0569_A_TAKE CCSI FIRE AND SMOKE DETECTION ALARM SYSTEM (1 YR) (SCSI) Rev. 1.doc
DOC document 428 KB Posted
- Attached to
- USNS RICHARD BYRD MTA
- Solicitation number
- N3220521R4156
About this file
This document outlines the requirements for inspection, service, and testing of the fire and smoke detection system aboard the USNS Richard E. Byrd. The system includes 169 heat detectors, 169 thermal detectors, 517 smoke detectors, six smoke/heat detectors, five flame detectors, one gas detector, and 123 pull stations. Key requirements include conducting annual inspections of all components; function testing detectors, pull stations, and notification appliances; verifying compliance with industry standards; replacing outdated or non-compliant components as needed; and submitting comprehensive reports upon completion. The contractor must utilize qualified personnel certified by ABS and USCG to perform all inspection, maintenance, repair and testing services for the firefighting systems.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| N3220521R4156 Amendment 00005.docx | DOCX document | |
| N3220521R4156 Amendment 00004.docx | DOCX document | |
| J - 2 Category A Items BYRD Amendment 00004.xls | XLS spreadsheet | |
| N3220521R4156 Amendment 00003.docx | DOCX document | |
| N3220521R4156 Amendment 00002.docx | DOCX document | |
| J - 2 Category A Items BYRD.xls | XLS spreadsheet | |
| J - 10 Interport Differential.docx | DOCX document | |
| N3220521R4156 Amendment 00001.docx | DOCX document | |
| N3220521R4156 USNS RICHARD BYRD.docx | DOCX document | |
| J-Attachments.zip | ZIP file | |
| New CDRLS.zip | ZIP file |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
USNS Byrd
( TAKE 4 )
| AUXILIARY MACHINERY |
| CONTRACT NO. N32205-21-R-4156 |
| ITEM NO. 0569 |
| CATEGORY "A" |
| 16 February 2021 |
| TAKE_CCSI_FIRE AND SMOKE DETECTION ALARM SYSTEM (1 YR) (SCSI) Rev.1 |
| Lombos, Willie |
1.0 ABSTRACT
The purpose of this item is to inspect, service, and test the ship’s fire and smoke detection system and associated alarm systems.
2.0 REFERENCES/ENCLOSURES
2.1 References
2.0 MSC Tech Manual TE168-BF-MMC-010, Technical Manual Detection System, Fire and Smoke, Model CS4000, Service and Maintenance
2.0 MSC Drawing NO. 801-8193671, Fire Control Plan
2.0 46 CFR §76.27 — Fire Detection and Alarm System, Details, §76.33 — Smoke Detection System, Details, § 76.35 — Manual Alarm System, Details
2.0 SOLAS II-2, Part C, Regulation 7; Detection and Alarm (Available Commercially)
2.0 NFPA Code 72 National Fire Alarm and Signaling Code (Available Commercially)
2.0 Enclosures
2.0 Fire and Smoke Detection and Alarm System – Inspection and Test Form
2.0 Fire and Smoke Detection and Alarm System – Initiating Device Test Results Form
3.0 ITEM LOCATION/DESCRIPTION
3.0 Location/Quantity
3.0 Locations: See Reference 2.1.3.
3.0 Quantity:
3.0 One hundred sixty-nine (169) heat detectors
3.0 One hundred sixty-nine (169) thermal detectors
3.0 Five hundred and seventeen (517) smoke detectors
3.0 Six (6) Smoke/Heat detectors
e. Five (5) flame detectors
f. One (1) gas detector
3.0 One hundred twenty-three (123) pull stations
3.0 Item Description/Manufacturer’s Data: Fire and smoke detection and alarm system
Manufacturer: Siemens
4.0 GOVERNMENT FURNISHED EQUIPMENT/MATERIAL/SERVICE: None
5.0 NOTES
5.0 The contractor and all subcontractors, regardless of tier must consult the General Technical Requirements (GTR) to determine applicability to this work item. In performance of this work item, the contractor and all subcontractors regardless of tier must comply with the requirements of all applicable GTR’s including but not limited to GTR’s 1 through 7, 22, 23, 24, 28, and 29.
5.0 The contractor and all subcontractors regardless of tier are advised to review other work items under this contract, including but not limited to Work Items 023, 567, 569, 569, 570, 571, 572, 573, and XXX to determine their effect on the work required under this work item. Many of the definitions relating to performance of this work item are found in Work Item 001.
6.0 QUALITY ASSURANCE REQUIREMENTS: None additional
7.0 STATEMENT OF WORK REQUIRED
7.0 Inspect, service, and test the fire and smoke detection system identified in paragraph 3.0 using References 2.1.1 through 2.1.5 for guidance. Accomplish inspection and testing in accordance with IMO, SOLAS, and manufacturer’s requirements.
7.0 Fire detection and alarm systems may output signals to other fire safety systems including, but not limited to, paging systems, fire alarm or public address systems, fan stops, fire doors, fire dampers, sprinkler systems, smoke extraction systems, low-location lighting systems, fixed local application fire extinguishing systems, and closed-circuit television systems.
7.0 With the assistance of ship’s force, secure and tag systems including any associated fire extinguishing system and controls to prevent accidental discharge.
7.0 Conduct an annual inspection of all fire and smoke detection and alarm systems and complete Enclosures 2.2.1 and 2.2.2. It is to be a thorough examination of the equipment and system ensuring there are no changes that affect performance and verifying that the system and components are in good operating condition. It is to include inspection for ship modifications, changes in environmental conditions, device locations, physical obstruction, physical damage and degree of cleanliness.
7.0 Examine the control equipment to verify normal system condition to include fuses, interfaced equipment, lamps and LEDs, power supply and trouble signals.
7.0 Verify location and condition of emergency communication equipment including public address system, general alarm and emergency elevator phone.
7.0 Examine batteries for corrosion or leakage. Verify month and year of manufacture, tightness of connections and level of electrolyte.
7.0 Examine UPS and verify meters, lamps and LEDs indicate normal operating status. Verify proper fuse ratings.
7.0 Examine location and condition of the remote annunciators.
7.0 Verify location and condition of fiber optic cable connections.
7.0 Conduct an external visual examination of all detectors and pull stations. Identify any obvious physical damage, dirt, corrosion, and missing device. Verify each is in the correct location, rigidly mounted, clearly marked and record all data including device/sensor type, name of manufacturer, sensitivity/range, explosion proof, and if weatherproof. For air sampling devices, verify that any in-line filters are clean. For detectors, verify the area requiring detection is not obstructed or outside the detectors field of view.
7.0 Clean detectors whenever there is evidence of dirt or other contamination.
7.0 Verify condition of any fire alarm control interface with other systems such as fire dampers, door and releases.
7.0 Verify location and condition of all notification appliances (audible alarms, visual alarms, combination a/v alarms, and exit markings).
7.0 Verify audible alarms are identified by at least 1-inch red lettering as “FIRE ALARM” as required by 46 CFR §78.47-13.
7.0 Verify location of the mass notification system and inspect to ensure the system is functioning properly. Inspection is to include control equipment, fuses, interfaces, lamps and LEDs, main power supply, UPS, initiating devices, notification devices, antennas and transceivers.
7.0 Verify system devices comply with the following standards, per 46 CFR §161.002-1:
7.0 Control units—UL 864 Heat
7.0 Detectors—UL 521
7.0 Smoke detectors—UL 268
7.0 Flame detectors—ANSI/FM 3260
7.0 Audible alarms—UL 464 or UL 1480
7.0 Visual alarms—UL 1971
7.0 Manual Signaling Boxes—UL 38
7.0 Verify location and condition of supervising station – receivers.
7.0 Verify that clear information about the operation of the fire detection and alarm system is displayed on or adjacent to its control panels.
7.0 Verify the detection and alarm system has had no modifications made since last inspection.
7.0 When inspections reveal any deficiency a condition report is to be submitted to the MSCREP with recommended repairs and parts required.
7.0 Functionally test the fire and smoke detection and alarm system. It is to include all devices, fault alarms and signals, and visual and audible alarms using References 2.1.1 through 2.1.5 for guidance. Complete Enclosures 2.2.1 and 2.2.2 recording the results of all inspections and tests.
7.0 Coordinate all testing prior to accomplishment. Advance notification is to be given to the Shipyard Superintendent and MSCREP. With assistance from ship crew, make announcements over the public address system prior to initiating any alarms.
7.0 Test and verify the control equipment functions by receiving correct alarm, supervisory and trouble signals (input); operation of evacuation signals and auxiliary functions (outputs); circuit supervision including detection of open circuits and ground faults; and power supply supervision for detection of loss of AC power and disconnection of secondary batteries. Verify rating and supervision of fuses. Illuminate all lamps and LEDs. Test the primary power under maximum load conditions, including all alarm appliances requiring simultaneous operation. Test the secondary power supply separately.
7.0 Develop a testing schedule to ensure that every initiating device is tested. Actuate every initiating device, including detectors and pull stations and verify proper operation and receipt of correct signal at the supervising station within 90 seconds. Upon completion of the test, restore the system to its functional operating condition. Activation of any detector or manual pull station must cause an audible and visual alarm signal at the control panel. Complete Enclosures 2.2.1 and 2.2.2 recording the results.
7.0 Verify that the detector/alarm initiating device is alarming the proper zone on the Master Panel and all Remote Annunciators.
7.0 Arrange the testing schedule so that all zones will be alarmed during testing. Conduct a cross-zone detection test. The last alarm given on a particular zone should be silenced only (not reset), then, to verify that the subsequent alarm is functioning properly, place another zone into alarm, then the system can be reset.
7.0 Test the detectors using the manufacturer’s guidance. Care and caution are to be used to prevent damage to the detectors and pull stations while testing.
7.0 In addition, test all smoke and flame type detectors to ensure that each is within its listed and marked sensitivity range using one of the following methods:
7.0 Calibrated test method
7.0 Manufacturers calibrated sensitivity test instrument
7.0 Listed control unit arranged for the purpose
7.0 Other approved calibrated flame sensitivity test method that is directly proportional to the input signal from a fire.
7.0 Other calibrated smoke sensitivity test method that is approved by the authority having jurisdiction (AHJ).
7.0 If detectors are designed to be adjustable, adjust to bring them into the approved range.
NOTE: DO NOT DETERMINE FLAME DETECTOR SENSITIVITY BY USING A LIGHT SOURCE THAT ADMINISTERS AN UNMEASURED QUANTITY OF RADIATION AT AN UNDEFINED DISTANCE FROM THE DETECTOR
7.0 Verify that the detectors are self-restoring.
7.0 Verify that if the alarm signal has not been acknowledged within 2 minutes, an audible fire alarm is automatically sounded throughout the crew accommodations and service spaces, control stations, and manned machinery spaces. Verify that each Bridge, Quarter-Deck Office and the Engine Room Control Station is receiving the proper delay before any alarms are sent.
7.0 Demonstrate the fire detection and alarm system monitors the power supplies necessary for the operation of the system during loss of power and fault conditions. Disconnect the primary (main) power supplies and verify a trouble or fault indication is given. Measure the systems standby and alarm current demand and verify the batteries ability to meet these requirements. Verify communication between sending and receiving units under both primary and secondary power. Reconnect the primary power upon completion.
7.0 Test the UPS for proper operation.
7.0 Prior to conducting any battery test, verify that all system software stored in volatile memory is protected from loss. Test the performance of the battery charger by measuring the voltage across the battery when they are fully charged and connected to the charger. Test the performance of the batteries by disconnecting the charger and conducting a load test (full fire alarm load) on the batteries verifying the voltage does not fall below the manufacturer’s specified levels.
7.0 Verify the local and remote annunciators operate and identify correctly under all conditions.
7.0 Test every notification device (audible and visual alarm) verifying each operates properly.
7.0 Check the supervisory circuits and indicators on the control panel and each annunciator panel by operating the Lamp Test Switch. All visual indicators should be lit, and the trouble horn should sound.
7.0 Test for automatic supervision (monitoring) of any fault in all external wiring such as an open circuit, short circuit, or ground. Any of these conditions should result in a visual fault/trouble signal.
7.0 Verify that every fault (such as an open circuit, short circuit, or ground fault) does not prevent the continued individual identification of the remaining detectors and manual pull stations.
7.0 Test and verify that the system automatically resets to a normal operating condition after alarm and fault situations are cleared.
7.0 Fire detection and alarm systems may accept signals from other safety systems. For example, a signal initiated from actuation of an automatic sprinkler valve or fusible link may be sent to a fire detection and alarm system. Test their proper functioning.
7.0 Test all interconnected auxiliary equipment or systems such as remotely controlled fire doors and dampers, fan shutdowns, or elevator recall for proper activation.
7.0 Accomplish maintenance on the fire and smoke detection system:
7.0 Replace those smoke or flame detectors found outside the approved range of sensitivity.
7.0 For estimating purposes assume zero (0) heat and zero (0) smoke detectors and zero (0) pull stations will require replacement.
7.0 Replace any system batteries when the recharged battery voltage or current falls below the manufacturer’s recommendation.
7.0 Coordinate and conduct a final functional test demonstrating satisfactory operation of the fire and smoke detection and alarm systems in the presence of the MSCREP.
7.0 Upon completion of all inspections, tests and repairs return the Fire and Smoke Detection and Alarm Systems to a ready for service condition. Conduct a final walk around survey with the MSCREP to verify status.
7.0 Reports
7.0 Upon completion of all inspections, tests and maintenance, prepare and submit the System Check sheet and Test Result forms shown in Enclosure 2.2.1 and 2.2.2. The reports are to be typewritten reports documenting the examination of the system and final “as released” conditions. Submit three (3) typewritten copies and one (1) electronic copy in Portable Document Format (PDF).
7.0 All reports and checklists are to be completed and signed by the person who carried out the inspection and maintenance work and countersigned by the Company's representative.
7.0 Painting/Lagging: None
7.0 Manufacturer’s Representative
7.11.1 Persons performing annual and periodic maintenance and recharging of fire detection and extinguishing equipment are to be certified and recognized as an authorized specialist by ABS.
7.11.2 Companies and persons performing maintenance and testing shall have available the appropriate certificates, servicing manuals, service bulletins, correct tools, materials, and manufacturer’s replacement parts.
7.11.3 Provide the services of a qualified and certified Original Equipment Manufacturer (OEM) technical field service representative(s) familiar with the T-AKE Class firefighting systems and equipment. The service representative(s) and company utilized to accomplish all firefighting systems inspections, testing and repairs shall be recognized and certified by ABS and USCG for the performance of these services.
7.11.4 An OEM technical field service representative is defined as either a direct employee of the OEM, or an employee of a company which has a current written agreement with the OEM to provide service and repair for that equipment. The OEM technical field service representative shall have full access to the OEM drawings, technical service bulletins, special tools, and OEM replacement parts.
a. The OEM technical field service representative shall provide documentation from the OEM authorizing the company to perform maintenance and repair on their behalf.
b. The OEM technical field service representative shall be experienced with the firefighting systems onboard the T-AKE Class and the testing of these systems.
7.0 Preparation of Drawings: None
8.0 GENERAL REQUIREMENTS: None additional.
Enclosure 2.2.1 Fire and Smoke Detection and Alarm System – Inspection and Test Form Shipyard:
Date of Inspection:
Service Company:
Inspector:
Phone:
Email address:
To be completed by the system inspector at the time of inspection or test. The inspection of the fire and smoke detection system shall at a minimum include checks and tests of the following:
SYSTEM VERIFICATION
1. TYPE
Fire Alarm System
Smoke Alarm System
Security System
Fire/Smoke Combination
Other (specify):
2. CONTROL UNIT
Manufacturer:
Model:
Serial #:
An owner’s manual, manufacturer’s instructions, a written sequence of operation and a copy of the system drawing is stored onboard.
3. SYSTEM SOFTWARE
Software revision number:
Last updated:
A copy of the ship specific software is stored onboard.
4. SYSTEM POWER
Primary Power
Control Panel Input voltage:
Control panel amps:
Secondary System
Nominal voltage:
Amp/hour rating:
In standby mode:
In alarm mode:
Batteries (date of mfg):
5. ANNUNCIATORS
Manufacturer - No.1:
Model:
Manufacturer - No.2:
Model:
Manufacturer - No.3:
Model:
Manufacturer - No.4:
Model:
6. DETECTORS
Thermal (qty):
Smoke (qty):
Flame (qty):
Other (qty):
7. PULL STATIONS
Manual stations (qty):
8. ALARMS
Audible (qty):
A/V Combination (qty):
Visual (qty):
9. NOTIFICATIONS MADE PRIOR TO TESTING
Shipyard Superintendent:
(time/date)
Vessel Master:
(time/date)
Vessel Chief Engineer:
(time/date)
Port Engineer:
(time/date)
Enclosure 2.2.1 Fire and Smoke Detection and Alarm System Inspection and Test Form
| # |
| DESCRIPTION |
| VISUAL INSPECTION |
| FUNCTIONAL TEST |
| SAT |
| UNSAT |
| NA |
| COMMENTs |
| 1 |
| Secure interconnected fire extinguishing systems and controls to prevent accidental discharge |
| 2 |
| Placards and Instructions in place and legible |
| 3 |
| Verify no modifications have been made since last inspection. |
| 4 |
| Control Unit and Related Equipment |
Lamps/LEDs/LCDs
Fuses
Input Signals (alarm/supervisory/trouble)
Output Signals
Supervision
(wire faults/power loss/fuses)
Local Annunciators
Remote Annunciators
Input from other safety systems
Fiber Optic Cable Connections
Other (specify)
| 5 |
| Power Supplies |
Primary AC power
Secondary Power
UPS
Battery condition
Load voltage
Discharge test
Charger test
| 6 |
| Notification Appliance |
Audible alarm
Visual alarm
Combination A/V alarm
General alarm
| 7 |
| Initiating Device – Detectors |
Heat
Flame
Security
Flooding
Other (specify)
| 8 |
| Initiating Device - Pull Stations |
| 9 |
| Emergency Communications |
Public Address system
Phone handsets
Emergency Elevator comm
Other
| 10 |
| Other Monitored Systems |
Fire Pumps
Special Fire Suppression system
Other (specify)
| 11 |
| Auxiliary Functions |
Door releasing device
Door unlocking
Fan shutdown
Smoke damper operation
Elevator recall
Elevator shunt trip
Paging system
Mass notification system
Closed-circuit television systems
Other (specify)
| 12 |
| Alarm Initiating Device |
Device test result sheets attached listing all devices and test results
| 13 |
| Supervisory Alarm Initiating Device |
Device test result sheets attached listing all devices and test results
| 14 |
| Alarm Notification Appliances |
Appliance test result sheets attached listing all appliances and test results
| 15 |
| Supervisory Station Monitoring |
Alarm signal
Alarm restoration
Fault/Trouble restoration
Supervisory signal
Supervisory restoration
| 16 |
| Final functional system test with MSC and ABS in attendance |
| 17 |
| System returned to active service |
| 18 |
| Inspection tags attached |
SAT = Satisfactory UNSAT = Unsatisfactory N/A = Not applicable
Enclosure 2.2.1 Fire and Smoke Detection and Alarm System Inspection and Test Form
1. CERTIFICATION
Inspector Certification:
This system, as specified, has been inspected and tested according to the standards cited in the work item.
Signed:
Printed Name:
Date:
Organization:
Title:
Phone:
Enclosure 2.2.2 Fire and Smoke Detection and Alarm System Inspection and Test Form
FIRE AND SMOKE DETECTION AND ALARM SYSTEM
INITIATING DEVICE TEST RESULTS FORM
(attach additional sheets if required)
| Device Type |
| Address |
| Location |
| Test Results |
Function Test Results
Sensitivity
| Thermal detector |
| Zone 1 |
| X-XX-XX |
| SAT |
| Heat detector |
| Zone 1 |
| X-XX-XX |
| SAT |
| XX |
| Smoke detector |
| Zone 1 |
| X-XX-XX |
| SAT |
| XX |
| Manual pull station |
| Zone 1 |
| X-XX-XX |
| SAT |
| Thermal detector |
| Zone 2 |
| X-XX-XX |
| SAT |
| Heat detector |
| Zone 2 |
| X-XX-XX |
| SAT |
| XX |
| Smoke detector |
| Zone 2 |
| X-XX-XX |
| SAT |
| XX |
| Manual pull station |
| Zone 2 |
| X-XX-XX |
| SAT |
| Ground fault detector |
| Control |
| X-XX-XX |
| SAT |
| Short circuit detector |
| Control |
| X-XX-XX |
| SAT |
| Open circuit detector |
| Control |
| X-XX-XX |
| SAT |
| Loss of primary power |
| Control |
| X-XX-XX |
| SAT |
0569 - 9