8.5.15_Amend-_New_Antenna_Location_-_E300.pdf
PDF 512 KB Posted
- Attached to
- Fire Alarm System Install
- Solicitation number
- MELLO-FTQW081022-CC-FIRE-ALARM-SYSYTEM-INSTALL
About this file
New Antenna
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
B
ZONE 1
ZONE 2
ZONE 5
ZONE 3
TANK
PS PS
SV
EA
SV
EA
SV EA
ZONE 3
SV EA
ZONE 2
SV EA
ZONE 1
PS
PS
PS
ZONE 5
WEST
MONITOR
HANGAR
BAY
MECHANICAL
ELECTRICAL
CORRIDOR
PAINTING &
PAINT PREP
BLAST
ROOM
CORR
VEST
RESTROOM
117A
RESTROOM
117B
JANITOR
CORR
TEL
DISPATCH
OFFICE
OFFICE
VEST
PROPANE
VAPORIZER
ZONE 5
EAST
MONITOR
B
FACP FSCPNEP1 PEP1
LT
CONTINUED ON E301
E300
FIRE SUPPRESSION PLAN - SOUTH
1/8" = 1'-0"
SPECIFIC NOTES
PROVIDE ADDRESSABLE OUTPUT MODULES (ONLY ONE SHOWN) MULTI-CONTACT RELAY OR CONTACTOR(S) TO INTERRUPT SIGNALS TO AIR HANDLER UNITS DURING FIRE ALARM EVENT WHEN FIRE ALARM CONTROL PANEL CALLS FOR SHUTDOWN OF AIR HANDLER UNIT(S).
CONTACTS OF CONTACTOR TO BE NORMALLY CLOSED SO NORMAL HVAC CONTROLS FUNCTION UNTIL FIRE ALARM CALLS FOR THESE UNITS TO BE SHUTDOWN. REFER TO TABLE OF UNITS WHICH ARE TO BE SHUTDOWN AND SKETCH OF MCC SHOWING APPROXIMATE
LOCATION ON 2/E401.
Elizabeth T.B. Johnston
No. FP14150 9-Apr-2015
Chris H. Miller
No. FP13572 9-Apr-2015
GENERAL SHEET E300-E301 NOTES
1. LOCATE MANUAL FIRE ALARM STATIONS AND MANUAL FOAM DISCHARGE
STATIONS NOT LESS THAN 5' APART.
2. PROVIDE NEMA4X FOR ALL BOXES AND FITTINGS IN HANGAR SPACES OR SPACES
WITH HOSE STATIONS. CONDUITS SHALL ENTER BOXES AND CONTROLS ONLY
FROM THE BOTTOM.
NEW ANTENNA LOCATION
ElizElElElElllllElElEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEE abeth T.B. JB. B. B. B. BBBB.BB.BBBBBBBBBBBBBBBBB ohnston 9 Apr 2015
Existing
New Location??
1027894042C Oval
1027894042C Oval
1027894042C Oval