Excerpt from original construction specifications –
Photometric Performance of High Mast System
1. Maintained illumination performance with all lamps operating (include maintenance factors of 0.72 (MH) and 0.08 (HPS) and tilt factors: Based upon specified pole locations, heights and selected luminaire types; roadway, parking and drive areas shall meet the following lighting levels and performance characteristics.
a. The area generally considered to be from the east edge of building segments A and B to the east shoulder of northbound I-29 shall average a minimum of 15 LUX. No area shall exceed an average to minimum ratio of
3 to 1 and a maximum to minimum ratio of 6 to 1. The north boundary for, illumination performance, shall be 55 meters due north of pole ‘T7’; the south boundary shall be 55 meters due south of pole ‘T6’.
b. The area generally considered to be from the west edge of building segments A and B to the west edge of paved driveway and parking area
(west of Segment C) shall average a minimum of 50 LUX. No area shall exceed an average to minimum ratio of 3 to 1 and a maximum to minimum ratio of 6 to 1. The north boundary for, illumination performance, shall be the Canadian/US border; the south boundary shall be 55 meters due south of pole ‘T4’.