Kodiak Standard Specs.doc
DOC document 652 KB Posted
- Attached to
- MULTIPLE AWARD TASK ORDER CONSTRUCTION CONTRACT BASE SUPPORT UNIT KODIAK, ALASKA Federal contract opportunity
- Solicitation number
- HSCG5011RPJT001
About this file
BSU Standard Construction Specifications
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Site Visit List.pdf | ||
| Amend0004.pdf | ||
| Wage Determination Amendment.doc | DOC document | |
| SF30 Amend3.pdf | ||
| Amendment Page 2.doc | DOC document | |
| ISCKODIAKINST 5100 3 Safety Manual _2_ - Copy.pdf | ||
| SF30 Amend2.pdf | ||
| Amendment Page 99.doc | DOC document | |
| Amendment Page 2.doc | DOC document | |
| Amend 0001 SF30.pdf | ||
| PAST PERFORMANCE.doc | DOC document | |
| Seed Project Half Size Drawings.pdf | ||
| MATOC laydown Area.pdf | ||
| UEG.pdf | ||
| Seed Project Specifications.pdf | ||
| HSCG50-11-R-PJT000.rtf | RTF text file | |
| ISCKODIAKINST 5100 3 Safety Manual | — | |
| KR Procedures Manual 15 june 2011.pdf | ||
| SF1442.pdf |
Show all 19
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BASE SUPPORT UNIT KODIAK
STANDARD CONSTRUCTION SPECIFICATIONS
February 1, 2010
DIVISION 01 – GENERAL REQUIREMENTS
SECTION 01 33 15 DOCUMENTATION STANDARDS
SECTION 01 55 00 TRAFFIC CONTROL
SECTION 01 71 23 FIELD ENGINEERING
DIVISION 02 – EXISTING CONDITIONS
SECTION 02 65 00 UNDERGROUND STORAGE TANK REMOVAL
SECTION 02 82 13 ASBESTOS ABATEMENT
SECTION 02 83 33 REMOVAL AND DISPOSAL OF MATERIAL CONTAINING LEAD
DIVISION 03 – CONCRETE
SECTION 03 00 00 CONCRETE
DIVISION 06 – WOOD, PLASTICS, AND COMPOSITES
SECTION 06 15 00 EXTERIOR DECKS AND DRIP PERIMETERS
DIVISION 07 – THERMAL AND MOISTURE PROTECTION
SECTION 07 30 00 STEEP SLOPE ROOFING
SECTION 07 46 00 SIDING
DIVISION 08 – OPENINGS
SECTION 08 10 00 DOORS AND FRAMES
SECTION 08 50 00 WINDOWS
DIVISION 09 -- FINISHES
SECTION 09 60 00 FLOORING
SECTION 09 90 00 PAINT AND COATINGS
DIVISION 11 – EQUIPMENT
SECTION 11 31 00 RESIDENTIAL APPLIANCES
DIVISION 12 -- FURNISHINGS
SECTION 12 30 00 CASEWORK
DIVISION 21 – FIRE SUPPRESSION
SECTION 21 10 00 FIRE SUPPRESSION
DIVISION 22 – PLUMBING
SECTION 22 11 00 FACILITY WATER DISTRIBUTION
SECTION 22 14 00 FACILITY STORM DRAINAGE
SECTION 22 41 00 RESIDENTIAL PLUMBING FIXTURES
DIVISION 23 – HEATING VENTILATING, AND AIR CONDITIONING
SECTION 23 09 00 INSTRUMENTATION AND CONTROL FOR HVAC
SECTION 23 13 00 FACILITY FUEL SYSTEMS
SECTION 23 22 00 STEAM AND CONDENSATE PIPING, HEAT EXCHANGERS, AND PUMPS
SECTION 23 50 00 CENTRAL HEATING EQUIPMENT
DIVISION 26 – ELECTRICAL
SECTION 26 00 00 ELECTRICAL
DIVISION 31 – EARTHWORK
SECTION 31 00 00 EARTHWORK
SECTION 32 31 00 FENCES AND GATES
DIVISION 01 – GENERAL REQUIREMENTS
SECTION 01 33 15 DOCUMENTATION STANDARDS
PART 1 general
1.1 SECTION INCLUDES
A. Requirements for electronic and hard copy documentation, including:
1. Electronic media format, including organization of files and file naming conventions
2. CAD standards
3. Document formatting and file naming of specifications, reports, and other text documents
4. Digital photograph standards
1.2 references
A. Definitions
1. CAD Drawing – an drawing created using computer programs. According to this definition, both hard copy print-outs and electronic files can include CAD drawings.
PART 2 products
2.1 government-furnished products
A. It is the Government’s intention to provide electronic materials to the Contractor which meet the specifications stated herein. The Government, however, reserves the right to furnish electronic materials to the Contractor which are not in conformance with these specification if it is in the best interest of the Government. The Contractor shall bring any Government-furnished materials into compliance prior to submitting them as contractually required electronic deliverables. Any effort by the Contractor to bring Government-furnished materials into compliance, must be included in the bid or fee proposal and shown as a separate line item titled ‘GFM
2.2 prohibited materials
A. No electronic or hard copy submittal shall contain copyright-protected materials. Submitted materials shall be in the public domain and freely usable and copyable without threat of copyright infringement. If the Scope of Work or Contracting Officer instructions require the submittal of copyright-protected materials the Contractor shall:
1. Pay all license fees
2. Clearly mark the materials as copyrighted
3. Indicated on the delivery media that it contains copyrighted materials
4. Mark the materials with the limitations of their use
2.3 cad drawings A. All CAD drawings shall be prepared in accordance with this guide and the latest edition of the National CAD Standard (NCS) published by the National Institute of Building Sciences. The current version of the published standard can be obtained from the NIBS web site: http://www.nibs.org . The standard published by the Tri-Services CADD/GIS Technology Center (complies with the National CAD Standard) can be obtained at http://tsc.wes.army.mil/products/standards/aec/intro.asp . Contact the project Contracting Officer for questions and clarifications.
B. The content and level of detail of CAD drawings shall be as specified in other sections of these specifications, or in the Special Provisions.
C. The Contractor is expected to have the experience and expertise to complete CAD drawings in accordance with these specifications without multiple iterations of submittal/rejection. The U.S. Coast Guard can answer questions to clarify the standards, but will not train the contractor. If the Contractor demonstrates the inability to follow these specifications, the Contracting Officer reserves the right to contract out the work to another organization and deduct sufficient funds to pay for the drafting, administrative, and all other direct and indirect costs incurred in doing so.
D. All drawing for Schematic design phases, and beyond must be produced using this standard in conjunction with AutoCADTM Release 2005. The U.S. Coast Guard cannot accept object-enabled drawings at this time. Drawings that were created with architectural, civil, mechanical or other discipline-specific products must not include imbedded objects.
E. No external references (XREFs) may be included in the completed drawing. Prior to submission all XREFs shall be bound to each drawing file using the ‘insert’ method.
F. Drawings which have image files attached shall be delivered with all the attached images. Attached image files shall be named with the drawing name as a prefix and image number as a suffix (e.g. 12X34567_A1_001.tif, 12X34567_A1_002.jpg, 12X34567_A1_003.gif, etc). Attached images shall reference the images out of the same folder as the drawing file. Valid image formats and resolutions are specified below.
G. Color, Lineweight, and Plot Style shall be assigned to drawing elements ‘BYLAYER’ or ‘BYELEMENT’. Using colors to assign lineweights at plot time is not acceptable unless otherwise approved by the Contracting Officer. Only lineweights defined by NCS are allowed.
H. Only linetypes as defined by the NCS. The LTSCALE factor shall be set to 1.0. The PSLTSCALE factor shall be set to 1.0. This allows the linetype scale to be set automatically by the paper space viewport scale.
I. The number of layers shall be kept to a practical minimum. More than 50 layers are considered excessive in a completed drawing. Layer names shall adhere to the NCS. Short form is preferred, long form will be accepted.
J. All completed drawings shall be fully purged of unused styles, layers, blocks, etc. All completed drawings shall be ‘WBLOCKed’ to a new file to remove any and all unused data and to insure a minimum file size.
K. The primary font shall be “ROMANS”. The TrueTypeTM font “ARIAL” may be used for cover sheet text, detail, section, elevation and plan titles. No third party or other WindowsTM fonts are acceptable. Drawings delivered with fonts other than those described herein will be rejected .
L. Minimum actual plotted text size on full size sheets shall be 1/10” (.10”) in order for the text to be readable on half size drawings. Minimum text size for dimensions shall be 1/10”. Text shall be set to either a thin or medium lineweight.
M. All files shall be stripped of 3rd party application data (including proxy images). Drawings that display error messages on USCG computers about missing applications will be rejected. No third party text fonts (.shx) or linetypes (.lin) will be accepted.
N. Files converted from other formats shall be checked by the Contractor for suitability and completeness prior to delivery to the USCG.
O. Only one drawing shall be in each drawing file. This restriction can be excepted in the case of floor, site, or other plans that span multiple sheets. In this case the full floor or site plan shall reside in model space and each drawing title block shall be in a separate layout (paper) space.
P. Submitted electronic drawing files shall be final and an exact representation of the submitted hardcopy drawing. When the file is opened up, no manipulations shall be required to plot the finished drawing.
Q. Revisions made to approved design drawings shall be noted using revision marks, revision clouds, and heavy lines as defined in the National CAD Standard. In general changes shall be indicated by crossing out the original drawing elements and drawing in the change. For each revision the issue block in the title block shall record the revision mark number, revision date, revision description, and reviser initials. Revisions shall also record handwritten USCG approval signatures, initials, approval signature date, and any reviser initials in the title block or issue block using block lettering. Revisions shall only be made to a copy of the original or previously revised electronic CAD file. The revised file shall be named using the original file name appended with “_rev1”, “_rev2”, etc to indicate the number of the revision (e.g. 13X02123_A5_rev1.dwg). Due care shall be taken to insure that no changes are made to the electronic files between the original or revised issue and the next revision. No revisions shall be made to hardcopy drawings. Revised drawings shall be initialed in the issue block in blue indelible ink by a registered professional.
R. If required by contract or task order, Record (as-built) changes shall be recorded to the drawings. Record changes shall be recorded as a standard revision with the following exceptions: the issue block description shall be titled “RECORD”; the drawing shall be marked in a prominent place near the lower right of the drawing with the word “RECORD” in ½” high “ROMANS” font with an bold lineweight; all sheets in the drawing set will be marked as above along with the issue block entry to record the date of the Record issue (even if no changes are required to the sheet). The Record file shall be named using the original file name appended with “_record” (e.g. 13X02123_A5_record.dwg).
S. Each plan view must include a north arrow (Site & Vicinity plans, Floor Plans, Roof Plans, etc.). Use a cross hair type north arrow showing both compass north and project north, as shown below.
T. Section and detail reference markers shall be a three-part symbol as is typically used on engineering plans, as shown below.
U. Sections are generally named with a letter, details with a number.
V. All submitted drawings shall be drawn to actual size and shall reside in AutoCADTM model space. All title blocks, sheet borders, general notes, and other general annotation will reside in layout space (paper space). Drawings that are schematic in nature and vicinity maps may also reside in paper space.
W. Plotting will done using the AutoCADTM “Color –Dependent Plot Style Table”, (.ctb) format. The plot table (CEC.ctb) can be downloaded from the FD&CC web site, www.uscg.mil/mlcpac/fdccp/contracting/index.html.
X. All site plans, plot plans, floor plans, contour maps and other drawings of this type shall be drawn to actual size in model space. The actual drawing scale will be determined by an exact setting of the paper space viewport scale. Use standard engineering/architectural scales in all cases. Each sheet shall contain a graphic scale for each different scale used on that sheet. If any portion of a drawing is not drawn to scale, that drawing shall be marked ‘NOT TO SCALE’.
Y. Use the following file naming convention for all submitted drawings:
Project Number _ Sheet Number
Examples: 13X02123_A5.dwg
13X02123_A12.dwg
Use underscores to separate project number from sheet number. Dashes, dots, tildes & etc. will not be accepted.
Z. The use of USCG sheet borders & title blocks is mandatory. Borders (ANSI A through ANSI E sizes) can be accessed through the FD&CC Pacific web site. FD&CC Pacific uses title block attributes to populate a corporate drawing database; the information must be correct and consistent. DO NOT “RENAME” OR “EXPLODE” THE SHEET BORDER, this will cause the attribute information to be corrupted. Contact the project EIC for the correct title block format & information.
AA. Use only the single character discipline designator as shown below. Do not use dashes between the discipline identifier and the sheet number.
AB. Note: For large projects, an alternative naming system may be used to easily insert additional sheets if necessary. Contact the Contracting Officer for more information.
2.4 text documents A. Text documents shall be delivered as editable Microsoft Word 2003 format document (.doc) files and as Adobe .pdf files.
B. Reports shall be named in the following format:
<project number> _ <title>
ex. 17X12345_Kodiak Cargo Pier Investigation.doc
ex. 11F45678_AIRSTA San Francisco Hazmat Survey.pdf
C. Use MS WindowsTM file naming rules subject to the following limitations: When naming a file use title case and spaces. Do not use periods for abbreviations, acronyms, or initials. Keep file names (excluding extensions) 40 characters or less in length.
D. Files shall be organized in a logical fashion such as by phase, chapter, and/or other distinct division, or as specifically required by the Contracting Officer. The number of files shall be kept to a reasonable minimum while keeping the file sizes within required limits. The complete report may be consolidated into a PDF file but the source .doc files are required to be delivered. If the consolidated report PDF files contain images, they shall be ‘Print Optimized’ using Adobe Distiller.
E. Images shall be inserted wholly into the report file and not attached. Prior to insertion, bitmap images shall be down sampled to a resolution suitable for the size of the image in the report.
PART 3 execution
3.1 electronic file deliverables
A. All drawings, specifications, photos and other electronic documents submitted to the Government shall meet the requirements of this section.
B. Electronic files shall not include copyright protected materials.
C. The contractor shall use current, recently updated virus detection software to scan all media and electronic files prior to transmittal to the Government. The Contractor will be responsible for the results of transmittal of malicious code, i.e., viruses, to the U.S. Coast Guard.
D. All electronic deliverables shall be submitted to the COTR unless otherwise directed by the Contracting Officer (KO).
E. Although email transmittal of certain files may be allowed by the Contracting Officer, final submittal of deliverables shall be on physical media.
F. Email file transmittals shall only be submitted with the permission of the COTR. The total size of email file attachments shall be less than 2 MB. Email attachments should be described in the body of the email message.
G. CD-ROM shall be used whenever electronic media is required to transmit files. Only new CD-ROM shall be used.
H. CD-ROM shall not contain documents from more than one Task Order.
I. The files shall be saved on CD-ROM in an organized fashion using appropriately named folders. If necessary, the CD-ROM should include a text file titled “README” that describes the contents of the CD and its organization.
J. CD-ROM shall be clearly labeled, and shall be delivered in a jewel case. Label information shall include:
1. Project Name
2. Contract or Task Order Number
3. Date
4. Contractor name
5. General description of contents
6. Notation that virus scanning was completed on finalized CD-ROM
K. The following electronic file formats are acceptable. Others may be permitted with written permission from the Contracting Officer.
1. MS Word .DOC = General correspondence, specifications, meeting minutes, etc.
2. MS Excel .XLS = Spreadsheets.
3. MS Powerpoint .PPT = Presentations.
4. MS Project .MPP = Project scheduling.
5. MS Access .MDB = Database.
6. Adobe Acrobat .PFD = Vendor / product information, code & standards (ANSI, ASTM, SMACMA, etc) information.
7. AutoCAD .DWG = Drawings.
8. AutoCAD .DWF = Drawing viewer.
9. .JPG = Photos.
10. .TIF = Scanned images.
11. .ZIP = File compression & consolidation (use the Zip executable .EXE for large number of files).
3.2 hard copy deliverables A. Reports shall be tabbed with labeled index tabs at major division points. Index tabs shall be durable paper with plastic laminate at wear and stress points, or other Contracting Officer approved system. Reports shall be bound in comb bindings, 3 ring binders, or other Contracting Officer approved methods. In the case where the report front and back covers are exposed paper, the paper shall be laminated in plastic on both sides of the paper.
B. Reports shall be professionally prepared and use high quality materials and techniques.
C. Use color is encouraged if it enhances the readability and quality of the information presented. Use color schemes the have high contrast which can be photocopied in black and white and retain readability and information integrity. Original report copies shall be in color and subsequent copies may be in black and white.
D. Hard Copies of O&M manuals, as-built drawings, etc. shall be submitted in a three ring binder consisting of:
1. Exterior cover with Project Name & Location, Project Number, Date of Submittal, Contractor Name, Type of Submittal (O&M Manual, As-Built Drawings, etc.).
2. Binder Edge label showing Project Name, Location and Date.
3. CD-ROM containing electronic files, labeled as specified herein.
E. Hard copy of all required submittal materials. For submittals including oversize drawings, the binder shall also include a 8 ½” x 11” print of each drawing contained on CD-ROM.
F. Drawings shall be delivered in rolls or neatly folded. Rolls and packages of folded drawings shall be labeled as specified above so that they can be easily identified without unrolling or unfolding the drawings.
SECTION 01 55 00 TRAFFIC CONTROL
PART 4 general
4.1 SECTION INCLUDES
A. Preparation and execution of Traffic Control Plans
4.2 references
A. Manual of Uniform Traffic Control Devices (MUTCD)
B. Alaska Department of Transportation and Public Facilities Standard Specifications for Highway Construction.
4.3 submittals
A. Certified Traffic Control Plan B. Supervisor resume, if applicable
4.4 Quality assurance
A. Traffic Control Plans shall be certified to be in accordance with the most recent edition of the MUTCD by a registered professional engineer (Alaska), or an officer of the Contractor.
B. When roadways maintained by parties other than the U.S. Coast Guard are affected, execution of the Traffic Control Plan shall be supervised by an individual qualified to identify and correct deficiencies. If this paragraph applies, submit a resume that demonstrates the individual’s qualifications.
PART 5 products
5.1 traffic control devices A. All traffic control devices shall be in good condition and shall meet the minimum requirements of the latest versions of MUTCD and the Alaska Department of Transportation and Public Facilities Standard Specifications PART 6 execution
6.1 preparation of traffic control plans A. Traffic Control Plans shall be prepared by qualified individuals and shall be in accordance with the latest edition of the MUTCD.
B. Submit Traffic Control Plans certified in accordance with paragraph 1.6. Execution shall not begin until the submittal has been approved in writing by the COTR.
C. The Contractor shall be responsible for collecting data necessary for preparing a good Traffic Control Plan. These data include, but are not limited to traffic patterns, vehicle types, signage, load restrictions, sight distance, and weather. The contractor shall not rely solely on information contained in the Contract Documents.
6.2 execution of traffic control plans A. Notify COTR of deviations from the approved Traffic Control Plan.
B. Report any significant traffic delays or traffic incidents to COTR within four hours, and sooner if they are serious.
C. Monitor conditions of traffic control devices frequently during each shift and replace as necessary. If signs blow down frequently, take appropriate measures to anchor them and/or increase frequency of inspections.
D. Monitor conditions during the Work and modify the Traffic Control Plan as necessary to maximize safety and reduce driver delays.
E. Remove appropriate signs (e.g., Flagger Ahead or Be Prepared to Stop) during any period of 8 hours or more in which no work is to be completed. If hazards will remain on or near road during this period, leave appropriate signs in place (e.g., No Shoulder).
SECTION 01 71 23 FIELD ENGINEERING
PART 7 general
7.1 SECTION INCLUDES
A. The Work covered by this section includes all labor materials, tools, and equipment necessary for:
1. Completion of the project in conformance with the plans and specifications, including all calculations required to accomplish the work.
2. Staking, referencing and all other actions as may be required to preserve or restore land monuments and property corners which are situated within the project area, and to establish monuments as shown on the plans.
3. Surveying.
4. Preparation of and submittal of as-built drawings.
5. Preparation and submittal of electronic file submittals.
7.2 references
A. U.S. Army Corps of Engineers:
1. EM 1110-1-1005, Control and Topographic Surveying.
2. EM 1110-1-1002, Survey Markers and Monumentation.
B. U.S. Coast Guard:
1. Architect-Engineer Guide, Appendix C, Documentation Standards
7.3 related sections
A. 01 33 15, Documentation Standards PART 8 products
8.1 NOT USED
PART 9 execution
9.1 Surveying
A. Surveying methods and procedures shall be consistent with accepted professional surveying and mapping industry standards and practice. The methods and procedures described in latest edition of EM 1110-1-1005 will be acceptable.
B. EM 1110-1-1005 adopts the American Society of Photogrammetry and Remote Sensing (ASPRS) accuracy specifications for large-scale mapping. The ASPRS accuracy specifications are included in their entirety by reference; however, a portion of these requirements are presented in the table below.
SURVEYING AND MAPPING REQUIREMENTS FOR CONSTRUCTION AND CIVIL WORKS
| PROJECT OR ACTIVITY |
| TYPICAL MAP SCALE, 1 IN. = X FT. |
| FEATURE LOCATION TOLERANCE (FEET-RMS) |
| CONTROL SURVEY ACCURACY |
| FEATURE ELEVATION TOLERANCE (FEET- RMS) |
| CONTROL SURVEY ACCURACY |
| TYPICAL CONTOUR INTERVAL (FT) |
| MAP ACCURACY CLASS |
| GENERAL SITE PLAN FEATURES AND TOPO DETAIL |
| 30-50 |
| 0.1-0.5 |
| 3RD - I |
| 0.1-0.3 |
| 3RD |
| 1 |
| 1 OR 2 |
| SURFACE/SUBSURFACE UTILITY DETAIL |
| 30-50 |
| 0.2-0.5 |
| 3RD - I |
| 0.1-0.2 |
| 3RD |
| N/A |
| 1 |
BUILDING OR STRUCTURE DESIGN
| 20-50 |
| 0.05-0.2 |
| 3RD - I |
| 0.1-0.3 |
| 3RD |
| 1 |
| 1 |
| AIRFIELD PAVEMENT DESIGN DETAIL |
| 20-40 |
| 0.05-0.1 |
| 3RD - I |
| 0.05-0.1 |
| 3RD |
| 0.5-1 |
| 1 |
| GRADING AND EXCAVATION |
| 30-100 |
| 0.05-2 |
| 3RD – I OR II |
| 1-2 |
| 3RD |
| 1-2 |
| 2 |
| MAINTENANCE AND REPAIR OR RENOVATION OF EXISTING FACILITIES (MOST AS-BUILTS) |
| 30-50 |
| 0.1-0.5 |
| 3RD - I |
| 0.1-0.5 |
| 3RD |
| 1 |
| 1 |
| RECREATIONAL SITES |
| 100 |
| 1-2 |
| 3RD - II |
| 0.2-2 |
| 3RD |
| 2-5 |
| 2 |
C. Surveying shall be completed by a fully equipped survey crew consisting of professional survey personnel experienced in performing the required surveys. Surveys shall be performed under adequate supervision and quality control measures.
D. All field data required to set and establish project control shall be recorded in standard permanent bound field books and shall be submitted upon completion of the project.
E. Horizontal control shall reference existing project area control. Controlling points shall be occupied as a station within a closed traverse that will meet or exceed Third-Order, Class I, 1:10,000 relative accuracy classification or as established for ASPRS mapping standards. The traverse shall initiate and close upon acceptable control monumentation used to establish the existing project grid system. All grid coordinates shown on the map products shall be expressed in or converted to U.S. Survey Feet. Coordinates shall be referenced to the local NAD 27, Zone 5 datum.
F. Vertical control shall be referenced to NOAA BM 10 – Power House, 1949. Controlling Points shall be established within a closed level loop that will meet or Third-Order, 1:5,000, accuracy standards as established for ASPRS mapping Standards. Elevations shall originate and close on acceptable benchmarks in the project area. Unless otherwise indicated, initiating and closing the level loop on the same benchmark shall not constitute an acceptable control circuit.
G. Existing Project/Network Control. A tabulation and/or map of existing project/network control points will be provided following award of the contract or task order. Approximately 150 control points were installed under a separate USCG contract in 2001, primarily in the well-developed industrial/housing areas on base. Prior to using any control points, the monuments should be checked to ensure that they have not been moved or disturbed.
1. If required, the contractor shall perform the necessary surveys to connect existing project control to assure that such control has sufficient relative accuracy to adequately control the overall project. Should these surveys indicate deficiencies in the existing control, the contractor shall advise the Contracting Officer or COTR. The contractor shall furnish the appropriate data indicating a deficiency. If the Contracting Officer or COTR deems it necessary to perform resurveys of the existing network, appropriate modification may be made to the contract.
2. Suitable control monumentation shall be set as required to adequately control construction phases. All stations shall be monumented in accordance with EM 1110-1-1002, Survey Markers and Monumentation. Monumentation for this project shall be Type G for horizontal and Type G for vertical, per EM 1110-1-1002 criteria, unless stated otherwise.
3. At each station, angle and distance measurements shall be made between a network station and reference/azimuth marks established in accordance with the requirements set forth in EM 1110-1-1002. All observations shall be recorded in a standard bound field book.
4. At each station, angle and distance measurements shall be made between a network station and reference/azimuth marks established in accordance with the requirements set forth in EM 1110-1-1002.
9.2 as-built drawings A. During the progress of the Work, the Contractor shall keep a careful record at the job site of all changes and corrections from the layouts shown on the Drawings, if applicable. The contractor shall enter such changes and corrections on the contract or record drawings promptly as neat red line changes to keep the record drawings current, and submit drawings to the COTR.
B. The drawings shall indicate, in addition to all changes and corrections, the actual locations of all subsurface utility lines encountered.
C. Valve boxes, splice boxes, and similar appurtenances shall be shown on the record drawings by dimensioning along the utility run from a reference point.
D. If the Contractor fails to maintain the record drawing as required herein, the Contracting Officer will consider that satisfactory progress has not been achieved for the period in question.
E. Request for pre-final inspection will not be approved until the marked prints are delivered and accepted.
F. As-built drawings shall clearly indicate the scope of the work completed during the project by placing new features on unique layers, and by labeling.
G. Final as-built drawings shall meet the accuracy requirements referenced in this section under Surveying, unless specified otherwise in the Task Order. In the absence of more specific requirements assume that the most detailed requirements indicated by a range will be required.
H. Electronic as-built drawings shall be submitted in AutoCAD 2005. The standards for CAD drafting are specified in the reference: USCG, Architect-Engineer Guide, Appendix C, which generally requires that the National CAD Standards (NCS) be followed.
I. The final as-built submittal shall consist of digital file(s) as described above and two printed copies on ANSI D (22x34) sheets. Additional requirements for electronic file submittals are specified below.
DIVISION 02 – EXISTING CONDITIONS
SECTION 02 65 00 UNDERGROUND STORAGE TANK REMOVAL
PART 10 general
10.1 SECTION INCLUDES
A. The work includes removal of non-regulated underground storage tanks (USTs) and associated piping as described on the drawings; provision of temporary fuel sources for occupied structures, cleaning and disposal of the removed USTs at an approved facility; issuance of a Release Notification if contamination is found, removal and temporary stockpiling and testing of contaminated soil, and remediation of contaminated soils (if encountered); backfilling or excavations with clean material. Perform work in accordance with the requirements specified herein.
10.2 MEASUREMENT AND PAYMENT
10.3 references
A. The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
1. ASTM D 4397 (1991) -- Polyethylene Sheeting for Construction, Industrial, and Agricultural Applications
2. 29 CFR 1910.145 -- Accident Prevention Signs and Tags
3. ADEC UST Procedures Manual (December 1, 1999)
4. ADEC UST Standard Sampling Guide
5. ADEC 18 AAC75 -- Oil and Other Hazardous Substances Pollution Control
B. Definitions
1. BTEX: Benzene, toluene, ethyl benzene, and xylene.
2. Petroleum Contaminated Soil (PCS): Soils containing concentrations greater than 50 milligrams per kilograms (mg/kg) gasoline range, 100 mg/kg diesel range, 0.02 mg/kg benzene, or 15 mg/kg total BTEX when tested as specified herein.
3. Petroleum Contaminated Water: Water containing concentrations greater than 1.3 parts per million (ppm) gasoline range, 1.5 ppm diesel range, 1.1 ppm residual range, 0.005 ppm benzene, 1.0 mg/kg Toluene, 0.7 mg/kg Ethylbenzene, or 10 mg/kg total Xylenes when tested as specified herein.
C. Abbreviations and Acronyms
10.4 submittals
A. Manufacturer's Catalog Data: Field Screening Photo Ionization Detector (PID).
B. Excavation and Material Handling Plan: Submit a plan describing methods, techniques, and phases of dealing with the excavation, a sequence of operations, the method of excavation, hauling, and handling of the potentially contaminated materials (including segregating soils and stockpiling), the proposed materials and equipment. Plan must include proposed methods to prevent the further spread of contamination into the environment. The plan, not to be combined with other hazard abatement plans, shall be prepared, signed, and sealed by the QP.
C. Tank and Piping Removal and Disposal Plan: The contractor shall submit a Tank and Piping Removal and Disposal Plan that describes methods, task sequence and schedule for testing, cleaning, inerting, inspecting, removing, and disposing of tanks.
D. Sampling and Testing Plan: Prepare and submit sampling and testing plan. Include the names of testing laboratories to be used to accomplish analysis of contaminated soil and water. Provide evidence that the laboratory is approved for petroleum analysis by the Alaska Department of Environmental Conservation. Describe field-screening methods, sampling procedures, testing methods, and quality control procedures. For sample reports, show sample identification for location, date, time, sample method, contamination level, name of individual sampler, identification of laboratory, and quality control procedures.
E. Qualified Person (QP) Qualifications: The contractor shall provide ADEC qualified personnel as found in ADEC UST Standard Sampling Guide. Submit the name, address, and telephone number of the QP selected to perform the duties in paragraph entitled "Qualified Person." Submit proper documentation that the QP meets the ADEC requirements.
F. Closeout Report: Submit a closeout report covering the UST excavations containing following items: Sketches of each excavation with notations denoting locations where PCS was encountered, the test results including readings and locations, chain of custody forms, the volume of soil removed and delivered to the remediation facility, laboratory test results associated with each excavation, a copy of all paperwork obtained from the lab, and certificate of remediation from the commercial remediation facility.
10.5 Quality assurance
A. Training: Instruct employees on the dangers of fuel oil exposure, and applicable OSHA and ADEC regulations.
B. Qualified Person: Obtain the services of a Qualified Person (QP), certified by ADEC to review and approve the PCS removal plan and perform field screening, take samples for analytical analysis, and write the close out report.
PART 11 products
11.1 plastic sheeting A. Conforming with ASTM D4397.
B. Sheeting used for underlayer of temporary soil stockpiles shall be 20 mil.
PART 12 execution
12.1 Protection of Workers and the Environment:
A. Protect workers and the environment from PCS hazards.
B. UST Control Area
1. Establish a UST control area to prevent unauthorized entry of personnel. Rope off area and provide 29 CFR 1910.145 signs at approaches and around perimeter. Locate signs at such a distance that personnel may read the sign and take the necessary precautions before entering the area. OSHA approved safety fencing is required around all excavations to effectively isolate the construction area from access to passers by. Any excavations left unattended shall be surrounded by such fencing. Allow only personnel briefed on the elements and trained as specified herein into the area. Do not permit food, drink, or smoking materials in the control area. Smoking is not permitted within 50 feet of the PCS control area. Provide "No Smoking" signs.
C. Air Quality
1. Include provisions to ensure that explosive atmospheres are not encountered in the excavations. Provide air monitoring to ensure workers safety as determined by the QP and as specified herein. If explosive vapors are encountered, immediately stop work and notify the Contracting Officer.
D. PCS Spill Prevention
1. Use appropriate vehicles and operating practices to prevent spillage or leakage of contaminated materials from occurring during operations. Inspect vehicles leaving the contaminated soil removal site to ensure that no contaminated soil adheres to the wheels or undercarriage. Immediately report any spills to the Contracting Officer and provide cleanup.
12.2 Excavation Procedures
A. Notify the Contracting Officer at least 48 hours prior to the start of excavation operations. Use methods and equipment that result in minimal disturbance to remaining soil beyond the excavation limits. Stage operations to minimize the time the excavation is exposed to the weather.
B. If contamination is encountered:
1. Notify the Contracting Officer
2. Provide protective measures around the area of contaminated soils to prevent runoff water from entering the excavation
3. Provide control measures to prevent contaminated runoff and/or sediment from leaving the excavation areas.
4. Use methods to reduce the amount of soil contaminated due to excavation operations.
5. Remove and dispose of any material that becomes contaminated as a result of the Contractor's operation, at no additional cost to the Government.
C. Underground Utilities:
1. Location of the existing utilities indicated is approximate and other underground utilities may be present.
2. Physically verify the location and elevation of the existing utilities indicated prior to starting construction.
3. If utilities other than those indicated are found, stop work and contact the Contracting Officer.
4. Protect existing utilities from damage and intrusion of PCS.
D. Excavation Limits:
1. Remove the minimum amount of soil necessary for removal of existing piping and tanks, and the installation of new piping and tanks.
2. Unless indicated otherwise, new piping shall follow the path of existing piping. If significant contamination is found, alternative routes may be directed by the Contracting Officer.
3. Remove contaminated soil encountered to the following limits, unless otherwise approved or directed by the Contracting Officer:
a. Excavate no closer than within 2 feet of any building foundation or other permanent structure.
b. Remove all contaminated soil to a distance of 4 feet from the sides and bottom of the tanks.
c. Remove all contaminated soil to a distance of 2 feet below, and 2 feet to each side of piping runs.
d. Collect samples and test by field screening. If field screening indicates the extremities of the excavation still exceed regulatory thresholds, cease excavation and notify the Contracting Officer.
4. If contaminated groundwater is encountered, notify the Contracting Officer.
5. Contaminated soils shall be temporarily stockpiled IAW the contractor’s Excavation and Material Handling Plan.
E. Field Screening and Segregating Excavated Material (PCS):
1. All material excavated shall be screened in the field with a Photo Ionization Detector (PID) using the Head Space Screening Method as found in the UST Procedures Manual 1999.
2. Based on field screening results the excavated material shall be segregated into temporary stockpiles at the excavation site and sampled according to the UST Procedures Manual, as follows:
a. Temporary stockpile 1: Essentially clean (no evidence of contamination). Return this soil to the excavation as backfill.
b. Temporary stockpile 2: Contaminated, lab sampled. Return this soil to the excavation if below ADEC Cleanup Standards. If above cleanup standards, remove from site to a remediation facility. Remediated soil is not to be returned to the government.
3. Temporary stockpiles shall be clearly marked as Clean or Contaminated. If placed on soil (as opposed to an asphalt or concrete) surface, perform a baseline sample of the soil prior to constructing the cell.
F. Confirmation Sampling and Testing:
1. Soil from the Clean Pile shall be used as backfill without further testing. The temporarily stockpiled PCS Pile shall be sampled and analyzed for RRO, DRO, GRO and BTEX compounds. At least two grab samples must be obtained from each temporary stockpile of 50 cubic yards or smaller, with one additional sample for each additional 50 cubic yards per pile. Compositing of samples for analysis is not allowed. Analyze samples in accordance with ADEC Table B2, Method Two, (over 40 inch zone )method AK 103, AK 102, AK 101, and EPA method 8020 by an ADEC approved laboratory. Provide quality control in accordance with EPA guidelines, and as a minimum as follows:
a. Duplicate samples - collect and analyze duplicate soil samples at the rate of 10 percent of the total number of samples (rounded to the next highest number).
b. Matrix spike and matrix spike duplicate - collect one matrix spike sample for every 20 samples collected (rounded to the next highest number). Split the matrix spike sample, and analyze both the matrix spike and the matrix spike duplicate.
G. Temporarily Stockpiled Material:
1. If field screening detects no contamination, the soil requires no special handling, and shall be used as backfill. If field screening indicates the presence of contamination, place soil in a temporary containment area near the excavation area or as specified. Bottom liner shall be 20 mil. Divert water from the containment area. Cover containment area with 10 mil polyethylene liner meeting 18 AAC75.370 Table D. Using field-screening methods, segregate the soil with detectable contamination into separate piles representing suspected clean and suspected contaminated soil. Place excavated soil on the liner and cover. Secure edges of sheets to keep the polyethylene sheeting in place. Secure the edges of the cover lapped over the bottom liner to prevent water from running through the soil. Cover excavated contaminated soil at all times when not being worked. Maintain sheeting and replace when worn or ripped.
H. Contaminated Water:
1. Prevent surface water and rainwater from entering the excavations. It is expected that groundwater will not be encountered during UST removal. However, if groundwater does collect within the excavation, and it appears contaminated, notify the Contracting Officer and await direction.
I. Tank Cleaning and Disposal
1. Prior to disposal the contractor shall clean the tanks to remove all remaining liquids and sludges in accordance with the submitted and approved “Tank and Piping Removal and Disposal Plan”. Cleaning and tank atmosphere testing shall be in accordance with API RP-1604, "Cleaning Petroleum Storage Tanks". All piping to be removed shall be cleaned to similar standards. The contractor shall test the tank atmosphere and the excavation area for flammable or combustible vapor concentrations with a combustible gas indicator until the tank is removed from the excavation and site.
2. After a tank has been vapor-freed, it should be rendered and labeled unsuitable for future use as a storage tank by puncturing, cutting, or other appropriate methods prior to leaving the site.
3. Tanks should be labeled after removal from the ground but prior to removal from the site. Regardless of the condition of the tank, the label should contain the following warning (in legible letters at least 2 inches high) against certain types of reuse. The former contents and present vapor state of each tank, including vapor-freeing treatment and date should also be indicated.
TANK HAS CONTAINED HEATING OIL
NOT VAPOR FREE
NOT SUITABLE FOR STORAGE OF FOOD OR LIQUIDS INTENDED FOR HUMAN OR ANIMAL CONSUMPTION
DATE OF REMOVAL: MONTH/DAY/YEAR
4. Disposal shall occur at a facility approved by ADEC to accept UST's. The contractor shall obtain any permits and pay all fees required for the disposal.
J. Transportation and Remediation:
1. Transportation: Transport petroleum contaminated soils in vehicles to prevent spillage onto streets or other non-contaminated surfaces.
2. Remediation: Obtain remediation as specified in the task order.
K. Cleanup:
1. Maintain surfaces of the PCS control area free of accumulations of PCS. Restrict the spread of dust and debris; keep waste from being distributed over work area. Do not remove the PCS control area and warning signs prior to the Contracting Officer's approval. Reclean areas showing residual PCS.
L. Backfilling, Grading, Topsoiling, and Seeding:
1. Provide backfill, compaction, grading, and seeding in accordance with standard practices or as specified on the drawings.
SECTION 02 82 13 ASBESTOS ABATEMENT
PART 13 general
13.1 SECTION INCLUDES
A. The work covered by this section includes the handling of asbestos containing materials, and describes some of the resultant procedures and equipment required to protect workers and occupants of the building or area, or both, from contact with airborne asbestos fibers. More specific operational procedures will be outlined in the Asbestos Hazard Abatement Plan called for elsewhere in this specification. Provide work as outlined in 29 CFR 1926.1101.
13.2 references
A. The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by the basic designation only.
B. American National Standards Institute (ANSI):
1. ANSI Z88.2
(1992), Respiratory Protection
C. American Society for Testing and Materials (ASTM):
1. ASTM C 732 (1995), Aging Effects of Artificial Weathering on Latex Sealants
2. ASTM D 522 (1993; Rev. A), Mandrel Bend Test of Attached Organic Coatings
3. ASTM D 1331 (1989; R 1995), Surface and Interfacial Tension of Solutions of Surface-Active Agents
4. ASTM D 2794 (1993), Resistance of Organic Coatings to the Effects of Rapid Deformation (Impact)
5. ASTM E 84 (1995; Rev. B), Surface Burning Characteristics of Building Materials
6. ASTM E 96
(1995), Water Vapor Transmission of Materials
7. ASTM E 119
(1995; Rev. A), Fire Tests of Building Construction and Materials
8. ASTM E 736 (1992), Cohesion/Adhesion of Sprayed Fire-Resistive Materials Applied to Structural Members
9. ASTM E 1368 (1990), Visual Inspection of Asbestos Abatement Projects
D. Code of Federal Regulations (CFR):
1. 29 CFR 1926.103, Respiratory Protection
2. 29 CFR 1926.200, Accident Prevention Signs and Tags
3. 29 CFR 1926.59, Hazard Communication
4. 29 CFR 1926.1101, Asbestos, Tremolite, Anthophyllite, Actinolite
5. 40 CFR 61-SUBPART A, General Provisions
6. 40 CFR 61-SUBPART M, National Emission Standard for Asbestos
7. 40 CFR 763, Asbestos Containing Material in Schools
E. Environmental Protection Agency (EPA):
1. EPA 560/5-85-024, Guidance for Controlling Asbestos Containing Materials in Buildings F. Underwriter’s Laboratories, Inc. (UL):
1. UL 586 (1990), High-Efficiency, Particulate, Air Filter Units
13.3 DEFINITIONS
A. ACM: Asbestos Containing Materials.
B. Amended Water: Water containing a wetting agent or surfactant with a maximum surface tension of 29 dynes per centimeter when tested in accordance with ASTM D 1331.
C. Asbestos: The term asbestos includes chrysotile, amosite, crocidolite, tremolite asbestos, anthophyllite asbestos, and actinolite asbestos and any of these minerals that has been chemically treated or altered. Materials are considered to contain asbestos if the asbestos content of the material is determined to be at least one percent.
D. Asbestos Control Area: That area where asbestos removal operations are performed which is isolated by physical boundaries that assist in the prevention of the uncontrolled release of asbestos dust, fibers, or debris.
E. Asbestos Fibers: Those fibers having an aspect ratio of at least 3:1 and longer than 5 micrometers as determined by National Institute for Occupational Safety and Health (NIOSH) Method 7400.
F. Asbestos Permissible Exposure Limit: 0.1 fibers per cubic centimeter of air as an 8-hour time weighted average measured in the breathing zone as defined by 29 CFR 1926.1101 or other Federal legislation having legal jurisdiction for the protection of workers health.
G. Encapsulants: Specific materials in various forms used to chemically or physically entrap asbestos fibers in various configurations to prevent these fibers from becoming airborne. There are four types of encapsulants as follows that must comply with performance requirements as specified herein.
1. Removal Encapsulant (can be used as a wetting agent)
2. Bridging Encapsulant (used to provide a tough, durable surface coating to asbestos containing material)
3. Penetrating Encapsulant (used to penetrate the asbestos containing material encapsulating all asbestos fibers and preventing fiber release due to routine mechanical damage)
4. Lock-Down Encapsulant (used to seal off or "lock-down" minute asbestos fibers left on surfaces from which asbestos containing material has been removed).
H. HEPA Filter Equipment: High efficiency particulate air (HEPA) filtered vacuum and/or exhaust ventilation equipment with a filter system capable of collecting and retaining asbestos fibers. Filters shall retain 99.97 percent of particles 0.3 microns or larger as indicated in UL 586.
I. Personal Sampling: Air sampling, which is performed to determine asbestos fiber concentrations within the breathing zone of a specific employee, as performed in accordance with 29 CFR 1926.1101.
J. Private Qualified Person (PQP): In addition to the definition of competent person in 29 CRF 1926.32(f), a person who is capable of identifying existing asbestos hazards as defined in 29 CFR 1926.1101, selecting the appropriate control strategy, has the authority to take prompt corrective measures to eliminate them. The PQP shall have EPA Model Accreditation Plan “Contractor/Supervisor” training as required by 40 CFR 763; and has successfully completed the National Institute of Occupational Safety and Health (NIOSH) 582 course "Sampling and Evaluating Airborne Asbestos Dust" or equivalent. The PQP must be qualified to perform visual inspections as indicated in ASTM E 1368.
K. Time Weighted Average (TWA): The TWA is an 8-hour time weighted average airborne concentration of asbestos fibers.
L. Wetting Agent: A chemical added to water to reduce the water's surface tension thereby increasing the water's ability to soak into the material to which it is applied. An equivalent wetting agent must have a surface tension of at most 29 dynes per centimeter when tested in accordance with ASTM D 1331.
administrative requirements
M. Coordination
N. Preinstallation Meetings
O. Sequencing
P. Scheduling
13.4 submittals
A. Asbestos Hazard Abatement Plan: Submit a detailed plan of the safety precautions such as fall protection, and confined space entry procedures and equipment and work procedures to be used in the removal and demolition of materials containing asbestos. The plan shall be prepared, signed, and sealed by the PQP. Provide a Table of Contents for each abatement submittal, which shall follow the sequence of requirements in the contract. Such plan shall include but not be limited to the precise personal protective equipment to be used including, but not limited to, respiratory protection, type of whole-body protection, the location of asbestos control areas including clean and dirty areas, buffer zones, showers, storage areas, change rooms, removal method, interface of trades involved in the construction, sequencing of asbestos related work, disposal plan, type of wetting agent and asbestos sealer to be used, locations of local exhaust equipment, planned air monitoring strategies, and a detailed description of the method to be employed in order to control environmental pollution. The plan shall also include (both fire and medical emergency) response plans. The Asbestos Hazard Abatement Plan is to be submitted to the Contracting Officer for information only – not for approval. The plan will be enforced as if an addition to the specification. Any changes required in the specification as a result of the plan shall be identified specifically in the plan to allow for free discussion prior to starting work.
B. Testing Laboratory: Submit the name, address, and telephone number of each testing laboratory selected for the sampling, analysis, and reporting of airborne concentrations of asbestos fibers along with certification that each laboratory is American Industrial Hygiene Association (AIHA) accredited and that persons counting the samples have been judged proficient by current inclusion on the AIHA Asbestos Analysis Registry (AAR) and successful participation of the laboratory in the Proficiency Analytical Testing (PAT) Program.
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .