INSTRUCTIONS FOR VENDORS

FEMA GENERATOR PURCHASE - DC GUAM AND DC MOFFETT (RFP: HSFE20-16-Q-0029)

COMPANY NAME:
Please Enter Company Name Above Here.
DATE SUBMITTED: (d/mm/yyyy)
Please Enter Date Submitted Above Here.
Checklist Directions:In order to receive a Technical Rating, vendors must complete the Specification Checklists in this workbook. Specifications must be filled out for ALL Generator sizes that vendors are bidding on. In addition to this checklist, vendors are required, as per the Statement of Work to provide detailed specification sheets.
Below are the instructions for completing this checklist:
1) Make sure to complete the section for Company Name and Date Submitted on this sheet (will auto populate)
2) On each of the respective sheets, only fill in those cells that are in YELLOW
3) If the proposed generator MEETS OR EXCEEDS the specification requirement type "Y"
4) If the proposed generator DOES NOT MEET the specification requirement type "N"
5) Information that you enter on the individual kW specification sheets will auto-populate the summary sheet

RFP: HSFE50-16-R-0004

&F &A

Spec_50kW FEMA REQUIRED GENERATOR SPECIFICATIONS - AUGUST 2016 - Revised (RFP:HSFE20-16-Q-0029)

COMPANY NAME:0
DATE SUBMITTED:12/31/99
GENERATOR KW SIZE:kW
RATING INFORMATION
Prime KW:50kW
FEMA Acceptable kW Min-Max Range:15kw - 60kW
Unit kVA (.8 power factor):0.8
GENERATOR SPECIFICATIONSY = YES / N = NO
EnclosureWeather Proof, stainless steel and sound attenuated
Phase:3 Phase
Switchable:The vendor SHALL provide any hardware and/or software, manuals, or other documentation (in digital or hard copy) that provide detailed directions which will allow FEMA mechanics to switch/set output voltages and phase configurations on the generator and voltage regulator
Voltage 3 Phase:208, 220, 240, 416, 440, 480V Switchable
Voltage 1 Phase:120, 127, 139, 240, 254, 277V Switchable
Generator RPM:1800
Frequency:60 HZ
No. Poles4
Excitation:Brushless with AVR
Frequency Regulation (Steady State):0.25%
Alternator Heat Rise:NTE 85°(F) with CLASS H insulation wire
Sound Level:NTE 75dB(A) full load @ 23 ft.
Trailer / Skid MountedSKID MOUNTED
Load Terminal CamLok Connectors:Yes
Integrally-mounted automated load bank system able to apply resistive load up to 40% during periods of low temperature/load conditions. SHALL have the capability to constantly monitor, sense and manage exhaust temperature with automatic shut-off for periods of high load conditions.Yes
ENGINEY = YES / N = NO
Emissions:Tier 4 FINAL
Engine Design:4-cycle, water cooled DIESEL, Ultra Low Sulfur Diesel, turbocharged, direct injection. Charged Air Cooled EGR
Tier 4 Engine Capability:SHALL be capable to perform "Passive Regen" on it's own with no operator at 40% - 50% load at full-rated speed.
SHALL have the capability to "Not Regen" at 80% - 90% load.
Engine Accessories:Fuel Filter
Lube Oil Filter
Intake Air Filter
Lube Oil Cooler
Fuel transfer pump
Fuel Priming Pump
Emergency Shut-off
Fuel/Water Separator
Water Pump
Oil Pump
Full flow lubrication oil filters
Pressure relief valve
Dipstick oil level indicator
Water Temperature & Lube Oil Pressure Gauge
BATTERYY = YES / N = NO
Battery Type:Sealed Gel Cell
Absorbed Glass Matt (AGM)
CONTROL PANELY = YES / N = NO
Control Panel, to Include (but not limited):Engine Analog Hour meter - 12volt or 24volt (unit depending)
Three position panel mounted switch (Stop-Manual-Auto)
Oil pressure gauge
Water temperature gauge
A/C output Amperage
Volt Meter
Frequency Meter
Fuel Gauge
Analog fuel pressure gauge
Battery Voltmeter
Phase selector switch with phase voltage & amperage
DPF cleaning cycle indication
Programmable remaining fuel (tank) level % indicator
Generator Output Bus Separate From Control Panel - Located in a Separate Lockable Panel:Yes
AC (Generator) & DC (Engine) Controls Enclosed in a Separate Box or Separated by Divider:Yes
COMPANY NAME:0
RATING INFORMATION
GENERATOR KW SIZE:0kW
SAFTEYY = YES / N = NO
Safety: Engine shutdown on:High water temperature
Low oil pressure
Over speed
Engine over crank
Low Coolant
Lowe DEF Level
FUELY = YES / N = NO
Fuel Tank: 24 hourUL 142 Double-wall w/ capacity sufficient - 24- hour tank
12 gauge steel body & two coat polyester power coat finish
Lifting points on base frame (two ea.: 4" x 10" x .250" fork pockets & rub spacers
Sheet steel components pre-treated w/ zinc phosphate
Fuel Valve:Yes, Parker H3 or H4 male and female quick disconnect & dust cap - sufficient enough to meet efficient fuel flow
Diesel Engine Fluid (DEF) Tank:Internal storage, EPA approved to provide fluid to operate at full rated load
WARRANTYY = YES / N = NO
Engine Warranty:Industry Standard Warranty
Generator Warranty:Industry Standard Warranty
Trailer: (if applicable)Not Applicable
OTHER REQUIREMENTSY = YES / N = NO
Unit Designed as a Portable Prime Power Unit (Not a Standby Unit Modified for Prime Power Use)Yes
Exhaust:Industrial Silencer/Muffler
Paralleling Capability (to include ALL BOM and required Cables):400kW & Above
Training:The vendor SHALL provide training opportunities for FEMA Mechanics on operational guidance with your equipment. Training is due once ALL units have been delievered to given location. Training shall occur AFTER the delivery of all units to given location; no later than 30 days after receipt of generators. Training date and time are TBD dependent on generator delivery timeline; to be agreed upon by the contractor and the Government. Training shall include how to switch/set the output voltages and phase configurations on the generator and voltage regulators.
Diagnostics/Software:The vendor SHALL provide any hardware and/or software, manuals or other documentation (in digital or hard copy), to include all diagnostic codes, that will enable FEMA Mechanics to perform all diagnostic's available for the generator(s)
Miscellaneous:Fabrication and permanent attachment of exterior metal spacers/rub-knuckles to facilitate side by side (rub free) transportation
Height Requirements for Air Transportation:Want to max transportation versatility - C17 load height limit 104"; C130 load height limit 96"
RFP: HSFE20-16-Q-0029&F
&AJuly 2016

Spec_100kW FEMA REQUIRED GENERATOR SPECIFICATIONS - JULY 2016 - Revised (RFP:HSFE20-16-Q-0029)

COMPANY NAME:0
DATE SUBMITTED12/31/99
GENERATOR KW SIZE:kW
RATING INFORMATION
Prime KW:100kW
FEMA Acceptable kW Min-Max Range:61kW - 100kW
Unit kVA (.8 power factor):0.8
GENERATOR SPECIFICATIONSY = YES / N = NO
EnclosureWeather Proof, stainless steel and sound attenuated
Phase:3 Phase
Switchable:The vendor SHALL provide any hardware and/or software, manuals, or other documentation (in digital or hard copy) that provide detailed directions which will allow FEMA mechanics to switch/set output voltages and phase configurations on the generator and voltage regulator
Voltage 3 Phase:208, 220, 240, 416, 440, 480V Switchable
Voltage 1 Phase:120, 127, 139, 240, 254, 277V Switchable
Generator RPM:1800
Frequency:60 HZ
No. Poles4
Excitation:Brushless with AVR
Frequency Regulation (Steady State):0.25%
Alternator Heat Rise:NTE 85°(F) with CLASS F insulation wire
Sound Level:NTE 75dB(A) full load @ 23 ft.
Trailer / Skid Mounted:SKID MOUNTED
Load Terminal CamLok Connectors:Yes
Integrally-mounted automated load bank system able to apply resistive load up to 40% during periods of low temperature/load conditions. SHALL have the capability to constantly monitor, sense and manage exhaust temperature with automatic shut-off for periods of high load conditions.Yes
ENGINEY = YES / N = NO
Emissions:Tier 4 FINAL
Engine Design:4-cycle, water cooled DIESEL, Ultra Low Sulfur Diesel, turbocharged, direct injection. Charged Air Cooled EGR
Tier 4 Engine Capability:SHALL be capable to perform "Passive Regen" on it's own with no operator at 40% - 50% load at full-rated speed.
SHALL have the capability to "Not Regen" at 80% - 90% load.
Engine Accessories:Fuel Filter
Lube Oil Filter
Intake Air Filter
Lube Oil Cooler
Fuel transfer pump
Fuel Priming Pump
Emergency Shut-off
Fuel/Water Separator
Water Pump
Oil Pump
Full flow lubrication oil filters
Pressure relief valve
Dipstick oil level indicator
Water Temperature & Lube Oil Pressure Gauge
BATTERYY = YES / N = NO
Battery Type:Sealed Gel Cell
Absorbed Glass Matt (AGM)
CONTROL PANELY = YES / N = NO
Control Panel, to Include (but not limited):Engine Analog Hour meter - 12volt or 24volt (unit depending)
Three position panel mounted switch (Stop-Manual-Auto)
Oil pressure gauge
Water temperature gauge
A/C output Amperage
Volt Meter
Frequency Meter
Fuel Gauge
Analog fuel pressure gauge
Battery Voltmeter
Phase selector switch with phase voltage & amperage
DPF cleaning cycle indication
Programmable remaining fuel (tank) level % indicator
Generator Output Bus Separate From Control Panel - Located in a Separate Lockable Panel:Yes
AC (Generator) & DC (Engine) Controls Enclosed in a Separate Box or Separated by Divider:Yes
COMPANY NAME:0
RATING INFORMATION
GENERATOR KW SIZE:0kW
SAFTEYY = YES / N = NO
Safety: Engine shutdown on:High water temperature
Low oil pressure
Over speed
Engine over crank
Low Coolant
Lowe DEF Level
FUELY = YES / N = NO
Fuel Tank: 24 hourUL 142 Double-wall w/ capacity sufficient - 24- hour tank
12 gauge steel body & two coat polyester power coat finish
Lifting points on base frame (two ea.: 4" x 10" x .250" fork pockets & rub spacers
Sheet steel components pre-treated w/ zinc phosphate
Fuel Valve:Yes, Parker H3 or H4 male and female quick disconnect & dust cap - sufficient enough to meet efficient fuel flow
Diesel Engine Fluid (DEF) Tank:Internal storage, EPA approved to provide fluid to operate at full rated load
WARRANTYY = YES / N = NO
Engine Warranty:Industry Standard Warranty
Generator Warranty:Industry Standard Warranty
Trailer: (if applicable)Not Applicable
OTHER REQUIREMENTSY = YES / N = NO
Unit Designed as a Portable Prime Power Unit (Not a Standby Unit Modified for Prime Power Use)Yes
Exhaust:Industrial Silencer/Muffler
Paralleling Capability (to include ALL BOM and required Cables):400kW & Above
Training:The vendor SHALL provide training opportunities for FEMA Mechanics on operational guidance with your equipment. Training is due once ALL units have been delievered to given location. Training shall occur AFTER the delivery of all units to given location; no later than 30 days after receipt of generators. Training date and time are TBD dependent on generator delivery timeline; to be agreed upon by the contractor and the Government. Training shall include how to switch/set the output voltages and phase configurations on the generator and voltage regulators.
Diagnostics/Software:The vendor SHALL provide any hardware and/or software, manuals or other documentation (in digital or hard copy), to include all diagnostic codes, that will enable FEMA Mechanics to perform all diagnostic's available for the generator(s)
Miscellaneous:Fabrication and permanent attachment of exterior metal spacers/rub-knuckles to facilitate side by side (rub free) transportation
Height Requirements for Air Transportation:Want to max transportation versatility - C17 load height limit 104"; C130 load height limit 96"
RFP: HSFE40-16-R-0004&F
&AMay 2016

Spec_200kW FEMA REQUIRED GENERATOR SPECIFICATIONS - JULY 2016 - Revised (RFP:HSFE20-16-Q-0029)

COMPANY NAME:0
DATE SUBMITTED12/31/99
GENERATOR KW SIZE:kW
RATING INFORMATION
Prime KW:200kW
FEMA Acceptable kW Min-Max Range:101kW - 200kW
Unit kVA (.8 power factor):0.8
GENERATOR SPECIFICATIONSY = YES / N = NO
EnclosureWeather Proof, stainless steel and sound attenuated
Phase:3 Phase
Switchable:The vendor SHALL provide any hardware and/or software, manuals, or other documentation (in digital or hard copy) that provide detailed directions which will allow FEMA mechanics to switch/set output voltages and phase configurations on the generator and voltage regulator
Voltage 3 Phase:208, 220, 240, 416, 440, 480V Switchable
Voltage 1 Phase:120, 127, 139, 240, 254, 277V Switchable
Generator RPM:1800
Frequency:60 HZ
No. Poles4
Excitation:Brushless with AVR
Frequency Regulation (Steady State):0.25%
Alternator Heat Rise:NTE 85°(F) with CLASS F insulation wire
Sound Level:NTE 75dB(A) full load @ 23 ft.
Trailer / Skid Mounted:SKID MOUNTED
Load Terminal CamLok Connectors:Yes
Integrally-mounted automated load bank system able to apply resistive load up to 40% during periods of low temperature/load conditions. SHALL have the capability to constantly monitor, sense and manage exhaust temperature with automatic shut-off for periods of high load conditions.Yes
ENGINEY = YES / N = NO
Emissions:Tier 4 FINAL
Engine Design:4-cycle, water cooled DIESEL, Ultra Low Sulfur Diesel, turbocharged, direct injection. Charged Air Cooled EGR
Tier 4 Engine Capability:SHALL be capable to perform "Passive Regen" on it's own with no operator at 40% - 50% load at full-rated speed.
SHALL have the capability to "Not Regen" at 80% - 90% load.
Engine Accessories:Fuel Filter
Lube Oil Filter
Intake Air Filter
Lube Oil Cooler
Fuel transfer pump
Fuel Priming Pump
Emergency Shut-off
Fuel/Water Separator
Water Pump
Oil Pump
Full flow lubrication oil filters
Pressure relief valve
Dipstick oil level indicator
Water Temperature & Lube Oil Pressure Gauge
BATTERYY = YES / N = NO
Battery Type:Sealed Gel Cell
Absorbed Glass Matt (AGM)
CONTROL PANELY = YES / N = NO
Control Panel, to Include (but not limited):Engine Analog Hour meter - 12volt or 24volt (unit depending)
Three position panel mounted switch (Stop-Manual-Auto)
Oil pressure gauge
Water temperature gauge
A/C output Amperage
Volt Meter
Frequency Meter
Fuel Gauge
analog fuel pressure gauge
Battery Voltmeter
Phase selector switch with phase voltage & amperage
DPF cleaning cycle indication
Programmable remaining fuel (tank) level % indicator
Generator Output Bus Separate From Control Panel - Located in a Separate Lockable Panel:Yes
AC (Generator) & DC (Engine) Controls Enclosed in a Separate Box or Separated by Divider:Yes
COMPANY NAME:0
RATING INFORMATION
GENERATOR KW SIZE:0kW
SAFTEYY = YES / N = NO
Safety: Engine shutdown on:High water temperature
Low oil pressure
Over speed
Engine over crank
Low Coolant
Lowe DEF Level
FUELY = YES / N = NO
Fuel Tank: 24 hourUL 142 Double-wall w/ capacity sufficient - 24- hour tank
12 gauge steel body & two coat polyester power coat finish
Lifting points on base frame (two ea.: 4" x 10" x .250" fork pockets & rub spacers
Sheet steel components pre-treated w/ zinc phosphate
Fuel Valve:Yes, Parker H3 or H4 male and female quick disconnect & dust cap - sufficient enough to meet efficient fuel flow
Diesel Engine Fluid (DEF) Tank:Internal storage, EPA approved to provide fluid to operate at full rated load
WARRANTYY = YES / N = NO
Engine Warranty:Industry Standard Warranty
Generator Warranty:Industry Standard Warranty
Trailer: (if applicable)Not Applicable
OTHER REQUIREMENTSY = YES / N = NO
Unit Designed as a Portable Prime Power Unit (Not a Standby Unit Modified for Prime Power Use)Yes
Exhaust:Industrial Silencer/Muffler
Paralleling Capability (to include ALL BOM and required Cables):400kW & Above
Training:The vendor SHALL provide training opportunities for FEMA Mechanics on operational guidance with your equipment. Training is due once ALL units have been delievered to given location. Training shall occur AFTER the delivery of all units to given location; no later than 30 days after receipt of generators. Training date and time are TBD dependent on generator delivery timeline; to be agreed upon by the contractor and the Government. Training shall include how to switch/set the output voltages and phase configurations on the generator and voltage regulators.
Diagnostics/Software:The vendor SHALL provide any hardware and/or software, manuals or other documentation (in digital or hard copy), to include all diagnostic codes, that will enable FEMA Mechanics to perform all diagnostic's available for the generator(s)
Miscellaneous:Fabrication and permanent attachment of exterior metal spacers/rub-knuckles to facilitate side by side (rub free) transportation
Height Requirements for Air Transportation:Want to max transportation versatility - C17 load height limit 104"; C130 load height limit 96"
RFP: HSFE20-16-Q-0029&F
&AJuly 2016

Spec_400kW FEMA REQUIRED GENERATOR SPECIFICATIONS - JULY 2016 - Revised (HSFE20-16-Q-0029)

COMPANY NAME:0
DATE SUBMITTED12/31/99
GENERATOR KW SIZE:kW
RATING INFORMATION
Prime KW:400kW
FEMA Acceptable kW Min-Max Range:201kW - 400kW
Unit kVA (.8 power factor):0.8
GENERATOR SPECIFICATIONSY = YES / N = NO
EnclosureWeather Proof, stainless steel and sound attenuated
Phase:3 Phase
Switchable:The vendor SHALL provide any hardware and/or software, manuals, or other documentation (in digital or hard copy) that provide detailed directions which will allow FEMA mechanics to switch/set output voltages and phase configurations on the generator and voltage regulator
Voltage 3 Phase:208, 220, 240, 416, 440, 480V Switchable
Voltage 1 Phase:120, 127, 139, 240, 254, 277V Switchable
Generator RPM:1800
Frequency:60 HZ
No. Poles4
Excitation:Brushless with AVR
Frequency Regulation (Steady State):0.25%
Alternator Heat Rise:NTE 85°(F) with CLASS F insulation wire
Sound Level:NTE 75dB(A) full load @ 23 ft.
Trailer / Skid MountedSKID MOUNTED
Load Terminal CamLok Connectors:Yes
Integrally-mounted automated load bank system able to apply resistive load up to 40% during periods of low temperature/load conditions. SHALL have the capability to constantly monitor, sense and manage exhaust temperature with automatic shut-off for periods of high load conditions.Yes
ENGINEY = YES / N = NO
Emissions:Tier 4 FINAL
Engine Design:4-cycle, water cooled DIESEL, Ultra Low Sulfur Diesel, turbocharged, direct injection. Charged Air Cooled EGR
Tier 4 Engine Capability:SHALL be capable to perform "Passive Regen" on it's own with no operator at 40% - 50% load at full-rated speed.
SHALL have the capability to "Not Regen" at 80% - 90% load.
Engine Accessories:Fuel Filter
Lube Oil Filter
Intake Air Filter
Lube Oil Cooler
Fuel transfer pump
Fuel Priming Pump
Emergency Shut-off
Fuel/Water Separator
Water Pump
Oil Pump
Full flow lubrication oil filters
Pressure relief valve
Dipstick oil level indicator
Water Temperature & Lube Oil Pressure Gauge
BATTERYY = YES / N = NO
Battery Type:Sealed Gel Cell
Absorbed Glass Matt (AGM)
CONTROL PANELY = YES / N = NO
Control Panel, to Include (but not limited):Engine Analog Hour meter - 12volt or 24volt (unit depending)
Three position panel mounted switch (Stop-Manual-Auto)
Oil pressure gauge
Water temperature gauge
A/C output Amperage
Volt Meter
Frequency Meter
Fuel Gauge
Analog fuel pressure gauge
Battery Voltmeter
Phase selector switch with phase voltage & amperage
DPF cleaning cycle indication
Programmable remaining fuel (tank) level % indicator
Generator Output Bus Separate From Control Panel - Located in a Separate Lockable Panel:Yes
AC (Generator) & DC (Engine) Controls Enclosed in a Separate Box or Separated by Divider:Yes
COMPANY NAME:0
RATING INFORMATION
GENERATOR KW SIZE:0kW
SAFTEYY = YES / N = NO
Safety: Engine shutdown on:High water temperature
Low oil pressure
Over speed
Engine over crank
Low Coolant
Lowe DEF Level
FUELY = YES / N = NO
Fuel Tank: 24 hourUL 142 Double-wall w/ capacity sufficient - 24- hour tank
12 gauge steel body & two coat polyester power coat finish
Lifting points on base frame (two ea.: 4" x 10" x .250" fork pockets & rub spacers
Sheet steel components pre-treated w/ zinc phosphate
Fuel Valve:Yes, Parker H3 or H4 male and female quick disconnect & dust cap - sufficient enough to meet efficient fuel flow
Diesel Engine Fluid (DEF) Tank:Internal storage, EPA approved to provide fluid to operate at full rated load
WARRANTYY = YES / N = NO
Engine Warranty:Industry Standard Warranty
Generator Warranty:Industry Standard Warranty
Trailer: (if applicable)Not Applicable
OTHER REQUIREMENTSY = YES / N = NO
Unit Designed as a Portable Prime Power Unit (Not a Standby Unit Modified for Prime Power Use)Yes
Exhaust:Industrial Silencer/Muffler
Paralleling Capability (to include ALL BOM and required Cables):400kW & Above
Training:The vendor SHALL provide training opportunities for FEMA Mechanics on operational guidance with your equipment. Training is due once ALL units have been delievered to given location. Training shall occur AFTER the delivery of all units to given location; no later than 30 days after receipt of generators. Training date and time are TBD dependent on generator delivery timeline; to be agreed upon by the contractor and the Government. Training shall include how to switch/set the output voltages and phase configurations on the generator and voltage regulators.
Diagnostics/Software:The vendor SHALL provide any hardware and/or software, manuals or other documentation (in digital or hard copy), to include all diagnostic codes, that will enable FEMA Mechanics to perform all diagnostic's available for the generator(s)
Miscellaneous:Fabrication and permanent attachment of exterior metal spacers/rub-knuckles to facilitate side by side (rub free) transportation
Height Requirements for Air Transportation:Want to max transportation versatility - C17 load height limit 104"; C130 load height limit 96"
RFP: HSFE20-16-Q-0029&F
&AJuly 2016

SUMMARY

FEMA REQUIRED GENERATOR SPECIFICATIONS - JULY 2016 - Revised (RFP:HSFE20-16-Q-0029)

COMPANY NAME:0
DATE SUBMITTED:12/31/99
RATING INFORMATION50kW100kW200kW400kW
Prime KW:Prime kW Rating and Range identification on individual spec sheets0000
FEMA Acceptable kW Min-Max Range:No AnswerNo AnswerNo AnswerNo Answer
Unit kVA (.8 power factor):0.8
GENERATOR SPECIFICATIONS
Enclosure:Weather Proof, stainless steel and sound attenuatedNo AnswerNo AnswerNo AnswerNo Answer
Phase:3 PhaseNo AnswerNo AnswerNo AnswerNo Answer
Switchable:The vendor SHALL provide any hardware and/or software, manuals, or other documentation (in digital or hard copy) that provide detailed directions which will allow FEMA mechanics to switch/set output voltages and phase configurations on the generator and voltage regulatorNo AnswerNo AnswerNo AnswerNo Answer
Voltage 3 Phase:208, 220, 240, 416, 440, 480V SwitchableNo AnswerNo AnswerNo AnswerNo Answer
Voltage 1 Phase:120, 127, 139, 240, 254, 277V SwitchableNo AnswerNo AnswerNo AnswerNo Answer
Generator RPM:1800No AnswerNo AnswerNo AnswerNo Answer
Frequency:60 HZNo AnswerNo AnswerNo AnswerNo Answer
No. Poles4No AnswerNo AnswerNo AnswerNo Answer
Excitation:Brushless with AVRNo AnswerNo AnswerNo AnswerNo Answer
Frequency Regulation (Steady State):0.25%No AnswerNo AnswerNo AnswerNo Answer
Alternator Heat Rise:NTE 85°(F) with CLASS H insulation wire / CLASS F insulation wire 100kW >No AnswerNo AnswerNo AnswerNo Answer
Sound Level:NTE 75dB(A) full load @ 23 ft.No AnswerNo AnswerNo AnswerNo Answer
Trailer / Skid MountedSKID MOUNTEDNo AnswerNo AnswerNo AnswerNo Answer
Load Terminal CamLok Connectors:YESNo AnswerNo AnswerNo AnswerNo Answer
Integrally-mounted automated load bank system able to apply resistive load up to 40% during periods of low temperature/load conditions. SHALL have the capability to constantly monitor, sense and manage exhaust temperature with automatic shut-off for periods of high load conditions.YESNo AnswerNo AnswerNo AnswerNo Answer
ENGINE
Emissions:Tier 4 FINALNo AnswerNo AnswerNo AnswerNo Answer
Engine Design:4-cycle, water cooled DIESEL, Ultra Low Sulfur Diesel turbocharged, direct injection. Charged Air Cooled EGRNo AnswerNo AnswerNo AnswerNo Answer
Tier 4 Engine Capability:SHALL be capable to perform "Passive Regen" on it's own with no operator at 40% - 50% load at full-rated speed.No AnswerNo AnswerNo AnswerNo Answer
SHALL have the capability to "Not Regen" at 80% - 90% load.No AnswerNo AnswerNo AnswerNo Answer
Engine Accessories:Fuel FilterNo AnswerNo AnswerNo AnswerNo Answer
Lube Oil FilterNo AnswerNo AnswerNo AnswerNo Answer
Intake Air FilterNo AnswerNo AnswerNo AnswerNo Answer
Lube Oil CoolerNo AnswerNo AnswerNo AnswerNo Answer
Fuel transfer pumpNo AnswerNo AnswerNo AnswerNo Answer
Fuel Priming PumpNo AnswerNo AnswerNo AnswerNo Answer
Emergency Shut-offNo AnswerNo AnswerNo AnswerNo Answer
Fuel/Water SeparatorNo AnswerNo AnswerNo AnswerNo Answer
Water PumpNo AnswerNo AnswerNo AnswerNo Answer
Oil PumpNo AnswerNo AnswerNo AnswerNo Answer
Full flow lubrication oil filtersNo AnswerNo AnswerNo AnswerNo Answer
Pressure relief valveNo AnswerNo AnswerNo AnswerNo Answer
Dipstick oil level indicatorNo AnswerNo AnswerNo AnswerNo Answer
Water Temperature & Lube Oil Pressure GaugeNo AnswerNo AnswerNo AnswerNo Answer
BATTERY
Battery Type:Sealed Gel CellNo AnswerNo AnswerNo AnswerNo Answer
Absorbed Glass Matt (AGM)No AnswerNo AnswerNo AnswerNo Answer
CONTROL PANEL
Control Panel, to Include (but not limited):Engine Analog Hour meter - 12volt or 24volt (unit depending)No AnswerNo AnswerNo AnswerNo Answer
Oil pressure gaugeNo AnswerNo AnswerNo AnswerNo Answer
Water temperature gaugeNo AnswerNo AnswerNo AnswerNo Answer
A/C output AmperageNo AnswerNo AnswerNo AnswerNo Answer
Volt MeterNo AnswerNo AnswerNo AnswerNo Answer
Frequency MeterNo AnswerNo AnswerNo AnswerNo Answer
Fuel GaugeNo AnswerNo AnswerNo AnswerNo Answer
Analog fuel pressure gaugeNo AnswerNo AnswerNo AnswerNo Answer
Battery VoltmeterNo AnswerNo AnswerNo AnswerNo Answer
Phase selector switch with phase voltage & amperageNo AnswerNo AnswerNo AnswerNo Answer
DPF cleaning cycle indicationNo AnswerNo AnswerNo AnswerNo Answer
Programmable remaining fuel (tank) level % indicatorNo AnswerNo AnswerNo AnswerNo Answer
Generator Output Bus Separate From Control Panel - Located in a Separate Lockable Panel:YesNo AnswerNo AnswerNo AnswerNo Answer
AC (Generator) & DC (Engine) Controls Enclosed in a Separate Box or Separated by Divider:YesNo AnswerNo AnswerNo AnswerNo Answer
SAFTEY
Safety: Engine shutdown on:High water temperatureNo AnswerNo AnswerNo AnswerNo Answer
Low oil pressureNo AnswerNo AnswerNo AnswerNo Answer
Over speedNo AnswerNo AnswerNo AnswerNo Answer
Engine over crankNo AnswerNo AnswerNo AnswerNo Answer
Low CoolantNo AnswerNo AnswerNo AnswerNo Answer
Low DEF LevelNo AnswerNo AnswerNo AnswerNo Answer
FUEL
Fuel Tank: 24 hourUL 142 Double-wall w/ capacity sufficient - 24- hour tankNo AnswerNo AnswerNo AnswerNo Answer
12 gauge steel body & two coat polyester power coat finishNo AnswerNo AnswerNo AnswerNo Answer
Lifting points on base frame (two ea.: 4" x 10" x .250" fork pockets & rub spacersNo AnswerNo AnswerNo AnswerNo Answer
Sheet steel components pre-treated w/ zinc phosphateNo AnswerNo AnswerNo AnswerNo Answer
Fuel Valve:Yes, Parker H3 or H4 male and female quick disconnect & dust cap - sufficient enough to meet efficient fuel flowNo AnswerNo AnswerNo AnswerNo Answer
Diesel Engine Fluid (DEF) Tank:Internal storage, EPA approved to provide fluid to operate at full rated loadNo AnswerNo AnswerNo AnswerNo Answer
WARRANTY
Engine Warranty:Industry Standard WarrantyNo AnswerNo AnswerNo AnswerNo Answer
Generator Warranty:Industry Standard WarrantyNo AnswerNo AnswerNo AnswerNo Answer
Trailer: (if applicable)Not ApplicableNo AnswerNo AnswerNo AnswerNo Answer
OTHER REQUIREMENTS
Unit Designed as a Portable Prime Power Unit (Not a Standby Unit Modified for Prime Power Use)YesNo AnswerNo AnswerNo AnswerNo Answer
Exhaust:Industrial Silencer/MufflerNo AnswerNo AnswerNo AnswerNo Answer
Paralleling Capability (to include ALL BOM and required Cables):400kW & AboveNo AnswerNo AnswerNo AnswerNo Answer
Training:The vendor SHALL provide training opportunities for FEMA Mechanics on operational guidance with your equipment. Training is due once ALL units have been delievered to given location. Training shall occur AFTER the delivery of all units to given location; no later than 30 days after receipt of generators. Training date and time are TBD dependent on generator delivery timeline; to be agreed upon by the contractor and the Government. Training shall include how to switch/set the output voltages and phase configurations on the generator and voltage regulators.No AnswerNo AnswerNo AnswerNo Answer
Diagnostics/Software:The vendor SHALL provide any hardware and/or software, manuals or other documentation (in digital or hard copy), to include all diagnostic codes, that will enable FEMA Mechanics to perform all diagnostic's available for the generator(s)No AnswerNo AnswerNo AnswerNo Answer
Miscellaneous:Fabrication and permanent attachment of exterior metal spacers/rub-knuckles to facilitate side by side (rub free) transportationNo AnswerNo AnswerNo AnswerNo Answer
Height Requirements for Air Transportation:Want to max transportation versatility - C17 load height limit 104"; C130 load height limit 96"No AnswerNo AnswerNo AnswerNo Answer