EIELSON AFB FIRE SYSTEMS STANDARDS

354TH CIVIL ENGINEER SQUADRON

ALARM MAINTENANCE SHOP

1.FIRE ALARM PANELS:
A.INTELLIGENT FIRE ALARM PANELS (ADDRESSABLE):
An Intelligent type fire panel is required for facilities that have five rooms or more. The Intelligent fire panel is also strongly encouraged for facilities with less than five rooms for its supervisory quality, troubleshooting ease, and information provided for responding fire fighters. Point to Point reporting is the required programming type of the addressable panel such as a MAAP+ panel, MAAP-X panel from Monaco. This is to get the point to point reporting back to the D-21 system at fire dispatch. The panel selected shall have at minimumtwo Signaling Loop Circuits (SLC). A failure of one SLC shall not cause a facility to lose over 50% of its detection capability. All newly installed panels must be able tocommunicate with the Monaco Fire alarm receiving station at the Fire Department by radio signal. The Radio transmitters must be compliant with Item #3.
B.CONVENTIONAL FIRE PANEL:
The traditional multi-zone fire alarm panel is fine for small buildings of four rooms or less,such as a 40’ x 80’ storage warehouse. However, do not lump all initiating devices (heatdetectors, pull stations, etc.) into a single zone. A single zone facility is unacceptable to theFire Department and Alarm Maintenance technicians. A failure of one zone shall not cause afacility to lose over 50% of its detection capability. The acceptable manufacturers areSimplex, Pyrotronics, and Monaco. All newly installed panels must be able to communicatewith the Monaco Fire alarm receiving station at the Fire Department by radio signal. TheRadio transmitters must be compliant with section #3.
C.REQUIEMENTS INCLUDING CODE FOR INSTALLATION OF FIRE PANELSAND SYSTEMS:
1.The fire panel shall have a dedicated branch circuit to power it and itsdisconnectingmeans shall be permanently identified inside the fire alarm controlpanel. Thedisconnecting means (Circuit Breaker) shall be identified as “FIRE ALARM CIRCUIT”on the panel. The disconnecting means handle or tab shallbe red for visualidentification. These requirements are all per NFPA 72 10.5.5.2-10.5.5.3.
2.For system maintenance, reprogramming, and testing a copy of all documentationand equipment relevant to the fire alarm panel or system shall be turned over to the Firealarm Shop (907)377-6666. This is to include per code 14.2.4.1, and 14.2.4.2 of NFPA72 a copy of the program, all programing software and interface equipment for both thefire alarm panel and all fire system devices requiring programing even if proprietary thisis to include operating software keys. The revisions of the fire alarm software, and therevisions of the software in the systems with which the fire alarm software interfaces,shall be verified for compatibility in accordance with the requirements of 23.2.2.1.1.
3.All conduits for Fire alarm systems shall be red. If not possible than all conduitsshall be marked every 10 ft. and all junction or connections boxes or points shall bemarked red.
4.There shall be a smoke detector installed above the Fire alarm control panel percode unless panel is installed in artic entryway, then a fixed temp heat detector shall beinstalled instead.
5.All Standby or backup batteries shall be installed if allowed in the fire alarm panel, ora manufacture list battery panel. There shall be enough room so that batteries can beproperly place in cabinet on their base not side or ends.
6.All fire alarm systems components including sprinkler system control valve shall besupervised and continuously monitored for troubles.
7.All fire alarm panels must include ability to override HVAC system and shut it downin fire emergency. This override ability must cause the panel to go into a troublecondition in the out of normal state.
8.Where addressable modules are used on conventional devices reporting back to panel,it shall be a one for one attachment. This being that each addressable initiating devicemodule shall monitor, at most, one conventional initiating device.
9.Contractor shall include a disable switch or function for the following items (locatedat the main fire alarm control panel): [air handler fan shutdown and smoke damperclosure, horns (speakers for combined systems), strobes, automatic door hold openrelease, elevator recall, elevator shunt trip, fire pump, exit sign flash, etc.] If a disableswitch or feature is activated, an LED will illuminate at the panel indicating a troublecondition, a trouble signal shall be transmitted to the fire department and a description ofthe feature disabled displayed at the fire alarm panel.
10.The fire alarm system wiring shall be Class A or X. Provide 1 foot vertical and 4 foothorizontal separation between outgoing and return raceways of looped circuits.Separation is not required for the first 10 feet of raceway to/from an individual device.Separation is not required for loops to multiple devices installed in rooms 1000 squarefeet and smaller.
11.All conductor connections shall be made under screw terminals. Provide insulatedbarrier type terminal strips at junction points. Use of wire nuts, crimped connectors, ortwisting of conductors is prohibited.
12.Any add-ons to the fire panel, such as exit lights that flash during alarm, must meetfire alarm panel manufacturer’s compatibility requirements.
13.All Spare keys will be turned into the Alarm Maintenance Shop. We recommend thatthe fire panel and all device panels are of a common type such as C415A, T45, or B type.
14.A surge protector shall be installed in each Fire Alarm system to preventpowersurges from burning sensitive electronic parts.
15.In addition to information listed above all panels must be installed per NFPA 72 andUFC 3-600-01.
16.All Fire Panels and devices shall be terminated by either a NICET level III technicianor an individual licensed by the State of Alaska for fire alarm systems installation (ClassIC). Proof of qualifications shall be submitted on request.
D.FIRE PANEL REPORTING:
The Contractor is responsible for programming all front end devices and getting a list of theirzone or device setup to the Fire Alarm Shop so that it can be programmed into the D-21 forthat facility. The fire alarm panel or transceiver shall transmit all addressable devices or atminimum the following zones in order:
1.Water flow alarm (1 per water flow switch)
2.Manual Pull Station (1 per floor)
3.Automatic detector initiating building alarm (1 per floor per device type)
4.Dwelling unit heat detector alarm signal (1 per floor)
5.Dwelling unit smoke detector supervisory signal (1 per floor)
6.Tamper Switch trouble signal
7.Low Temperature supervisory signal for mechanical rooms
8.Duct Detector alarm signal (1 per floor)
9.Mass Notification override of the fire alarm notification system supervisory signal
10.General supervisory signal
11.Common Trouble signal
12.Two spare zones, including necessary relays and hardware in the fire alarm panel andtransmitter panel.
2.REMOTE ANNUNCIATOR:
A. We recommend locating the fire alarm panel near the main entrance to the building. Ifthis is not possible than an annunciator must be located at the entrance. We require aTextural annunciator panel if possible for fire alarm panel that is compatible with that type offire panel.
B.The annunciators must have both a silence and reset button, and provide the same LCDmessage display as the fire panel. Any annunciator included in building specifications mustbe 100% compatible with the fire alarm panel. Some of the existing annunciator’s on baseindicate pointless system troubles that are a waste of time and resources, due to not beingcompatible.
3.RADIO TRANSMITTER / ANTENNA:
A.Fire alarm transmitters must be Monaco D2100 compatible. The current frequency is139.675 MHz narrowband. The Monaco BT -XM transmitter is required if fire panel beinginstalled is a panel other than a Monaco. Monaco M-series fire alarm panels have a radiotransmitter built-in helping to reducing cost. The contract should specify that the contractoris responsible for programming the transmitter as well as the fire alarm panel. The AlarmMaintenance shop can be contacted at 907-377-6666 to provide the transmitter numbers fromthe Monaco D2100 for the contractor.
B.The antenna must be mounted on the gable end of the building (closest to the FireDepartment) when there is a pitched roof to prevent damage from ice buildup. Thegrounding wire cannot be attached to any fixed ladders. The antenna shall be mounted aminimum of 2’ above the roof line and must be mounted securely (nut and bolt) to withstandthe wind load. Mounting the bracket using screws through thebuilding’s metal skin is notacceptable. The contractor is responsible for cutting the antenna to its proper length, in orderto match the frequency and transmit correctly, and is responsible for installing the antennacable connectors correctly. The antenna cable must have a lightning arrester installed inline,in a weatherproof box. The assembly must be properly grounded per manufacturerspecifications.
C.As part of the 100% functional acceptance test, witnessed by Alarm Maintenance, thetransmitter must pass manufacturer’s specifications for forward and reflective power, and allsignals transmitted to the Fire Department must be accurate.
4.INTIATION DEVICES:
A.HEAT DETECTORS:
1.We require the use of fixed type temperature heat detectors, unless otherwise requiredby code. Rate of rise type detectors cause repeated nuisance alarms for the firedepartment due to the arctic temperatures.
2.Make sure to install heat detectors per code. At normal ceiling height below 10’ aheat detectors shall not be placed any more than 50’ apart and 25’ from the wall unlessmanufacture calls for different spacing.
B.SMOKE DETECTORS:
1.Detectors located in Dormitory sleeping areas should have smoke detectors thatsound locally, and heat detectors that put the whole system in alarm. In Dormitoryactivation of a single dwelling unit smoke detector shall transmit a supervisory signal tothe Fire Department. In Dormitory Activation of any two dwelling unit smoke detectorsshall activate all fire alarm occupant notification appliances within the facility.
2.Fire/smoke doors in egress path shall be held open by magnetic devices controlled bythe fire alarm panel. Smoke detectors shall be provided at all doors held open bymagnetic hold open device, regardless of door type.
3.Location of smoke detectors shall comply with the NFPA 72. Per code Smokedetectors shall be place no farther apart than 30’ and they shall be placed within 15’ ofall walls. This can vary depending on ceiling style and angle.
C.DUCT DETECTORS:
1.All duct detectors that are installed must be easily accessible and clearly labeled.Climbing over ductwork or needing a ladder over 8’ for access is unacceptable.
2.Any duct detectors over 10’ from the floor will have a remote LED/test/reset deviceeasily accessible to a person standing on the floor that is labeled for the duct detector thatit is associated with.
3.All duct detectors shall be of the auto reset type. If this is not possible than a remoteLED/test/reset device needs to be easily accessible to reset the detector manually.
D.PULL STATION:
Provide pull stations where required by applicable codes and criteria. At a minimum, apull station shall be located with 5 feet of each exit. Fire alarm system pull stations shall benon-glass break type and shall require a key to reset. Do not use pull stations with a Tamperglass rod installed in them unless specifically requested for that job by Fire Department, orFire Alarm Shop.
E.LOW TEMPERATURE SENSORS:
Mechanical rooms that sprinkler risers are located in are required to have a low temperaturesensor in them to prevent freeze ups. Upon activation of the low temperature alarm, asupervisory signal shall be sent to the Fire Department.
F.ELEVATOR CONTROLS:
The fire alarm control panel shall provide smoke detection, flow switches, and supervisedaddressable relays for elevator functions as required by UFC 3-600-01. Control system forelevator must be wired up and programmed by contractor if required.
G.LABELING:
A device label shall be provided on the exterior of each device that matches the devicesnumber for Addressable fire panels or zone number for Conventional devices.
5.ALARM ANNUNCIATION:
A.All Annunciation devices shall be of the Horn Strobe type except on the exterior of thebuilding unless otherwise authorized by Fire Department or Fire Alarm Shop. The deviceson exterior of building can be bells installed in weatherproof enclosures.
B.A weatherproof bell or horn/strobe shall be installed on each side of the exterior of thebuilding.
C.Strobes shall be provided to alert persons with hearing disabilities and shall be installedper NFPA 72 and located as required to meet ADA-ABA and UFAS requirements. Wall-mounted appliances shall be mounted such that the entire lens is not less than 80 inchesabove the highest floor level or 6 inches below the ceiling, whichever is lower. Ceilingstrobes are permitted and shall be located and installed per NFPA 72 and may be part of acombined audible/visual device. Amber strobes shall be provided for the mass notificationsystem and clear strobes shall be provided for the fire alarm system. [Mass notification andfire alarm visual appliances shall be provided in dwelling units.]
D.Contractor shall provide sound pressure and light level calculations at the final designsubmittal or as a Government Approved submittal after design. As a minimum, provide thefollowing for each room and space: ambient sound pressure level (SPL) includingcontributions from equipment, maximum and minimum intelligibility, maximum andminimum strobe light level and maximum and minimum alarm SPL.
6.SPRINKLER/SUPPRESSION SYSTEMS:
A.New installs under the terms of UFC 3-600-01, shall be considered major projects, andrequires the services of a fire protection engineer. At the initial design conference, or atanother time convenient to all parties prior to final design submission, the fire protectionengineer shall meet with the Eielson Fire Alarm shop and Fire Department personnel toreview all the fire protection aspects of the design.
B.Inspector’s test valve is to be located at the farthest point of the suppression system.
C.All open bay area’s or area’s where freezing is probable required a dry pipe system forsuppression. A low air pressure switch is mandatory for a dry system, and must be addressor zoned independently.
D.If a wet pipe system is utilized, ensure a time-delay programming for the flow switchinstalled to counter any water pressure instability. Any area that is susceptible to arctictemperature requires self-regulating heat tape and insulation.
E.Communication centers must follow UFC 3-600-01 and or NFPA requirements and have a sprinkler suppression system. This system should not use any type of water suppression; they should use an Air Force Approved Alternate suppression system if possible. Contact Fire Department, or Fire Alarm shop for current expectable systems or for waiver of this requirement.
F.The recommended tamper switch is a plug and cord type. Potter PTS-B or similar deviceis preferred. This type of switch will help to prevent nuisance alarms. All tamper switchesneed to beaddressed individually (intelligent system). Each valve of the double backflowpreventers in a suppression system requires a tamper switch.
G.All Materials and Equipment shall have been tested by Underwriters Laboratories, Inc.and listed in UL Fire Prot Dir or approved by FM Global for the intended use.
H.Hydraulic calculations shall take into account the domestic water demand in addition tothe fire sprinkler and hose stream demand. All calculations shall include a 10 percent safetyfactor on the system pressure. Water velocity in the piping system shall not exceed 20 feetper second. Software that uses k-factors for typical branch lines is not acceptable.
I.All control valves shall be OS&Y gate type and shall be provided with tamper switchesconnected to the FACP.
J.Provide manual air vents and/or auxiliary drains to allow bleeding of air from all thesprinkler piping.
K.Sprinkler pipe shall not be located in the communications room or elevator machineroom. Sprinklers protecting the communications room or elevator machine rooms shallbe sidewall type and provided with a guard.
L.Sprinklers shall be provided to protect all floor areas under the first floor stair includinglandings and risers.
M.Hydrant flow shall be re-tested prior to design work on the sprinkler system to obtain theflow quantities. Fire Protection Engineer Designer of Record is required to witness flowtests.
N.Fittings for non-grooved steel pipe shall be malleable iron conforming to ASME B16.3.Fittings into which sprinklers, drop nipples or riser nipples (sprigs) are screwed shall bethreaded type. Plain-end fittings with mechanical couplings, fittings that use steel grippingdevices to bite into the pipe and segmented welded fittings shall not be used. Gasket forgrooved couplings shall be the flush type that fills the entire cavity between the fitting andthe pipe. Reductions in pipe sizes shall be made with one-piece tapered reducing fittings.
O.Water motor alarms shall not be used. All sprinkler system alarms shall be electricallypowered and controlled by the fire alarm panel.
P.Contractor shall provide a floor control valve assembly or separate riser for each floor inthe building. Assembly shall comply with Figure 4-1 of UFC 3-600-01.
Q.Plastic pipe is prohibited.
R.Flexible hose connections for sprinklers are prohibited.
S.Control valves shall be installed in a location accessible by maintenance personnel andinaccessible to building occupants.
T.A double-check backflow prevention assembly that complies with ASSE 1013 or ASSE1015 shall be provided at the sprinkler riser connection to the potable water system. Providepiping, valves, test header, and other devices necessary to provide a permanent method forforward flow testing of the backflow prevention assembly at system demand. Forward flowtest shall not require removal of check valve disk. If a reduced pressure backflow preventeris provided, the disinfection requirements located elsewhere are not required.Vent from thereduced pressure backflow preventer shall be provided with drain piping to an adequatelysized floor drain. Prior to final sprinkler testing, the backflow preventer shall be tested by acertified backflow assembly tester. Backflow preventer testing documentation will need tobe supplied to Utilities Shop Supervisor. (Sheldon Sites.)
U.Barracks only: Flushed concealed sprinkler heads shall be provided in thedwelling unitsand the corridors located outside the dwelling units.
V.If an elevator pit sprinkler is provided, a flow switch shall be provided in the samelocation as the pit sprinkler control valve.
W.All piping used on the fire suppression system shall be black steel.
7.MASS NOTIFICATION SYSTEM:
A.In-facility Mass Notification systems shall be installed in all DoD inhabited buildings,billeting, and high occupancy family housing, and to all DoD expeditionary structures inaccordance with the following:
1.New construction regardless of funding source.
2.Existing Buildings when triggered as specified below regardless of funding source.
a.Implementation of these standards to bring entire inhabited buildings into complianceis mandatory for all DoD buildings renovations, modification, repairs, revitalizations,and restorations where those costs exceed 50% of the buildings replacement value ofthe existing building in accordance with UFC 3-701-01 based on a building of the samesize except as otherwise stated in these standards.
3. For additional reference on facilities needing Mass Notification reference UFC 4-010-01, and 4-021-01.
B.The acceptable manufacturer for the Mass Notification is Cooper Wheelock, with the unitbeing a SP40 or equivalent model.
C.If a Mass Notification system is installed a Monaco BT-XM transceiver must also beinstalled and wired so that Remote live voice and remote buttons functions can be used fromthe Fire Dispatch center. If a Monaco BT-XM is already installed for the facility, then youmay just to add an additional zone and wire in the controls
D.Contractor is responsible for all programing of the BT-XM and Mass Notificationsystem, Fire Alarm Shop will assist with the programing of the D-21. For more informationreference area #3 of this paper or contact the Fire Alarm Shop at 907-377-6666.
E.A surge protector shall be installed in each Mass Notification system to prevent powersurges from burning sensitive electronic parts.
F.Contractor shall provide sound pressure and light level calculations at the final designsubmittal or as a Government Approved submittal after design. As a minimum, provide thefollowing for each room and space: ambient sound pressure level (SPL) includingcontributions from equipment, maximum and minimum intelligibility, maximum andminimum strobe light level and maximum and minimum alarm SPL.
G.The Mass Notification system and the fire alarm system shall be wired independent ofeach other especially speaker. The only exception is for the monitor wiring, and the relay tosilence the horns while making an announcement. When announcement is finished the firealarm horns should continue ringing automatically if fire system was going off.
H.Design criteria for locating audible appliances. The sound pressure level in a room orarea shall not vary by more than 6 dB across the room or area (starting at a point 10 feet fromthe speaker or horn).
I.Voice notification appliances shall have adjustable or multi-tap settings with availablesettings both above and below the design settings (except that 15 watt devices, wherepermitted, can be at the highest setting). Devices shall be spaced such that the device doesnot need to be tapped higher than 0.5 watt to meet audibility and intelligibility requirements.
J.Amplifier circuits shall be loaded to no more than 70 percent of rated continuous capacitywhen producing sound levels as required by NFPA 72 against normal ambient backgroundnoise levels for this occupancy for simultaneous operation of all speakers for all areas in thevoice zone. Annotate data for each circuit on the drawing.
K.Mass notification system panels and devices shall be terminated by either a NICET levelIII technician or an individual licensed by the State of Alaska for fire alarm systeminstallation (Class IC). Proof of qualifications shall be submitted if requested.
L.Mass notification system and speakers shall have power source and backup power sourceseparate from Fire Alarm system.
M.All Local Operator Consoles (LOC) are required to have an adjustable microphone gain.
N.Contractor shall provide instructions located inside the LOC cabinet and at the ACUdescribing the procedures for initiating either live voice messages or pre-recorded messages.These instructions shall be permanently attached to the cabinet.
O.LOC microphones shall be located and adjusted so that the microphones can be used toprovide a message meeting the intelligibility requirements of UFC 4-021-01. LOC’s may belocated in the stairs; however travel distance defined in UFC 4-021-01 must still be met. IfLOC’s are provided in the stairs, Contractor shall provide an amber strobe at each floorlanding in the stairs.
P.LOC enclosures shall be lockable by a key. All extra LOC enclosure and activation Keysshall be turned into the Fire Alarm Shop.
Q.The LOC shall be capable of a minimum of 8 pre-recorded messages. The followingpre-recorded messages shall be programmed into and clearly labeled on the LOC’s:
1.Attention all personnel:There has been a bomb threat. Evacuate immediatelyand proceed to your designated evacuation point. This is not a drill.
2.Attention all personnel: Lockdown, lockdown, lockdown. There is an activeshooter on the premises. This is not a drill.
3.Attention all personnel:Please evacuate the building immediately. Listen forannouncement of alternate exit path if required. This is not a drill.
4.Attention all personnel:There is a fire in the building. Stay low and evacuateimmediately. Proceed to your designated evacuation point. This is not a drill.
5.Attention all personnel:Please proceed to your designated shelter-in-place roomimmediately and wait for further instruction. This is not a drill.
6.Attention all personnel:This is a severe weather warning. Make sure to keep trackof weather conditions and be prepared to take shelter.
7.Attention all personnel:The building emergency or test has now ended. Pleaseresume your normal duties. Thank you for your cooperation.
8.Attention all personnel:This is a test of the Mass Notification system. This is onlya test.
8.TRAINING MANUALS AND INSPECTIONS:
A.FIRE ALARM TRAINING:
1.Fire Alarm Training. Training course shall be provided for Alarm Shop personnel.The course shall be conducted in the building where the system is installed or asdesignated by the Contracting Officer. The training shall consist of two [2]-hour trainingsessions held on consecutive days with one training session per day, unless otherwisesetup with the shop. The training shall start after the system is functionally completed butprior to final acceptance tests. The instruction shall cover items contained in theoperation and maintenance instructions. The contractor shall provide all required trainingmaterial, visual aids, software/hardware to supply the number of personnel to be trainedin each training session.
2.Sprinkler System Training. Training course shall be provided for Alarm Shoppersonnel. The course shall be conducted in the building where the system is installed.The training shall consist of a two hour training sessions. The training shall start after thesystem is functionally complete.
3.Mass Notification Training. Training course shall be provided for Alarm Shoppersonnel. The course shall be conducted in the building where the system is installed.The training shall consist of a two hour training sessions. The training shall start after thesystem is functionally complete.
4.All blueprints and as-builds related to the fire alarm and suppression systems need tobe forwarded to Alarm Shop 48 hours prior to the 100% acceptance test. As-builddrawing must show the location and address or zone of each device in the system.Intelligent devices must be labeled with their address.
5.Two suitably framed drawings are required in the suppression room: one drawingshowing all interconnections of suppression components, and one drawing listing thesequence of operation for testing, and resetting after a system trip.
6.Sprinkler System Testing. The system, including the underground water mains, andthe aboveground piping and system components, shall be tested in accordance withNFPA 13 and NFPA 24 to assure that equipment and components function as intended.Upon completion of specified tests, the Contractor shall complete and submit theContractor's Material and Test Certificates. The Contractorshall coordinate with theContracting Officer’s Representative to invite Fire Alarm Shop personnel and FireDepartment personnel to witness final testing. Final testing schedule shall be flexible toaccommodate Fire Alarm Shop schedule.
7.Fire Alarm & Mass Notification Testing. The fire alarm and mass notificationsystems shall be fully tested with a functional and operational performance testsincluding each installed initiating and notification device, meggering of conductors forgrounded, shorted or open circuits. An acceptance test shall be performed in accordancewith NFPA 72. Each device shall be tested. After testing is completed, the Contractor shall furnish to the Contracting Officers Representative completed originals of the NFPA72 Record of Completion and the NFPA 72 Testing and Inspection form. The Contractorshall coordinate with the Contracting Officer’s Representative to invite Fire Alarm Shoppersonnel and Fire Department personnel to witness final testing. Final testing scheduleshall be flexible to accommodate Fire Alarm Shop schedule.
8.Contractor Mass Notification Final Test. Audibility and intelligibility testing of themass notification system shall be accomplished in accordance with UFC 4-021-01. UFC4-021-01 requires an average of 3 readings of each room to determine the CIS score. The3 readings will be taken as follows: the most remote point from the speakers in the room;a middle point between speakers to be field determined based on wall or ceiling mountedspeakers; and a point close to the speaker. Readings will be recorded on an 11x17 plan ofthe building with CIS scores identified on the drawings.
9.Copies of all systems manuals need to be turned over to the Fire Alarm Shop whenbuilding is complete.
9.WARRANTY COVERAGE:
Include in the warranty statement that any code violations not discovered during acceptancetesting, but found during the warranty period, will be corrected by the contractor. The 1 yearwarranty should begin when the entire facility is signed off, not when the fire alarm portionof the project is complete. (Contact the Alarm Maintenance Shop for further clarification ifneeded).

10. ALARM SHOP SUPPORT:

In the event that a contractor requires 354 CES Alarms shop support for the performance of duties as outlined in a contract or is doing work on a fire system, the contractor must coordinate with the Alarm Shop Supervisor/NCOIC, 24 to 72 hours in advance for scheduling purposes.