2_GLEN131403_Drawings.pdf
PDF 701 KB Posted
- Attached to
- B500 HVAC Federal contract opportunity
- Solicitation number
- GLEN13-1403_Solicitation
About this file
Drawings
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| RFI_Questions_3_Jul_2018.docx | DOCX document | |
| FA255018R1012_GLEN_13-1403_Amendment_002.pdf | ||
| M-101_-_MECHANICAL_DUCTWORK_FLOOR_PLAN_13-1403.PDF | ||
| Amendment_002_Information.pdf | ||
| GLEN_13-1403_SOW_Addendum.pdf | ||
| Amendment_Information.docx | DOCX document | |
| 1_GLEN131403_SOW.pdf | ||
| 4_GLEN131403_AF_Form_66.xls | XLS spreadsheet | |
| 0_FA2550-18-R-1012.pdf | ||
| 3_Specifications.pdf | ||
| 5_Wage_Determination.pdf |
Show all 11
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
THE SEAL APPEARING ON THIS
BY JOHN R. ODUM.
DOCUMENT WAS AUTHORIZED
E
N
R
GIADO
L O
E F
P R
O
C O
A S
S
I NO N G
EL
I
31890
J
R
ST
RE
E E
E D
R
H M N
O
R. ODU
THE SEAL APPEARING ON THIS
BY KEVIN PETER BRESLIN, JR.
DOCUMENT WAS AUTHORIZED
E
N
R
GIADO
L O
E F
P R
O
C O
A S
S
I NO N G
EL
I
E
32681K
R R
S
ST
RE
E E
E D
R
V
B
NI
E
LIN
PE
TER
JR
FOR OFFICIAL USE ONLY
FOR OFFICIAL USE ONLY
FO
R
O
FF
IC
IA
L U
S E
O N
LY
FO
R
O
FF
IC
IA
L U
S E
O N
LY
DESIGN, REPAIR HVAC UNITS,
BUILDING 500
ELECTRICAL
ENGINEER
MECHANICAL
ENGINEER
SEPTEMBER 2013
CONSTRUCTION SET SUBMITTAL
ISSUED FOR CONSTRUCTION
DRAWING INDEX
BUILDING 500
SCHRIEVER AFB
BID OPTION #1
REPLACE EXISTING 3-WAY CHILLER WATER COIL
CONTROL VALVES WITH NEW 2-WAY CHILLED
WATER COIL CONTROL VALVES.
BID OPTION #2
PROVIDE CARBON DIOXIDE SENSORS AND DEMAND
CONTROLLED VENTILATION (DCV) OUTSIDE AIR
OVERRIDE SEQUENCE.
P.E. 32681 ON 18 SEPT 2013 P.E. 31890 ON 18 SEPT 2013
Sheet Number Sheet Name Sheet Issue Date
M-001 MECHANICAL LEGEND 18 SEPT 2013
M-101 MECHANICAL DUCTWORK FLOOR PLAN 18 SEPT 2013
M-102 MECHANICAL PIPING FLOOR PLAN 18 SEPT 2013
M-501 MECHANICAL DETAILS, SCHEDULES & ISOMETRICS 18 SEPT 2013
M-601 MECHANICAL CHILLED WATER FLOW SCHEMATICS 18 SEPT 2013
M-701 MECHANICAL SYSTEM CONTROL DIAGRAMS 18 SEPT 2013
M-702 MECHANICAL CONTROL FLOOR PLAN 18 SEPT 2013
E-001 ELECTRICAL LEGEND 18 SEPT 2013
E-101 ELECTRICAL FLOOR PLAN 18 SEPT 2013
E-102 ELECTRICAL SCHEDULES 18 SEPT 2013
GENERAL SYMBOLS
ADJ ADJUSTABLE
AFF ABOVE FINISHED FLOOR
AMPS AMPERES
ATC ACOUSTICAL TILE CEILING
BHP BRAKE HORSEPOWER
BTU BRITISH THERMAL UNIT
BTUH BTU PER HOUR
CD CONDENSATE DRAIN
CFM CUBIC FEET PER MINUTE
CFH CUBIC FEET PER HOUR
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
CO CARBON MONOXIDE
CO2 CARBON DIOXIDE
COND CONDENSATE
CW DOMESTIC COLD WATER
CWR CONDENSER WATER RETURN
CWS CONDENSER WATER SUPPLY
DB DRY BULB
dB DECIBELS
DDC DIRECT DIGITAL CONTROL
DEG DEGREES
DEG F DEGREES FAHRENHEIT
DN DOWN
DPT DIFFERENTIAL PRESSURE TRANSMITTER
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EDB ENTERING DRY BULB TEMPERATURE
ESP EXTERNAL STATIC PRESSURE
EWB ENTERING WET BULB TEMPERATURE
EWT ENTERING WATER TEMPERATURE
°F DEGREES FAHRENHEIT
FF FINAL FILTER
FILL FILL LINE
FLA FULL LOAD AMPS
FPM FEET PER MINUTE
FT FEET
FT HD FEET HEAD
G NATURAL GAS
GA GAUGE
GC GENERAL CONTRACTOR
GPM GALLONS PER MINUTE
HC HEATING COIL
HP HORSEPOWER
HR HOUR
HWR HEATING WATER RETURN
HWS HEATING WATER SUPPLY
Hz HERTZ
IF INTERMEDIATE FILTER
IN W.G. INCHES OF WATER GAUGE
kPa KILOPASCALS kW KILOWATT
LAT LEAVING AIR TEMPERATURE
LDB LEAVING DRY BULB TEMPERATURE
LRA LOCKED ROTOR AMPS
LVG LEAVING
LWB LEAVING WET BULB TEMPERATURE
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
MCA MINIMUM CIRCUIT AMPACITY
MBH THOUSAND BTU PER HOUR
MIN MINIMUM
MTWS MEDIUM TEMP WATER SUPPLY
MTWR MEDIUM TEMP WATER RETURN
MUA MAKE-UP AIR
MZ MULTI-ZONE
NC NORMALLY CLOSED
NGV NATURAL GAS VENT
NO NORMALLY OPEN
NTS NOT TO SCALE
MECHANICAL ABBREVIATIONS
GENERAL EQUIPMENT
AHU AIR HANDLING UNIT
AC AIR COMPRESSOR
AS AIR SEPARATOR
AV AIR VENT
B BOILER
BBH BASEBOARD HYDRONIC HEATER
BP BOILER PUMP
CC COOLING COIL
CH CHILLER
CHWP CHILLED WATER PUMP
CRAC COMPUTER ROOM AIR CONDITIONING
CRU CONDENSATE RECOVERY UNIT
CT COOLING TOWER
CUH CABINET UNIT HEATER
CWP CONDENSER WATER PUMP
DXE DOMESTIC HOT WATER HEAT EXCHANGER
EAU EXHAUST AIR UNIT
EF EXHAUST FAN
EG EXHAUST GRILLE
ERV ENERGY RECOVERY VENTILATOR
ET EXPANSION TANK
F&T FLOAT AND THERMOSTATIC STEAM TRAP
FCU FAN COIL UNIT
FD FIRE DAMPER
FPVAV FAN POWERED VARIABLE AIR VOLUME UNIT
FSD FIRE SMOKE DAMPER
FT FLASH TANK
FTU FAN TERMINAL UNIT
GF GLYCOL FEEDER DOSING PUMP
HC HEATING COIL
HP HEAT PUMP
HRCP HEAT RECOVERY PUMP
HUM STEAM HUMIDIFICATION UNIT
HWP HEATING WATER CIRCULATION PUMP
HX HEAT EXCHANGER
IB INVERTED BUCKET TRAP
L LOUVER
LS LINEAR SLOT SUPPLY DIFFUSER
P PUMP
PHC HYDRONIC PREHEAT COIL
RAD REFRIGERATED AIR DRYER
RF RETURN AIR FAN
RG RETURN GRILLE
RH RELIEF HOOD
RHC REHEAT COIL
SA SUPPLY ATTENUATOR
SCBA SELF CONTAINED BREATHING APPARATUS
SD SUPPLY DIFFUSER
SF SUPPLY FAN
SG SUPPLY GRILLE
SR SUPPLY REGISTER
ST STEAM TRAP
TG TRANSFER GRILLE
UH UNIT HEATER
UNO UNLESS NOTED OTHERWISE
VAV VARIABLE AIR VOLUME UNIT
WB WET BULB TEMPERATURE
WC WATER COLUMN
WG WATER GAUGE
MECHANICAL LEGEND
HYDRONIC PIPING ABBREVIATIONS
CHS CHILLED WATER SUPPLY
CHR CHILLED WATER RETURN
HWR HEATING WATER RETURN
HWS HEATING WATER SUPPLY
GLR GROUND LOOP RETURN
GLS GROUND LOOP SUPPLY
CD CONDENSATE DRAIN
VALVE, SEE SPECIFICATIONS
FOR VALVE TYPE
CHECK VALVE
TWO WAY CONTROL VALVE
THREE WAY CONTROL VALVE
BALANCING VALVE
SOLENOID CONTROL VALVE
PRESSURE REDUCING VALVE
FLEXIBLE CONNECTION
TEST PLUG
PRESSURE GAUGE
MANUAL AIR VENT
PIPE BREAK
DIRECTION OF FLOW
PIPE UP
PIPE DOWN
PIPE T DOWN
PIPE T UP
PIPE CAP
UNION
REDUCER
PIPE ANCHOR
PIPE GUIDE
STRAINER
STRAINER WITH VALVE AND
HOSE CONNECTION
THERMOMETER OR SIGHT GLASS
FLOW METER
LPS LOW PRESSURE STEAM
LPC LOW PRESSURE CONDENSATE
HPS HIGH PRESSURE STEAM
HPC HIGH PRESSURE CONDENSATE
RL REFRIGERANT LIQUID
RS REFRIGERANT SUCTION
PIPE SLOPE
PC PUMPED CONDENSATE
CONNECT NEW TO
EXISTING AT THIS POINT
DEMOLISH TO THIS POINT
10 KEYNOTE
EQUIPMENT DESIGNATIONAHU-1
1. SOME ABBREVIATIONS AND SYMBOLS SHOWN ON THIS SHEET MAY NOT BE
USED IN THIS DRAWING SET.
2. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS PRIOR TO
ORDERING EQUIPMENT OR ANY FABRICATION.
3. IF IT BECOMES NECESSARY DURING DEMOLITION TO TEMPORARILY REMOVE
ANY EQUIPMENT, PIPING, ETC. WHICH IS NOT SPECIFICALLY NOTED TO BE
REMOVED (THEREBY IMPLYING THAT THEY ARE TO BE LEFT FOR FUTURE
USE), THE CONTRACTOR SHALL REINSTALL SAID SYSTEMS TO FULLY
OPERABLE CONDITION IN THEIR ORIGINAL LOCATIONS.
4. FILE METHOD OF PROCEDURE (MOP) DOCUMENTATION AT LEAST THREE
WEEKS PRIOR TO ANY SYSTEM INTERRUPTION, SHUTDOWN, DEMOLITION OR
CHANGE-OVER.
5. ANY DAMAGE TO THE OWNER'S OR TENANT'S PROPERTY, TO THE
STRUCTURE OR BUILDING, OR TO EQUIPMENT RESULTING FROM THE
CONTRACTOR'S OPERATIONS SHALL BE REPAIRED OR REPLACED BY THE
CONTRACTOR TO THE SATISFACTION OF THE OWNER WITHOUT ADDITIONAL
COST TO THE OWNER. REPAIR OR REPLACEMENT SHALL, AS A MINIMUM,
EQUAL EXISTING CONDITIONS.
6. ASBESTOS IS NOT EXPECTED BE PRESENT IN THE BUILDING. IF DURING THE
COURSE OF THE WORK MATERIAL WHICH MAY CONTAIN ASBESTOS IS
DISCOVERED, STOP WORK IMMEDIATELY AND NOTIFY THE COTR.
7. ALL NEW UNINSULATED PIPING SHALL BE DEGREASED, PRIMED AND PAINTED
TO MATCH EXISTING, SEE SECTION 09 90 00 FOR SPECIFICATION.
8. ALL NEW PIPING SHALL BE PROVIDED WITH PIPING IDENTIFIERS PER
SECTION 09 90 00.
9. ALL NEW STEEL STRUCTURAL AND SUPPORT ITEMS SHALL BE DEGREASED,
PRIMED AND PAINTED TO MATCH EXISTING, SEE SECTION 09 90 00 FOR
SPECIFICATION.
10. ALL INSULATED PIPING SHALL INCLUDE SHEET METAL SADDLES AND 3 LB
PER C.F. POLYISOCYANURATE INSERTS AT THE HANGERS PER SECTION 23 07
00.
11. SEE MECHANICAL PLANS FOR EXISTING HOUSEKEEPING PAD LOCATIONS
AND APPROXIMATE SIZES. THE CONTRACTOR SHALL COORDINATE
HOUSEKEEPING PAD SIZES AND LOCATIONS BASED ON ACTUAL EQUIPMENT
PROVIDED AND EQUIPMENT LAYOUT.
12. INTERRUPTION TO THE BUILDING CHILLED WATER LOOP IS ACCEPTABLE
FOR A DURATION OF UP TO 8 HOURS ON NIGHTS (1700-0500) AND WEEKENDS
ONLY.
13. REFER TO PROJECT SPECIFICATIONS FOR SITE ACCESS RESTRICTIONS AND
ESCORT PROCEDURES.
14. CONTRACTOR SHALL PROVIDE UNIQUE IDENTIFIERS FOR ALL NEW VALVES,
METERS AND INSTRUMENTATION. THE IDENTIFIER NOMENCLATURE SHALL BE
COMPATIBLE WITH THE SITE STANDARD AND COORDINATED WITH THE SITE
MAINTENANCE STAFF PRIOR TO SUBMITTING THE BAS AND PIPING SHOP
DRAWINGS.
15. SEE SPECIFICATION SECTION 23 64 26 FOR PIPE INSTALLATION
REQUIREMENTS AND SUPPORT REQUIREMENTS.
16. CONTRACTOR SHALL PREPARE DETAILED STEP-BY-STEP CONSTRUCTION
SCHEDULE DETAILING ALL WORK TASKS AND OPERATIONS REQUIRED TO
ACCOMPLISH PROJECT WITHOUT CHILLED WATER FLOW INTERRUPTION,
SUBJECT TO NOTES ABOVE. CONSTRUCTION SCHEDULE DETAILING SHALL
BE SUBMITTED CONCURRENT WITH MOBILIZATION AND EQUIPMENT
SUBMITTALS. SEE SPECIFICATION SECTION 01 33 00 FOR SUBMITTAL
REQUIREMENTS.
17. PROVIDE HANGARS AS REQUIRED BY DIVISION 23. HANGARS SHALL BE RIGID
AND SUPPORTED FROM STRUCTURAL STEEL. HANGARS SHALL NOT BE
SUPPORTED FROM THE ROOF DECK.
GENERAL NOTES
V VENT
G NATURAL GAS
MTWR MEDIUM TEMP WATER RETURN
MTWS MEDIUM TEMP WATER SUPPLY
RWL
NGV
RAIN WATER LEADER
NATURAL GAS VENT
OA OUTSIDE AIR
OAT OUTSIDE AIR TEMPERATURE
Pa PASCALS
PD PRESSURE DROP
PF PRE FILTER
PH PHASE
PPE PERSONAL PROTECTIVE EQUIPMENT
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIG PSI GAUGE
PT PRESSURE TRANSMITTER
RA RETURN AIR
RH RELATIVE HUMIDITY
RLA RUNNING LOAD AMPS
RPM REVOLUTIONS PER MINUTE
RWL RAIN WATER LEADER
SA SUPPLY AIR
SOV SHUT OFF VALVE
SP STATIC PRESSURE
TDH TOTAL DYNAMIC HEAD
TEMP TEMPERATURE
TSP TOTAL STATIC PRESSURE
TT TEMPERATURE TRANSMITTER
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
V VOLTS
WB WET BULB TEMPERATURE
WC WATER COLUMN
WG WATER GAUGE
GENERAL
HYDRONIC PIPING SYMBOLS
THE SEAL APPEARING ON THIS
BY KEVIN PETER BRESLIN, JR.
DOCUMENT WAS AUTHORIZED
E
N
R
GIADO
L O
E F
P R
O
C O
A S
S
I NO N G
EL
I
E
32681K
R R
S
ST
RE
E E
E D
R
V
B
NI
E
LIN
PE
TER
JR
D E
S C
R
IP
T
IO
N M
A R
K D
A T
E A
P P
R
D E
S
IG
N E
D B
Y
D W
N B
Y
S U
B M
IT
T
E D
B Y
F
IL
E N
A M
E
S
IZ
E
P
LO
T S
C A
LE
P
LO
T D
A T
E
F
IL
E N
U M
B E
R
C O
N T
R A
C T
N O
S O
LI
C
IT
A
T
IO
N N
O
D A
T E
D E
S C
R
IP
T
IO
N M
A R
K D
A T
E A
P P
R
SHEET
IDENTIFICATION
C K
D B
Y
D E
S
IG
N , R
E P
A
IR
H V
A C
U N
IT
S
B
U
IL
D
IN
G
A N
S I D
A S
N O
T E
D
FOR OFFICIAL USE ONLY
FOR OFFICIAL USE ONLY
FO
R
O
FF
IC
IA
L U
S E
O N
LY
FO
R
O
FF
IC
IA
L U
S E
O N
LY
ME
OMC
SPA C N
D
A
D
2 3
C
A
B
8/
3/
S E
P T
E M
B E
R
D A
V
ID
A . L
U K
E , P
.E
G
LE
N
-1
P.E. 32681 ON 18 SEPT 2013
FO
R
C O
N S
TR
U
C
TI
O N
M-001
P . P
LE
IS
S
K . B
R E
S
LI
N
J.
R
E S
ZE
TU
C H
A
M E
C H
A N
IC
A
L
LE
G E
N D
1 2
AHU-SSB-101
RAF-SSB-101
CHP-SSB-101
CHP-SSB-102
HX-SSB-101
CU-SSB-101
AS HWP-SSB-101 HWP-SSB-102
ELEC
PANEL
ELEC
SWITCHGEAR
ELEC
PANEL
2 54
NEW BAS CONTROL PANEL
ELEC
PANEL
THE SEAL APPEARING ON THIS
BY KEVIN PETER BRESLIN, JR.
DOCUMENT WAS AUTHORIZED
E
N
R
GIADO
L O
E F
P R
O
C O
A S
S
I NO N G
EL
I
E
32681K
R R
S
ST
RE
E E
E D
R
V
B
NI
E
LIN
PE
TER
JR
D E
S C
R
IP
T
IO
N M
A R
K D
A T
E A
P P
R
D E
S
IG
N E
D B
Y
D W
N B
Y
S U
B M
IT
T
E D
B Y
F
IL
E N
A M
E
S
IZ
E
P
LO
T S
C A
LE
P
LO
T D
A T
E
F
IL
E N
U M
B E
R
C O
N T
R A
C T
N O
S O
LI
C
IT
A
T
IO
N N
O
D A
T E
D E
S C
R
IP
T
IO
N M
A R
K D
A T
E A
P P
R
SHEET
IDENTIFICATION
C K
D B
Y
D E
S
IG
N , R
E P
A
IR
H V
A C
U N
IT
S
B
U
IL
D
IN
G
A N
S I D
A S
N O
T E
D
FOR OFFICIAL USE ONLY
FOR OFFICIAL USE ONLY
FO
R
O
FF
IC
IA
L U
S E
O N
LY
FO
R
O
FF
IC
IA
L U
S E
O N
LY
ME
OMC
SPA C N
D
A
D
2 3
C
A
B
8/
3/
S E
P T
E M
B E
R
D A
V
ID
A . L
U K
E , P
.E
G
LE
N
-1
P.E. 32681 ON 18 SEPT 2013
FO
R
C O
N S
TR
U
C
TI
O N
M-101
P . P
LE
IS
S
K . B
R E
S
LI
N
J.
R
E S
ZE
TU
C H
A
M E
C H
A N
IC
A
L D
U C
T W
O R
K F
LO
O
R P
LA
N
SCALE: 1/2" = 1'-0"
MECHANICAL DUCTWORK FLOOR PLAN 2' 4'0 1'
SCALE:1/2"=1'-0"
N
KEYED NOTES:
REPLACE EXISTING RELIEF AIR DAMPER ACTUATOR.
REPLACE EXISTING RETURN AIR DAMPER ACTUATOR.
REMOVE EXISTING 132" X 78" DAMPER & ACTUATOR.
REPLACE WITH NEW OUTSIDE AIR & ECONOMIZER
DAMPERS PER KEYED NOTES 4 & 5.
PROVIDE NEW 18" X 78" OUTSIDE AIR DAMPER &
ACTUATOR.
PROVIDE NEW 114" X 78" ECONOMIZER DAMPER &
ACTUATOR.
GENERAL NOTES:
REFURBISH EXISTING DAMPERS AND ASSOCIATED
LINKAGES; PROVIDE LUBRICATION OF ALL WORKING
PARTS & REPLACE FASTENERS AS NEEDED TO
ENSURE SMOOTH OPERATION ACROSS FULL RANGE
OF MOTION.
SEE M-701 FOR CONTROL SEQUENCE.
REMOVE AND REPLACE EXISTING DUCTWORK AS
NEEDED TO PERFORM SCOPE OF WORK.
1.
2.
3.
KEYPLAN
1" C
1" S
3" H
W R
3/ 4"
C W
1/ 2"
H W 1/ 2"
H W
C
4" C
H S
4" C
H R
1 1/2" S
1 1/4" C
4" CHR
4" CHS
1 1/2" S
1 1/4" C
4" C
H S
4" C
4" S
4" C
3" H
W R
3" H
W R
4" CHS
4" CHS
4" CHR
4" C
H R
3" HWR
4" C
3/ 4"
C W
1/ 2"
H W 1/
2" H
W C
HWP-SSB-102HWP-SSB-101
CU-SSB-101
CHP-SSB-101
CHP-SSB-102
HX-SSB-101 AS
AHU-SSB-101
VFD
ELEC
PANEL
ELEC
SWITCHGEAR
ELEC
PANEL
ELEC
PANEL
NEW FLOW SENSOR
THE SEAL APPEARING ON THIS
BY KEVIN PETER BRESLIN, JR.
DOCUMENT WAS AUTHORIZED
E
N
R
GIADO
L O
E F
P R
O
C O
A S
S
I NO N G
EL
I
E
32681K
R R
S
ST
RE
E E
E D
R
V
B
NI
E
LIN
PE
TER
JR
D E
S C
R
IP
T
IO
N M
A R
K D
A T
E A
P P
R
D E
S
IG
N E
D B
Y
D W
N B
Y
S U
B M
IT
T
E D
B Y
F
IL
E N
A M
E
S
IZ
E
P
LO
T S
C A
LE
P
LO
T D
A T
E
F
IL
E N
U M
B E
R
C O
N T
R A
C T
N O
S O
LI
C
IT
A
T
IO
N N
O
D A
T E
D E
S C
R
IP
T
IO
N M
A R
K D
A T
E A
P P
R
SHEET
IDENTIFICATION
C K
D B
Y
D E
S
IG
N , R
E P
A
IR
H V
A C
U N
IT
S
B
U
IL
D
IN
G
A N
S I D
A S
N O
T E
D
FOR OFFICIAL USE ONLY
FOR OFFICIAL USE ONLY
FO
R
O
FF
IC
IA
L U
S E
O N
LY
FO
R
O
FF
IC
IA
L U
S E
O N
LY
ME
OMC
SPA C N
D
A
D
2 3
C
A
B
8/
3/
S E
P T
E M
B E
R
D A
V
ID
A . L
U K
E , P
.E
G
LE
N
-1
P.E. 32681 ON 18 SEPT 2013
FO
R
C O
N S
TR
U
C
TI
O N
M-102
P . P
LE
IS
S
K . B
R E
S
LI
N
J.
R
E S
ZE
TU
C H
A
M E
C H
A N
IC
A
L P
IP
IN
G F
LO
O
R P
LA
N
SCALE: 1/2" = 1'-0"
MECHANICAL PIPING FLOOR PLAN 2' 4'0 1'
SCALE:1/2"=1'-0"
N
KEYED NOTES:
REPLACE EXISTING PUMP WITH NEW PUMP AS SHOWN,
SEE 1/M-501.
MOUNT NEW VFD'S ON UNISTRUT STAND IN STACKED
CONFIGURATION. PROVIDE GALV. STEEL DRIP PAN
OVERHEAD.
PROVIDE NEW 4" CONTROL VALVE IN CHR MAIN, SEE
ISO 1/M-501.
PROVIDE NEW BAS CONTROL PANEL WITH GALV. STEEL
DRIP PAN OVERHEAD.
REPLACE EXISTING VALVE WITH NEW 4" CONTROL
VALVE, SEE ISO 2/M-501. PROVIDE SPOOL INSERTS AS
NEEDED.
KEYPLAN
GENERAL NOTES:
SEE M-701 FOR CONTROL SEQUENCE.1.
STRAINER WITH HOSE
END DRAIN VALVE.
WAFER STYLE
CHECK VALVE
PRESSURE GAUGE
EXISTING
STRUCTURAL PAD
EXISTING
ISOLATION VALVE
CORREGATED S.S.
WITH S.S. BRAIDED
SHEATH
TYPE FLEXIBLE
CONNECTION, TYP.
PROVIDE ECCENTRIC REDUCING
ELBOW & SPOOL PIECES AS
NEEDED TO MATCH EXISTING
PIPE CONNECTIONS
4" CHR
4" CHS
4" C
3" HWR
3" HWR
DOWN TO UTILITY TUNNEL
EXISTING BYPASS VALVE (N.C.)
NEW 4" CONTROL VALVE
4" C
4" S
NEW FLOW SENSOR
REMOVE EXISTING BALANCING
VALVE AND REPLACE WITH SPOOL
INSERT AS NEEDED.
REPLACE TESTING VALVE WITH NEW
4" CONTROL VALVE. PROVIDE SPOOL
INSERT AS NEEDED.
REMARKS:
1. FLOW CAPACITY BASED ON 0% PROPYLENE GLYCOL CHILLED WATER.
2. VARIABLE FREQUENCY DRIVE, SEE ELECTRICAL
3. PROVIDE PREMIUM EFFICIENCY INVERTER-DUTY RATED MOTOR WITH SHAFT GROUNDING BRUSHES, SEE ELECTRICAL
4. REQUIRED NPSH AT SCHEDULED OPERATING POINT SHALL NOT EXCEED 0.8*NPSHR.
5. REFER TO DRAWINGS TO DETERMINE REQUIRED PUMP ROTATION. COORDINATE WITH MECHANICAL CONTRACTOR PRIOR TO ORDERING.
THE SEAL APPEARING ON THIS
BY KEVIN PETER BRESLIN, JR.
DOCUMENT WAS AUTHORIZED
E
N
R
GIADO
L O
E F
P R
O
C O
A S
S
I NO N G
EL
I
E
32681K
R R
S
ST
RE
E E
E D
R
V
B
NI
E
LIN
PE
TER
JR
D E
S C
R
IP
T
IO
N M
A R
K D
A T
E A
P P
R
D E
S
IG
N E
D B
Y
D W
N B
Y
S U
B M
IT
T
E D
B Y
F
IL
E N
A M
E
S
IZ
E
P
LO
T S
C A
LE
P
LO
T D
A T
E
F
IL
E N
U M
B E
R
C O
N T
R A
C T
N O
S O
LI
C
IT
A
T
IO
N N
O
D A
T E
D E
S C
R
IP
T
IO
N M
A R
K D
A T
E A
P P
R
SHEET
IDENTIFICATION
C K
D B
Y
D E
S
IG
N , R
E P
A
IR
H V
A C
U N
IT
S
B
U
IL
D
IN
G
A N
S I D
A S
N O
T E
D
FOR OFFICIAL USE ONLY
FOR OFFICIAL USE ONLY
FO
R
O
FF
IC
IA
L U
S E
O N
LY
FO
R
O
FF
IC
IA
L U
S E
O N
LY
ME
OMC
SPA C N
D
A
D
2 3
C
A
B
8/
3/
S E
P T
E M
B E
R
D A
V
ID
A . L
U K
E , P
.E
G
LE
N
-1
P.E. 32681 ON 18 SEPT 2013
FO
R
C O
N S
TR
U
C
TI
O N
M-501
P . P
LE
IS
S
K . B
R E
S
LI
N
J.
R
E S
ZE
TU
C H
A
M E
C H
A N
IC
A
L D
E T
A
IL
S , S
C H
E D
U
LE
S
IS
O
M E
T R
IC
S
SCALE: N.T.S.
BASE MOUNTED PUMP DETAIL
PUMP SCHEDULE
PLAN MARK SERVICE TYPE
CAPACITY
(GPM)
TOT. HEAD
(FT) EFF (%)
MOTOR MOTOR
VOLT/PH/HZ SPEED CONTROL REMARKS BASIS OF DESIGNRPM BHP
CHP-SSB-101 CHIILLED WATER BHSC 233 59 78 1760 4.456 460/3/60 VFD 1,2,3,4,5 TACO TAO624 CHP-SSB-102 CHILLED WATER BHSC 233 59 78 1760 4.456 460/3/60 VFD 1,2,3,4,5 TACO TAO624
SCALE:
ISOMETRIC 1
SCALE:
ISOMETRIC 2
BHSC = BASE-MOUNTED HORIZONTAL SPLIT CASE
AHU-SSB-101-A 44°F
56°F
465900 BTU/H
77.5 GPM
AHU-SSB-103 44°F
56°F
30100 BTU/H
5 GPM
AHU-SSB-10244°F
56°F
270600 BTU/H
45 GPM
AHU-SSB-10544°F
56°F
138300 BTU/H
23 GPM
AHU-SSB-10444°F
56°F
30100 BTU/H
5 GPM
CHP-SSB-101
232.9 GPM
58.4 FT
CHP-SSB-102
232.9 GPM
58.4 FT
AHU-SSB-101-B 44°F
56°F
465900 BTU/H
77.5 GPM
BV-1
BV-2
BV-3
TCV-AHU-SSB-101A/B
TCV-AHU-SSB-102
TCV-AHU-SSB-103
TCV-AHU-SSB-105
TCV-SSB-01
TCV-AHU-SSB-104
BV-12
TCV-SSB-02
4"
4"
4"
4"
4"
4"
4"
2"
2"
4"
2"
4"
4"
4"
4"
4"
4"
1"
4"
2"
2"
1"
2"
4"
2"
4"
4"
MECHANICAL ROOM (123)
WAREHOUSE (155)
LOGISTICS STORAGE (154)
VEHICLE STORAGE (167)
4" CHS/R FROM
CENTRAL PLANT
NEW CHILLED WATER
RETURN TEMPERATURE
CONTROL VALVE
NEW CHILLED WATER
CONTROL VALVE
NEW CHILLED WATER
CONTROL VALVE
NEW CHILLED WATER
CONTROL VALVE
NEW CHILLED WATER
CONTROL VALVE
NEW CHILLED
WATER PUMPS
NEW CHILLED WATER
BYPASS CONTROL VALVE
AHU-SSB-101-A 44°F
56°F
465900 BTU/H
77.5 GPM
CV-1
BV-4
AHU-SSB-103 44°F
56°F
30100 BTU/H
5 GPM
CV-2
BV-5
AHU-SSB-10244°F
56°F
270600 BTU/H
45 GPM
CV-3
BV-6
AHU-SSB-10544°F
56°F
138300 BTU/H
23 GPM
CV-4
BV-7
AHU-SSB-10444°F
56°F
30100 BTU/H
5 GPM
CV-5
BV-8
CHP-SSB-101
232.9 GPM
59 FT
CHP-SSB-102
232.9 GPM
59 FT
AHU-SSB-101-B 44°F
56°F
465900 BTU/H
77.5 GPM
BV-9
BV-10
BV-11
TCV-SSB-01
TCV-SSB-02
4"
4"
4"
4"
4"
4"
4"
2"
2"
4"
2"
4"
4"
4"
4"
4"
4"
1"
4"
2"
2"
1"
2"
4"
2"
4"
4"
MECHANICAL ROOM (123)
WAREHOUSE (155)
LOGISTICS STORAGE (154)
VEHICLE STORAGE (167)
4" CHS/R FROM
CENTRAL PLANT
NEW CHILLED WATER
RETURN TEMPERATURE
CONTROL VALVE
NEW CHILLED
WATER PUMPS
CLOSE BYPASS
BALANCING VALVE
CLOSE BYPASS
BALANCING VALVE
CLOSE BYPASS
BALANCING VALVE
CLOSE BYPASS
BALANCING VALVE
NEW CHILLED WATER
BYPASS CONTROL VALVE
THE SEAL APPEARING ON THIS
BY KEVIN PETER BRESLIN, JR.
DOCUMENT WAS AUTHORIZED
E
N
R
GIADO
L O
E F
P R
O
C O
A S
S
I NO N G
EL
I
E
32681K
R R
S
ST
RE
E E
E D
R
V
B
NI
E
LIN
PE
TER
JR
D E
S C
R
IP
T
IO
N M
A R
K D
A T
E A
P P
R
D E
S
IG
N E
D B
Y
D W
N B
Y
S U
B M
IT
T
E D
B Y
F
IL
E N
A M
E
S
IZ
E
P
LO
T S
C A
LE
P
LO
T D
A T
E
F
IL
E N
U M
B E
R
C O
N T
R A
C T
N O
S O
LI
C
IT
A
T
IO
N N
O
D A
T E
D E
S C
R
IP
T
IO
N M
A R
K D
A T
E A
P P
R
SHEET
IDENTIFICATION
C K
D B
Y
D E
S
IG
N , R
E P
A
IR
H V
A C
U N
IT
S
B
U
IL
D
IN
G
A N
S I D
A S
N O
T E
D
FOR OFFICIAL USE ONLY
FOR OFFICIAL USE ONLY
FO
R
O
FF
IC
IA
L U
S E
O N
LY
FO
R
O
FF
IC
IA
L U
S E
O N
LY
ME
OMC
SPA C N
D
A
D
2 3
C
A
B
8/
3/
S E
P T
E M
B E
R
D A
V
ID
A . L
U K
E , P
.E
G
LE
N
-1
P.E. 32681 ON 18 SEPT 2013
FO
R
C O
N S
TR
U
C
TI
O N
M-601
P . P
LE
IS
S
K . B
R E
S
LI
N
J.
R
E S
ZE
TU
C H
A
M E
C H
A N
IC
A
L C
H
IL
LE
D
W A
T E
R F
LO
W
S C
H E
M A
T
IC
S
SCALE: N.T.S.
CHILLED WATER FLOW SCHEMATIC (BID OPTION #1)
SCALE: N.T.S.
CHILLED WATER FLOW SCHEMATIC (BASE BID)
CHILLED WATER PUMP
CHP-SSB-101
VFDVFD
CHR
PT
AI
CHILLED WATER PUMP
CHP-SSB-102
AI
FMT
AO
CHS
CHS
CHS
C H
R
TT
AI
NO
TCV
AO
DO
AI DI (2)
AO
DO
AI DI (2)
TT
AI
NO
XX
TCV
AO
C
C
CHR
CHS
SIEMENS
CONTROLLER
AO (8)
DO (2)
AI (9)
DI (4)
NEW SIEMENS
CONTROLLER WITH
ANALOG & DIGITAL I/O
FOR DEVICES SHOWN
TO SIEMENS GATEWAY
NOTES:
SEE M-102 & M-501 FOR LOCATION OF LOOP
FLOW SENSORS.
SEE M-601 FOR TCV TAGS.
1.
2.
TT
AI
BID
OPTION #1
TYP. OF
FOUR (4)
NO
O2
TCV
AO
H AI
AI
FMT
E
E
E
E
T
T
T
T
E
S P
NC
NO
TO ROOF
VENTILATION FOR
AHU-SSB-102, 105
OUTSIDE AIR
FROM ROOF
INTAKE
SPILL AIR TO MECH ROOM
(EXISTING)
RELIEF AIR
DAMPER
(EXISTING)
NO
RETURN AIR
DAMPER
(EXISTING)
NEW
OUTSIDE
AIR
DAMPER
FILTERS
STEAM
PREHEAT
COIL
FREEZE
STAT
V4
NC
COOLING
COIL V3
SUPPLY
AIR
BLOWER
SMOKE
DETECTOR
EXISTING
PRESSURE
TRANSMITTER
RETURN
AIR
BLOWER
H
FK-H90
HUMIDITY
SENSOR
SMOKE
DETECTOR
S
RETURN
SUPPLY
AO
AO
DO
AO
E
AO
NEW
ECONOMIZER
DAMPER
VFD
VFD
DO
AO
AI DI(2)
EXISTING VFD
AI
DP AI
CO2 AI
(RM 142)
BID OPTION #2
SIEMENS
CONTROLLER
AO (5)
DO (3)
AI (6)
DI (4)
NEW SIEMENS
CONTROLLER WITH
ANALOG & DIGITAL I/O
FOR DEVICES SHOWN
TO SIEMENS GATEWAY
CO2
AI
BID OPTION #2 DO
AO
AI
DI(2)
NOTES:
CONFIRM VFD CONTROL INTERFACE I/O
POINTS IN FIELD.
SEE M-702 FOR LOCATION OF DIFFERENTIAL
PRESSURE, HUMIDITY & CO2 SENSORS.
1.
2. THE SEAL APPEARING ON THIS
BY KEVIN PETER BRESLIN, JR.
DOCUMENT WAS AUTHORIZED
E
N
R
GIADO
L O
E F
P R
O
C O
A S
S
I NO N G
EL
I
E
32681K
R R
S
ST
RE
E E
E D
R
V
B
NI
E
LIN
PE
TER
JR
D E
S C
R
IP
T
IO
N M
A R
K D
A T
E A
P P
R
D E
S
IG
N E
D B
Y
D W
N B
Y
S U
B M
IT
T
E D
B Y
F
IL
E N
A M
E
S
IZ
E
P
LO
T S
C A
LE
P
LO
T D
A T
E
F
IL
E N
U M
B E
R
C O
N T
R A
C T
N O
S O
LI
C
IT
A
T
IO
N N
O
D A
T E
D E
S C
R
IP
T
IO
N M
A R
K D
A T
E A
P P
R
SHEET
IDENTIFICATION
C K
D B
Y
D E
S
IG
N , R
E P
A
IR
H V
A C
U N
IT
S
B
U
IL
D
IN
G
A N
S I D
A S
N O
T E
D
FOR OFFICIAL USE ONLY
FOR OFFICIAL USE ONLY
FO
R
O
FF
IC
IA
L U
S E
O N
LY
FO
R
O
FF
IC
IA
L U
S E
O N
LY
ME
OMC
SPA C N
D
A
D
2 3
C
A
B
8/
3/
S E
P T
E M
B E
R
D A
V
ID
A . L
U K
E , P
.E
G
LE
N
-1
P.E. 32681 ON 18 SEPT 2013
FO
R
C O
N S
TR
U
C
TI
O N
M-701
P . P
LE
IS
S
K . B
R E
S
LI
N
J.
R
E S
ZE
TU
C H
A
M E
C H
A N
IC
A
L S
Y S
T E
M C
O N
T R
O L
D
IA
G R
A M
S
CHILLED WATER LOOP SEQUENCE OF OPERATION
CHILLED WATER PUMP (CHP) SPEED CONTROL:
THE CHILLED WATER PUMP (CHP) WILL BE PROVIDED WITH A VARIABLE FREQUENCY DRIVE (VFD). THE VFD SHALL HAVE A “LOCAL-OFF-AUTO” SELECTOR TO ALLOW FOR LOCAL OPERATION OF THE PUMP. THE VFD SHALL BE PROVIDED WITH THE I/O POINTS INDICATED IN THE POINTS LIST. THE BAS SHALL CONTROL THE PUMP TO PROVIDE THE
REQUIRED PRESSURE TO MAINTAIN A SYSTEM SUPPLY PRESSURE SETPOINT.
CHILLED WATER PUMP (CHP) PRIMARY/STANDBY CONTROL:
UPON A FAILURE OF PRIMARY OPERATING PUMP, THE STANDBY PUMP SHALL BE ENERGIZED AND AN ALARM GENERATED AT THE BAS. WHEN A PUMP IS STARTED, IT SHALL RAMP UP TO ITS TARGET SPEED WITHIN 20 SECONDS.
CHILLED WATER PUMP (CHP) ALTERNATION:
THE BAS SHALL MONITOR RUNTIME OF THE CHP(S) AND SHALL ALTERNATE THE DESIGNATED LEAD PUMP ON A
MONTHLY BASIS.
CHILLED WATER LOOP RETURN TEMPERATURE CONTROL VALVE CONTROL:
THE RETURN TEMPERATURE CONTROL VALVE (TCV-01) SHALL BE MODULATED BY THE BAS TO PROVIDE 58 DEGREE F
(USER ADJUSTABLE) RETURN WATER TO THE CHILLED WATER PLANT.
BUILDING HUMIDITY OVERRIDE CONTROL:
THE BAS SHALL POLL ALL SPACE HUMIDITY SENSORS AND REPORT THE MAXIMUM SPACE HUMIDITY TO THE LOCAL CONTROLLER. IF ANY SPACE RISES ABOVE 60% RH (USER ADJUSTABLE), THE CHILLED WATER LOOP RETURN TEMPERATURE CONTROL VALVE SETPOINT SHALL BE DECREASED BY 3 DEGREES F (USER ADJUSTABLE). THE BAS SHALL CONTINUE DECREASING THE SETPOINT EVERY 15 MINUTES UNTIL THE MAXIMUM SPACE HUMIDITY FALLS BELOW 50% OR THE CHILLED WATER RETURN TEMPERATURE REACHES MINIMUM SETPOINT (52 DEGREES F, USER ADJUSTABLE). IF THE MAXIMUM SPACE HUMIDITY FALLS BELOW 40%, THE BAS SHALL REVERT TO THE DEFAULT
RETURN TEMPERATURE CONTROL VALVE CONTROL BASED ON SYSTEM RETURN TEMPERATURE.
LOOP TEMPERATURE MONITORING:
THE BAS SHALL MONITOR CHILLED WATER LOOP TEMPERATURE. AN ALARM SHALL BE GENERATED IF TEMPERATURE
IS OUTSIDE OF NORMAL OPERATING PARAMETERS (SETPOINT +/- 3 DEG F, ADJUSTABLE).
LOOP ENERGY METERING:
THE BAS SHALL MONITOR & LOG LOOP ENERGY USED BASED ON CHILLED WATER FLOW AND TEMPERATURE
DIFFERENTIAL.
CHILLED WATER PUMP (CHP) SPEED CONTROL OPTIMIZATION (BID OPTION #1):
THE BAS SHALL POLL ALL CHILLED WATER COIL CONTROL VALVES AND REPORT THE MAXIMUM COIL VALVE POSITION TO THE LOCAL CONTROLLER. IF THE MAXIMUM VALVE POSITION IS LESS THAN 85%, THE BAS SHALL DECREASE THE VFD SPEED BY 5%. THE BAS SHALL CONTINUE DECREASING THE OVERRIDE SIGNAL EVERY 5 MINUTES UNTIL THE MAXIMUM VALVE POSITION RISES ABOVE 90% OPEN OR MINIMUM VFD SPEED IS ATTAINED. IF THE VALVE MAXIMUM POSITION RISES ABOVE 95%, THE BAS SHALL REVERT TO THE DEFAULT SPEED CONTROL BASED ON SYSTEM
PRESSURE SETPOINT.
SCALE: N.T.S.
CHILLED WATER LOOP CONTROL DIAGRAM
SCALE: 1/8" = 1'-0"
AHU-SSB-101 SYSTEM CONTROL DIAGRAM
AHU-SSB-101 SEQUENCE OF OPERATION
SUPPLY FAN PRESSURE RESET:
THE STATIC PRESSURE SETPOINT SHALL BE RESET SO THAT AT LEAST ONE OF THE VAV BOXES IS AT 90% (ADJUSTABLE) OPEN. UPON A LOSS OF COMMUNICATION WITH THE CONTROLLER, THE VFD SHALL REVERT TO PROGRAMMED STATIC
PRESSURE SETPOINT.
BUILDING PRESSURE CONTROL:
THE SYSTEM RELIEF DAMPER SHALL BE ENABLED WHEN THE SUPPLY FAN IS ENERGIZED IN THE OCCUPIED MODE. AS THE SPACE STATIC PRESSURE BEGINS TO EXCEED SETPOINT, THE RELIEF DAMPER SHALL BE MODULATED OPEN TO MAINTAIN THE SPACE STATIC PRESSURE SETPOINT. AS THE SPACE STATIC PRESSURE SETPOINT DROPS BELOW SETPOINT THE RELIEF DAMPER SHALL OPERATE IN THE OPPOSITE MANNER. THE SPACE STATIC PRESSURE SETPOINT SHALL BE OF 0.05 INCH OF
WATER (ADJUSTABLE) REFERENCED TO OUTSIDE AIR STATIC PRESSURE.
ECONOMIZER CONTROL:
ECONOMIZER COOLING IS ENABLED WHENEVER THE OUTSIDE AIR TEMPERATURE IS BELOW 73F AND ABOVE 37F (ADJUSTABLE). THE OUTSIDE AIR/RETURN AIR/ ECONOMIZER DAMPERS SHALL MODULATE AS DESCRIBED BELOW. WHEN THE OUTSIDE AIR TEMPERATURE IS ABOVE 75F AND BELOW 35F (ADJUSTABLE), ECONOMIZER COOLING IS DISABLED.
ECONOMIZER DAMPER CONTROL:
WHEN ECONOMIZER COOLING IS ENABLED, THE ECONOMIZER DAMPER SHALL MODULATE TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT. WHEN ECONOMIZER IS DISABLED, THE ECONOMIZER DAMPER SHALL CLOSE AND THE MINIMUM
OUTSIDE AIR DAMPER SHALL PROVIDE MINIMUM OUTSIDE AIR AS DESCRIBED BELOW.
RETURN AIR DAMPER CONTROL:
WHEN ECONOMIZER COOLING IS ENABLED, THE RETURN AIR DAMPER SHALL INVERSELY TRACK THE ECONOMIZER DAMPER. AT
ALL OTHER TIMES, THE RETURN AIR DAMPER SHALL BE IN ITS MAXIMUM POSITION.
OUTSIDE AIRFLOW CONTROL:
WHEN ECONOMIZER COOLING IS DISABLED, THE MINIMUM OUTSIDE AIR DAMPER SHALL MODULATE TO MAINTAIN THE MINIMUM OUTSIDE AIR FLOW SETPOINT THROUGH FAN TRACKING (SEE TEST AND BALANCING INFORMATION NOTES BELOW).
TEST AND BALANCING INFORMATION NOTES:
SET OUTSIDE AIR DAMPER POSITION AT MAXIMUM SUPPLY AIRFLOW CONDITION (APPROXIMATELY 80% OF SUM-OF-PEAKS CONDITION BASED ON DIVERSITY) AND MINIMUM SUPPLY AIRFLOW CONDITION (APPROXIMATELY 25% OF SUM-OF-PEAKS CONDITION BASED ON MINIMUM DIVERSITY) TO PROVIDE 4,500 CFM. OUTSIDE AIR DAMPER SHALL MODULATE BETWEEN THESE
TWO DAMPER POSITIONS BASED ON THE FAN VFD SPEED SIGNAL.
DEMAND-CONTROLLED VENTILATION (DCV) RESET (BID OPTION #2):
WHEN ECONOMIZER COOLING IS DISABLED, THE BAS SHALL POLL ALL CARBON DIOXIDE (CO2) SENSORS AND REPORT MAXIMUM CO2 LEVEL. IF THE MAXIMUM CO2 LEVEL IS BELOW SETPOINT (AMBIENT + 400 PPM), THE OUTSIDE AIR DAMPER OUTPUT SIGNAL SHALL BE REDUCED BY 10%. THIS PROCESS SHALL REPEAT EVERY 5 MINUTES UNTIL THE SETPOINT IS 30% OF ITS PROGRAMMED VALUE. IF THE MAXIMUM CO2 LEVEL RISES ABOVE THE CURRENT SETPOINT, THE PROCESS SHALL REVERSE
UNTIL THE OUTSIDE AIR DAMPER OUTPUT SIGNAL IS AT ITS MAXIMUM PROGRAMMED VALUE.
C
H P
CO2 SENSOR
@ 60" AFF DIFFERENTIAL PRESSURE SENSOR
@ CEILING
HUMIDITY SENSOR
@ CEILING
Room
MECH
THE SEAL APPEARING ON THIS
BY KEVIN PETER BRESLIN, JR.
DOCUMENT WAS AUTHORIZED
E
N
R
GIADO
L O
E F
P R
O
C O
A S
S
I NO N G
EL
I
E
32681K
R R
S
ST
RE
E E
E D
R
V
B
NI
E
LIN
PE
TER
JR
D E
S C
R
IP
T
IO
N M
A R
K D
A T
E A
P P
R
D E
S
IG
N E
D B
Y
D W
N B
Y
S U
B M
IT
T
E D
B Y
F
IL
E N
A M
E
S
IZ
E
P
LO
T S
C A
LE
P
LO
T D
A T
E
F
IL
E N
U M
B E
R
C O
N T
R A
C T
N O
S O
LI
C
IT
A
T
IO
N N
O
D A
T E
D E
S C
R
IP
T
IO
N M
A R
K D
A T
E A
P P
R
SHEET
IDENTIFICATION
C K
D B
Y
D E
S
IG
N , R
E P
A
IR
H V
A C
U N
IT
S
B
U
IL
D
IN
G
A N
S I D
A S
N O
T E
D
FOR OFFICIAL USE ONLY
FOR OFFICIAL USE ONLY
FO
R
O
FF
IC
IA
L U
S E
O N
LY
FO
R
O
FF
IC
IA
L U
S E
O N
LY
ME
OMC
SPA C N
D
A
D
2 3
C
A
B
8/
3/
S E
P T
E M
B E
R
D A
V
ID
A . L
U K
E , P
.E
G
LE
N
-1
P.E. 32681 ON 18 SEPT 2013
FO
R
C O
N S
TR
U
C
TI
O N
M-702
P . P
LE
IS
S
K . B
R E
S
LI
N
J.
R
E S
ZE
TU
C H
A
M E
C H
A N
IC
A
L C
O N
T R
O L
F
LO
O R
P
LA
N
SCALE: 1/16" = 1'-0"
BUILDING 500 CONTROL FLOOR PLAN
NORMALLY OPEN CONTACTS
NORMALLY CLOSED CONTACTS
ELECTRICAL METER
FUSE, SIZE AS INDICATED
M
3A
SA
15KV
SURGE ARRESTOR - VOLTAGE RATING AND
CLASS AS NOTED
GROUND CONNECTION - TO STANDARD ROD
TYPE ELECTRODE TO NEAREST STRUCTURE STEEL
(#6 MIN. CONDUCTOR IF NOT SHOWN)
SS
ELECTRICAL POWER SYMBOLS
POWER TRANSFORMER, DELTA-WYE
CONFIGURATION
POWER TRANSFORMER, PLAN SYMBOL
MOTOR - EQUIPMENT SCHEDULE IDENTIFICATION
AS SHOWN
MOTOR - HORSE POWER IDENTIFIED AS SHOWN
EFX
M
Y
DISCONNECT SWITCH, SIZE AND TYPE AS INDICATED
IN SCHEDULE
FUSED DISCONNECT SWITCH, SIZE AND TYPE
AS INDICATED IN SCHEDULE
DISCONNECT SWITCH, SIZE AND TYPE AS INDICATED
IN SCHEDULE
F
DISCONNECT SWITCH, FURNISHED WITH EQUIPMENT
MOTOR STARTER, SIZE AND TYPE AS INDICATED
IN SCHEDULE
MOTOR STARTER, FURNISHED WITH EQUIPMENT
COMBINATION MOTOR STARTER w/EXTERNALLY
OPERATED DISCONNECT
COMBINATION MOTOR STARTER w/EXTERNALLY
OPERATED DISCONNECT, FURNISHED WITH EQUIPMENT
VFD VARIABLE FREQUENCY DRIVE
SHUNT TRIP SWITCH WITH SAFETY COVER
KIRK KEY INTERLOCK
ST
K
A
A
A
A
RECESSED COMPACT FLUORESCENT OR H.I.D. LUMINAIRE,
UPPER CASE LETTER IDENTIFIES FIXTURE TYPE. UPPER CASE 'E' AND
DARKENED AREA INDICATES EMERGENCY POWERED BY A BATTERY
PACK / INVERTER.
WALL MOUNTED COMPACT FLUORESCENT OR H.I.D. LUMINAIRE,
UPPER CASE LETTER IDENTIFIES FIXTURE TYPE. UPPER CASE 'E'
AND DARKENED AREA INDICATES EMERGENCY POWERED BY A
BATTERY PACK / INVERTER.
SURFACE MOUNTED OR SUSPENDED INDUSTRIAL FLUORESCENT
FIXTURE-NO LENS. UPPER CASE LETTER IDENTIFIES FIXTURE TYPE.
LOWER CASE 'e' INDICATES EXISTING FIXTURE/EQUIPMENT. UPPER
CASE 'E' AND DARKENED AREA INDICATES EMERGENCY POWERED
BY A BATTERY PACK / INVERTER.
RECESSED OR PENDANT MOUNTED FLUORESCENT TROFFER
FIXTURE. UPPER CASE LETTER IDENTIFIES FIXTURE TYPE.
UPPER CASE 'E' AND DARKENED AREA INDICATES
EMERGENCY POWERED BY A BATTERY PACK / INVERTER.
AEA
AEA
WALL (SURFACE) MOUNTED FLUORESCENT LIGHT FIXTURE
W/LENS. UPPER CASE LETTER IDENTIFIES FIXTURE TYPE.
UPPER CASE 'E' AND DARKENED AREA INDICATES EMERGENCY
POWERED BY A BATTERY PACK / INVERTER.
WALL MOUNTED EXIT LIGHT (SINGLE FACE) - MOUNTING
HEIGHT INDICATED, (DOUBLE FACE) - CEILING MOUNTING.
ARROWS IDENTIFY DIRECTION OF EGRESS, WHERE NOTED.
AEA
SINGLE POLE SWITCH
MANUAL STARTER WITH THERMAL OVERLOADS
THREE WAY SWITCH
FOUR WAY SWITCH
DIMMER SWITCH
THREE SPEED, FOUR POSITION FAN CONTROL
SWITCH RATED FOR NO. OF FANS INDICATED
OCCUPANCY SENSOR0
SF
SD
S4
S3
S
ST0
48" A.F.F.
SPECIAL TYPE RECEPTACLE (2P,3W) - 125/250V OUTLETS,
NEMA SERIES AS SHOWN AN PLANS, LOCATE AS NOTED.
2P, 3W GROUNDING TYPE RECEPTACLE - 125V, CONVENTIONAL
DUPLEX AND FLOOR CLEANING TYPE OUTLETS, NEMA 5-20A
SERIES "GFI" ADJACENT TO SYMBOL DESIGNATES GROUND FAULT
INTERRUPTER. "IG" DESIGNATOR INDICATES ISOLATED GROUND
RECEPTACLE. LOCATE 18" AFF, UNLESS NOTED OTHERWISE.
(2) 2P, 3W GROUNDING TYPE RECEPTACLE - 125V, DOUBLE DUPLEX
TYPE OUTLETS, (2) NEMA 5-20A, IN 4-SQUARE BOX
FLOOR DUPLEX RECEPTACLE OUTLET
2P, 3W GROUNDING TYPE SIMPLEX CLOCK RECEPTACLE
- 125V OUTLETS, NEMA 5-20A SERIES, "GFCI" ADJACENT TO
SYMBOL DESIGNATES GROUND FAULT CIRCUIT INTERRUPTER.
F
C
RECESSED FLOOR JUNCTION BOX WITH BLANK FACE PLATE FOR
MODULAR FURNITURE
ELECTRICAL PANELBOARD.
JUNCTION BOX, 4" SQUARE UNLESS NOTED OTHERWISEJ
LIGHTING PLAN SYMBOLS
GENERAL ELECTRICAL SYMBOLS
ARROWS ALL CONDUIT SHALL CONTAIN A GREEN INSULATED
GROUND WIRE SIZED IN ACCORDANCE WITH NEC TABLE
250.122, UNLESS OTHERWISE NOTED. MARKS INDICATE
CONDUCTORS [ (3)H,N,G ]. IF NO TICK MARKS ARE SHOWN
PROVIDE [(1)H #12, (1)N #12, (1) G #12]
PP21-2,4,6
MISCELLANEOUS ELECTRICAL SYMBOLS
KEYED NOTES
EQUIPMENT CONNECTION, REFER TO APPROPRIATE
SCHEDULE FOR ADDITIONAL INFORMATION.
1. FOR GENERAL NOTES AND NON-ELECTRICAL SYMBOLS, SEE LEGEND.
ALSO REFER TO ABBREVIATIONS SHEET.
2. LETTERS SUCH AS ''WP'', ''GFI'' ADJACENT TO ANY SYMBOL INDICATE
SPECIAL CONSTRUCTION IS REQUIRED. SEE ABBREVIATIONS SHEET
FOR DEFINITIONS.
X1
3. SIZES OF WIRE AND CABLE ARE BASED ON COPPER CONDUCTORS.
ALUMINUM CONDUCTOR IS NOT ACCEPTABLE.
4. UNLESS OTHERWISE NOTED, ALL DIMENSIONS ARE IN INCHES.
5. ELEVATIONS FOR ELECTRICAL EQUIPMENT ARE SHOWN TO CENTER OF
DEVICE OR ENCLOSURE UNLESS NOTED OTHERWISE.
6. RECEPTACLES AND TELE/DATA JACKS SHALL BE LOCATED 18" AFF
UNLESS NOTED OTHERWISE. LIGHT SWITCHES SHALL BE LOCATED 48"
AFF UNLESS NOTED OTHERWISE.
7. NOT ALL SYMBOLS USED ON THIS PROJECT.
NOTES:
A, AMP
ACCP
AF AFF
AIC
ASYM
AT
ATS
AWG
AMPERE
ALARM CENTER CONTROL PANEL
AMPS FRAME
ABOVE FINISH FLOOR
AMPS INTERRUPTING CAPACITY (SYM RMS) ASYMMETRICAL
AMPS TRIP
AUTOMATIC TRANSFER SWITCH
AMERICAN WIRE GAGE
BLDG
BP/IS
BUILDING
BYPASS/ISOLATION
HPF HIGH POWER FACTOR
C
CATV
CB
CKT
C
COMM
CONT
Cu
CONDUIT
COMMUNITY ANTENNA TELEVISION
CIRCUIT BREAKER
CIRCUIT
CENTER LINE
COMMUNICATION
CONTINUOUS
COPPER
L dB dBA
DIM
DISC
DWG
DECIBEL
DECIBEL, A-WEIGHTED
DIMENSION
DISCONNECT
DRAWING
e E
ELEC
EMCS
EMT
ENCL
EPO
EQ
EQUIP
EXIST
EXP
EXT
EXISTING
EAST
ELECTRICAL OR ELECTRIC
ENERGY MANAGEMENT CONTROL SYSTEM
ELECTRICAL METALLIC TUBING
ENCLOSURE
EMERGENCY POWER OFF
EQUAL
EQUIPMENT
EXISTING
EXPOSED
EXTERIOR
FACP
FE
FIRE ALARM CONTROL PANEL
FURNISHED WITH EQUIPMENT
GFGI
GFI
G, GND, GRD
GOVT
GOVERNMENT FURNISHED, GOVERNMENT INSTALLED
GROUND FAULT INTERRUPTER
GROUND
GOVERNMENT
IMC
IG
INTERMEDIATE METAL CONDUIT
ISOLATED GROUND
J-BOX JUNCTION BOX
KAIC
KV
KVA
KW
KWH
KILOAMPS INTERRUPTING CAPACITY (SYM RMS)
KILOVOLTS
KILOVOLT AMPERES
KILOWATT
KILOWATT HOURS
MIN MINIMUM
N
NEC
N, NEUT
N.O.
N C N.C.
NL
NSMR
NORTH
NATIONAL ELECTRICAL CODE
NEUTRAL
NORMALLY OPEN
NO CONNECTION
NORMALLY CLOSED
NIGHT LIGHT
NON-STRUCTURAL METAL ROOF
PA
PNL
PH
PVC
PUBLIC ADDRESS
PANEL
PHASE
POLYVINYL CHLORIDE
RECP
REF
REQD
RGS
RECEPTACLE
REFERENCE
REQUIRED
RIGID GALVANIZED STEEL
S
SEC
SPEC
SPD
SPKR
SSMR
ST
SYM
SOUTH
SECONDARY
SPECIFICATIONS
SURGE PROTECTIVE DEVICE
SPEAKER
STANDING SEAM METAL ROOF
SHUNT TRIP
SYMMETRICAL
TEL
TMGB
TYP
TELEPHONE
TELEPHONE MASTER GROUND BUS
TYPICAL
UG
UNO
UNDERGROUND
UNLESS NOTED OTHERWISE
V
VA
VFD
VT
VOLT
VOLT AMPERE
VARIABLE FREQUENCY DRIVE
VOLTAGE TRANSFORMER
W W/ W/O
WP
WEST
WITH
WITHOUT
WEATHERPROOF
XFMR TRANSFORMER
208/120 208Y/120V SYSTEM
480/277 480Y/277V SYSTEM
ELECTRICAL ABBREVIATIONS POWER PLAN SYMBOLS
CIRCUIT BREAKER DISCONNECT SIZE AND
TYPE AS INDICATED IN SCHEDULE
CB
OCCPANCY WALL SWITCH
LOW VOLTAGE LIGHT SWITCH, REFER TO
LIGHTING CONTROL RELAY SCHEDULE.
SLV#
SO
A-N,B-N,C-N THESE TAGS IDENTIFY
PHASES "A", "B", & "C"
ON THE PANEL SCHEDULES
AE
AE
DEMOLITION HATCH PATTERN
e
LOWER CASE 'e' INDICATES EXISTINGe
STAB-IN CONNECTION
MCC CIRCUIT BREAKER,
X = FRAME SIZE, Y = TRIP RATING
X
MCC STARTER,
Z = NEMA SIZE
Z
S
VARIABLE
FREQUENCY
DRIVE
VFD
THE SEAL APPEARING ON THIS
BY JOHN R. ODUM.
DOCUMENT WAS AUTHORIZED
E
N
R
GIADO
L O
E F
P R
O
C O
A S
S
I NO N G
EL
I
31890
J
R
ST
RE
E E
E D
R
H M N
O
R. ODU
D E
S C
R
IP
T
IO
N M
A R
K D
A T
E A
P P
R
D E
S
IG
N E
D B
Y
D W
N B
Y
S U
B M
IT
T
E D
B Y
F
IL
E N
A M
E
S
IZ
E
P
LO
T S
C A
LE
P
LO
T D
A T
E
F
IL
E N
U M
B E
R
C O
N T
R A
C T
N O
S O
LI
C
IT
A
T
IO
N N
O
D A
T E
D E
S C
R
IP
T
IO
N M
A R
K D
A T
E A
P P
R
SHEET
IDENTIFICATION
C K
D B
Y
D E
S
IG
N , R
E P
A
IR
H V
A C
U N
IT
S
B
U
IL
D
IN
G
A N
S I D
A S
N O
T E
D
FOR OFFICIAL USE ONLY
FOR OFFICIAL USE ONLY
FO
R
O
FF
IC
IA
L U
S E
O N
LY
FO
R
O
FF
IC
IA
L U
S E
O N
LY
ME
OMC
SPA C N
D
A
D
2 3
C
A
B
8/
3/
S E
P T
E M
B E
R
D A
V
ID
A . L
U K
E , P
.E
G
LE
N
-1
P.E. 31890 ON 18 SEPT 2013
FO
R
C O
N S
TR
U
C
TI
O N
E-001
P . P
LE
IS
S
R . O
D U
M
R . O
D U
M
E
LE
C T
R
IC
A L
LE
G
E N
NEW VFD'S
CHP-SSB-101
CHP-SSB-102
NEW
NEW
EXISTING MCC-S1
2 3
2 3
3NEW
BAS
CONTROL
PANEL
EXISTING
PNL SL1A
VFD
THE SEAL APPEARING ON THIS
BY JOHN R. ODUM.
DOCUMENT WAS AUTHORIZED
E
N
R
GIADO
L O
E F
P R
O
C O
A S
S
I NO N G
EL
I
31890
J
R
ST
RE
E E
E D
R
H M N
O
R. ODU
D E
S C
R
IP
T
IO
N M
A R
K D
A T
E A
P P
R
D E
S
IG
N E
D B
Y
D W
N B
Y
S U
B M
IT
T
E D
B Y
F
IL
E N
A M
E
S
IZ
E
P
LO
T S
C A
LE
P
LO
T D
A T
E
F
IL
E N
U M
B E
R
C O
N T
R A
C T
N O
S O
LI
C
IT
A
T
IO
N N
O
D A
T E
D E
S C
R
IP
T
IO
N M
A R
K D
A T
E A
P P
R
SHEET
IDENTIFICATION
C K
D B
Y
D E
S
IG
N , R
E P
A
IR
H V
A C
U N
IT
S
B
U
IL
D
IN
G
A N
S I D
A S
N O
T E
D
FOR OFFICIAL USE ONLY
FOR OFFICIAL USE ONLY
FO
R
O
FF
IC
IA
L U
S E
O N
LY
FO
R
O
FF
IC
IA
L U
S E
O N
LY
ME
OMC
SPA C N
D
A
D
2 3
C
A
B
8/
3/
S E
P T
E M
B E
R
D A
V
ID
A . L
U K
E , P
.E
G
LE
N
-1
P.E. 31890 ON 18 SEPT 2013
FO
R
C O
N S
TR
U
C
TI
O N
E-101
P . P
LE
IS
S
R . O
D U
M
R . O
D U
M
E
LE
C T
R
IC
A L
F
LO
O R
P
LA
N
SCALE: 1/2" = 1'-0"
ELECTRICAL FLOOR PLAN
2' 4'0 1'
SCALE:1/2"=1'-0"
N
KEYPLAN
KEYED NOTES:
PROVIDE NEW CONDUCTORS AND CONDUIT FROM
EXISTING MCC TO NEW VFD'S FOR CHP-SSB-101 AND
CHP-SSB-102.
PROVIDE NEW CONDUCTORS AND CONDUIT FROM
NEW VFD'S TO NEW PUMPS CHP-SSB-101 AND CHP-
SSB-102.
PROVIDE 120V CIRCUIT (2#12+#12G IN 3/4"C) FOR DDC
CONTROLLER. FROM NEW 20A CB IN EXISTING
PANELBOARD SL1A TO NEW BAS CONROL PANEL.
GENERAL NOTES:
REMOVE EXISTING CONDUITS AND CONDUCTORS
AFTER NEW CONDUCTORS AND CONDUITS ARE
INSTALLED.
SEE ELECTRICAL ONE-LINE DIAGRAMS ON SHEET E-102
FOR SPECIFIC ELECTRICAL EQUIPMENT SIZES.
1.
2.
MECHANICAL EQUIPMENT CONNECTION SCHEDULE
ITEM
CHP-SSB-101
CHP-SSB-102
CONNECTION SCHEDULE NOTES:
1.
2.
3.
4.
NAME
CHILLED WATER PUMP
CHILLED WATER PUMP
CONTRACTOR SHALL COORDINATE ALL ELECTRICAL CONNECTION AND CIRCUITING REQUIREMENTS WITH OTHER TRADES PRIOR TO ELECTRICAL WORK.
REFER TO SHEET E-101 FOR NEW WORK FLOOR PLAN AND EQUIPMENT LOCATIONS.
PROVIDE A 3/4" EMT CONDUIT TO 'EMCS' FROM EACH DRIVE EQUIPMENT LOCATION.
VFD's SHALL HAVE "H.O.A." MANUAL SWITCH.
VOLT
PH
EQUIP KW MOTOR HP
5.0
5.0
FLA (A)
7.6
7.6
DISCONNECT
30A/3P INTEGRAL TO VFD
30A/3P INTEGRAL TO VFD
STARTER
5 HP VFD
5 HP VFD
C/B SIZE
100AF/15AT
WIRE SIZE
3#10 +#12G
3#10 +#12G
CONDUIT
3/4" RMC
3/4" RMC
FED BY
MCC-S1
MCC-S1
NOTES
NOTE 1,2,3,4,5
NOTE 1,2,3,4,5 100AF/15AT
5. PROVIDE 3/4" C WITH PULL WIRE FOR CONTROL WIRING.
AI
R
HA
ND
LI
NG
UN
IT
A
HU
-S
SB
-1
AH
U
-1
MOTOR CONTROL CENTER "MCC-S1"
100A/ 3P
225AF
150AT
RE
TU
RN
A
IR
F
AN
RA
F-
SS
B-
R
AF
-1
60A/ 3P
100AF
50AT
CH
IL
LE
D
W
AT
ER
PU
M P
CH
P-
SS
B-
P-
30A/ 3P
100AF
15AT
CH
IL
LE
D
W
AT
ER
PU
M P
CH
P-
SS
B-
P-
30A/ 3P
100AF
15AT
1 1/2
HO
T
W
AT
ER
P
UM
P
HW
P-
SS
B-
P-
30A/ 3P
100AF
15AT
1 1/2
P-
30A/ 3P
100AF
15AT
SP
AC
E
SP
AC
E
71/2/2
HE
AT
IN
G
V
EN
TI
LA
TI
NG
UN
IT
H
VU
-1
H
VU
-1
30A/ 6P
100AF
20AT
M O
TO
R
O
PE
R.
D
O O
R
NO
. 5 M
O
TO
R O
PE
R.
D O
O R
NO
. 1
SS
D
100AF
20AT
3/4
CO
ND
EN
SA
TE
U
NI
T
CU
-S
SB
-1
P-
30A/ 3P
100AF
15AT
AI
R
CO
M
PR
ES
SO
R
AC
-S
SB
-1
AC
-1
30A/ 3P
100AF
40AT
1/2
EX
HA
US
T
AI
R
FA
N
EA
F-
SS
B-
EA
F-
30A/ 3P
100AF
15AT
HO
T
W
AT
ER
P
UM
P
HW
P-
SS
B-
2 P
P
3/4 HP EA
M C
C S1
1 2
AI
R
HA
ND
LI
NG
UN
IT
A
HU
-S
SB
-1
AH
U
-1
MOTOR CONTROL CENTER "MCC-S1"
100A/ 3P
225AF
150AT
RE
TU
RN
A
IR
F
AN
RA
F-
SS
B-
R
AF
-1
60A/ 3P
100AF
50AT
CH
IL
LE
D
W
AT
ER
PU
M P
CH
P-
SS
B-
100AF
15AT
CH
IL
LE
D
W
AT
ER
PU
M P
CH
P-
SS
B-
100AF
15AT
1 1/2
HO
T
W
AT
ER
P
UM
P
HW
P-
SS
B-
P-
30A/ 3P
100AF
15AT
1 1/2
P-
30A/ 3P
100AF
15AT
SP
AC
E
SP
AC
E
71/2/2
HE
AT
IN
G
V
EN
TI
LA
TI
NG
UN
IT
H
VU
-1
H
VU
-1
30A/ 6P
100AF
20AT
M O
TO
R
O
PE
R.
D
O O
R
NO
. 5 M
O
TO
R O
PE
R.
D O
O R
NO
. 1
SS
D
100AF
20AT
3/4
CO
ND
EN
SA
TE
U
NI
T
CU
-S
SB
-1
P-
30A/ 3P
100AF
15AT
AI
R
CO
M
PR
ES
SO
R
AC
-S
SB
-1
AC
-1
30A/ 3P
100AF
40AT
1/2
EX
HA
US
T
AI
R
FA
N
EA
F-
SS
B-
EA
F-
30A/ 3P
100AF
15AT
HO
T
W
AT
ER
P
UM
P
HW
P-
SS
B-
2 P
P
3/4 HP EA
M C
C S1
VFD VFD
THE SEAL APPEARING ON THIS
BY JOHN R. ODUM.
DOCUMENT WAS AUTHORIZED
E
N
R
GIADO
L O
E F
P R
O
C O
A S
S
I NO N G
EL
I
31890
J
R
ST
RE
E E
E D
R
H M N
O
R. ODU
D E
S C
R
IP
T
IO
N M
A R
K D
A T
E A
P P
R
D E
S
IG
N E
D B
Y
D W
N B
Y
S U
B M
IT
T
E D
B Y
F
IL
E N
A M
E
S
IZ
E
P
LO
T S
C A
LE
P
LO
T D
A T
E
F
IL
E N
U M
B E
R
C O
N T
R A
C T
N O
S O
LI
C
IT
A
T
IO
N N
O
D A
T E
D E
S C
R
IP
T
IO
N M
A R
K D
A T
E A
P P
R
SHEET
IDENTIFICATION
C K
D B
Y
D E
S
IG
N , R
E P
A
IR
H V
A C
U N
IT
S
B
U
IL
D
IN
G
A N
S I D
A S
N O
T E
D
FOR OFFICIAL USE ONLY
FOR OFFICIAL USE ONLY
FO
R
O
FF
IC
IA
L U
S E
O N
LY
FO
R
O
FF
IC
IA
L U
S E
O N
LY
ME
OMC
SPA C N
D
A
D
2 3
C
A
B
8/
3/
S E
P T
E M
B E
R
D A
V
ID
A . L
U K
E , P
.E
G
LE
N
-1
P.E. 31890 ON 18 SEPT 2013
FO
R
C O
N S
TR
U
C
TI
O N
E-102
P . P
LE
IS
S
R . O
D U
M
R . O
D U
M
E
LE
C T
R
IC
A L
S C
H E
D U
LE
S
SCALE: N.T.S.
MECHANICAL EQUIPMENT CONNECTION SCHEDULE
TO CHP-101 CHILLED WATER PUMP
TO CHP-102 CHILLED WATER PUMP
SCALE: N.T.S.
EXISTING MOTOR CONTROL CENTER - S1
KEYED NOTES:
REMOVE EXISTING CBs AND MOTOR STARTERS IN EXISTING MCC-S1
REMOVE EXISTING DISCONNECT SWITCHES, CONDUIT AND CONDUCTORS
PROVIDE NEW CB (22 KAIC MIN)
SCALE: N.T.S.
EXISTING ELECTRICAL ONE-LINE DIAGRAM
SCALE: N.T.S.
NEW ELECTRICAL ONE-LINE DIAGRAM
| G-000 - COVER PAGE |
| M-001 - MECHANICAL LEGEND |
| M-101 - MECHANICAL DUCTWORK FLOOR PLAN |
| M-102 - MECHANICAL PIPING FLOOR PLAN |
| M-501 - MECHANICAL DETAILS, SCHEDULES & ISOMETRICS |
| M-601 - MECHANICAL CHILLED WATER FLOW SCHEMATICS |
| M-701 - MECHANICAL SYSTEM CONTROL DIAGRAMS |
| M-702 - MECHANICAL CONTROL FLOOR PLAN |
| E-001 - ELECTRICAL LEGEND |
| E-101 - ELECTRICAL FLOOR PLAN |
| E-102 - ELECTRICAL SCHEDULES |
File details come from the government source that posted it.