Solicitation # FA8126-15-Q-0010: Site Visit November 19, 2014 question and answers Q. Section 3.1.14 Utilities Interconnection addresses the responsibility of each party concerning the utilities and their connections. One item omitted from the list is the sanitary waste line for the sink. Please identify the limit of work by the supplier.
A. The contractor will connect drain to sump tank provided by the government within 25’ of the sinks
| Q. | Section 3.1.7 Lighting and Electrical. Please clarify that the surge protection is for the 480v 3-phase electric panel and all of the supplier’s equipment only and not the customer’s equipment. |
| A. | Surge protection in for the contractor supplied electrical equipment, and not the customer equipment. |
| Q. | Will the customer be responsible for receiving and off-loading our trucks? |
| A. | Offloading of delivery trucks will be done by the contractor |
Q. Will the customer be supplying lift equipment for the supplier’s use during the installation?
A. The contractor will provide all necessary material and manlift equipment to install the booths.