JE Smith Lib Chiller Rep 2026-02 Project Dwgs.pdf
PDF 16 MB Posted
- Attached to
- J. E. Smith Library Chiller Replacement
- Solicitation number
- ECSU 2027-200
- Issued by
- Tolland County, Connecticut
About this file
Summary
This is a set of project drawings and bid documents for the J. E. Smith Library Chiller Replacement project at Eastern Connecticut State University in Willimantic, Connecticut. The project involves the removal and replacement of roofing, roof drainage systems, structural steel support framing, and rooftop-mounted air-cooled chillers serving the library's chiller mezzanine area. The scope includes demolition of two existing 200-ton air-cooled chillers and installation of new MULTISTACK Model ACF240MNHCE 225-ton air-cooled chillers, end-suction chilled water pumps, variable frequency controllers, hydronic specialties including an expansion tank and air separator, new roof curb and rail systems, and new roof drainage with associated piping, wiring, and controls. Bids are due August 4, 2026, with construction scheduled to begin on or before September 23, 2026, and substantial completion required by May 1, 2027—a 227-calendar-day duration. Liquidated damages are assessed at $300 per calendar day for schedule delays. Bidders must pre-qualify under Connecticut General Statutes Section 4a-100 in General Building Construction (Group C), Mechanical (HVAC) Contractor, and Structural (Iron, Structural & Misc Metal) Contractor classifications.
The estimated contract value does not exceed $3 million, structured as a lump-sum base bid. The project includes a 25% Connecticut Registered Small Business Set-Aside subcontractor participation requirement, of which 25% must be woman or minority-owned. Bidders must submit a 10% bid bond or certified check with bids firm for 60 days. Contractors must perform not less than 30% of the work with their own forces and comply with prevailing wage requirements under Connecticut General Statutes Section 31-53. Performance and labor/materials payment bonds, each equal to 100% of the total bid price, are required within ten days of award. All work must comply with the 2022 Connecticut State Building Code, AISC 360-16 structural standards, ASME pressure vessel codes, and FM Global roofing system requirements. Bids are submitted electronically through the Eastern Bid Portal, with written questions due prior to the portal-specified deadline and responses distributed via addendum.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
J. E. SMITH LIBRARY
CHILLER REPLACEMENT
PROJECT # ECSU 2026-02
Facilities Management & Planning
KARIM ISMAILI
PRESIDENT
DATE: 6-24-2026
EASTERN CONNECTICUT STATE UNIVERSITY
WILLIMANTIC, CONNECTICUT
PROJECT
LOCATION
LOCATION PLAN
LIST OF DRAWINGS
COVER
AD-1 ARCHITECTURAL DEMOLITION PLAN
CHILLER ROOF AREA
A-1 ARCHITECTURAL ROOF PLAN
CHILLER ROOF AREA
A-2 ARCHITECTURAL WORK PLAN
CHILLER ROOF AREA
A-3 ARCHITECTURAL DETAILS
S-0 STRUCTURAL NOTES AND PARTIAL MEZZ
FRAMING DEMO PLAN
S-1 DUNNAGE PARTIAL DEMOLITION AND
ROOF FRAMING PLANS
S-2 DUNNAGE AND PARTIAL ROOF
FRAMING PLANS.
MEPD-1 MECHANICAL ELECTRICAL AND PLUMBING
DEMOLITION PLAN.
MEP-1 MECHANICAL ELECTRICAL AND PLUMBING
NEW WORK PLAN
MEP-2 MECHANICAL ELECTRICAL AND PLUMBING
DETAILS
MEP-3 MECHANICAL ELECTRICAL AND PLUMBING
SCHEDULES
M
AN
SF
IE
LD
C
IT
Y
RO
AD
x x x x x x x x x x x xx xx x x x xx x x x xxx x xx xx x x x x x x x x x x x x x x x x xxxxx x x x x x x x x x x x x x x x xxx x xxxx x x x x x xx x x x x x x x x xx x xx xx x x x x x x x x xxxx x x x x x x xx x x x x x xx x x x x x xxx x x x x x x x x x x x x x x
BA
N
K
ST
RE
ET
W
AL
N
UT
S
TR
EE
T
MAIN STREET
CL
O
CK
ROAD
TOWER
MAIN STREET
BR
ID
G E
ST
RE
ET
RO
UT
E
W
IN
D
HA
M S
TR
EE
T
C
LO
C K
TO
W
ER
R
O
AD
YO
UN
G R
O
AD
EXT.
VILLAGE ROAD
BI
RC
H
ST
RE
ET
CHARTER OAK ROAD
PIGEON ROAD
RIDGEWOOD ROAD
SERWAN AVE.
WINDHAM HIGH SCHOOL
HI
G
H
ST
RE
ET
WASHBURN STREET
EASTERN ROAD
LEWISTON AVE.
SUMMIT STREET
PROSPECT STREET
W
IN
D
HA
M S
TR
EE
T
VALLEY STREET
HI
G
H
ST
RE
ET
SCHOOL HOUSE LANE
W
ES
T
RO
AD
VILLAGE ROAD
CHA
RTE
R O
AK
RO
AD
O
AK RO
AD
EASTERN
RO
AD
CHARTER
OAK
RO
AD
CH
AR
TE
R
ROUTE 6 EASTBOUND
ROUTE 6 WESTBOUND
LIB ANSI D COV.DWG
SITE PLAN
LOCATION OF SITE
x x xxxx
ECSU
ATHLETIC
COMPLEX
ECSU "NORTH" CAMPUS
ECSU "SOUTH" CAMPUS
CL
O
CK
ROAD
TOWER
C
LO
C K
TO
W
ER
R
O
AD
EXT.
VILLAGE ROAD
EASTERN ROAD
PROSPECT STREET
W
ES
T
RO
AD
VILLAGE ROAD
X:\projects\Library\LB-Chiller Replacement 2026\2 BLUE - DESIGN\B6-DWGS & SPECS\4 Bid Documents\CAD Files\Backgrounds\LIB ANSI D COV.dwg, 6/23/2026 11:37:46 AM, AutoCAD PDF (High Quality Print).pc3, 1:1
AutoCAD SHX Text
SW
AutoCAD SHX Text W
AutoCAD SHX Text
NW
AutoCAD SHX Text
SE
AutoCAD SHX Text E
AutoCAD SHX Text
NE
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text Dr.
AutoCAD SHX Text Bit.
AutoCAD SHX Text Paved
AutoCAD SHX Text Paved
AutoCAD SHX Text Bit.
AutoCAD SHX Text
EXISTING CURB
AutoCAD SHX Text
SW
AutoCAD SHX Text W
AutoCAD SHX Text
NW
AutoCAD SHX Text
SE
AutoCAD SHX Text E
AutoCAD SHX Text
NE
AutoCAD SHX Text S
AutoCAD SHX Text N
EXISTING SMOKE EXHAUST FAN.
REMOVE AND SAVE FOR
REINSTALLATION ON NEW CURB.
ETR & NEW CHILLERS NOT
SHOWN FOR DRAWING
CLARITY.
REFER TO "ME" DRAWINGS
FOR CHILLER LAYOUT.
REFER TO "S" DRAWINGS
FOR STRUCTURAL LAYOUT.
ETR & NEW CHILLERS NOT
SHOWN FOR DRAWING
CLARITY.
REFER TO "ME" DRAWINGS
FOR CHILLER LAYOUT.
REFER TO "S" DRAWINGS
FOR STRUCTURAL LAYOUT.
EXISTING CONDENSING UNIT WITH
ROOF RAILS REMOVE , SAVE AND
REINSTALL ON NEW RAILS (TYP).
EXISTING LOUVER TO REMAIN (TYP).
REMOVE MTL CAP (TYP ALONG
WALL).
REMOVE EXISTING PITCH POCKET
SERVING STRUCTURAL FRAMING
MEMBERS (TYP).
REMOVE ALL EXISTING CONCRETE
PAVERS FROM ROOF (TYP).
REMOVE ALL EXISTING ROOFING, CLOTH
MATT, INSULATION WITH FASTENERS DOWN
TO CONCRETE DECK. REPAIR/PATCH
DAMAGED CONCRETE (TYP).
REMOVE ROOF DRAIN.
COORDINATE WITH MEP.
REMOVE EXISTING PITCH POCKET
AND PATCH ROOF PENETRATION
FOR ALL UNUSED MEP ROOF
PENETRATIONS (TYP 8 PLACES).
REMOVE DAMAGED STUCCO
FINISH AND INSULATION AS
NEEDED TO PROVIDE A
SUITABLE REPAIR, TYPICAL
FULL HEIGHT OF WALL UNDER
ALL EXISTING BEAM
PENETRATIONS.
EXISTING CONTROLS CONDUIT ROOF
PENETRATION LOCATION TO REMAIN.
PROVIDE NEW PITCH POCKET PER
DETAIL (TYP OF 2 PLACES).
AD-1
REMOVE DAMAGED STUCCO
FINISHES TO PROVIDE A
SUITABLE REPAIR AT AREAS
ABOVE THIS WALL
LINETYPE LEGEND
EXISTING TO BE REMOVED (DEMOLITION)
EXISTING TO REMAIN
STRUCTURAL FRAME TO BE
REMOVED AND REPLACED. REFER
TO "S" DRAWINGS
REMOVE EXISTING PITCH POCKET
SERVING STRUCTURAL FRAMING
MEMBERS (TYP).
EXISTING CONCRETE ROOF
DECK TO REMAIN (TYP).
REMOVE EXISTING CONCRETE
PAVERS FROM ROOF (TYP).
REMOVE EXISTING PAVERS,
RUBBER ROOFING, ROOF
INSULATION, AND ASSOCIATED
COMPONENTS FROM CONCRETE
ROOF DECK (TYP).
CUT EIFS SYSTEM HORIZONTALLY
1" BELOW TOP OF EXISTING
LOUVER SILL FLASHING AND
REMOVE EIFS SYSTEM BELOW
THIS LEVEL FOR THE ENTIRE
PERIMETER OF THE ROOF
MEMBRANE. LOUVER SILL
FLASHING TO REMAIN. REMOVE
EXISTING EPMD ROOF FLASHING
AND ASSOCIATED COMPONENTS.
EXISTING CHILLERS TO BE
REMOVED & SHOWN FOR
REFERENCE ONLY.
REFER TO "ME" DRAWINGS
FOR CHILLER LAYOUT.
REFER TO "S" DRAWINGS
FOR STRUCTURAL LAYOUT.
REMOVE TOP FLASHING FULL
LENGTH OF THIS WALL, TYP. BOTH
SIDES.
REMOVE BEAM WRAP AT RIDGE
BEAM.
REMOVE BEAM WRAP AT RAFTERS
PATCH UNUSED ROOF
PENETRATIONS (TYP).
REMOVE EXISTING CONCRETE
PAVERS FROM ROOF INCLUDING
RUBBER ROOFING AND ROOF
INSULATION (TYP).
REMOVE EXISTING PITCH POCKET
SERVING STRUCTURAL FRAMING
MEMBERS (TYP).
STRUCTURAL FRAME TO BE
REMOVED AND REPLACED. REFER
TO "S" DRAWINGS
EXISTING CHILLER(S), PIPING AND
SUPPORTS TO BE REMOVED.
REFER TO "ME" DRAWINGS (TYP).
CRACKED STUCCO FINISH
REQUIRING REMOVAL AND
REPLACEMENT (TYP).
EXISTING ROOF BEAM TO
REMAIN (TYP).
REFER TO "S" DWGS.
REMOVE BEAM WRAP.
EXISTING ROOF RIDGE BEAM
TO REMAIN (TYP).
REFER TO "S" DWGS.
EXISTING ROOF BEAM TO
BE REMOVED (TYP).
REFER TO "S" DWGS.
EXISTING CHILLER TO BE
REMOVED (TYP).
REFER TO "ME" DWGS.
CRACKED STUCCO FINISH
REQUIRING REMOVAL AND
REPLACEMENT (TYP).
REMOVE EXISTING CONCRETE
PAVERS FROM ROOF INCLUDING
RUBBER ROOFING AND ROOF
INSULATION (TYP).
EXISTING EX LOUVER TO
REMAIN (TYP).
REFER TO "ME" DWGS.
REMOVE EXISTING PITCH POCKET
SERVING STRUCTURAL FRAMING
MEMBERS (TYP).
STRUCTURAL FRAME TO BE
REMOVED AND REPLACED. REFER
TO "S" DRAWINGS
EXISTING STRUCTURAL POST TO
REMAIN.
REFER TO "S" DRAWINGS
REMOVE EXISTING CONCRETE
PAVERS FROM ROOF INCLUDING
RUBBER ROOFING AND ROOF
INSULATION (TYP).
EXISTING EX LOUVER TO
REMAIN (TYP).
REFER TO "ME" DWGS.
EXISTING EXHAUST FAN TO
REMAIN (TYP).
REFER TO "ME" DWGS.
REMOVE & REPLACE WITH NEW
COUNTER FLASHING MTL CAP
(TYP ALONG WALL).
AS NOTED
ARCHITECTURAL
DEMOLITION PLAN
A-1_REV 6-23-2026.DWG
1/4"=1'-0"
GRAPHIC SCALE
SCALE IN FEET
0 4 8
ARCHITECTURAL DEMOLITION NOTES
NOTES:
1. FOR DRAWING CLARITY NOT ALL EXISTING SYSTEMS ARE SHOWN OR NOTED ON THE DRAWINGS. CONTRACTOR SHALL VISIT THE SITE TO UNDERSTAND THE EXTENT OF EXISTING CONDITIONS, CONFIRM THE SCOPE OF WORK AND EXISTING CONDITIONS PRIOR TO SUBMITTING BID. DRAWINGS AND INFORMATION SHOWN ARE APPROXIMATE. THE CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD
VERIFICATION OF EXISTING CONDITIONS PRIOR TO THE START OF WORK.
2. THE CONTRACTOR SHALL VERIFY THE EXTENT OF DEMOLITION AND CONFIRM CONNECTION POINTS OF EXISTING COMPONENTS TO REMAIN IN THE FIELD. BEGINNING OF DEMOLITION WORK MEANS CONTRACTOR ACCEPTS EXISTING CONDITIONS AND FULLY UNDERSTANDS SCOPE FOR CONNECTION TO EXISTING. PREMATURE OR EXCESSIVE DEMOLITION OR FAILURE TO RETAIN COMPONENTS OF THE SYSTEM SHALL RESULT IN THE CONTRACTOR PROVIDING REPLACEMENT AT NO ADDITIONAL COST TO THE OWNER.
3. THE CONTRACTOR SHALL NOTIFY ECSU FACILITIES MANAGEMENT & PLANNING A MINIMUM OF 2 WEEKS PRIOR TO ANY UTILITY SHUTDOWN AND A MINIMUM OF 48 HRS PRIOR TO START OF ANY WORK.
4. ALL EQUIPMENT, DEVICES, PIPING, WIRING AND CONTROLS SHALL BE ISOLATED AND BROUGHT TO A ZERO ENERGY STATE IN ACCORDANCE WITH OSHA REGULATIONS PRIOR TO THE START OF ANY WORK.
ISOLATION AND DISCONNECTION OF ALL ELECTRICAL POWER & CONTROLS SHALL BE DONE BY A LICENSED ELECTRICIAN. ISOLATION, DRAINING OF PIPING AND REFRIGERATION SYSTEM SHALL BE BE DONE BY A LICENSED MECHANIC. FOLLOW ENVIRONMENTAL REGULATIONS INCLUDING RECLAMATION OF REFRIGERANT.
5. CONTRACTOR SHALL CLEAN/REPAIR AND MAKE READY ANY EXISTING MATERIALS AND/OR EQUIPMENT THAT IS TO REMAIN IN SERVICE AND REUSED AS A FUNCTIONING PART OF THIS PROJECT.
6. COORDINATE ARCHITECTURAL DEMOLITION WITH THE WORK OF OTHER DIVISIONS TO AVOID ANY CONFLICTS WHICH MAY AFFECT SAFETY, COST TO THE OWNER, OR SCHEDULE.
7. COORDINATE WORK WITH STRUCTURAL AND MEP SCOPE SHOWN/SPECIFIED WITHIN OTHER DIVISIONS (TYP).
CHILLER ROOF AREA
06/24/2026
ECSU-2026-02
Fa ci lit ie s M an ag em en t a nd P la nn in g
W in dh am S tre et
, W ill im an tic C
T
E A
ST
E
R N
C O
N N
E C
T
IC
U T
S T
A T
E U
N
IV
E R
SI
T
Y
J.E SMITH LIBRARY
CHILLER
REPLACEMENT
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
UP - 34 R @ 6.89"
AutoCAD SHX Text
CHILLER ROOF AREA
AutoCAD SHX Text
CHILLER ROOF AREA
AutoCAD SHX Text
CU-1
AutoCAD SHX Text
SEF-2
AutoCAD SHX Text
CU-1
AutoCAD SHX Text
SEF-2
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EXIST
AutoCAD SHX Text W 8 x 24
AutoCAD SHX Text W 8 x 24
AutoCAD SHX Text
CHILLER ROOF AREA
AutoCAD SHX Text
CHILLER
AutoCAD SHX Text
EXIST
AutoCAD SHX Text
CHILLER
AutoCAD SHX Text
AD-1
AutoCAD SHX Text
AutoCAD SHX Text
AD-1
AutoCAD SHX Text
AutoCAD SHX Text
SCALE: 1/4" = 1'-0"
AutoCAD SHX Text
%%UARCHITECTURAL DEMOLITION PLAN
AutoCAD SHX Text
AD-1
AutoCAD SHX Text
AutoCAD SHX Text
SCALE: NTS
AutoCAD SHX Text
%%UPHOTOS OF EXISTING CONDITIONS FOR REFERENCE
AutoCAD SHX Text Drawing Name:
AutoCAD SHX Text CAD File Name:
AutoCAD SHX Text Drawing No.:
AutoCAD SHX Text Date
AutoCAD SHX Text Revision/Issue
AutoCAD SHX Text No.
AutoCAD SHX Text Project Name:
AutoCAD SHX Text Sheet No.:
AutoCAD SHX Text Project No.:
AutoCAD SHX Text Date:
AutoCAD SHX Text Scale:
AutoCAD SHX Text
SW
AutoCAD SHX Text W
AutoCAD SHX Text
NW
AutoCAD SHX Text
SE
AutoCAD SHX Text E
AutoCAD SHX Text
NE
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text
AD-1
AutoCAD SHX Text
AutoCAD SHX Text
SCALE: 1/4" = 1'-0"
%%UARCHITECTURAL DEMOLITION SECTION - CHILLER ROOF AREA
RD
PI
TC
H
TO
D
RA
IN
1/ 8"
FT
M
IN
PITCH TO DRAIN
1/8" / FT MIN.
PITCH TO DRAIN
1/8" / FT MIN.
ROOF A
ROOF A ROOF A
ROOF A
NEW CHILLERS NOT SHOWN
FOR DRAWING CLARITY.
REFER TO "ME" DRAWINGS
FOR CHILLER LAYOUT.
REFER TO "S" DRAWINGS
FOR STRUCTURAL LAYOUT.
PROVIDE/INSTALL NEW ROOFING
SYSTEM WITH VB, RIGID BOARD
INSULATION AND COVER BOARD
MECHANICALLY FASTENED, FULLY
ADHERED 90 MIL EPDM MEMBRANE
ROOF WITH ENHANCED FLASHINGS FOR
30 YEAR WARRANTY.
INSTALL AND TEST PER FM GLOBAL
STANDARDS.
CU-1 SEF-2
PROVIDE NEW ROOF
WALKWAY PADS.
COORDINATE INSTALL IN
THE FIELD WITH EXISTING
CONDITIONS AND NEW
EQUIPMENT LAYOUT (TYP).
REMOVE & REPLACE SEF-2 AS NEEDED
TO INSTALL NEW ROOFING.
PROVIDE/EXTEND ROOF CURB TO
MAINTAIN X" FLASHING & DRIP EDGE.
REFER TO DETAIL (TYP).
REMOVE & REPLACE CU-1 AS
NEEDED TO INSTALL NEW
ROOFING.
PROVIDE/EXTEND ROOF
CURB TO MAINTAIN X"
FLASHING & DRIP EDGE.
REFER TO DETAIL (TYP).
PROVIDE NEW PITCH POCKET
WITH SEALANT FOR EACH
EXISTING STRUCTURAL FRAME
POST.
REFER TO "S" DRAWINGS FOR
ADDITIONAL INFORMATION.
REFER TO DETAIL 4 / A-3 (TYP).
NEW CHILLERS NOT SHOWN
FOR DRAWING CLARITY.
REFER TO "ME" DRAWINGS
FOR CHILLER LAYOUT.
REFER TO "S" DRAWINGS
FOR STRUCTURAL LAYOUT.
SRD SRD
PP PP PP PP
PP PP PP PP
PP PP PP PP
PP
PROVIDE NEW PITCH POCKET WITH
SEALANT FOR EACH EXISTING
ELECTRICAL CONDUIT.
REFER TO "ME" DRAWINGS FOR
ADDITIONAL INFORMATION.
REFER TO DETAIL (TYP).
PP
PATCH MTL DECK WHERE EXISTING
PIPE PENETRATIONS ARE REMOVED.
REFER TO "ME" DRAWINGS FOR
ADDITIONAL INFORMATION.
NEW ROOF DRAIN. FURNISHED AND
PIPED BY PLUMBING CONTRACTOR
(DIV 22). SET IN PLACE AND FLASHED
BY ROOFING CONTRACTOR.
REFER TO "ME" DRAWINGS FOR
ADDITIONAL INFORMATION.
REFER TO DETAIL 5 / A-3 (TYP).
PI
TC
H
TO
D
RA
IN
1/ 8"
FT
M
IN
A-3
A-3
A-3 TYP.
ALL PP
A-2
A-3
A-3
A-2
LINETYPE LEGEND
NEW WORK
EXISTING TO REMAIN
0.324" CONCRETE SLAB
POLYISO. INSULATION
THICKNESS 5-INCH
FIRST LAYER 1.5 " (R8.6)
SECOND LAYER 2" (R11.4)
STAGGERED, THIRD LAYER
TAPERED AVERAGE 1.5" (R8.6)
0.17
EPDM MEMBRANE
OUTSIDE AIR FILM
2.50
0.24
28.6
INSIDE AIR FILM
TOTAL "R" VALUE =
"U" = 1/"R" = 0.0301
0.60
32.43
1/2" PROTECTION BD
TYPICAL NEW ROOF:
FULLY ADHERED 90 MIL EPDM MEMBRANE
BONDING ADHESIVE
2 INCH POLYOSPCYANURATE COVER BOARD
5 INCHES POLYISOCYANURATE INSULATION
(3 LAYERS STAGGERED JOINTS, 1.5 INCH, 2 INCH, AND
TAPERED LAYER MECHANICALLY FASTENED TO
EXISTING CONCRETE DECK)
EXISTING 4" CONCRETE SLAB OVER METAL DECKING
EXISTING STEEL
NOTES:
1. UPLIFT DESIGN SHALL BE IN ACCORDANCE WITH THE AMERICAN SOCIETY OF CIVIL ENGINEERS - ASCE / SEI 7-10 -
MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES.
2. UPLIFT RESISTANCE SHOWN BASED ON FM GLOBAL 1-29 - ROOF DECK SECUREMENT AND ABOVE-DECK ROOF
COMPONENTS REQUIREMENTS AND RECOMMENDATIONS.
3. SYSTEM COMPONENTS AND DESIGN MUST BE VERIFIED TO BE IN ACCORDANCE WITH THIS LAYOUT.
4. ASCE / SEI 7-10 DEFINES THE PERIMETER (X) (SEE SCHEMATIC ROOF PLANS BELOW) AS THE LESSER OF 10-PERCENT OF THE LEAST HORIZONTAL DIMENSION OR .4 X THE HEIGHT, BUT NOT LESS THAN 4-PERCENT OF THE LEAST HORIZONTAL DIMENSION OR 3-FEET FOR BUILDINGS UNDER 60 FEET IN HEIGHT. OVER 60-FEET IN HEIGHT - ASCE / SEI 7-10 DEFINES THE PERIMETER (X) AS THE LESSER OF 10-PERCENT OF THE LEAST HORIZONTAL DIMENSION ONLY.
5. THE CORNERS MAY BE TREATED AS PERIMETERS IF THE PARAPET IS GREATER THAN OR EQUAL TO 3-FEET
ACCORDING TO ASCE/SEI 7-10.
6. IF ANY PORTIONS OF ANY INSULATION BOARDS CROSS INTO THE PERIMETER ROOF AREA AND / OR THE CORNER ROOF AREAS, THEN THE ENTIRE INSULATION BOARD SHOULD BE SECURED ACCORDING TO THE REQUIRED PERIMETER
OR CORNER RATE, AS NEEDED.
1.5-INCH MINIMUM TOP LAYER PER FM GLOBAL
PROVIDE SHOP DRAWINGS BY MANUFACTURER SHOWING
TAPERED INSULATION LAYOUT, INSTALLATION METHOD,
ATTACHMENT, AND SLOPE FOR ARCHITECT'S APPROVAL
PRIOR TO ORDERING OF MATERIALS AND INSTALLATION.
1/8-INCH PER FOOT MINIMUM FINISHED ROOF SLOPE, TYP.
5 INCH TOTAL AVERAGE MINIMUM INSULATION THICKNESS
FIELD (ZONE 1)
8'-0"
1' -0
4' -0
2'-0"
2' -0
1'
-0
2'-0"2'-0" 1'-0"1'-0"
ROOF WIND DESIGN DATA
BASIC WIND SPEED: V: 135 MPH
EXPOSURE CATEGORY: B
RISK CATEGORY: III
BUILDING HEIGHT: 69 FT
WIDTH OF PERIMETER: 4 FT
CALCULATED WIND PRESSURES:
ZONE 1 = 51 PSF
ZONE 2 = 68 PSF
ZONE 3 = 93 PSF
DESIGN WIND UP-LIFT RATINGS:
ZONE 1 = 60 PSF
ZONE 2 = 90 PSF
ZONE 3 = 135 PSF
FASTENING ZONE PLAN
(NOT TO SCALE)
0.00METAL DECK
PERIMETER (ZONE 2)
8'-0" 6"
4' -0
"1' -6
6"
1' -6
6"
1'-0" 1'-6" 1'-6"1'-0" 6"6"
2'-0"
1'-0" 6"
2' -0
8'-0"
6"
4' -0
"1' -0
1'-0"
1' -0
6"
1'-0" 4'-0"6"6"
1' -0
1'-0"
CORNER (ZONE3)
INSULATED
COVER
BOARD
VAPOR
BARRIER
2"
FLAT
STOCK
RIGID
INSUL.
LIGHT WEIGHT
FILL AND
CONCRETE
DECK
EPDM MEMBRANE ADHESIVE
IN
SU
LA
TI
O N
A D
H
ES
IV
E
IN
SU
LA
TI
O N
A D
H
ES
IV
E
IN
SU
LA
TI
O N
A D
H
ES
IV
E
TAPERED
RIGID
INSUL.
(12" MIN.)
1 12"
FLAT
STOCK
RIGID
INSUL. PRIMER
ARCHITECTURAL NOTES
NOTES:
1. FOR DRAWING CLARITY NOT ALL EXISTING SYSTEMS ARE SHOWN OR NOTED ON THE DRAWINGS. CONTRACTOR SHALL VISIT THE SITE TO UNDERSTAND THE EXTENT OF EXISTING CONDITIONS, CONFIRM THE SCOPE OF WORK AND EXISTING CONDITIONS PRIOR TO SUBMITTING BID. DRAWINGS AND INFORMATION SHOWN ARE APPROXIMATE. THE CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD
VERIFICATION OF EXISTING CONDITIONS PRIOR TO THE START OF WORK.
2. THE CONTRACTOR SHALL VERIFY THE EXTENT OF DEMOLITION AND CONFIRM CONNECTION POINTS OF EXISTING COMPONENTS TO REMAIN IN THE FIELD. BEGINNING OF DEMOLITION WORK MEANS CONTRACTOR ACCEPTS EXISTING CONDITIONS AND FULLY UNDERSTANDS SCOPE FOR CONNECTION TO EXISTING. PREMATURE OR EXCESSIVE DEMOLITION OR FAILURE TO RETAIN COMPONENTS OF THE SYSTEM SHALL RESULT IN THE CONTRACTOR PROVIDING REPLACEMENT AT NO ADDITIONAL COST TO THE OWNER.
3. THE CONTRACTOR SHALL NOTIFY ECSU FACILITIES MANAGEMENT & PLANNING A MINIMUM OF 2 WEEKS PRIOR TO ANY UTILITY SHUTDOWN AND A MINIMUM OF 48 HRS PRIOR TO START OF ANY WORK.
4. ALL EQUIPMENT, DEVICES, PIPING, WIRING AND CONTROLS SHALL BE ISOLATED AND BROUGHT TO A ZERO ENERGY STATE IN ACCORDANCE WITH OSHA REGULATIONS PRIOR TO THE START OF ANY WORK.
ISOLATION AND DISCONNECTION OF ALL ELECTRICAL POWER & CONTROLS SHALL BE DONE BY A LICENSED ELECTRICIAN. ISOLATION, DRAINING OF PIPING AND REFRIGERATION SYSTEM SHALL BE BE DONE BY A LICENSED MECHANIC. FOLLOW ENVIRONMENTAL REGULATIONS INCLUDING RECLAMATION OF REFRIGERANT.
5. CONTRACTOR SHALL CLEAN/REPAIR AND MAKE READY ANY EXISTING MATERIALS AND/OR EQUIPMENT THAT IS TO REMAIN IN SERVICE AND REUSED AS A FUNCTIONING PART OF THIS PROJECT.
6. COORDINATE ARCHITECTURAL DEMOLITION WITH THE WORK OF OTHER DIVISIONS TO AVOID ANY CONFLICTS WHICH MAY AFFECT SAFETY, COST TO THE OWNER, OR SCHEDULE.
7. COORDINATE WORK WITH STRUCTURAL AND MEP SCOPE SHOWN/SPECIFIED WITHIN OTHER DIVISIONS (TYP).
8. CONTRACTOR SHALL INSPECT CONCRETE DECKING AND PATCH AND REPAIR DAMAGED SECTIONS.
9. EXISTING MECHANICAL UNITS (CU-1 & SEF-2) SHALL BE LIFTED TO INCREASE CURB HEIGHT. RESET UNITS PROVIDE NEW FLASHING, CURB EXTENSIONS, ELECTRICAL POWER WIRING & RACEWAY, REFRIGERATION PIPING NECESSARY TO ACCOMMODATE NEW CURB HEIGHT.
10. REMOVE AND REPLACE ROOF DRAIN WITH NEW ASSEMBLY. PROVIDE NEW FLASHING.
11. PROVIDE NEW ROOFING SYSTEM AND INSTALL IN ACCORDANCE WITH FM GLOBAL REQUIREMENTS INCLUDING TESTING.
12. ALL WORK SHALL BE IN ACCORDANCE WITH CT STATE CODES AND REGULATIONS.
13. DRAWINGS ARE NOT TO BE SCALED. USE DIMENSIONS OBTAINED IN THE FIELD.
14. CONTRACTOR SHALL PROVIDE SHOP DRAWINGS FOR ALL WORK AND SHALL INCLUDE EXISTING CONDITIONS AND COORDINATION WITH THE WORK OF OTHER DIVISIONS (TYP).
AS NOTED
ARCHITECTURAL
ROOF PLAN
A-1_REV 6-23-2026.DWG
1/4"=1'-0"
GRAPHIC SCALE
SCALE IN FEET
0 4 8
CHILLER ROOF AREA
06/24/2026
ECSU-2026-02
Fa ci lit ie s M an ag em en t a nd P la nn in g
W in dh am S tre et
, W ill im an tic C
T
E A
ST
E
R N
C O
N N
E C
T
IC
U T
S T
A T
E U
N
IV
E R
SI
T
Y
J.E SMITH LIBRARY
CHILLER
REPLACEMENT
NOTE: NONE OF THE ITEMS SHOWN ON THE LEGEND, NOR ANY OF THE CORRESPONDING IMAGES ON THE DRAWINGS
ARE SHOWN TO SCALE. ALL SIZES MUST BE VERIFIED IN THE FIELD.
ROOF PITCH
STACK VENT
ROOF HATCH
EXISTING HVAC - MECHANICAL
EXHAUST FAN WITH FULL
PERIMETER CURB
HOT PIPE
ROOF DRAIN
EXISTING HVAC - MECHANICAL
UNIT WITH RAILS
NEW 2'X2' EPDM WALKWAY PAD - ADHERED
PITCH POCKET
SCUPPER ROOF DRAIN
LEGEND
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
UP - 34 R @ 6.89"
AutoCAD SHX Text
CHILLER ROOF AREA
AutoCAD SHX Text
CHILLER ROOF AREA
AutoCAD SHX Text
CU-1
AutoCAD SHX Text
SEF-2
AutoCAD SHX Text BLDG. HT. GREATER THAN 60-FEET (This roof 52')
AutoCAD SHX Text
ZONE 2
AutoCAD SHX Text
ZONE 1
AutoCAD SHX Text
WALLS EXTEND ~11' ABOVE NEW ROOF
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A-1
AutoCAD SHX Text
AutoCAD SHX Text A-1
AutoCAD SHX Text
AutoCAD SHX Text
SCALE: 1/4" = 1'-0"
AutoCAD SHX Text
%%UROOF PLAN
AutoCAD SHX Text Drawing Name:
AutoCAD SHX Text CAD File Name:
AutoCAD SHX Text Drawing No.:
AutoCAD SHX Text Date
AutoCAD SHX Text Revision/Issue
AutoCAD SHX Text No.
AutoCAD SHX Text Project Name:
AutoCAD SHX Text Sheet No.:
AutoCAD SHX Text Project No.:
AutoCAD SHX Text Date:
AutoCAD SHX Text Scale:
AutoCAD SHX Text
SW
AutoCAD SHX Text W
AutoCAD SHX Text
NW
AutoCAD SHX Text
SE
AutoCAD SHX Text E
AutoCAD SHX Text
NE
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text V
AutoCAD SHX Text
HP
AutoCAD SHX Text
CU
AutoCAD SHX Text
RD
AutoCAD SHX Text
PP
AutoCAD SHX Text
SEF
AutoCAD SHX Text
SRD
AutoCAD SHX Text A-1
AutoCAD SHX Text
AutoCAD SHX Text
SCALE: NTS
%%UNEW ROOF ASSEMBLY
CU-1 SEF-2
FDSW
CH
-1
EXISTING SMOKE EXHAUST FAN
AND CURB TO REMAIN (TYP).
EXISTING CONDENSING UNIT WITH
ROOF RAILS TO REMAIN (TYP).
NEW AIR COOLED CHILLER SUPPORTED
BY NEW STEEL SUPPORT FRAME (TYP).
PROVIDE NEW PITCH POCKET(S) WITH
SEALANT PER DETAIL (TYP).
COORDINATE DIMENSIONS IN THE
FIELD WITH EXISTING CONDITIONS AND
NEW SUPPORT STEEL WORK (TYP).
FDSW
CH
-2
FDSWFDSW
OAOA
OA
OAOA
EX EX
EX EX EX
ETR OA PLENUM ETR OA PLENUM
ET
R
E X
PL
EN
U M
ET
R
E X
PL
EN
U M
ETR EX PLENUM
EXISTING FUSED DISCONNECT
SWITCH TO REMAIN (TYP).
EXISTING 120V CONVENIENCE
OUTLET TO REMAIN (TYP).
REMOVE & REPLACE COVER TO
ACCOMMODATE NEW WORK (TYP).
EXISTING 120V EXTERIOR LIGHT
REMAIN (TYP).
REMOVE & REPLACE AS NEEDED TO
ACCOMMODATE NEW WORK (TYP).
EXISTING OA LOUVER
TO REMAIN (TYP).
EXISTING OA LOUVER TO
REMAIN (TYP).
REMOVE & REPLACE ALUMINUM
FLASHING AT TOP OF WALL.
COLOR: MATCH EXISTING.
PROVIDE SEALANT WEATHER&
LIQUID TIGHT (TYP).
INFILL EXISTING BEAM POCKET
WITH MORTAR AND FINISH FLUSH
TO ADJACENT SURFACES
(TYP EACH BEAM REMOVED).
EXISTING BEAM TO BE REMOVED
EX
IS
TI
N
G R
ID
G
E
BE
AM
T
O R
EM
AI
N
EXISTING BEAM TO BE REMOVED
EXISTING BEAM TO BE REMOVED
EXISTING BEAM TO BE REMOVED
EXISTING BEAM TO BE REMOVED
EXISTING BEAM TO BE REMOVED
EXISTING BEAM TO BE REMOVED
EXISTING BEAM TO BE REMOVED
EXISTING BEAM TO REMAIN
EXISTING BEAM TO REMAIN
EXISTING BEAM TO REMAIN
NEW CHILLERS SHOWN FOR
REFERENCE ONLY.
REFER TO "ME" DRAWINGS
FOR CHILLER LAYOUT.
REFER TO "S" DRAWINGS
FOR STRUCTURAL LAYOUT.
NEW CHILLERS SHOWN FOR
REFERENCE ONLY.
REFER TO "ME" DRAWINGS
FOR CHILLER LAYOUT.
REFER TO "S" DRAWINGS
FOR STRUCTURAL LAYOUT.
REMOVE & PROVIDE NEW
ALUMINUM WRAP COVERING
RIDGE BEAM & NEW STIFFING
CHANNELS (TYP).
COLOR: MATCH EXISTING.
FINISH CUT BEAM FLUSH TO
ADJACENT SURFACES, PATCH AS
NEEDED. FILL INSULATION VOID WITH
INSULATION TO MATCH EXISTING.
(TYP EACH BEAM REMOVED).
REMOVE & REPLACE ALUMINUM
FLASHING AT TOP OF WALL.
COLOR: MATCH EXISTING.
PROVIDE SEALANT WEATHER &
LIQUID TIGHT (TYP).
PROVIDE TEMPORARY PANEL AT OA
INTAKE OPEN TO CHILLER MEZZ
AREA. SEAL LIQUID & GAS TIGHT.
MAINTAIN FOR DURATION OF
CONSTRUCTION ACTIVITIES (TYP).
REMOVE AT COMPLETION OF
CONSTRUCTION ACTIVITIES AND
CLEAN EXISTING SURFACES (TYP 2
PLACES).
EXISTING OA LOUVER TO
REMAIN (TYP).
A-2
INSULATED STUCCO FINISH SYSTEM REPAIR NOTES:
1. REPAIR ALL EXISTING STUCCO FINISHES ADJACENT TO MECHANICAL ROOF AREA.
2. MECHANICALLY REMOVE ANY DAMAGED INSULATION AS NOTED ON AD-1.
3. MECHANICALLY REMOVE ANY CRACKED AND DELAMINATED STUCCO FINISHES AS NOTED ON AD-1.
4. USE A GRINDER TO REMOVE THE FINISH SURROUNDING SECTIONS OF REMOVED INSULATION AND
REINFORCING MESH AT LEAST 3" IN ALL DIRECTIONS. DO NOT GRIND INTO REINFORCING MESH.
5. REMOVE ALL DEBRIS AND CLEAN ALL EXISTING STUCCO SURFACES WITH Prosoco® Enviro Klean®
EIFS Clean 'N Prep, Shore Corporation SB2600 EIFScrub, or ABR® Products, Inc. Building Wash 3.
6. WHERE INSULATION IS REMOVED, CUT AND INSTALL NEW EPS INSULATION TO MATCH EXISTING
AND CREATE A TIGHT FITTING REPAIR. APPLY NEW BASE COAT TO INSULATION AND PRESS INTO
PLACE. FILL ANY GAPS GREATER THAN 1
16" WITH INSULATION. ENSURE NEW INSULATION IS FLUSH
WITH EXISTING INSULATION. MECHANICALLY FASTEN INSULATION FOR REPAIR AREAS LARGER
THAN 1' IN ANY DIRECTION AT 1' O.C IN BOTH DIRECTIONS.
7. MASK AREA AROUND REPAIR.
8. CUT NEW REINFORCING MESH TO OVERLAP AT LEAST 1" OVER EXISTING BASE COAT AND MESH.
EMBED MESH INTO BASE COAT, ENSURING THAT FRESH BASECOAT AND MESH IS FLUSH IWTH
EXISTING LAMINA.
9. APPLY COLOR AND TEXTURE MATCHED FINISH COAT. FLOAT FINISH TO MATCH EXISTING FINISH.
REMOVE MASK BEFORE FINISH DRIES AND USE BRUSH TO BLEND THE WET EDGE INTO THE
EXISTING FINISH AND ALLOW TO DRY. CORE BORE THRU EXISTING BLOCK WALL FOR NEW MEP SYSTEMS
INCLUDING 6" CWS&R PIPE PENETRATION(S) SERVING EACH NEW
CHILLER (TYP).
PROVIDE SEALANT AROUND SLEEVE ACCORDING TO STUCCO
MANUF REQUIREMENTS (TYP OF 4 PLACES). MATCH WALL COLOR.
REFER TO ME DWGS FOR CHILLER
AND "S" DWGS FOR STRUCTURAL
SUPPORT FRAMING.
REFER TO ME DWGS FOR CHILLER
AND "S" DWGS FOR STRUCTURAL
SUPPORT FRAMING.
INSTALL NEW ALUMINUM TOP
FLASHING FULL LENGTH OF THIS
WALL, TYP. BOTH SIDES. CUSTOM
PROFILE TBD TO PROVIDE
APPROPRIATE WATER PROTECTION
FOR EXISTING CONDITION.
A-3
PROVIDE NEW ALUMINUM BEAM WRAP
TO MATCH EXISTING AT RIDGE BEAM.
COORDINATE EXISTING RAFTER
PENETRATIONS WITH NEW TOP OF
WALL FLASHING.
LINETYPE LEGEND
NEW WORK
EXISTING TO REMAIN
AS NOTED
ARCHITECTURAL
WORK PLAN
A-1_REV 6-23-2026.DWG
1/4"=1'-0"
GRAPHIC SCALE
SCALE IN FEET
0 4 8
CHILLER ROOF AREA
06/24/2026
ECSU-2026-02
Fa ci lit ie s M an ag em en t a nd P la nn in g
W in dh am S tre et
, W ill im an tic C
T
E A
ST
E
R N
C O
N N
E C
T
IC
U T
S T
A T
E U
N
IV
E R
SI
T
Y
J.E SMITH LIBRARY
CHILLER
REPLACEMENT
REFER TO MANUFACTURERS INSTALLATION REQUIREMENTS FOR ALL PRODUCTS.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
UP - 34 R @ 6.89"
AutoCAD SHX Text
CHILLER ROOF AREA
AutoCAD SHX Text
CHILLER ROOF AREA
AutoCAD SHX Text
CU-1
AutoCAD SHX Text
SEF-2
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EXIST
AutoCAD SHX Text W 8 x 24
AutoCAD SHX Text W 8 x 24
AutoCAD SHX Text
CHILLER ROOF AREA
AutoCAD SHX Text
CHILLER
AutoCAD SHX Text
EXIST
AutoCAD SHX Text
CHILLER
AutoCAD SHX Text W 8 x 24
AutoCAD SHX Text W 8 x 24
AutoCAD SHX Text A-2
AutoCAD SHX Text
AutoCAD SHX Text A-2
AutoCAD SHX Text
AutoCAD SHX Text
SCALE: 1/4" = 1'-0"
AutoCAD SHX Text
%%UARCHITECTURAL SECTION - CHILLER ROOF AREA
AutoCAD SHX Text Drawing Name:
AutoCAD SHX Text CAD File Name:
AutoCAD SHX Text Drawing No.:
AutoCAD SHX Text Date
AutoCAD SHX Text Revision/Issue
AutoCAD SHX Text No.
AutoCAD SHX Text Project Name:
AutoCAD SHX Text Sheet No.:
AutoCAD SHX Text Project No.:
AutoCAD SHX Text Date:
AutoCAD SHX Text Scale:
AutoCAD SHX Text
SW
AutoCAD SHX Text W
AutoCAD SHX Text
NW
AutoCAD SHX Text
SE
AutoCAD SHX Text E
AutoCAD SHX Text
NE
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text A-2
AutoCAD SHX Text
AutoCAD SHX Text
SCALE: 1/4" = 1'-0"
AutoCAD SHX Text
%%UARCHITECTURAL PARTIAL PLAN - CHILLER ROOF AREA
AutoCAD SHX Text
SCALE: NTS
AutoCAD SHX Text
%%UACCESS DOOR THRESHOLD DETAIL
AutoCAD SHX Text A-2
TA
PE
R
ED
VA
R
IE
S
2" 11 2"
EPDM MEMBRANE
MEMBRANE ADHESIVE
RUSS STRIP
EXISTING CONCRETE BLOCK WALL
2" M
IN
TERMINATION BAR AND SEALANT
NEW BASE FLASHING UNDER EXISTING
CONTINUOUSLY INSULATED STUCCO
FINNISH SYSTEM.
EXISTING CONTINUOUSLY INSULATED
STUCCO FINNISH SYSTEM. REPAIR
STUCCO FINISH TO MATCH EXISTING.
41 2" 4"
EXISTING LOUVER BASE FLASHING
BEYOND
NEW ROOF SYSTEM
CAST IRON DRAIN WITH
THREADED ADJUSTABLE
EXTENSION
MEMBRANE ADHESIVE
EPDM MEMBRANE
ROOF ASSEMBLY -
REFER TO DETAIL
MANUFACTURED TAPERED
INSULATION SUMP OVER BASE
LAYER OF POLYISO INSULATION
CAST IRON DRAIN
DOME
EXISTING CONCRETE DECK,
PATCH AS REQUIRED
HUBLESS TIE-IN OF NEW CAST
IRON DRAIN LEADER PIPING TO
EXISTING CAST IRON PIPE
11 2" 2"
PIPE INSULATION TO MATCH
EXISTING, SEAL NEW
INSULATION TO EXISTING
INSULATION BEYOND PIPE
REPLACEMENT
LEAD AND OAKUM JOINT
DURING DRAIN REMOVAL, ASSEMBLY AND INSTALLATION, THE
INTERIOR SURFACES SHALL BE PROTECTED FROM INFILTRATION OF
WATER AND DEBRIS. COORDINATE THESE OPERATIONS WITH THE
OWNER PRIOR TO COMMENCEMENT.
NOTES:
EXISTING SHEET METAL CURB
EXISTING HVAC EQUIPMENT,
REMOVE AND SALVAGE FOR
REINSTALLATION, EXTEND
SERVICES AS REQUIRED TO
REINSTALL ON EXISTING
SALVAGED CURB
1' -0
" M
IN
ROOF ASSEMBLY -
REFER TO DETAIL
MEMBRANE ADHESIVE
RUSS STRIP
TERMINATION BAR AND
SEALANT
EPDM MEMBRANE FLASHINGR
AI
SE
E
Q U
IP
M
EN
T
TA
PE
R
VA
R
IE
S 11 2"
2"
TA
PE
R
VA
R
IE
S 2"
ROOFING ASSEMBLY -
REFER TO DETAIL
SEAM TAPE
EPDM MEMBRANE
PIPE/CONDUIT
SUPPORT
2" TYP.
11 2"
MOULDED
WALKWAY PAD
2" RIGID INSULATION , ADHERE
TO INSIDE FACE OF CURB
EPDM 6" PEEL & STICK FLASHING
OVER SCUPPER FLANGES
EPDM TAPE PRIMER
SEE NOTE 4
EPDM 9" PEEL & STICK FLASHING
OVER EPDM 6" PEEL & STICK
FLASHING
LAP SEALANT
LAP
SEALANT
EPDM 9" PEEL & STICK FLASHING
EPDM TAPE PRIMER
SEE NOTE 4
EPDM 12" PEEL & STICK FLASHING
OVER EPDM 9" PEEL & STICK FLASHING
EXISTING SCUPPER SLEEVE
EXISTING WALL/COLUMN
EXISTING WALL/COLUMN
EXISTING CONTINUOUSLY INSULATED
STUCCO FINNISH SYSTEM. REPAIR
STUCCO FINISH TO MATCH EXISTING.
NEW BASE FLASHING UNDER EXISTING
CONTINUOUSLY INSULATED STUCCO
FINNISH SYSTEM.
NOTES:
1. REFER TO SPECIFICATIONS FOR ADDITIONAL
INFORMATION.
2. PLEASE SEE SINLGE PLY FLASHING
SPECIFICATIONS FOR A FULL DESCRIPTION OF
INSTALLATION INSTRUCTIONS AND
REQUIREMENTS, WHICH ARE CONSIDERED PART
OF THE DRAWINGS.
3. ANY CARPENTRY OR METAL WORK SHOULD BE
DESIGNED AND CONSTRUCTED IN ACCORDANCE
WITH LOCAL CODE REQUIREMENTS AND/OR
PROJECT SPECIFICATIONS. THESE COMPONENTS
SHALL BE INCLUDED IN SUBMITTALS.
4. EPDM TAPE PRIMER MUST BE APPLIED ON ALL
SURFACES COMING INTO CONTACT WITH EPDM
PEEL & STICK FLASHING. EPDM MEMBRANE
REQUIRES EPDM TAPE PRIMER OR SINGLE PLY
MEMBRANE PRIMER (LOW VOC).
5. ALL SEALANTS/CAULKING SHALL BE INSPECTED
BY CONTRACTOR PRIOR TO FINAL INSPECTION BY
OSBI.
EXISTING CONCRETE DECK
EXISTING CONCRETE DECK
EXISTING CONCRETE DECK
EXISTING CONCRETE DECK
EXISTING CONCRETE DECK
EXISTING WALL
EXISTING CONCRETE DECK
2X WOOD BLOCKING, RIP AS REQUIRED
TO OVERHANG OUTSIDE OF EXISTING
CURB BY 12"
RUSS STRIP
EPDM FLASHING MEMBRANE
TERMINATION BAR
EXISTING COLUMN BEYOND
EPDM TAPE PRIMER, SEE NOTE 4
EPDM 6" PEEL & STICK FLASHING
OVER SCUPPER FLANGES
EPDM 9" PEEL & STICK FLASHING
OVER SCUPPER FLANGES
LAP SEALANT AT ALL FLASHING EDGES
2" STAINLESS STEEL THREADED ROD
SET IN HIT-HY 70 ADHESIVE ANCHOR
W/SCREEN TUBE @ 16" O.C.
STAGGERED, COUNTERSINK HEAD
18-GAUGE C-CHANNEL PRE-PUNCHED
AND CUSTOM FORMED TO FIT
BLOCKING AS SHOWN. SECURE TO
WOOD BLOCKING WITH 1-14" HP
FASTENERS @ 8" O.C.
3" MIN. LAP
ONTO METAL
2"
EXISTING LOUVER
2"
CONTINUOUS CLEAT
SL
O
PE
SI
D
E
LA
P
6" (T
YP
IC
AL
SI
D
E
LA
P
6" (T
YP
IC
AL
SH
EE
T W
ID
TH
6"
LAP SEALANT, EXTEND 2"
BEYOND MEMBRANE SPLICE
STAGGERED END LAP
6"X6" PRESSURE-SENSITIVE T-JOINT COVER
WITH 12"X12" PRESSURE-SENSITIVE
T-JOINT COVER, TYPICALLAP SEALANT,
EXTEND 2" BEYOND MEMBRANE SPLICE
LAP SEALANT, EXTEND
AROUND PERIMETER OF
T-JOINT COVER AND 2"
BEYOND COVER
6" FACTORY-APPLIED
SEAM TAPE
A
EPDM
MEMBRANE
B
C
EPDM MEMBRANE
LAP SEALANT
1/2"1/2"
6X6 PRESSURE
SENSITIVE FLASHING
12X12 PRESSURE
SENSITIVE FLASHING
LAP
SEALANT
EPDM
MEMBRANE
LAP SEALANT
EPDM
MEMBRANE
LAP SEALANT
A
B
C
FLASHING
MEMBRANE
6X6 PRESSURE
SENSITIVE FLASHING
9X9 PRESSURE
SENSITIVE
FLASHING
12X12 PRESSURE
SENSITIVE FLASHING
LAP SEALANT
EPDM
MEMBRANE
EPDM
MEMBRANE
AS NOTED
ARCHITECTURAL
DETAILS
A-1_REV 6-23-2026.DWG
06/24/2026
ECSU-2026-02
Fa ci lit ie s M an ag em en t a nd P la nn in g
W in dh am S tre et
, W ill im an tic C
T
E A
ST
E
R N
C O
N N
E C
T
IC
U T
S T
A T
E U
N
IV
E R
SI
T
Y
J.E SMITH LIBRARY
CHILLER
REPLACEMENT
AutoCAD SHX Text C
AutoCAD SHX Text L
AutoCAD SHX Text NOTES: 1. THE MAXIMUM ALLOWABLE SURFACE TEMPERATURE OF THE PENETRATION SHALL THE MAXIMUM ALLOWABLE SURFACE TEMPERATURE OF THE PENETRATION SHALL NOT EXCEED 180° F (82° C).2. ALL DEBRIS (PAINT, RUST, LEAD, OTHER FLASHINGS, ETC.) MUST BE REMOVED ALL DEBRIS (PAINT, RUST, LEAD, OTHER FLASHINGS, ETC.) MUST BE REMOVED FROM THE PENETRATION. 3. ALL SURFACES MUST BE PRIMED WITH EPDM PRIMER PRIOR TO APPLYING ALL SURFACES MUST BE PRIMED WITH EPDM PRIMER PRIOR TO APPLYING POURABLE SEALER. 4. POURABLE SEALER MUST COMPLETELY FILL POURABLE SEALER POCKET TO POURABLE SEALER MUST COMPLETELY FILL POURABLE SEALER POCKET TO PREVENT PONDING OF WATER. 5. POURABLE SEALER MUST CONTACT PRIMED PRESSURE-SENSITIVE ELASTOFORM POURABLE SEALER MUST CONTACT PRIMED PRESSURE-SENSITIVE ELASTOFORM FLASHING AND DECK MEMBRANE. 6. SECUREMENT IS REQUIRED FOR POURABLE SEALER POCKETS WHICH ARE GREATER SECUREMENT IS REQUIRED FOR POURABLE SEALER POCKETS WHICH ARE GREATER THAN 18" (46cm) IN DIAMETER. REFER TO SPECIFICATIONS. 7. ON MECHANICALLY-FASTENED ROOFING SYSTEMS, ADDITIONAL MEMBRANE ON MECHANICALLY-FASTENED ROOFING SYSTEMS, ADDITIONAL MEMBRANE SECUREMENT IS REQUIRED (SIMILAR TO DETAIL MF-8A) REGARDLESS OF SIZE AND DETAIL MF-8A) REGARDLESS OF SIZE AND ) REGARDLESS OF SIZE AND REGARDLESS OF SIZE AND DIAMETER, UNLESS WOOD NAILERS ARE PRESENT. 8. DECK FLANGE MUST BE CONTINUOUS WITH ROUNDED CORNERS. DECK FLANGE MUST BE CONTINUOUS WITH ROUNDED CORNERS. 9. WHEN ANY ONE SIDE OF THE FIELD FABRICATED POURABLE SEALER POCKET WHEN ANY ONE SIDE OF THE FIELD FABRICATED POURABLE SEALER POCKET EXCEEDS 12" (30cm), USE WOOD BLOCKING TO ANCHOR SHEET METAL. 10. MINIMUM 1" (2.5cm) CLEARANCE REQUIRED BETWEEN PENETRATIONS.MINIMUM 1" (2.5cm) CLEARANCE REQUIRED BETWEEN PENETRATIONS.
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text
PENETRATION
AutoCAD SHX Text 1"
AutoCAD SHX Text 2.5
AutoCAD SHX Text A
AutoCAD SHX Text cm
AutoCAD SHX Text
DIMENSIONS
AutoCAD SHX Text 2"
AutoCAD SHX Text
AutoCAD SHX Text
MIN.
AutoCAD SHX Text B
AutoCAD SHX Text
MIN.
AutoCAD SHX Text MANDATORY EPDM PRIMER AT ALL INTERFACES OF POURABLE SEALER VS. ANY OTHER COMPONENT & AS SHOWN UNDER FLASHING
AutoCAD SHX Text ADDITIONAL 9" (23cm) WIDE PRESSURE-SENSITIVE ELASTOFORM FLASHING
AutoCAD SHX Text
FILLER
AutoCAD SHX Text C
AutoCAD SHX Text C
AutoCAD SHX Text 3"
AutoCAD SHX Text 7.5
AutoCAD SHX Text C
AutoCAD SHX Text MANDATORY EPDM PRIMER AT ALL INTERFACES OF POURABLE SEALER EXCEPT BLUE PLASTIC SUPPORT STRIP
AutoCAD SHX Text
AutoCAD SHX Text
POURABLE SEALER
AutoCAD SHX Text
PRESSURE-SENSITIVE ELASTOFORM FLASHING IN CONJUNCTION WITH EPDM PRIMER
AutoCAD SHX Text A-3
AutoCAD SHX Text
AutoCAD SHX Text Drawing Name:
AutoCAD SHX Text CAD File Name:
AutoCAD SHX Text Drawing No.:
AutoCAD SHX Text Date
AutoCAD SHX Text Revision/Issue
AutoCAD SHX Text No.
AutoCAD SHX Text Project Name:
AutoCAD SHX Text Sheet No.:
AutoCAD SHX Text Project No.:
AutoCAD SHX Text Date:
AutoCAD SHX Text Scale:
AutoCAD SHX Text
AutoCAD SHX Text A-3
AutoCAD SHX Text
THROUGH WALL SCUPPER DETAIL
AutoCAD SHX Text
SCALE: NTS
AutoCAD SHX Text
AutoCAD SHX Text A-3
AutoCAD SHX Text
ROOF DRAIN DETAIL
AutoCAD SHX Text
SCALE: 3" = 1'-0"
AutoCAD SHX Text
AutoCAD SHX Text A-3
AutoCAD SHX Text
WALL FLASHING DETAIL
AutoCAD SHX Text
SCALE: 3" = 1'-0"
AutoCAD SHX Text
AutoCAD SHX Text A-3
AutoCAD SHX Text
PITCH POCKET DETAIL
AutoCAD SHX Text
SCALE: 3" = 1'-0"
AutoCAD SHX Text
AutoCAD SHX Text A-3
AutoCAD SHX Text
PIPE/CONDUIT SUPPORT DETAIL
AutoCAD SHX Text
SCALE: 3" = 1'-0"
AutoCAD SHX Text
AutoCAD SHX Text A-3
AutoCAD SHX Text
EQUIPMENT CURB DETAIL
AutoCAD SHX Text
SCALE: 3" = 1'-0"
AutoCAD SHX Text
AutoCAD SHX Text A-3
AutoCAD SHX Text
TYPICAL EPDM SEAM DETAILS
AutoCAD SHX Text
SCALE: NTS
AutoCAD SHX Text
AutoCAD SHX Text A-3
AutoCAD SHX Text
ROOF EDGE DETAIL
SCALE: NTS
L
4 5
K
J
H
EX. W24X76 EX. W24X76 EX. W24X76
EX. W24X55
EX. W30X108
W X
W X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
EX. W24X55
EX. W24X55
EX. W16X26
EX. W16X26
EX. W16X26
EX. W16X26
EX. W16X26
EX. W16X26
EX. W16X26
EX. W12X22
EX. W24X55
4.2 4.4 4.84.6
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
H.6
H.3
EX. W24X68
EX. W12X26
EXISTING HSS 4x4 DUNNAGE
POSTS; TYPICAL (12) LOCATIONS;
POSTS TO REMAIN TO SUPPORT
NEW DUNNAGE BEAMS ABOVE; TOP
OF POSTS TO BE CUT DOWN 10";
SEE DETAIL
APPROXIMATE LOCATION OF
EXTERIOR WALLS AT
MECHANICAL AREA; VIF; FOR
REFERENCE ONLY; TYPICAL
EXISTING MECHANICAL
EQUIPMENT ON EXISTING
DUNNAGE FRAMING ABOVE TO
BE REMOVED
EXISTING L3x3 KNEE
BRACES TO BE REMOVED;
TYPICAL (12) LOCATIONS;
REFER TO ARCH DWGs
FOR REPAIRS TO PITCH
POCKETS AT POST BASES
EXISTING ADJACENT
MECHANICAL EQUIPMENT;
PROTECT EQUIPMENT AS REQ'D
EXISTING BUILDING
COLUMN; TYPICAL
4.5
NORTH
30'-0" ±
/6 S-2
* * NOTE * *
DUNNAGE DIMENSIONS WERE ESTABLISHED USING DIMENSIONS OF MULTISTACK BASE
FRAME MODEL WELDFRAME-ACF-6V-96 WITH MULTISTACK MODEL ACF220MNHCE 225-TON
CHILLERS. DIMENSIONS ARE SUBJECT TO CHANGE BASED ON SELECTED MANUFACTURER
AND BASE FRAME TYPE. STRUCTURAL STEEL FOR DUNNAGE FRAMING SHALL NOT BE
DETAILED OR FABRICATED UNTIL BASE FRAME SHOP DRAWINGS HAVE BEEN SUBMITTED
AND DUNNAGE FRAMING DIMENSIONS HAVE BEEN ADJUSTED AS REQUIRED.
Drawing Name:
CAD File Name:
Drawing No.:
DateRevision/IssueNo.
ProjectName:
Sheet No.:
Project No.:
Date:
Scale:
F ac il it ie s
M an ag em en t an d
P la n n in g
W in d h am S tr ee t, W il li m an ti c
C T
E
A S
T E
R N
C O
N N
E C
T I C
U T
S T
A T
E U
N I V
E R
S I T
Y
J.E SMITH LIBRARY
CHILLER
REPLACEMENT
1/4" = 1'-0"
ECSU-2025-08
06/24/2026
S-0
STRUCTURAL
NOTES AND
PARTIAL MEZZ
FRAMING DEMO
PLAN
1/4" = 1'-0"
PARTIAL MEZZANINE FRAMING DEMOLITION PLAN
DESIGN BASIS
DB1. The alterations to this structure have been designed in accordance with the applicable structural provisions of the 2022 Connecticut State Building Code which includes “The International Building Code/2021”, “The International Existing Building Code/2021”, and the applicable Connecticut amendments.
DB2. All demolition and construction shall be in accordance with NFPA 241, "Standard for Safeguarding Construction, Alteration and Demolition Operations" (latest edition).
DB3. AISC "Specification for Structural Steel Buildings" (ANSI/AISC 360-16).
DB4. All structural steel shall conform to the following:
Wide-Flange Sections ASTM A992 Channel Sections ASTM A36 Angles ASTM A36 Plates and Bars ≤ 4” thick ASTM A36
DB5. All high-strength bolts, nuts and washers shall be in accordance with "Specification for Structural Joints Using High-Strength Bolts" approved by the Research Council on Structural Connections (RCSC).
DB6. All high-strength steel expansion bolts shall be Hollo-Bolts as manufactured by Lindapter.
DB7. All welds to structural steel to conform to "Structural Welding Code - Steel" (AWS D1.1 -latest edition).
DB8. All galvanizing shall conform with ASTM A123, ASTM A153 or ASTM A653, as applicable.
DB9. Risk Category: III
FLOOR LIVE LOAD DATA 1603.1.1
Occupancy/Use Uniform
Load
Concentrated
Load
Live Load
Reduction Chiller Enclosure Floor* 100 psf 2,000# N
* Does not include mechanical equipment loads
ROOF SNOW LOAD DATA 1603.1.3
Ground Snow Load, pg 30 psf Flat Roof Snow Load, pf 27.7 psf Minimum flat roof snow load, pf-min 30 psf Snow Exposure Factor, Ce 1.0 Snow Load Importance Factor, Is 1.1 Thermal Factor, Ct 1.2 (at chillers) Slope Factor, Cs 1.0 Snow Drift Loads N/A to Project Existing Roofs: No existing adjacent lower roofs were impacted by this Project.
WIND DESIGN DATA 1603.1.4
Basic Wind Speed, V 135 mph Allowable Stress Design Wind Speed, Vasd 105 mph Risk Category III Wind Exposure B Internal Pressure Coefficient, GCpi ±0.18 Hurricane Prone Region Yes Wind-Borne Debris Region No
EARTHQUAKE DESIGN DATA 1603.1.5
Risk Category III Seismic Importance Factor, Ie 1.25 Mapped Spectral Response Accel. Parameters:
0.190g 0.055g at Short Periods, SS at 1-second Period, S1
Site Class C Design Spectral Response Accel. Parameters:
0.165g 0.055g at Short Periods, SDS at 1-second Period, SD1
Seismic Design Category A Basic Seismic Force-Resisting System(s) * Design Base Shear(s) * Seismic Response Coefficient(s), CS * Response Modification Coefficient(s), R * Analysis Procedure Used *
* Denotes items not applicable to this project. No alterations that impact seismic load resisting system.
SPECIAL LOADS 1603.1.8
Mechanical Equipment Loads:
Chiller CH-1: 17,260# Chiller CH-2: 17,260#
GENERAL NOTES
GN1. All work to conform to requirements of all publications and notes listed under “Design Basis”.
GN2. Architectural drawings, Mechanical/Electrical/Plumbing drawings, equipment vendor drawings, and all other drawings as required shall be used in conjunction with Structural drawings to develop details and dimensions for shop drawings, fabrication, erection, and construction.
GN3. Contractor to verify all existing conditions and all dimensions in field prior to start of construction and protect and maintain all existing construction and its contents in full.
GN4. Existing building dimensions and elevations shown are to be verified in field by Contractor.
GN5. It is the Contractor's sole responsibility to follow all applicable safety codes and regulations during all phases of construction.
GN6. Should any information on the structural drawings conflict with the specifications or any other part of the drawings, the Contractor shall notify the Mechanical Engineer, and an interpretation will be given.
GN7. There shall be no change to the work that is indicated and/or directed by the structural contract documents without a revision describing that change which shall be issued in writing by DiBlasi Associates, P.C.
GN8. All sections, details, notes, dimensions, and conditions are applicable at any other location where conditions and details are similar but are not specifically noted as such or are not shown.
GN9. Throughout the structural construction documents, the term “install” shall mean “furnish and install”, unless specifically noted otherwise. The terms “furnish” and “provide” shall mean “furnish and install” and “provide and install” respectively, unless specifically noted otherwise.
GN10. For quality control inspection and testing requirements during construction, see Specifications and "Schedule of Special Inspections".
STEEL NOTES
ST1. All bolted connections to use ASTM A325 high-strength bolts.
ST2. All high-strength bolts to be fully tensioned.
ST3. All high-strength structural steel expansion bolts shall be installed in accordance with the applicable ICC Evaluation Services report.
ST4. All welded connections to use E70-XX electrodes.
ST5. All structural steel framing and connections thereof shall be hot-dipped galvanized. All field welds and abrasions shall be touched-up with galvanizing repair paint.
ST6. Existing steel surfaces requiring welding are to be prepared in accordance with AWS D1.1 requirements.
SUBMITTALS
Structural Steel Shop Drawings Certificates of Compliance for High-Strength Bolts Product Data for High-Strength Structural Steel Expansion Bolts
This item has been electronically sealed by Thomas A. DiBlasi, P.E., on 19-JUN-2026, using an SHA-256 authentication code. Printed copies of this document are not considered signed and sealed, and the SHA-256 verification code must be verified on the first page of the structural drawing set.
K
J
H
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
EX. W10X12
EX. W10X12
EX. W10X12
EX. W10X12
EX. W10X12
EX. W10X12
EX. W16X26 EX. W16X26
EX. W16X26
EX. W16X26
EX. W16X26
EX. W16X26 EX. W16X26
EX. W16X26
EX. W16X26
EX. W12X26
EX. W16X26
EX. W16X26
EX. W24X55 EX. W24X55
EX. W14X22 EX. W14X22
EXISTING RAFTER BEAMS TO
BE REMOVED; TYPICAL (6)
LOCATIONS
APPROXIMATE LOCATION OF
EXTERIOR WALLS OF
MECHANICAL AREA BELOW;
VIF; FOR REFERENCE ONLY;
TYPICAL
REMOVE EXISTING RAFTER BEAM
END CONNECTIONS AND GRIND
ANY WELDS FLUSH TO PERMIT
INSTALLATION OF NEW
CHANNELS; TYPICAL (6)
LOCATIONS
CUT RAFTER BEAM FLUSH WITH
OUTSIDE FACE OF EX. CMU
WALL; TYPICAL (6) LOCATIONS;
EXISTING WALL FINISHES TO BE
PROTECTED FROM DAMAGE AS
REQUIRED
EX. W21X68 BENT
EX. W24X76 BENT
EX. W24X76 BENT
4.5
V
IF
15'-0" VIF 15'-0" VIF
NORTH
OPEN
L
4 5
K
J
H
4.2 4.4 4.84.6
H.6
H.3
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
EX. W8X24 EX. W8X24
EX. W8X24 EX. W8X24
EX. W8X24EX. W8X24
EXISTING HSS 4x4
DUNNAGE POSTS;
TYPICAL (12)
LOCATIONS; POSTS TO
REMAIN TO SUPPORT
NEW DUNNAGE BEAMS
APPROXIMATE
LOCATION OF
EXTERIOR WALLS AT
MECHANICAL AREA;
FOR REFERENCE
ONLY; TYPICAL
EXISTING W8 DUNNAGE
BEAMS TO BE REMOVED;
TYPICAL (14) LOCATIONS
EXISTING ROOF TOP
UNITS TO BE REMOVED;
BY OTHERS
EXISTING L3x3 KNEE
BRACES TO BE
REMOVED; TYPICAL
(12) LOCATIONS
EXISTING ADJACENT
MECHANICAL
EQUIPMENT; PROTECT
EQUIPMENT AS REQ'D
EXISTING BUILDING
COLUMN; TYPICAL
4.5
NORTH
30'-0" ±
Drawing Name:
CAD File Name:
Drawing No.:
DateRevision/IssueNo.
ProjectName:
Sheet No.:
Project No.:
Date:
Scale:
F ac il it ie s
M an ag em en t an d
P la n n in g
W in d h am S tr ee t, W il li m an ti c
S
T E
R N
C O
N N
E C
T I C
U T
S T
A T
E U
N I V
E R
S I T
Y
J.E SMITH LIBRARY
CHILLER
REPLACEMENT
1/4" = 1'-0"
ECSU-2025-08
06/24/2026
S-1
DUNNAGE PARTIAL
DEMOLITION AND
ROOF FRAMING
PLANS
1/4" = 1'-0"
DUNNAGE DEMOLITION PLAN
1/4" = 1'-0"
PARTIAL ROOF FRAMING DEMOLITION PLAN
This item has been electronically sealed by Thomas A. DiBlasi, P.E., on 19-JUN-2026, using an SHA-256 authentication code. Printed copies of this document are not considered signed and sealed, and the SHA-256 verification code must be verified on the first page of the structural
19-JUN-2026
K
J
H
4.2 4.4 4.84.6
H.6
H.3
EXISTING HSS 4x4 DUNNAGE
POSTS; TOP OF POST TO BE
CUT DOWN 10" AND NEW POST
CAP INSTALLED TO RECEIVE
NEW W8 DUNNAGE BEAMS;
TYPICAL (12) LOCATIONS; SEE
DETAIL
APPROXIMATE LOCATION OF
EXTERIOR WALLS AT
MECHANICAL AREA; FOR
REFERENCE ONLY; TYPICAL
NEW W8 DUNNAGE BEAMS
ON EXISTING HSS4x4 POSTS;
TYPICAL (14) LOCATIONS
W8X24 GALV
W8X24 GALV
W8X24 GALV
W X
G
A L V
W X
G
A L V
W X
G
A L V
W X
G
A L V
W X
G
A L V
W X
G
A L V
W8X24 GALV
W8X24 GALV
W8X24 GALV
W X
G
A L V
W X
G
A L V
EXISTING ADJACENT
MECHANICAL
EQUIPMENT; PROTECT
EQUIPMENT AS REQ'D
END OF W8 TO ALIGN WITH
OUTER EDGE OF ADJACENT
W8; TYPICAL (12) LOCATIONS
EXISTING BUILDING
COLUMN; TYPICAL
4.5
S-2
S-2
V
IF
V
IF
3 1/2"
7'-2 1/4" VIF
3 1/2"
7'-9 1/4"
3 1/2"
7'-2 1/4" VIF
3 1/2"
7'-9 1/4"
8'-0 1/4" *
/4
8'-0 1/4" *
/4
NEW MECHANICAL UNIT
SIZE OF NEW MECHANICAL UNIT
(*) TO BE CONFIRMED PRIOR TO
DUNNAGE STEEL FABRICATION;
LAYOUT OF DUNNAGE FRAMING
MAY NEED TO BE ALTERED IF
UNIT DIMENSIONS ARE
DIFFERENT; TYPICAL
NORTH
30'-0" ±
/6 S-2
CHILLER
CUT DOWN EXISTING
DUNNAGE POST 10";
SEE DETAIL
BASE RAIL OF
MECHANICAL UNIT;
SEE DETAIL FOR
CONNECTION TO
DUNNAGE
W8 DUNNAGE BEAM; FASTEN
TO SUPPORTING BEAM W/
3/8" SINGLE PLATE CONNX.
W/ (2) 3/4"Ø BOLTS (NOT
SHOWN FOR CLARITY)
W8 DUNNAGE BEAM
6 1/2" x 3/4" x 1'-0" CAP
PLATE WITH (4) 3/4" DIAM
GALV BOLTS TO W8
DUNNAGE BEAM
1/4
EXISTING HSS 4x4
DUNNAGE POST
/4 S-2
3 1/2"
/6 S-2
CHILLER
4" x 1/2" x 0'-5" HIGH CONN
PLATE WITH 3/4"Ø GALV
STEEL EXPANSION BOLT
1/4
1/4
NOTE:
PROVIDE SIX (6) CONNECTIONS AT EACH
BEAM NOTED THUS ( ) ON PLAN. LOCATE
CONNECTIONS 1'-0" FROM EACH END OF
DUNNAGE BEAM AND SPACE EQUALLY IN
BETWEEN (48 CONNECTIONS TOTAL)
BASE RAIL OF CHILLER;
FIELD DRILL RAIL FOR
STEEL EXPANSION
BOLTS (1 5/8" HOLE
DIAMTER)
W8 DUNNAGE BEAM
PROVIDE 1/4"± SHIM
SPACE BETWEEN
BASE RAIL AND CONN
PLATE; PROVIDE 3"x3"
GALV PLATE SHIM
3 1/2"
1 3/4"
L
4 5
K
J
H
S-2
4.5
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
EX. W16X26 EX. W16X26
EX. W16X26
EX. W16X26
EX. W16X26
EX. W16X26 EX. W16X26
EX. W16X26
EX. W16X26
EX. W12X26
EX. W16X26
EX. W16X26
EX. W24X55 EX. W24X55
EX. W14X22 EX. W14X22
N E
W C x .4
O
N E
E A
C H
S
ID
E
APPROXIMATE LOCATION OF
EXTERIOR WALLS OF
MECHANICAL AREA BELOW;
VIF; FOR REFERENCE ONLY;
TYPICAL
EX. W21X68 BENT
EX. W24X76 BENT
EX. W24X76 BENT
V
IF
15'-0" VIF 15'-0" VIF
NORTH
OPEN
4.5
/8
EXIST W18
RIDGE BEAM
EXIST W21
BENT BEYOND
1/4 2-12
6" WELD EA
END; TYP
CONT C9
REINFORCING EACH
SIDE OF EXIST W18
RIDGE BEAM 1
6 3/4"
EXISTING W8 TO
BE REMOVED
EXISTING CAP PLATE
TO BE REMOVED
PORTION OF EXISTING
HSS4x4 POST TO BE
REMOVED
NEW 6 1/2"x3/4"x1'-0"
CAP PLATE
PORTION OF EXISTING
HSS4x4 POST TO REMAIN;
TOP OF POST TO BE GROUND
SMOOTH PRIOR TO WELDING
NEW CAP PLATE; PAINT ON
EXPOSED PORTION OF POST
TO BE REMOVED; PAINT WITH
GALVANIZING REPAIR PAINT
TOP OF ALL NEW
CAP PLATES TO BE
AT SAME ELEVATION
* * NOTE * *
DUNNAGE DIMENSIONS WERE ESTABLISHED USING DIMENSIONS OF MULTISTACK BASE
FRAME MODEL WELDFRAME-ACF-6V-96 WITH MULTISTACK MODEL ACF220MNHCE 225-TON
CHILLERS. DIMENSIONS ARE SUBJECT TO CHANGE BASED ON SELECTED MANUFACTURER
AND BASE FRAME TYPE. STRUCTURAL STEEL FOR DUNNAGE FRAMING SHALL NOT BE
DETAILED OR FABRICATED UNTIL BASE FRAME SHOP DRAWINGS HAVE BEEN SUBMITTED
AND DUNNAGE FRAMING DIMENSIONS HAVE BEEN ADJUSTED AS REQUIRED.
Drawing Name:
CAD File Name:
Drawing No.:
DateRevision/IssueNo.
ProjectName:
Sheet No.:
Project No.:
Date:
Scale:
F ac il it ie s
M an ag em en t an d
P la n n in g
W in d h am S tr ee t, W il li m an ti c
S
T E
R N
C O
N N
E C
T I C
U T
S T
A T
E U
N I V
E R
S I T
Y
J.E SMITH LIBRARY
CHILLER
REPLACEMENT
As indicated
ECSU-2025-08
06/24/2026
S-2
DUNNAGE AND
PARTIAL ROOF
FRAMING PLANS
1/4" = 1'-0"
DUNNAGE FRAMING PLAN
1" = 1'-0"
SECTION
1" = 1'-0"
SECTION
1 1/2" = 1'-0"
DUNNAGE BEAM TO CHILLER BASE FRAME CONNECTION DETAIL
1/4" = 1'-0"
PARTIAL ROOF FRAMING PLAN
1 1/2" = 1'-0"
DUNNAGE POST MODIFICATION DETAIL
This item has been electronically sealed by Thomas A. DiBlasi, P.E., on 19-JUN-2026, using an SHA-256 authentication code. Printed copies of this document are not considered signed and sealed, and the SHA-256 verification code must be verified on the first page of the structural
19-JUN-2026
REMOVE EXISTING 200 TON CHILLER INCLUDING
PIPING, POWER WIRING, RACEWAY, CONTROLS
WIRING & RACEWAY, AND ISOLATORS.
COORDINATE REMOVAL WITH STRUCTURAL AND
ARCHITECTURAL WORK.
REMOVE AND REPLACE EXISTING
CONDENSING UNIT WITH ROOF RAILS
TO ACCOMIDATE ROOFING WORK
(TYP).
PROVIDE REFRIGERATION SERVICES
INCLUDING RECOVERING
REFRIGERANT, EXTENDING
REFRIGERANT PIPING AND, VACUUM
& RECHARGE.
EXTEND ELECTRICAL POWER FEED
AS REQUIRED TO ACCOMMODATE
NEW ROOFING RAIL HEIGHT (TYP).
RECOVER/REMOVE REFRIGERANT FOR EACH
REFRIGERATION CKT FOR BOTH CHILLERS.
REMOVE EXISTING REFRIGERATION PIPING,
HANGERS/SUPPORTS AND INSULATION SERVING
BOTH SPLIT-EVAP CHILLERS.
(2) SETS OF 1-1/8" LIQ LINE
(2) SETS OF 3-1/8" SUCT LINE
REMOVE CONTROLS WIRING AND RACEWAY
BACK TO BELOW ROOF DECK SERVING EACH
CHILLER (TYP).
COORDINATE REMOVAL WITH STRUCTURAL AND
ARCHITECTURAL WORK.
FDSWFDSW
OA
OA
OA
EX EX
EX EX EX
ETR OA PLENUM
ET
R
E X
PL
EN
U M
ET
R
E X
PL
EN
U M
ETR EX PLENUM
OA
REMOVE ROOF DRAIN INCLUDING PIPING AND
INSULATION.
COORDINATE REMOVAL WITH STRUCTURAL AND
ARCHITECTURAL WORK.
EXISTING FUSED DISCONNECT
SWITCH TO REMAIN (TYP).
EXISTING 120V CONVENIENCE
OUTLET TO REMAIN (TYP).
EXISTING 120V EXTERIOR LIGHT
REMAIN (TYP).
REMOVE AND REPLACE EXISTING CURB
MOUNTED ROOF EXHAUST FAN TO
ACCOMMODATE ROOFING WORK (TYP).
FURNISH NEW ROOF CURB TO ROOFER
FOR INSTALL. COORDINATE NEW CURB
HEIGHT WITH ROOFING CONTRACTOR
PRIOR TO ORDERING.
EXTEND DUCT AND ELECTRICAL
POWER FEED AS REQUIRED TO
ACCOMMODATE NEW CURB HEIGHT
(TYP).
REMOVE EXISTING 200 TON CHILLER
INCLUDING REFRIGERATION PIPING,
CONTROL & POWER WIRING, RACEWAY,
SUPPORTS AND SPRING ISOLATORS.
COORDINATE REMOVAL WITH STRUCTURAL
AND ARCHITECTURAL WORK.
RECOVER/REMOVE REFRIGERANT FOR EACH
REFRIGERATION CKT FOR EACH CHILLER.
REMOVE EXISTING REFRIGERATION PIPING,
HANGERS/SUPPORTS AND INSULATION SERVING
BOTH SPLIT-EVAP CHILLERS.
(2) SETS OF 1-1/8" LIQ LINE / PER CHILLER
(2) SETS OF 3-1/8" SUCT LINE / PER CHILLER
COORDINATE REMOVAL WITH STRUCTURAL AND
ARCHITECTURAL WORK.
EXISTING UNIT HEATER
W/CONTROLS TO REMAIN (TYP).
EXISTING AIR HANDLER UNIT
W/CONTROLS TO REMAIN (TYP).
VFD-R3
VFD-R1
VFD-RF4
VFD-RF2
ST
REMOVE EXISTING STORM WATER
PIPING, FITTINGS, HANGERS &
INSULATION SERVING CHILLER AREA
ROOF DRAIN (TYP).
4" STORM RISER TO REMAIN.
EX
8" CWS
8" C
W R
8" CWR
8" CWSCHWP-2
8" C
W R
8" C
W R
CHWP-1
AIR
SEPERATOR
MS CHWP-1
MS CHWP-2
ATC
ATC
DUCT SMOKE DET
REMOVE 4" STORM PIPING &
PIPE INSULATION UP TO
ROOF DRAIN.
REMOVE ROOF DRAIN WITH PIPE
INSULATION SERVING CHILLER ROOF
AREA.
REFER TO ROOF PLAN VIEW FOR
NEW ROOF DRAIN LOCATION.
COORDINATE WITH EXISTING
CONDITIONS & THE WORK OF OTHER
DIVISIONS (TYP).
REMOVE EXISTING END SUCTION
PUMPS, INCLUDING ALL
ASSOCIATED VALVES, RISER
PIPING, TRIM (TYP).
REMOVE HYDRONIC PIPING
WITHIN MECHANICAL ROOM
INCLUDING VALVES, SUPPORTS,
INSULATION (TYP).
EXISTING CHWS&R PIPING
TO/FROM AIR HANDLERS
TO REMAIN (TYP).
EXISTING AUTOMATIC
TEMPERATURE CONTROLS (ATC)
PANEL TO REMAIN (TYP).
REMOVE EXISTING PUMP MOTOR
CONTROLLERS(S)
BY ELECTRICAL CONTRACTOR
(TYP).
EXISTING DUCT SMOKE TEST
STATION TO REMAIN (TYP).
REMOVE CHILLER CONTROL
PANEL, CONTROL POINTS
WIRING & RACEWAY SERVING
EXISTING CHILLERS (TYP).
8" C
W S
REMOVE EXISTING FLOOR
MOUNTED AIR SEPERATOR ,
INCLUDING ALL ASSOCIATED
SUPPORTS, PIPING, TRIM (TYP).
REMOVE EXISTING REMOTE
EVAPORATORS, SUPPORT FRAME,
INCLUDING ALL ASSOCIATED,
PIPING AND TRIM (TYP).
REMOVE HYDRONIC PIPING
WITHIN MECHANICAL ROOM
INCLUDING VALVES, SUPPORTS,
INSULATION (TYP).
REMOVE HYDRONIC PIPING
WITHIN MECHANICAL ROOM
INCLUDING VALVES, SUPPORTS,
INSULATION (TYP).
3/ 4"
D
CW
EXISTING FLOOR DRAIN TO
REMAIN (TYP).
EXISTING DOMESTIC COLD
WATER PIPING TO REMAIN.
REMOVE MAKE-UP WATER
PIPING, VALVES AND TRIM TO
AIR SEPERATOR &
EXPANSION TANK (TYP).
REMOVE EXISTING EXPANSION
TANK SERVING CHILLED WATER
SYSTEM INCLUDING SUPPORT
FRAME AND ALL ASSOCIATED,
PIPING AND TRIM (TYP).
"TRANE TRACE"
REMOVE EXISTING REFRIGERANT LEAK
DETECTOR/SENSOR, ALARM AND EM SWITCH
(FROM CORRIDOR & MECH ROOM) INCLUDING ANY
VISUAL & AUDIBLE ALARMS, SIGNAGE AND
CONTROLS PROGRAMING.
PROVIDE STAINLESS STEEL COVER PLATE TO
COVER EXISTING J-BOXES.
LINETYPE LEGEND
EXISTING TO BE REMOVED (DEMOLITION)
EXISTING TO REMAIN AS NOTED
MECHANICAL
DEMOLITION PLAN
M-1.DWG
1/4"=1'-0"
GRAPHIC SCALE
SCALE IN FEET
0 4 8
MEP DEMOLITION NOTES
NOTES:
1. FOR DRAWING CLARITY NOT ALL EXISTING SYSTEMS ARE SHOWN OR NOTED ON THE DRAWINGS. CONTRACTOR SHALL VISIT THE SITE TO UNDERSTAND THE EXTENT OF EXISTING CONDITIONS, CONFIRM THE SCOPE OF WORK AND EXISTING CONDITIONS PRIOR TO SUBMITTING BID.
2. ECSU MAY CHOOSE TO RETAIN ITEMS/DEVICES/EQUIPMENT INDICATED AS REMOVED OR AS DEMOLITION FOR THIS PROJECT. CONTRACTOR SHALL CONFIRM WITH ECSU FACILITIES & PLANNING WHAT (IF ANY) MATERIALS ARE INTENDED TO BE RETAINED BY…
This is the start of the file's text. The full file is on GovTribe.