| FEMA Specification | ||
| Prime kW | kW | 36 |
| Standby kW | kW | 40 |
| Voltage Selection | 3 Position Selector Switch | |
| Voltage 3 Phase | 208, 220, 240, 416, 440, 480V Switchable | |
| Voltage 1 Phase | 120, 127, 139, 240, 254, 277V Switchable | |
| Armature Connection | Star w/Neutral / Zig Zag | |
| Alternator Manufacturer | Denyo | |
| Heat Rise at 40 Degrees Celsius | 85C | |
| Insulation Class | Class H | |
| Excitation Method | Open Delta | |
| Voltage Regulation (No load to full load) | 0.50% | |
| Frequency | 60 HZ | |
| Frequency Regulation (Steady State) | 0.25% | |
| Electronic Governor | Yes | |
| Auto Start/Stop ECU | Yes | |
| Amps-120V Single Phase | 108 X 2 | |
| Amps-240V Single Phase | 108 | |
| Amps-240V Three Phase | 108 | |
| Amps-480V Three Phase | 54 | |
| Control Panel | Analog | |
| Courtesy Panel - Single Phase | Yes | |
| 120V Single Phase GFCI Receptacles | 2 | |
| 120/240V Single Phase Twist Lock Receptacles | 3 | |
| Generator Output Bus Separate From Control Panel - Located in a Separate Lockable Panel | Yes | |
| AC (Generator) & DC (Engine) Controls Enclosed in a Separate Box or Separated by Divider | Yes | |
| Unit Designed as a Portable Prime Power Unit (Not a Standby Unit Modified for Prime Power Use) | Yes | |
| Diesel Engine Manufacturer | ||
| Engine Model | ||
| Number of Cylinders | ||
| EPA Certification Rating | Interim Tier 4 | |
| Water Separator Filter w/Drain Plug | Yes | |
| Air Filter | Single Stage | |
| UL 142 Double Wall Sub Base Fuel Tank - 24 Hour Run Time w/Leak Sensor, Low Fuel Level Switch, 6" x 10" x .250" Fork Pockets & Rub Spacers | GAL | 80 |
| Fuel Consumption @ Full Load | GPH | 2.8 |
| Fuel Consumption @ 3/4 Load | GPH | 2.1 |
| Fuel Consumption @ 1/2 Load | GPH | 1.5 |
| Idle Switch | Yes | |
| 3 Way Fuel Valve w/External Connections | Yes | |
| Parker H-3 Male Quick Disconnect & Dust Cap | Yes | |
| Parker H-3 Female Quick Disconnect & Dust Cap | Yes | |
| Gel Battery | Yes | |
| Sound Level @ 23 Feet | dB(A) | 65 |
| Enclosure Hardware - Stainless Steel | Yes | |
| Paint Type | Powder Coat | |
| Color | White | |
| Dimensions - L x W x H | IN | 76 x 35.5 x 70 |
| Weight - Dry | LBS | 3157 |
| Generator Warranty | 2year/2000 hrs | |
| Engine Warranty | 1st Year Unlimited/2nd Year 2000 Hours |
Criteria_2015
| FEMA Generator Specification | |
| ALTERNATOR | |
| Voltage Selection (20kW - 120kW) | 3 Position Selector Switch |
| Voltage Selection (144kW - 640kW) | Reconnectable Buss Bar (No substitution) |
| Voltage 3 Phase | 208, 220, 240, 416, 440, 480V Switchable |
| Voltage 1 Phase | 120, 127, 139, 240, 254, 277V Switchable |
| Frequency | 60 HZ |
| Frequency Regulation (Steady State) | 0.25% |
| Voltage Regulation (No load to full load) | 0.50% |
| Excitation Method | Open Delta |
| Heat Rise at 40 Degrees Celsius | not to exceed 90 degrees Celsius |
| ENGINE | |
| Engine | Water Cooled, turbo charged (where applicable) |
| Four Cycle | |
| No. 2 Disel Fuel | |
| Speed: 1,800rpm | |
| Engine Accessories | Fuel Filter |
| Lube Oil Filter | |
| Intake Air Filter | |
| Lube Oil Cooler | |
| Fuel transfer pump | |
| Fuel Priming Pump | |
| Automatic Elec. Shut off | |
| Fuel/Water Separator | |
| Water Pump | |
| Oil Pump | |
| Full flow lubrication oil filters | |
| Pressure relief valve | |
| Dipstick oil level indicator | |
| Water Temperature & Lube Oil Pressure Gauge | |
| Auto Start/Stop ECU (REQUIRED on >36kW) | Yes |
| Electronic Governor | Yes: Isochroneous; maintain engine speed within .25%, steady state; and .5% no load to full load |
| CONTROL PANEL | |
| Control Panel, to Include (but not limited) | Analog |
| Engine running time meter | |
| Oil pressure gauge | |
| Water temperature gauge | |
| A/C output Amperage | |
| Frequency Meter | |
| Fuel Gauge | |
| Battery Voltmeter | |
| Generator Output Bus Separate From Control Panel - Located in a Separate Lockable Panel | Yes |
| AC (Generator) & DC (Engine) Controls Enclosed in a Separate Box or Separated by Divider | Yes |
| SAFTEY | |
| Saftey: Engine shutdown on: | High water temperature |
| Low oil pressure | |
| Over speed | |
| Engine over crank | |
| low fuel | |
| COURTESY PANEL | |
| Courtesy Panel - Single Phase | Yes |
| 120V Single Phase GFCI Receptacles | 2 |
| 120/240V Single Phase Twist Lock Receptacles | 3 |
| FILTERS | |
| Water Separator Filter w/Drain Plug | Yes |
| Air Filter (20kW - 56kW) | Single Stage |
| Air Filter (>56kW) | Two Stage |
| FUEL | |
| Fuel Tank | UL 142 Double-wall w/ capacity sufficient - 24hr Run time under maximum load |
| 12 guage steel body & two coat polyester power coat finish | |
| Lifting points on base frame (two ea: 6" x 10" x .250" fork pockets & rub spacers | |
| Stainless steel flush-fitting latches and hinges | |
| Sheet steel components pre-treated w/ zinc phosphate | |
| lockable wide door on each side (allow 180 degree rotation) | |
| Lube Oil and coolant drains piped to exterior of enclosure skid base | |
| Sound attenuation components shall limit noise; NTE (74dB average @ 7 meters (23 feet)) | |
| Leak sensor & low fuel level engine cutoff switch | |
| Fuel Tank Capacity | 80 Gallons |
| 3 Way Fuel Valve w/External Connections | Yes |
| Fuel Valve: 20kW - 56kW | Yes, Parker H3 male and female quick disconnect & dust cap |
| Fuel Valve: >56kW | Yes, Parker H4 male and female quick disconnect & dust cap |
| Fuel Consumption @ Full Load | 2.8 GPH |
| Fuel Consumption @ 3/4 Load | 2.1 GPH |
| Fuel Consumption @ 1/2 Load | 1.5 GPH |
| BATTERY | |
| Battery Type | Sealed Gel Cell |
| Quick Disconnects | YES |
| WARRANTY | |
| Generator Warranty | 2year/2000 hrs |
| Engine Warranty (20kW - 200kW) | 1st Year Unlimited/2nd Year 2000 Hours |
| Engine Warranty (240kW) | 1 year Unlimited hours |
| Engine Warranty (320kW) | 1st Year Unlimited/2nd Year 2000 Hours |
| Engine Warranty (480kW) | 2 years unlimited hours |
| Engine Warranty (640kW) | 1 year or 1000 hours |
| OTHER REQUIREMENTS | |
| Unit Designed as a Portable Prime Power Unit (Not a Standby Unit Modified for Prime Power Use) | Yes |
| NEED CLARIFICATION | |
| Number of Cylinders | |
| EPA Certification Rating | |
| Idle Switch | |
| Paint Type | |
| Color | |
| Amps-120V Single Phase | |
| Amps-240V Single Phase | |
| Amps-240V Three Phase | |
| Amps-480V Three Phase | |
| Armature Connection | |
| Alternator Manufacturer | |
| Insulation Class | |
| Dimensions - L x W x H | |
| Weight - Dry |
Dims 2015
| KW (Prime) Rating | Cube | WT |
| 15 | 67x26x39 | 1,574 |
| 67X26X40 | ||
| 72x30x44 | 1,537 | |
| 16 | 44X30X65 | 1,500 |
| 108X52X65 | 1,855 | |
| 1,820 | ||
| 1,850 | ||
| 17 | 67x34x57 | 1,372 |
| 76x40x47 | 2,650 | |
| 19.2 | 67X29X46 | 1,653 |
| 20 | 21"X79"X40" | 5,500 |
| 30"X36.5"X43.5" | 1,717 | |
| 32"X71.5"X42.5" | 1,823 | |
| 44X30X65 | 1,500 | |
| 44X97X60 | 3,600 | |
| 70.5X30X53 | 1,844 | |
| 72x30x44 | 1,537 | |
| 72X30X46 | 1840 | |
| 72x31x43 | 1,823 | |
| 73X30X40 | 1,844 | |
| 74x38x55 | 2,050 | |
| 2,065 | ||
| 75X38X52 | 2,000 | |
| 76x30x49 | 1,717 | |
| 1,840 | ||
| 88x35x47 | 3,000 | |
| 21.6 | 44X30X65 | 1,500 |
| 25 | 76X67X34 | 2,906 |
| 82X29.5X73 | 1,620 | |
| 82x36x49 | 2,136 | |
| 83x42x72 | 3,040 | |
| 84x36x63 | 2,346 | |
| 27 | 82x36x66 | 2,226 |
| 83x38x65 | 2,249 | |
| 30 | 87x40x80 | 3,060 |
| 87x40x90 | 3,300 | |
| 32 | 37"X78"50" | 3,500 |
| 35 | 36.5"X81.5"X50" | 2,900 |
| 41"X85"X74" | 3,150 | |
| 58x38x67 | 1,760 | |
| 82X31.5X72 | 3,200 | |
| 82x36x52 | 2,212 | |
| 83x40x82 | 3,150 | |
| 83x40x88 | ||
| 83x44x83 | 3,130 | |
| 85X42X79 | 3,165 | |
| 3,125 | ||
| 3,155 | ||
| 3,110 | ||
| 3,135 | ||
| 35 | 80X38X64 | 3,300 |
| 3,265 | ||
| 3,280 | ||
| 3,305 | ||
| 3,285 | ||
| 3,260 | ||
| 3,295 | ||
| 3,215 | ||
| 3,270 | ||
| 42"X112"X53" | 3,000 | |
| 83X35.5X68.5 | 3,024 | |
| 88x37x65 | 3,000 | |
| 2,940 | ||
| 3,024 | ||
| 2,940 | ||
| 90x42x76 | 2,640 | |
| 38 | 39"X86"X55" | 3,300 |
| 85x38x59 | 2,700 | |
| 2,679 | ||
| 40 | 72X80X34 | 2,781 |
| 89x40x89 | 3,410 | |
| 89x44x68 | 2,700 | |
| 97x36x78 | 3,661 | |
| 45 | 101x38x58 | 3,350 |
| 45 | 40.5"X100.5"X55 | 3,700 |
| 48 | 109x44x55 | 4,400 |
| 2,783 | ||
| 40"X97"X50" | 4,000 | |
| 50 | 80x33x76 | 2,781 |
| 80x33x82 | 3,005 | |
| 3,261 | ||
| 89x44x80 | 3,910 | |
| 96x36x78 | 3,974 | |
| 54 | 88x49x67 | 3,685 |
| 99x46x65 | 3,350 | |
| 56 | 109X49X71 | 6,200 |
| 109X49X71.5 | 4,180 | |
| 182x82x88 | 6,200 | |
| 75X37X124 | 5,002 | |
| 97X38X69 | 4,285 | |
| 4,220 | ||
| 4,135 | ||
| 4,165 | ||
| 4,255 | ||
| 4,240 | ||
| 4,260 | ||
| 4,245 | ||
| 4,280 | ||
| 4,215 | ||
| 4,200 | ||
| 59 | 90x39x75 | 4,607 |
| 60 | 102x49x67 | 4,150 |
| 110X44.5X63 | 4,360 | |
| 124x49x66 | 5,250 | |
| 37"X96.5"X64.5" | 3,600 | |
| 72X80X33 | 2,800 | |
| 83x44x92 | 3,268 | |
| 85x35x67 | 3,041 | |
| 2,700 | ||
| 3,041 | ||
| 85x35x68 | 2,752 | |
| 89x40x89 | 3,630 | |
| 89x43x68 | 2,912 | |
| 89x44x68 | 2,997 | |
| 92x36x75 | 3,975 | |
| 96x36x68 | 3,600 | |
| 62 | 82X29X73 | 2,840 |
| 82X29X77.5 | 3,700 | |
| 82X31.5X73 | 2,840 | |
| 82X31.5X77.5 | 3,700 | |
| 65 | 101x39x55 | 3,800 |
| 147x62x85 | 3,848 | |
| 66 | 124X49X63 | 4,780 |
| 67 | 90x40x66 | 2,500 |
| 67.3 | 90X40X66 | 6,780 |
| 68 | 118x44x59 | 5,200 |
| 124x49x63 | 5,600 | |
| 46"119X60" | 5,200 | |
| 72 | 89x43x63 | 3,500 |
| 80 | 104.5X40X82 | 4,250 |
| 105x40x80 | 4,108 | |
| 106x44x81 | 4,380 | |
| 120X55X43 | 4,675 | |
| 143x54x71 | 5,800 | |
| 4,250 | ||
| 42"X106"X75.5" | 4,108 | |
| 44"X106"X70" | 4,108 | |
| 160X43X77 | 4,135 | |
| 4,145 | ||
| 4,105 | ||
| 4,095 | ||
| 90 | 51"X132"X73 | 7,200 |
| 91 | 100x43x70 | 4,065 |
| 100x43x74 | 4,065 | |
| 94 | 122x40x67 | 5,200 |
| 95 | 112x44x67 | 5,500 |
| 96 | 100x40x70 | 5,676 |
| 5,626 | ||
| 5,786 | ||
| 5,757 | ||
| 7,381 | ||
| 100x40x77 | 7,630 | |
| 101x49x68 | 4,650 | |
| 122x40x67 | 5,200 | |
| 100 | 101x39x55 | 3,800 |
| 105.5X31X87 | 4,000 | |
| 110x42x66 | 6,780 | |
| 116x43x77 | 5,000 | |
| 167x42x94 | 7,630 | |
| 94x36x67 | 3,457 | |
| 94x36x84 | 7,630 | |
| 96X29.5X99 | 4,080 | |
| 125X46X69 | 6,195 | |
| 6,245 | ||
| 6,135 | ||
| 6,065 | ||
| 6,120 | ||
| 6,085 | ||
| 6,060 | ||
| 6,125 | ||
| 6,175 | ||
| 104 | 102x45x79 | 7,630 |
| 106 | 128x43x72 | 6,780 |
| 107 | 180x69x94 | 5,600 |
| 114 | 138x45x72 | 5,786 |
| 5,626 | ||
| 116 | 138x45x81 | 7,381 |
| 7,630 | ||
| 120 | 114x39x84 | 8,117 |
| 131x48x73 | ||
| 6,690 | ||
| 125 | 105x40x89 | 5,500 |
| 105x40x96 | 5,100 | |
| 106x45x95 | 5,540 | |
| 114x39x84 | 5,400 | |
| 116x44x92 | 5,120 | |
| 120x48x71 | 5,400 | |
| 132x48x72 | 5,500 | |
| 138x45x70 | 7,630 | |
| 144X40X92 | 4,850 | |
| 180x69x94 | 5,600 | |
| 42"X106"X70" | 4,338 | |
| 42"X106"X89" | 4,388 | |
| 50"X119.5"70.5" | 5,400 | |
| 137X50X75 | 7,205 | |
| 7,075 | ||
| 7,030 | ||
| 7,190 | ||
| 7,170 | ||
| 106X42X95 | 5,385 | |
| 5,355 | ||
| 128 | 132x50x76 | 5,800 |
| 134 | 140x51x72 | 6,780 |
| 140 | 118x42x77 | 5,500 |
| 144 | 139x47x89 | 7,020 |
| 148 | 129x51x80 | 7,230 |
| 155x56x100 | 8,250 | |
| 150 | 101x51x154 | 7,500 |
| 150 | 103x40x94 | 8,350 |
| 150 | 167x42x94 | 7,630 |
| 112X53X111 | 5,675 | |
| 5,735 | ||
| 159 | 138x44x108 | 7,330 |
| 138x45x70 | 5,139 | |
| 160 | 128x44x77 | 5,100 |
| 7,350 | ||
| 172 | 153X57X89 | 5,359 |
| 173 | 138x44x77 | 4,600 |
| 153x57x89 | ||
| 175 | 128x44x77 | 5,600 |
| 153X57X89 | 5,359 | |
| 176 | 153x57x89 | 9,500 |
| 180 | 153x57x89 | 10,080 |
| 180 | 167x42x94 | 7,740 |
| 169X52X93 | 10,080 | |
| 200 | 130x51x103 | 10,080 |
| 131x56x100 | 7,450 | |
| 156x51x86 | 6,100 | |
| 6,204 | ||
| 208 | 158X52X85 | 15,455 |
| 214 | 128X44X77 | 10,500 |
| 230 | 176x56x96 | 7,200 |
| 240 | 148x55x76 | 9,520 |
| 57"X148"X77" | 6,500 | |
| 159X57X88 | 12,790 | |
| 12,520 | ||
| 12,505 | ||
| 12,525 | ||
| 12,430 | ||
| 12,465 | ||
| 250 | 158x52x85 | 6,900 |
| 55"X157.5"X83 | ||
| 260 | 209X61X110 | 13,690 |
| 264 | 157x42x82 | 7,300 |
| 270 | 209X61X110 | 16,537 |
| 216x69x100 | 18,000 | |
| 275 | 134X50X98 | 8,700 |
| 153x57x89 | 9,800 | |
| 280 | 157x45x84 | 15,455 |
| 160x54x100 | 8,500 | |
| 300 | 118x42x77 | 5,500 |
| 159x80x133 | 15,455 | |
| 193x60x110 | 8,260 | |
| 305 | 636x96x158 | 15,455 |
| 320 | 165.35x55.11x82.68 | 9,414 |
| 166x60x88 | 12,750 | |
| 181.10X55.12X82.68 | 14,080 | |
| 166X57X88 | 12,630 | |
| 12,580 | ||
| 171X57X98 | 15,120 | |
| 15,300 | ||
| 15,320 | ||
| 15,140 | ||
| 350 | 142x50x87 | 9,960 |
| 142x52.5x89 | 12,271 | |
| 143x55x89 | 9,700 | |
| 178X60X103 | 16,725 | |
| 365 | 178X60X103 | 16,725 |
| 209x61x110 | 14,542 | |
| 23,610 | ||
| 400 | 156X160X97 | 12,280 |
| 156X60X101 | 13,700 | |
| 157x66x102 | 12,340 | |
| 334x94x153 | 30,320 | |
| 96"X239"X102 | 14,000 | |
| 436 | 198x59x107 | 4,650 |
| 450 | 168x67x117 | 14,380 |
| 168x70x125 | 14,730 | |
| 1,500 | ||
| 455 | 161x62x105 | 12,030 |
| 168x70x120 | 15,100 | |
| 168x70x125 | 13,430 | |
| 238X97X148 | 17,500 | |
| 458 | 200X61X106 | 16,314 |
| 480 | 220x65x111 | 22,709 |
| 222x70x100 | 21,440 | |
| 67"X219"X102" | 22,700 | |
| 227X68X112 | 24,550 | |
| 24,380 | ||
| 24,930 | ||
| 500 | 151x69x96 | 13,040 |
| 156x60x108 | 13,553 | |
| 157X60X93.5 | 14,500 | |
| 159x65x104 | 12,030 | |
| 159x69x96 | 11,400 | |
| 205X65X110 | 13,040 | |
| 335X102X156 | 17,000 | |
| 338x101x158 | 42,320 | |
| 539X96X157 | 28,500 | |
| 96"X239"X102 | 14,000 | |
| 528 | 389x102x128 | 48,680 |
| 600 | 240x108x112 | 35,090 |
| 25,090 | ||
| 360x108x155 | 26,640 | |
| 640 | 241x77x115 | 28,992 |
| 244X82X116 | 30,525 | |
| 30,545 | ||
| 704 | 416x102x135 | 49,500 |
| 725 | 372x108x155 | 36,800 |
| 725 | 57,200 | |
| 800 | 504x108x155 | 38,920 |
| 800 | 45,160 | |
| 800 | 96"X239"X102 | 14,000 |
| 1250 | 489x96x158 | 55,136 |
| 1500 | 489x96x114 | 46,900 |
| 1825 | 504X108X155 | 80,000 |
| 1825 | 73,620 |
Criteria_200kW 2015 (2)
| FEMA Generator Specification - 200kW (101-200kW) | |||
| RATING INFORMATION | NOTES FROM FLEET: | NOTES FROM USACE (TAKEN FROM ORGINAL DOCUMENT 5/27/15) | |
| Prime KW | 176kW | Is it assumed 0.8 pf for these machines? | |
| Standby kW | 194kW | ||
| Unit kVA (.8 power factor) | 242kVA | ||
| ALTERNATOR | |||
| Voltage Selection (144kW - 640kW) | Reconnectable Buss Bar (No substitution) | Is it assumed 0.8 pf for these machines? SEE ABOVE | |
| Voltage 3 Phase | 208, 220, 240, 416, 440, 480V Switchable | Where are these requirements coming from? Are 50Hz voltages required in FEMA's area of responsibility? | |
| Voltage 1 Phase | 120, 127, 139, 240, 254, 277V Switchable | All the listed requirements imply WYE connections and appear to exclude DELTA configurations. | |
| Frequency | 60 HZ | See above. | |
| Frequency Regulation (Steady State) | 0.25% | ||
| Voltage Regulation (No load to full load) | 0.50% | ||
| Excitation Method | Open Delta | We are not concerned how the manufacturer accomplishes this. | |
| Heat Rise at 40 Degrees Celsius | 85 degree celsius | Is this MQ Specific- if so - do not include | Does the temporary emergency power mission require this level of insulation? It seems that Class H with 125 degree C Temp rise would be fine. |
| Disconnect/Circuit Breaker | does not exceed 75 degree celsius termination rating | 249th Requested that this be added in as a requirement | |
| Sound Level | 75dB(A) full load @ 23 ft | ||
| Armature Connection | Star w/ Neutral | ||
| Alternator Manufacturer | Denyo | Is this MQ Specific- if so - do not include | |
| Insulation Class | Class F | ||
| ENGINE | |||
| Engine | Water Cooled, turbo charged (where applicable) | ||
| Four Cycle | |||
| No. 2 Disel Fuel | TIER IV engines require ULSD (ultra low sulfur diesel), will this create a need for two fuel supply systems? | ||
| Speed: 1,800rpm | |||
| Number of Cylinder: 6 | |||
| EPA Certification Rating: Tier 4 | |||
| Engine Accessories | Fuel Filter | ||
| Lube Oil Filter | |||
| Intake Air Filter | |||
| Lube Oil Cooler | |||
| Fuel transfer pump | |||
| Fuel Priming Pump | |||
| Automatic Elec. Shut off | Is this the Emergency Shut Off? | ||
| Fuel/Water Separator | |||
| Water Pump | Does this mean extra, like repair parts? | ||
| Oil Pump | |||
| Full flow lubrication oil filters | |||
| Pressure relief valve | |||
| Dipstick oil level indicator | |||
| Water Temperature & Lube Oil Pressure Gauge | |||
| Auto Start/Stop ECU (REQUIRED on >36kW) | Yes | The generators will never be connected to the start signal sent from an ATS, so where is this requirement coming from? | |
| Electronic Governor | Yes: Isochroneous; maintain engine speed within .25%, steady state; and .5% no load to full load | ||
| CONTROL PANEL | |||
| Control Panel, to Include (but not limited) | Analog | Analog what? Everything that follows? I don't think analog everything is necessary. | |
| Engine running time meter | |||
| Oil pressure gauge | |||
| Water temperature gauge | |||
| A/C output Amperage | Volt meter too? | ||
| Frequency Meter | |||
| Fuel Gauge | |||
| Battery Voltmeter | |||
| Generator Output Bus Separate From Control Panel - Located in a Separate Lockable Panel | Yes | ||
| AC (Generator) & DC (Engine) Controls Enclosed in a Separate Box or Separated by Divider | Yes | ||
| SAFTEY | |||
| Saftey: Engine shutdown on: | High water temperature | ||
| Low oil pressure | |||
| Over speed | |||
| Engine over crank | |||
| Low Fuel | |||
| Low Coolant | |||
| COURTESY PANEL | |||
| Courtesy Panel - Single Phase | Yes | This requirement seems like overkill and not necessary. | |
| 120V Single Phase GFCI Receptacles | 2 | ||
| 120/240V Single Phase Twist Lock Receptacles | 3 | ||
| FILTERS | |||
| Water Separator Filter w/Drain Plug | Yes | ||
| Air Filter (>56kW) | Two Stage | ||
| FUEL | |||
| Fuel Tank | UL 142 Double-wall w/ capacity sufficient - 24hr Run time under maximum load | ||
| 12 guage steel body & two coat polyester power coat finish | |||
| Lifting points on base frame (two ea: 6" x 10" x .250" fork pockets & rub spacers | |||
| Stainless steel flush-fitting latches and hinges | |||
| Sheet steel components pre-treated w/ zinc phosphate | |||
| lockable wide door on each side (allow 180 degree rotation) | |||
| Lube Oil and coolant drains piped to exterior of enclosure skid base | |||
| Leak sensor & low fuel level engine cutoff switch | |||
| Fuel Tank Capacity | 100 gallons | ||
| 3 Way Fuel Valve w/External Connections | Yes | ||
| Fuel Valve: >56kW | Yes, Parker H4 male and female quick disconnect & dust cap | ||
| Fuel Consumption @ Full Load | 12.4 GPH | ||
| Fuel Consumption @ 3/4 Load | 9.5 GPH | ||
| Fuel Consumption @ 1/2 Load | 6.9 GPH | ||
| BATTERY | |||
| Battery Type | Sealed Gel Cell | ||
| Quick Disconnects | Tweco Cable Connector(s) NSN: TWE-94251100, TWE-94251200, and TWE-94251400 | ||
| WARRANTY | |||
| Generator Warranty | 2year/2000 hrs | ||
| Engine Warranty (20kW - 200kW) | 1st Year Unlimited/2nd Year 2000 Hours | ||
| OTHER REQUIREMENTS | |||
| Unit Designed as a Portable Prime Power Unit (Not a Standby Unit Modified for Prime Power Use) | Yes | This gets things more complicated. The ISO standard for Prime Power use is 70% rated load continuous and 100% rated load for one hour out of every 24. That being said, there needs to be clarification in the requested rating whether the kW rating is 100% (peak rating) or 70% (continuous rating) ie: 20kW continuous machine would be 28.6kW Prime. | |
| NEED CLARIFICATION | |||
| Idle Switch | Yes | ||
| Paint Type | Powder Coat | ||
| Enclosure Hardware | Stainless Steel | ||
| Color | White | ||
| Amps-120V Single Phase | 488.9 (4 wire) | Is this MQ Specific- if so - do not include | |
| Amps-240V Single Phase | 244.4 (4 wire) | Is this MQ Specific- if so - do not include | |
| Amps-240V Three Phase | 529 | Is this MQ Specific- if so - do not include | |
| Amps-480V Three Phase | 265 | Is this MQ Specific- if so - do not include | |
| Dimensions - L x W x H | 138" x 52" x 69" | Is this MQ Specific- if so - do not include | |
| Weight - Dry | 6,636 lbs | Is this MQ Specific- if so - do not include |
Generator Spec_July 2016
| FEMA REQUIRED GENERATOR SPECIFICATIONS - AUGUST 2016 Revised (400kW BELOW) | ||||
| RATING INFORMATION | ||||
| Prime Power Rating (kW): | 50kW | 100kW | 200kW | 400kW |
| Minimum kW - Maximum KW Range (FEMA Acceptable) | 15-60kW | 61kw - 100kW | 101kw - 200kW | 201kW - 400kW |
| Minimum kW - Maximum KW Range (FEMA Acceptable) | 50kw - 60kW | 100kW - 120kW | 200kW - 220kW | 400kW - 420kW |
| Unit kVA (.8 power factor): | 0.8 | 0.8 | 0.8 | 0.8 |
| GENERATOR SPECIFICATIONS | ||||
| Enclosure | Weather Proof, stainless steel and sound attenuated | Weather Proof, stainless steel and sound attenuated | Weather Proof, stainless steel and sound attenuated | Weather Proof, stainless steel and sound attenuated |
| Phase: | 3 Phase | 3 Phase | 3 Phase | 3 Phase |
| Switchable: | The vendor SHALL provide any hardware and/or software, manuals, or other documentation (in digital or hard copy) that provide detailed directions which will allow FEMA mechanics to switch/set output voltages and phase configurations on the generator and voltage regulator | The vendor SHALL provide any hardware and/or software, manuals, or other documentation (in digital or hard copy) that provide detailed directions which will allow FEMA mechanics to switch/set output voltages and phase configurations on the generator and voltage regulator | The vendor SHALL provide any hardware and/or software, manuals, or other documentation (in digital or hard copy) that provide detailed directions which will allow FEMA mechanics to switch/set output voltages and phase configurations on the generator and voltage regulator | The vendor SHALL provide any hardware and/or software, manuals, or other documentation (in digital or hard copy) that provide detailed directions which will allow FEMA mechanics to switch/set output voltages and phase configurations on the generator and voltage regulator |
| Voltage 3 Phase: | 208, 220, 240, 416, 440, 480V Switchable | 208, 220, 240, 416, 440, 480V Switchable | 208, 220, 240, 416, 440, 480V Switchable | 208, 220, 240, 416, 440, 480V Switchable |
| Voltage 1 Phase: | 120, 127, 139, 240, 254, 277V Switchable | 120, 127, 139, 240, 254, 277V Switchable | 120, 127, 139, 240, 254, 277V Switchable | 120, 127, 139, 240, 254, 277V Switchable |
| Generator RPM: | 1800 | 1800 | 1800 | 1800 |
| Frequency: | 60 HZ | 60 HZ | 60 HZ | 60 HZ |
| No. Poles | 4 | 4 | 4 | 4 |
| Excitation: | Brushless with AVR | Brushless with AVR | Brushless with AVR | Brushless with AVR |
| Frequency Regulation (Steady State): | 0.25% | 0.25% | 0.25% | 0.25% |
| Alternator Heat Rise: | NTE 85°(F) with CLASS H insulation wire | NTE 85°(F) with CLASS F insulation wire | NTE 85°(F) with CLASS F insulation wire | NTE 85°(F) with CLASS F insulation wire |
| Sound Level: | NTE 75dB(A) full load @ 23 ft. | NTE 75dB(A) full load @ 23 ft. | NTE 75dB(A) full load @ 23 ft. | NTE 75dB(A) full load @ 23 ft. |
| Trailer or Skid Mounted: | SKID | SKID | SKID | SKID |
| Load Terminal - CamLok Connectors: | YES | YES | YES | YES |
| Integrally-mounted automated load bank system able to apply resistive load up to 40% during periods of low temperature/load conditions. SHALL have the capability to constantly monitor, sense and manage exhaust temperature with automatic shut-off for periods of high load conditions. | YES | YES | YES | YES |
| ENGINE | ||||
| Emissions: | Tier 4 FINAL | Tier 4 FINAL | Tier 4 FINAL | Tier 4 FINAL |
| Engine Design: | 4-cycle, water cooled DIESEL, Ultra Low Sulfur Diesel, turbocharged, direct injection. Charged Air Cooled EGR | 4-cycle, water cooled DIESEL, Ultra Low Sulfur Diesel, turbocharged, direct injection. Charged Air Cooled EGR | 4-cycle, water cooled DIESEL, Ultra Low Sulfur Diesel, turbocharged, direct injection. Charged Air Cooled EGR | 4-cycle, water cooled DIESEL, Ultra Low Sulfur Diesel, turbocharged, direct injection. Charged Air Cooled EGR |
| Tier 4 Engine Capability: | SHALL be capable to perform "Passive Regen" on it's own with no operator at 40% - 50% load at full-rated speed | SHALL be capable to perform "Passive Regen" on it's own with no operator at 40% - 50% load at full-rated speed | SHALL be capable to perform "Passive Regen" on it's own with no operator at 40% - 50% load at full-rated speed | SHALL be capable to perform "Passive Regen" on it's own with no operator at 40% - 50% load at full-rated speed |
| SHALL have the capability to "Not Regen" at 80%-90% Load | SHALL have the capability to "Not Regen" at 80%-90% Load | SHALL have the capability to "Not Regen" at 80%-90% Load | SHALL have the capability to "Not Regen" at 80%-90% Load | |
| Engine Accessories: | Fuel Filter | Fuel Filter | Fuel Filter | Fuel Filter |
| Lube Oil Filter | Lube Oil Filter | Lube Oil Filter | Lube Oil Filter | |
| Intake Air Filter | Intake Air Filter | Intake Air Filter | Intake Air Filter | |
| Lube Oil Cooler | Lube Oil Cooler | Lube Oil Cooler | Lube Oil Cooler | |
| Fuel transfer pump | Fuel transfer pump | Fuel transfer pump | Fuel transfer pump | |
| Fuel Priming Pump | Fuel Priming Pump | Fuel Priming Pump | Fuel Priming Pump | |
| Emergency Shut-off | Emergency Shut-off | Emergency Shut-off | Emergency Shut-off | |
| Fuel/Water Separator | Fuel/Water Separator | Fuel/Water Separator | Fuel/Water Separator | |
| Water Pump | Water Pump | Water Pump | Water Pump | |
| Oil Pump | Oil Pump | Oil Pump | Oil Pump | |
| Full flow lubrication oil filters | Full flow lubrication oil filters | Full flow lubrication oil filters | Full flow lubrication oil filters | |
| Pressure relief valve | Pressure relief valve | Pressure relief valve | Pressure relief valve | |
| Dipstick oil level indicator | Dipstick oil level indicator | Dipstick oil level indicator | Dipstick oil level indicator | |
| Water Temperature & Lube Oil Pressure Gauge | Water Temperature & Lube Oil Pressure Gauge | Water Temperature & Lube Oil Pressure Gauge | Water Temperature & Lube Oil Pressure Gauge | |
| BATTERY | ||||
| Battery Type: | Sealed Gel Cell or Absorbed glass matt (AGM) | Sealed Gel Cell or Absorbed glass matt (AGM) | Sealed Gel Cell or Absorbed glass matt (AGM) | Sealed Gel Cell or Absorbed glass matt (AGM) |
| CONTROL PANEL | ||||
| Control Panel, to Include (but not limited): | Engine Analog Hour meter - 12volt or 24volt (unit depending) | Engine Analog Hour meter - 12volt or 24volt (unit depending) | Engine Analog Hour meter - 12volt or 24volt (unit depending) | Engine Analog Hour meter - 12volt or 24volt (unit depending) |
| Three Position panel mounted switch (Stop-Manual-Auto) | Three Position panel mounted switch (Stop-Manual-Auto) | Three Position panel mounted switch (Stop-Manual-Auto) | Three Position panel mounted switch (Stop-Manual-Auto) | |
| Oil pressure gauge | Oil pressure gauge | Oil pressure gauge | Oil pressure gauge | |
| Water temperature gauge | Water temperature gauge | Water temperature gauge | Water temperature gauge | |
| A/C output Amperage | A/C output Amperage | A/C output Amperage | A/C output Amperage | |
| Volt Meter | Volt Meter | Volt Meter | Volt Meter | |
| Frequency Meter | Frequency Meter | Frequency Meter | Frequency Meter | |
| Fuel Gauge | Fuel Gauge | Fuel Gauge | Fuel Gauge | |
| Analog fuel pressure gauge | Analog fuel pressure gauge | Analog fuel pressure gauge | Analog fuel pressure gauge | |
| Battery Voltmeter | Battery Voltmeter | Battery Voltmeter | Battery Voltmeter | |
| Phase selector switch with phase voltage & amperage | Phase selector switch with phase voltage & amperage | Phase selector switch with phase voltage & amperage | Phase selector with phase voltage | |
| DPF cleaning cycle indication | DPF cleaning cycle indication | DPF cleaning cycle indication | DPF cleaning cycle indication | |
| Programmable Remaining Fuel (tank) Level % Indicator | Programmable Remaining Fuel (tank) Level % Indicator | Programmable Remaining Fuel (tank) Level % Indicator | Programmable Remaining Fuel (tank) Level % Indicator | |
| Generator Output Bus Separate From Control Panel - Located in a Separate Lockable Panel: | Yes | Yes | Yes | Yes |
| AC (Generator) & DC (Engine) Controls Enclosed in a Separate Box or Separated by Divider: | Yes | Yes | Yes | Yes |
| SAFTEY | ||||
| Safety: Engine shutdown and lockout upon: | High water temperature | High water temperature | High water temperature | High water temperature |
| Low oil pressure | Low oil pressure | Low oil pressure | Low oil pressure | |
| Over speed | Over speed | Over speed | Over speed | |
| Engine over crank | Engine over crank | Engine over crank | Engine over crank | |
| Low Coolant | Low Coolant | Low Coolant | Low Coolant | |
| Low DEF Level | Low DEF Level | Low DEF Level | Low DEF Level | |
| FUEL | ||||
| Fuel Tank: 24 hour | UL 142 Double-wall w/ capacity sufficient - 24- hour tank | UL 142 Double-wall w/ capacity sufficient - 24- hour tank | UL 142 Double-wall w/ capacity sufficient - 24- hour tank | UL 142 Double-wall w/ capacity sufficient - 24- hour tank |
| 12 gauge steel body & two coat polyester power coat finish | 12 gauge steel body & two coat polyester power coat finish | 12 gauge steel body & two coat polyester power coat finish | 12 gauge steel body & two coat polyester power coat finish | |
| Lifting points on base frame (two ea.: 4" x 10" x .250" fork pockets & rub spacers | Lifting points on base frame (two ea.: 4" x 10" x .250" fork pockets & rub spacers | Lifting points on base frame (two ea.: 4" x 10" x .250" fork pockets & rub spacers | Lifting points on base frame (two ea.: 4" x 10" x .250" fork pockets & rub spacers | |
| Sheet steel components pre-treated w/ zinc phosphate | Sheet steel components pre-treated w/ zinc phosphate | Sheet steel components pre-treated w/ zinc phosphate | Sheet steel components pre-treated w/ zinc phosphate | |
| Basin equipped with liquid level sensor for leakage into basin | Basin equipped with liquid level sensor for leakage into basin | Basin equipped with liquid level sensor for leakage into basin | Basin equipped with liquid level sensor for leakage into basin | |
| Fuel Valve: | Yes, Parker H3 or H4 male and female quick disconnect & dust cap - sufficient enough to meet efficient fuel flow | Yes, Parker H3 or H4 male and female quick disconnect & dust cap - sufficient enough to meet efficient fuel flow | Yes, Parker H3 or H4 male and female quick disconnect & dust cap - sufficient enough to meet efficient fuel flow | Yes, Parker H3 or H4 male and female quick disconnect & dust cap - sufficient enough to meet efficient fuel flow |
| Diesel Engine Fluid (DEF) Tank: | Internal storage, EPA approved to provide fluid to operate at full rated load | Internal storage, EPA approved to provide fluid to operate at full rated load | Internal storage, EPA approved to provide fluid to operate at full rated load | Internal storage, EPA approved to provide fluid to operate at full rated load |
| WARRANTY | ||||
| Engine Warranty: | Industry Standard Warranty | Industry Standard Warranty | Industry Standard Warranty | Industry Standard Warranty |
| Generator Warranty: | Industry Standard Warranty | Industry Standard Warranty | Industry Standard Warranty | Industry Standard Warranty |
| Trailer: (if applicable) | Not Applicable | Not Applicable | Not Applicable | 500kW and Above |
| OTHER REQUIREMENTS | ||||
| Unit Designed as a Portable Prime Power Unit (Not a Standby Unit Modified for Prime Power Use) | Yes | Yes | Yes | Yes |
| Exhaust: | Industrial Silencer/Muffler | Industrial Silencer/Muffler | Industrial Silencer/Muffler | Industrial Silencer/Muffler |
| Paralleling Capability (to include ALL BOM and required Cables): | 400kW and Above Only | 400kW and Above Only | 400kW and Above Only | Yes, 400kW and Above Only |
| Training: | The vendor SHALL provide training opportunities for FEMA Mechanics on operational guidance with your equipment. This includes how to switch/set the output voltages and phase configurations on the generator and voltage regulators. Training shall occur AFTER the delivery of all units to that given location; no later than 30 days after receipt of generators. Training date and time are TBD dependent on generator delivery timeline; to be agreed upon by the contractor and the Government. | The vendor SHALL provide training opportunities for FEMA Mechanics on operational guidance with your equipment. This includes how to switch/set the output voltages and phase configurations on the generator and voltage regulators. Training shall occur AFTER the delivery of all units to that given location; no later than 30 days after receipt of generators. Training date and time are TBD dependent on generator delivery timeline; to be agreed upon by the contractor and the Government. | The vendor SHALL provide training opportunities for FEMA Mechanics on operational guidance with your equipment. This includes how to switch/set the output voltages and phase configurations on the generator and voltage regulators. Training shall occur AFTER the delivery of all units to that given location; no later than 30 days after receipt of generators. Training date and time are TBD dependent on generator delivery timeline; to be agreed upon by the contractor and the Government. | The vendor SHALL provide training opportunities for FEMA Mechanics on operational guidance with your equipment. This includes how to switch/set the output voltages and phase configurations on the generator and voltage regulators. Training shall occur AFTER the delivery of all units to that given location; no later than 30 days after receipt of generators. Training date and time are TBD dependent on generator delivery timeline; to be agreed upon by the contractor and the Government. |
| Diagnostic/Troubleshooting: | Diagnostics/Troubleshooting: The vendor SHALL provide any hardware and/or software, manuals or other documentation (in digital or hard copy), to include all diagnostic codes, that will enable FEMA Mechanics to perform all diagnostic's available for the generator(s) | Diagnostics/Troubleshooting: The vendor SHALL provide any hardware and/or software, manuals or other documentation (in digital or hard copy), to include all diagnostic codes, that will enable FEMA Mechanics to perform all diagnostic's available for the generator(s) | Diagnostics/Troubleshooting: The vendor SHALL provide any hardware and/or software, manuals or other documentation (in digital or hard copy), to include all diagnostic codes, that will enable FEMA Mechanics to perform all diagnostic's available for the generator(s) | Diagnostics/Troubleshooting: The vendor SHALL provide any hardware and/or software, manuals or other documentation (in digital or hard copy), to include all diagnostic codes, that will enable FEMA Mechanics to perform all diagnostic's available for the generator(s) |
| Miscellaneous: | Fabrication and permanent attachment of exterior metal spacers/rub-knuckles to facilitate side by side (rub free) transportation | Fabrication and permanent attachment of exterior metal spacers/rub-knuckles to facilitate side by side (rub free) transportation | Fabrication and permanent attachment of exterior metal spacers/rub-knuckles to facilitate side by side (rub free) transportation | Fabrication and permanent attachment of exterior metal spacers/rub-knuckles to facilitate side by side (rub free) transportation |
| Height Requirements for Air Transportation: | Want to max transportation versatility - C17 load height limit 104"; C130 load height limit 96" | Want to max transportation versatility - C17 load height limit 104"; C130 load height limit 96" | Want to max transportation versatility - C17 load height limit 104"; C130 load height limit 96" | Want to max transportation versatility - C17 load height limit 104"; C130 load height limit 96" |
&C&9RFP: HSFE20-16-Q-0029
Attachment 2: Generator Criteria Specifications (50-400kW)&RAs of: 25 July 2016
v. 1.11 Page &P of &N &C&9Attachment 1:
Minimum FEMA Generator Technical Specifications (OCONUS) Page &P of &N
Generator_Spec_Criteria
| Description of Goods or Service | Quantity |
| Generator - 30kW | 5 |
| Generator - 80kW | 10 |
| Generator - 125kW | 11 |
| Generator - 175kW | 4 |
| Generator - 200kW | 2 |
| Generator - 250kW | 2 |
| Generator - 300kW | 1 |
| Generator - 400kW | 1 |
| Total Generator Allocation | 36 |
| FEMA Generator Technical Specification | |
| RATING INFORMATION | |
| Prime KW: | See Above for kW and QTY |
| Standby kW: | |
| Unit kVA (.8 power factor): | |
| ALTERNATOR | |
| Voltage Selection (<144kW): | 3 Position Selector Switch |
| Voltage Selection (144kW - 640kW): | Reconnectable Buss Bar (No substitution) |
| Voltage 3 Phase: | 208, 220, 240, 416, 440, 480V Switchable |
| Voltage 1 Phase: | 120, 127, 139, 240, 254, 277V Switchable |
| Frequency: | 60 HZ |
| Frequency Regulation (Steady State): | 0.25% |
| Voltage Regulation (No load to full load): | 0.50% |
| Disconnect/Circuit Breaker: | does not exceed 75 degree Celsius termination rating |
| Sound Level: | NTE 75dB(A) full load @ 23 ft. |
| Armature Connection: | Star w/Neutral / Zig Zag |
| Star w/ Neutral | |
| WYE | |
| Insulation Class: | Class F or Greater |
| ENGINE | |
| Engine: | Water Cooled, turbo charged (where applicable) |
| No. 2 Diesel Fuel | |
| Speed: NTE 2,200 rpm | |
| Emissions Control Regulation: Tier 4; California Complaint | |
| Number of Cylinder: 4 - 6 | |
| Engine Accessories: | Fuel Filter |
| Lube Oil Filter | |
| Intake Air Filter | |
| Lube Oil Cooler | |
| Fuel transfer pump | |
| Fuel Priming Pump | |
| Emergency Shut-off | |
| Fuel/Water Separator | |
| Water Pump | |
| Oil Pump | |
| Full flow lubrication oil filters | |
| Pressure relief valve | |
| Dipstick oil level indicator | |
| Water Temperature & Lube Oil Pressure Gauge | |
| Electronic Governor: | Yes: Isochronous; maintain engine speed within .25%, steady state; and .5% no load to full load |
| CONTROL PANEL | |
| Control Panel, to Include (but not limited): | Engine Analog Hour meter - 12volt or 24volt (unit depending) |
| Oil pressure gauge | |
| Water temperature gauge | |
| A/C output Amperage | |
| Volt Meter | |
| Frequency Meter | |
| Fuel Gauge | |
| Battery Voltmeter | |
| Generator Output Bus Separate From Control Panel - Located in a Separate Lockable Panel: | Yes |
| AC (Generator) & DC (Engine) Controls Enclosed in a Separate Box or Separated by Divider: | Yes |
| SAFTEY | |
| Safety: Engine shutdown on: | High water temperature |
| Low oil pressure | |
| Over speed | |
| Engine over crank | |
| Low Coolant | |
| COURTESY PANEL | |
| Courtesy Panel - Single Phase | Yes |
| 120V Single Phase GFCI Receptacles | 2 |
| FILTERS | |
| Water Separator Filter w/Drain Plug | Yes |
| Air Filter | Single Stage |
| FUEL | |
| Fuel Tank: | UL 142 Double-wall w/ capacity sufficient - Units below 150kW 24-hour tank; units above 150kW 8 hour tank |
| 12 gauge steel body & two coat polyester power coat finish | |
| Lifting points on base frame (two ea.: 4" x 10" x .250" fork pockets & rub spacers | |
| Stainless steel flush-fitting latches and hinges | |
| Sheet steel components pre-treated w/ zinc phosphate | |
| lockable wide door on each side (allow 180 degree rotation) | |
| Lube Oil and coolant drains piped to exterior of enclosure skid base | |
| Leak sensor & low fuel level engine cutoff switch | |
| 3 Way Fuel Valve w/External Connections: | Yes |
| Fuel Valve: | Yes, Parker H3 or H4 male and female quick disconnect & dust cap - sufficient enough to meet efficient fuel flow |
| BATTERY | |
| Battery Type: | Sealed Gel Cell or Absorbed glass matt (AGM) |
| Battery Quick Disconnects: | Tweco Cable Connector(s) NSN: TWE-94251100, TWE-94251200, and TWE-94251400 |
| WARRANTY | |
| Complete Unit Warranty: | Minimum of : 2year/2000 hrs. |
| OTHER REQUIREMENTS | |
| Unit Designed as a Portable Prime Power Unit (Not a Standby Unit Modified for Prime Power Use) | Yes |
| Idle Switch: | Yes |
| Paint Type: | Powder Coat |
| Enclosure Hardware | Stainless Steel |
| Color: | White |
| Semi Trailer Mounted : | 1000kW (1mW) and Greater |
| Containerization: | Minimum: 600kW and greater |
| Container Steps (@ entry): | Yes |
| Paralleling Capability | Yes, if applicable |
| Miscellaneous | Fabrication and permanent attachment of exterior metal spacers/rub-knuckles to facilitate side by side (rub free) transportation |
| Height Requirements for Air Transportation | Want to max transportation versatility - C17 load height limit 104"; C130 load height limit 96" |
&C&9Attachment 1:
Minimum FEMA Generator Technical Specifications (OCONUS) Page &P of &N &C&9Attachment 1:
Minimum FEMA Generator Technical Specifications (OCONUS) Page &P of &N
MQ Power
| Description of Goods or Service | Quantity | |
| Generator - 30kW | 5 | 50 |
| Generator - 80kW | 10 | 100 |
| Generator - 125kW | 11 | 200 |
| Generator - 175kW | 4 | 200 |
| Generator - 200kW | 2 | 200 |
| Generator - 250kW | 2 | 400 |
| Generator - 300kW | 1 | 400 |
| Generator - 400kW | 1 | 400 |
| Total Generator Allocation | 36 | |
| FEMA Generator Technical Specification | ||
| RATING INFORMATION | ||
| Prime KW: | See Above for kW and QTY | |
| Standby kW: | ||
| Unit kVA (.8 power factor): | ||
| ALTERNATOR | ||
| Voltage Selection (<144kW): | 3 Position Selector Switch | |
| Voltage Selection (144kW - 640kW): | Reconnectable Buss Bar (No substitution) | |
| Voltage 3 Phase: | 208, 220, 240, 416, 440, 480V Switchable | |
| Voltage 1 Phase: | 120, 127, 139, 240, 254, 277V Switchable | |
| Frequency: | 60 HZ | |
| Frequency Regulation (Steady State): | 0.25% | |
| Voltage Regulation (No load to full load): | 0.50% | |
| Disconnect/Circuit Breaker: | does not exceed 75 degree Celsius termination rating | |
| Sound Level: | NTE 75dB(A) full load @ 23 ft. | |
| Armature Connection: | Star w/Neutral / Zig Zag | |
| Star w/ Neutral | ||
| WYE | ||
| Insulation Class: | Class F or Greater | |
| ENGINE | ||
| Engine: | Water Cooled, turbo charged (where applicable) | |
| No. 2 Diesel Fuel | ||
| Speed: NTE 2,200 rpm | ||
| Emissions Control Regulation: Tier 4; California Complaint | ||
| Number of Cylinder: 4 - 6 | ||
| Engine Accessories: | Fuel Filter | |
| Lube Oil Filter | ||
| Intake Air Filter | ||
| Lube Oil Cooler | ||
| Fuel transfer pump | ||
| Fuel Priming Pump | ||
| Emergency Shut-off | ||
| Fuel/Water Separator | ||
| Water Pump | ||
| Oil Pump | ||
| Full flow lubrication oil filters | ||
| Pressure relief valve | ||
| Dipstick oil level indicator | ||
| Water Temperature & Lube Oil Pressure Gauge | ||
| Electronic Governor: | Yes: Isochronous; maintain engine speed within .25%, steady state; and .5% no load to full load | |
| CONTROL PANEL | ||
| Control Panel, to Include (but not limited): | Engine Analog Hour meter - 12volt or 24volt (unit depending) | |
| Oil pressure gauge | ||
| Water temperature gauge | ||
| A/C output Amperage | ||
| Volt Meter | ||
| Frequency Meter | ||
| Fuel Gauge | ||
| Battery Voltmeter | ||
| Generator Output Bus Separate From Control Panel - Located in a Separate Lockable Panel: | Yes | |
| AC (Generator) & DC (Engine) Controls Enclosed in a Separate Box or Separated by Divider: | Yes | |
| SAFTEY | ||
| Safety: Engine shutdown on: | High water temperature | |
| Low oil pressure | ||
| Over speed | ||
| Engine over crank | ||
| Low Coolant | ||
| COURTESY PANEL | ||
| Courtesy Panel - Single Phase | Yes | |
| 120V Single Phase GFCI Receptacles | 2 | |
| FILTERS | ||
| Water Separator Filter w/Drain Plug | Yes | |
| Air Filter | Single Stage | |
| FUEL | ||
| Fuel Tank: | UL 142 Double-wall w/ capacity sufficient - Units below 150kW 24-hour tank; units above 150kW 8 hour tank | |
| 12 gauge steel body & two coat polyester power coat finish | ||
| Lifting points on base frame (two ea.: 4" x 10" x .250" fork pockets & rub spacers | ||
| Stainless steel flush-fitting latches and hinges | ||
| Sheet steel components pre-treated w/ zinc phosphate | ||
| lockable wide door on each side (allow 180 degree rotation) | ||
| Lube Oil and coolant drains piped to exterior of enclosure skid base | ||
| Leak sensor & low fuel level engine cutoff switch | ||
| 3 Way Fuel Valve w/External Connections: | Yes | |
| Fuel Valve: | Yes, Parker H3 or H4 male and female quick disconnect & dust cap - sufficient enough to meet efficient fuel flow | |
| BATTERY | ||
| Battery Type: | Sealed Gel Cell or Absorbed glass matt (AGM) | |
| Battery Quick Disconnects: | Tweco Cable Connector(s) NSN: TWE-94251100, TWE-94251200, and TWE-94251400 | |
| WARRANTY | ||
| Complete Unit Warranty: | Minimum of : 2year/2000 hrs. | |
| OTHER REQUIREMENTS | ||
| Unit Designed as a Portable Prime Power Unit (Not a Standby Unit Modified for Prime Power Use) | Yes | |
| Idle Switch: | Yes | |
| Paint Type: | Powder Coat | |
| Enclosure Hardware | Stainless Steel | |
| Color: | White | |
| Semi Trailer Mounted : | 1000kW (1mW) and Greater | |
| Containerization: | Minimum: 600kW and greater | |
| Container Steps (@ entry): | Yes | |
| Paralleling Capability | Yes, if applicable | |
| Miscellaneous | Fabrication and permanent attachment of exterior metal spacers/rub-knuckles to facilitate side by side (rub free) transportation | |
| Height Requirements for Air Transportation | Want to max transportation versatility - C17 load height limit 104"; C130 load height limit 96" |
&C&9Attachment 1:
Minimum FEMA Generator Technical Specifications (OCONUS) Page &P of &N &C&9Attachment 1:
Minimum FEMA Generator Technical Specifications (OCONUS) Page &P of &N
MQ Power (2)
| MQ Power Generator Technical Specification | ||||
| RATING INFORMATION | ||||
| Prime KW: | 100kW | 240kW (200) | 56kW (50) / 50kW | 480kW (400) |
| Standby kW: | 110kw | 264kW | 62kW / 44kW | 528 kW |
| Unit kVA (.8 power factor): | 0.8 | 0.8 | 0.8 / 1.0 | 0.8 |
| GENERATOR SPECIFICATIONS | ||||
| Design | Revolving field, self-ventilated drip proof, single bearing | Revolving field, self ventalated, drip proof single bearing | Revolving field, self ventalated, drip proof single bearing | |
| Armature Connection: | Star w/Neutral / Zig Zag | Star w/ Neutral | Star w/ Nuetral (3 ph) | Start w/ Neutral (3 phase) |
| Star w/ Neutral | Zig Zag (Single) | |||
| WYE | ||||
| Phase: | 3 - Single | 3 | 3 - single | 3 phase |
| Voltage 3 Phase: | 208, 220, 240, 416, 440, 480V Switchable | 208, 220, 240 | 208, 220, 240, 416, 440, 480v Switchable | 208, 220, 240, 416, 440, 480v Reconnectable |
| Voltage 1 Phase: | 120, 127, 139, 240, 254, 277V Switchable | n/a | 240v Switchable | 120, 127, 139, 240, 254, 277V Adjustable |
| Voltage Regulation (No load to full load): | ±0.5% | ±0.5% | ±0.5% | ±0.5% |
| Generator RPM: | 1800 | 1800 | 1800 | 1800 |
| Frequency: | 60 HZ | 60 HZ | 60 HZ | 60 HZ |
| No. Poles | 4 | 4 | 4 | 4 |
| Excitation: | Brushless with AVR | Brushless with AVR | Brushless with AVR | Brushless with AVR |
| Frequency Regulation: No Load to Full Load: | Isochronous under varying loads from no load to 100% rated load | Isochronous under varying loads from no load to 100% rated load | Isochronous under varying loads from no load to 100% rated load | Isochronous under varying loads from no load to 100% rated load |
| Electronic Governor | Yes | YES | YES | YES |
| Frequency Regulation (Steady State): | 0.25% | 0.25% | 0.25% | 0.25% |
| Insulation Class: | Class F | Class F | Class H | Class F |
| Sound Level: | NTE 75dB(A) full load @ 23 ft. | 70 db(a) full load @ 23ft | 65 db(a) full load @ 23ft | 74 dB(A) full load @ 23ft |
| Disconnect/Circuit Breaker: | does not exceed 75 degree Celsius termination rating | |||
| ENGINE | ||||
| Make / Model: | Isuzu / BR-4HK1X | John Deere/ 6090 HFG09 | Isuzu / BR-4JJ1X | Volvo / TAD1642GE |
| Emissions: | EPA Tier 4 | EPA Tier 4 | EPA Tier 4 Final Certified | EPA Tier 2 Certified |
| Starting System: | Electronic | Electronic | electronic | Elecronic |
| Design: | 4-cycle, water cooled, turbocharged, direct injection. Charged Air Cooled EGR, DOC and SCR | 4-cycle, water cooled, turbocharged, direct injection. Charged Air Cooled EGR, DOC and SCR | 4-cycle, water cooled, turbocharged, direct injection. Charged Air Cooled EGR, DOC and SCR | 4-cycle, water cooled, direct injection, turbo charge, air to air intercooled |
| Discplacement: | 317 in³ (5193 cc) | 549.2 in³ (9L) | 183 in³ (9L) | 16120 cc |
| No. Cylinders: | 4 | 6 | 4 | 6 |
| Bore x Stroke | 4.53 x 4.92 in (115 x 125mm) | 4.64 x 5.34in | 95.4 x 104.9 | 144 x 165 |
| Gross Engine Power Output | 152 hp (113kW) | 437 hp (326kW) | 95.2 hp | 810 bhp |
| BMEP | 211 psi (1458 kPa) | 315 psi | 208 psi | 362 psi |
| Position Speed | 1476 ft/min (7.5 m/s) | 1606 ft/min | 1237 ft/min | 1949 ft/min |
| Engine Accessories: | Fuel Filter | Fuel Filter | Fuel Filter | Fuel Filter |
| Lube Oil Filter | Lube Oil Filter | Lube Oil Filter | Lube Oil Filter | |
| Intake Air Filter | Intake Air Filter | Intake Air Filter | Intake Air Filter | |
| Lube Oil Cooler | Lube Oil Cooler | Lube Oil Cooler | Lube Oil Cooler | |
| Fuel transfer pump | Fuel transfer pump | Fuel transfer pump | Fuel transfer pump | |
| Fuel Priming Pump | Fuel Priming Pump | Fuel Priming Pump | Fuel Priming Pump | |
| Emergency Shut-off | Emergency Shut-off | Emergency Shut-off | Emergency Shut-off | |
| Fuel/Water Separator | Fuel/Water Separator | Fuel/Water Separator | Fuel/Water Separator | |
| Water Pump | Water Pump | Water Pump | Water Pump | |
| Oil Pump | Oil Pump | Oil Pump | Oil Pump | |
| Full flow lubrication oil filters | Full flow lubrication oil filters | Full flow lubrication oil filters | Full flow lubrication oil filters | |
| Pressure relief valve | Pressure relief valve | Pressure relief valve | Pressure relief valve | |
| Dipstick oil level indicator | Dipstick oil level indicator | Dipstick oil level indicator | Dipstick oil level indicator | |
| Water Temperature & Lube Oil Pressure Gauge | Water Temperature & Lube Oil Pressure Gauge | Water Temperature & Lube Oil Pressure Gauge | Water Temperature & Lube Oil Pressure Gauge | |
| Compression Ration: | 16.5:1 | 16.1:1 | 16.5:1 | 16.5:1 |
| Overspeed Limit: | 2070 rpm% | 2070 rpm | 2070 rpm | 2070 rpm |
| Oil Capacity: | 6.05 gallons (22.9 litters) | 9.3 gallons | 3.96 gallons | 12.7 gallons |
| BATTERY | ||||
| Battery Type: FEMA REQUIREMENT | Sealed Gel Cell or Absorbed glass matt (AGM) | Sealed Gel Cell or Absorbed glass matt (AGM) | Sealed Gel Cell or Absorbed glass matt (AGM) | Sealed Gel Cell or Absorbed glass matt (AGM) |
| Battery Quick Disconnects: FEMA REQUIREMENT | Tweco Cable Connector(s) NSN: TWE-94251100, TWE-94251200, and TWE-94251400 | Tweco Cable Connector(s) NSN: TWE-94251100, TWE-94251200, and TWE-94251400 | Tweco Cable Connector(s) NSN: TWE-94251100, TWE-94251200, and TWE-94251400 | Tweco Cable Connector(s) NSN: TWE-94251100, TWE-94251200, and TWE-94251400 |
| CONTROL PANEL | ||||
| Control Panel, to Include (but not limited): | Engine Analog Hour meter - 12volt or 24volt (unit depending) | Engine Analog Hour meter - 12volt or 24volt (unit depending) | Engine Analog Hour meter - 12volt or 24volt (unit depending) | Engine Analog Hour meter - 12volt or 24volt (unit depending) |
| Oil pressure gauge | Oil pressure gauge | Oil pressure gauge | Oil pressure gauge | |
| Water temperature gauge | Water temperature gauge | Water temperature gauge | Water temperature gauge | |
| A/C output Amperage | A/C output Amperage | A/C output Amperage | A/C output Amperage | |
| Volt Meter | Volt Meter | Volt Meter | Volt Meter | |
| Frequency Meter | Frequency Meter | Frequency Meter | Frequency Meter | |
| Fuel Gauge | Fuel Gauge | Fuel Gauge | Fuel Gauge | |
| Battery Voltmeter | Battery Voltmeter | Battery Voltmeter | Battery Voltmeter | |
| Generator Output Bus Separate From Control Panel - Located in a Separate Lockable Panel: | Yes | |||
| AC (Generator) & DC (Engine) Controls Enclosed in a Separate Box or Separated by Divider: | Yes | |||
| SAFTEY | ||||
| Safety: Engine shutdown on: | High water temperature | High water temperature | High water temperature | High water temperature |
| Low oil pressure | Low oil pressure | Low oil pressure | Low oil pressure | |
| Over speed | Over speed | Over speed | Over speed | |
| Engine over crank | Engine over crank | Engine over crank | Engine over crank | |
| Low Coolant | Low Coolant | Low Coolant | Low Coolant | |
| COURTESY PANEL (are these FEMA minimum?) | ||||
| Courtesy Panel - Single Phase | Yes | Yes | Yes | Yes |
| 120V Single Phase GFCI Receptacles | 2 | 2 | 2 | 2 |
| FILTERS | ||||
| Water Separator Filter w/Drain Plug | Yes | Yes | Yes | Yes |
| Air Filter (FEMA? Requirement) | Single Stage | Single Stage | Single Stage | Single Stage |
| FUEL | ||||
| Fuel Tank: | UL 142 Double-wall w/ capacity sufficient - Units below 150kW 24-hour tank; units above 150kW 8 hour tank | |||
| 12 gauge steel body & two coat polyester power coat finish | Internal fuel tank w/ direct reading fuel guages are standard | Internal fuel tank w/ direct reading fuel guages are standard | ||
| Lifting points on base frame (two ea.: 4" x 10" x .250" fork pockets & rub spacers | ||||
| Stainless steel flush-fitting latches and hinges | ||||
| Sheet steel components pre-treated w/ zinc phosphate | ||||
| lockable wide door on each side (allow 180 degree rotation) | ||||
| Lube Oil and coolant drains piped to exterior of enclosure skid base | ||||
| Leak sensor & low fuel level engine cutoff switch | ||||
| Maximum Fuel Flow (per hour): | 19 gallons | 43 gallons | 16 gallons | 53 gallons |
| Maximum Inlet Restriction: | 2.9 in | 5.9 in | 2.9 in | 2.59 in |
| Fuel Tank Capacity: | 169 gallons (640 liters) | 100 gallons | 103 gallons | 129 gallons |
| Fuel Consumption: | GPH | GPH | GPH | GPH |
| Fuel Load | 7 | 17.2 | 4.4 | 33.1 |
| 3/4 Load | 6 | 12.4 | 3.5 | 24.2 |
| 1/2 Load | 4 | 9.1 | 2.6 | 17.3 |
| 1/4 Load | 3 | 5.5 | 1.7 | 10.5 |
| DEF Tank Capacity | 7.4 gallons (28 liters) | 14.5 gallons | 7.4 gallons | |
| Fuel Valve: FEMA REQUIREMENT | Yes, Parker H3 or H4 male and female quick disconnect & dust cap - sufficient enough to meet efficient fuel flow | Yes, Parker H3 or H4 male and female quick disconnect & dust cap - sufficient enough to meet efficient fuel flow | Yes, Parker H3 or H4 male and female quick disconnect & dust cap - sufficient enough to meet efficient fuel flow | |
| 3 Way Fuel Valve w/External Connections: | Yes | |||
| COOLING SYSTEM | ||||
| Fan Load: | 6.57 hp | 26.8 HP | 4.7 hp | 25.5 hp |
| Coolant Capacity (w/ Radiator): | 10.3 gallons | 17.7 gallons | 5.5 gallons | 24.6 gallons |
| Heat Rejection to Coolant (per minute): | 4456 Btu | 11,411 Btu | 2483 Btu | 14104 Btu |
| Maximum Coolant Frication Head: | 1.1 psi | 7.3 psi | 1.2 psi | 9.0 psi |
| Maximum Coolant Static Head: | 3.3 feet | 78.8 ft | 3.3 feet | 34 ft |
| Ambient Temperature Rating: | 104°F | 104°F | 104°F | 104°F |
| Coolant Flow Rate (per minute): | 60.8 gallons | 102 gallons | 15.9 gallons | 122 gallons |
| AIR | ||||
| Combustion Air: | 244 cfm | 742 cfm | 138 cfm | 1646 cfm |
| Maximum Air Cleaner Restriction | 25in H20 | 25in H20 | 25in H20 | 20.1 in H20 |
| Alternator Cooling Air: | 1352 cfm | 2797 cfm | 526 cfm | 3023 cfm |
| Radiator Cooling Air: | 6065 cfm | 11,800 cfm | 3700 cfm | 19224 cfm |
| EXHAUST SYSTEM | ||||
| Gas Flow (full load) | 512 cfm | 1,448 cfm | 272 cfm | 4153 cfm |
| Gas Temperature: | 658°F | 775°F | 572°F | 954°F |
| Maximum Back Pressure | 100 in H20 | 60 in H20 | 7.2in H20 | 40.2 in H20 |
| AMPERAGE | ||||
| Related Voltage: | Maximum Voltage: | Maximum Voltage: | Maximum Voltage: | Maximum Voltage: |
| 1Ø 120volt | 277.8 Amps (4 wire) 300A x 2 (Zigzag) | 666.7 amps (4 wire) | 155.4 Amps (4 wire) 168A x 2 (Zig Zag) | 1333.3 Amps (4 wire) |
| 1Ø 240volt | 138.9 Amps (4 wire) 300A (Zigzag) | 333.3 amps (4 wire) | 77.8 Amps (4 wire) 168A (Zigzag) | 666.7 Amps (4 wire) |
| 3Ø 240volt | 300 Amps | 722 amps | 168 Amps | 1443.4 amps |
| 3Ø 480volt | 150 Amps | 360 amps | 84 amps | 721.7 amps |
| Main Line Circuit Breaker Rating: | 300 Amps | 800 amps | 175 amps | 1600 amps |
| Over Current Relay Trip Set point (480v Mode only) | 152 amps | 361 amps | 84 amps | 720 amps |
| WARRANTY | ||||
| Engine Warranty: | 12 months from date of purchase w/ unlimited hours or 60 months from date of purchase with 5000 hours (whichever comes first) | 12 months from date of purchase w/ unlimited hours or 60 months from date of purchase with 5000 hours (whichever comes first) | 12 months from date of purchase w/ unlimited hours or 60 months from date of purchase with 5000 hours (whichever comes first) | 24 months from date of purchase and unlmited hours |
| Generator | 2year/2000 hrs. whichever occurs first | 2year/2000 hrs. whichever occurs first | 2year/2000 hrs. whichever occurs first | 2year/2000 hrs. whichever occurs first |
| Trailer: OPTIONAL | 12 months excluding normal wear items | 12 months excluding normal wear items | 12 months excluding normal wear items | |
| OTHER REQUIREMENTS | ||||
| Unit Designed as a Portable Prime Power Unit (Not a Standby Unit Modified for Prime Power Use) FEMA REQUIREMENT | Yes | Yes | Yes | Yes |
| Idle Switch: | Yes | Yes | Yes | Yes |
| Paint Type: | Powder Coat | E Coat and Powder Coat paint | E Coat and Powder Coat paint | E Coat and Powder Coat paint |
| Enclosure Hardware: | Stainless Steel | Stainless Steel | Stainless Steel | Stainless Steel |
| Color: | White | White | White | White |
| Paralleling Capability: FEMA REQUIREMENT | Yes, if applicable | Yes, if applicable | Yes, if applicable | Yes, if applicable |
| Miscellaneous: FEMA REQUIREMENT | Fabrication and permanent attachment of exterior metal spacers/rub-knuckles to facilitate side by side (rub free) transportation | Fabrication and permanent attachment of exterior metal spacers/rub-knuckles to facilitate side by side (rub free) transportation | Fabrication and permanent attachment of exterior metal spacers/rub-knuckles to facilitate side by side (rub free) transportation | Fabrication and permanent attachment of exterior metal spacers/rub-knuckles to facilitate side by side (rub free) transportation |