and a pressure transducer that can send a 4-20 milliamp signal used to verify mechanical reading.
Question 10
Is an Impressed Cathodic Protection required for the two new tanks (rectifier, buried anodes, etc.)? If yes please provide us the related specs describing exactly the type of the system required.
Answer 10
Refer to ANSI/AWWA D103-97 or UFC 3-230-01 Water Storage, Distribution, and Transmission
Question 11
Is any U/G piping network involved to this project. If yes please provide details of the Scope of Work
Answer 11
No U/G piping network involved.
Question 12
Is any Water metering device involved to this project? If yes please provide details of the Scope of Work
Answer 12
There is a mechanical water level gauge on each tank. No metering device.
Question 13
Is any backflow prevention system involved to this project? If yes please provide details of the Scope of Work
Answer 13
No backflow prevention system involved.
Question 14
Is any fire Hydrants system involved to this project? If yes please provide details of the Scope of Work
Answer 14
No fire hydrant systems involved.
Question 15
Is the paragraph G3020 applicable within the Scope of Work of this Project? Please clarify which parts of this paragraph are involved to this project.
Answer 15
No. The Author of the RFP included the G3020 SANITARY SEWER in part 4 as part of the minimum materials, engineering and construction requirements only. Shall the scope in part 3 does not require any items concerning
G3020, the KTR shall disregard such reference.
Question 16
Is the paragraph G3030 applicable within the Scope of Work of this Project? Please clarify which parts of this paragraph are involved to this project.
Answer 16
Yes, please see G3030 STORM SEWER on part 3 Statement of Work/Project Program. KTR to verify location of overflow piping and connection and its tapping point on site.
Question 17
For Contract CLIN002 Option 1 work is mentioned: “Price for all work including labor, materials, supplies and supervision, associated with replacement of deteriorated stainless-steel pipe and rerouting of reverse osmosis membrane pipe to UV device / equipment”. From the Technical information sent to us we are able only to understand that only discharge pipes for RO No4 & RO No2 are corroded plus the portion of header pipe connected to U/V
Treatment device (see below marked drawing).
The queries raised are the following:
Is it required the complete replacement of discharge pipes for RO No1,2,3 and 4, plus the header pipe connected to U/V treatment device?
If yes please provide distances between the RO Equipment and U/V treatment device as without Site Survey it is impossible to define the exact materials and welds needed to accommodate this scope of work.
Is required to supply new bracing supports? If yes how many of those?
What is the size of the piping to be replaced?
Answer 17
By way of this amendment, CLIN 0002 Option1 is hereby removed.
Question 18
Laydown Area: Is it known where the designated 50x50 meters laydown area will be located and the distance from the laydown area to the project site?
Answer 18
Several areas are appropriate; however, none adjacent to the project site
Question 19
Haul route: Is there any planned route or restrictions for heavy trucks driving from designated laydown area to the project site?
Answer 19
Routes are all paved. There are sidewalks and underground lines in the area.
Question 20
Per 01 31 19.05 20 POST AWARD MEETINGS, the DQC Manager and the DOR are to attend the PAK. Will this be required to attend in person or virtual?
Answer 20
Whatever method that can most effectively meet the intent of the referenced section is acceptable
Question 21
Please indicate if virtual attendance for the design engineering team is acceptable for the Post Award Kick-Off meeting, Design review meetings, Pre-Construction Conference, Coordination meetings and similar
Answer 21
Whatever method that can most effectively meet the intent of the referenced section is acceptable
Question 22
For Option 1 Bid - Replacement of Deteriorated Stainless Steel Pipe and Rerouting of RO
Membrane Pipe to UV Device/Equipment - the contractor shall be responsible for the investigation and verification of the piping size, length, materials type, location, and routing of the existing set-up of the RO train. Is this re-routing within the same ROWPU building? Can the Government provide the existing as-built drawings? This information is needed to evaluate the level of effort for the design and construction of Option 1.
Answer 22
Question 23
Section G3030 (PDF page 42) refers to overflow piping and connection to the existing storm sewer collection system at the point indicated on the drawings in Part 6 of the RFP. Connection point is not found in Part 6. Please clarify.
Answer 23
The intent of the RFP is to connect the overflow piping to existing storm water conveyance system manhole. The nearest connection point is located on Third Street north of the tanks.
Question 24
RFP Section A10 FOUNDATION indicate that the Importance Factor must be based on Risk Category III and IV (Part
3 Statement of Work, Page 6). The difference is essentially if this system is required, or not, to maintain water pressure for a fire suppression system. Per the elements provided, this information is not clear. Please clarify.
Answer 24
The system will be required to maintain water pressure for fire suppression.
Question 25
According to UFC 3-230-01, paragraph 4-2.2 level controls are required for water storage facilities, including low and high level sensors/alarms and interaction with existing pump control system. Please confirm that these level sensors/alarms are required and that the existing pump control system is prepared to receive signal from the sensors.
Answer 25
All level sensors and alarms are located in the pump house, off of main header. Not on the tanks.
Question 26
Please clarify if an Automatic Tank Gauge system is required for remote monitoring of water level on each tank.
Answer 26
Not at this time. Suggest adding automated valves and automatic tank gauges at time of new SCADA install.
Question 27
In order to provide the best possible proposal, please consider a time extension of 3 weeks after clarifications for the submission of the bid. This will allow the development of the design solution and determination of precise constructions costs.
Answer 27
Per issuance of this amendment, the proposal due date has been extended
Question 28
Need details like Length, die, path for Deteriorated Stainless Steel Pipe and Reverse Osmosis Membrane Pipe
Answer 28
Question 29
Which Leakage tests are have to perform
Answer 29
Leak test and disinfect in accordance with ANSI/AWWA D103-97 and UFC 3-230-01 Water Storage, Distribution, and
Transmission; whichever is more stringent. Leak testing, disinfection & flushing, bacteriological test procedure shall be performed to all provided tanks and pipelines for this project.
Question 30
Need the side utilities details of the existing tank that have to demolish "Replace the corroded 3” (80 mm) stainless steel pipe connected to the pneumatic actuator valve from RO membrane to prevent further damage on the water production of the ROWPU system.
Answer 30
Dia. 38', Ht. 24', Design spec. AWWA D103-97, NSF Columbian TecTank, Nom. Capacity 211908
Question 31
What is the distance from UV Treatment device to each reverse osmosis device?
Answer 31
Question 32
What is the existing pipe material and pipe size (Specifications) from the UV Treatment device to each reverse osmosis device?
Answer 32
Question 33
What is the distance from UV Treatment device to High pressure pump?
Answer 33
Question 34
What is the existing pipe material and pipe size (Specifications) from the UV Treatment device to High pressure pump?
Answer 34
Question 35
What is the distance from longest Purifier tank to High pressure pump?
Answer 35
Question 36
What is the existing pipe material and pipe size (Specifications) from the Purifier tank to High pressure pump?
Answer 36
Question 37
Please confirm if pipe from the RO membrane to High pressure pump need to be replaced? If yes, please let us know the existing pipe specs and distance
Answer 37
No, the line from high pressure pump to RO membrane will not be replaced. Kindly refer to Drawing M-101 Existing
Pipe Schematic of Reverse Osmosis Train Demolition Layout and M-102 New Pipe Schematic Layout of Reverse
Osmosis Train to verify which pipe lines are needed to replace.
Question 38
What is the distance from UV Treatment device to water reticulation tank?
Answer 38
Question 39
What is the existing pipe material and pipe size (Specifications) from the UV Treatment device to water reticulation tank?
Answer 39
(End of Summary of Changes)