This document contains a solicitation for renovations and additions to a hangar at an Air Force Reserve base. The solicitation is set aside for HUBZone small businesses and seeks a firm-fixed price contract to renovate portions of Hangar 129 for C-17 aerospace ground equipment shops, offices, bathrooms, storage rooms, and maintenance bays. The project also includes building a 550 square foot addition for an aircraft jack stand tester requiring a substantial concrete foundation. Interested parties must register on the System for Award Management to receive consideration. The estimated contract value is between $1 million and $5 million and work must be completed within 270 calendar days of receiving the notice to proceed. The pre-proposal site visit will take place on or around February 10, 2021 and proposals are due by February 17, 2021.
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
R E
F
M GHJKL
FIELD LOCATE EXISTING CW AND HW HEADERS AND TIE IN NEW LAV, SH,
UR, HS AND WC USING EXISTING BRANCHES. PROVIDE 1/2" CW AND 1/2" HW
TO LAV; 3/4" CW AND 3/4" HW TO SH, 3/4" CW TO UR, 3/4" CW AND 3/4" HW TO
HS, 1/2" CW AND 1/2" HW TO KS, AND 1-1/2" CW TO WC CONNECTIONS.
WASH BAY
UNIVERSAL JACK
TESTER
AGE
MAINTENANCE
BAY
AGE
PARTS/TOOLS/BATTERY
AGE
CLASS/BREAK/COMPUTER
ROOM
EXISTING
MECHANICAL
EXISTING
MECHANICAL
AGE OFFICES
AGE PARTS
ROOM
MENS ROOM
WOMENS ROOM
P-111
S A
N
E
2" V (E)
4" SAN (E)
FD (E)
FD (E)
FD (E)
FD (E)
FD (E)
1 1/4" CA (E)
(E)1 1/4" CA
(E)
1 1/4" CA (E)
3/4" CW (E)
EWS (E)
HB (E)
CW (E)
CA (E)
1 1/4" CA (E)
HS
3/4" CW (E)
9 (TYP)
1-1/4" CW DN
TO EWS (E)
KS
3/4" CW
1 1/4" CW (E)
E
P-001
IWH-1
EW
14 14
14 14
3/4" CA
3/4" CA
3/4" CA 3/4" CA
3/4" CA 3/4" CA
3/4" CA
E
P-001
IWH-1
EW
3/4" CW
FIELD LOCATE 1/2" CW AND
1/2" HW FROM KS TO
RESTROOM HEADERS
1 3 4 7 8
CONNECT NEW 2" SAN
BRANCH FROM KS TO
EXISTING 4" SAN
CONNECT NEW 1-1/2"
V BRANCH FROM KS
TO EXISTING 2" V
S A
N
E
S A
N
E
4" SAN (E)
A
KEY PLAN
JK
MENS ROOM
WOMENS ROOM
AGE OFFICES
2" V
WC
UR
LAV
SH
LAV
WC
SH
2" V
2" V (E)
2" V (E)
1 1/2" V
3" VTR (E)
1-1/2" CW (E)
3/4" HW (E)1" CW (E)
HS
JK
2" SAN (E)
4" SAN (E)
3" SAN (E)
S A
N
E
4" FD (E)
CO (E)
SAWCUT FLOOR AT
THIS BOUNDARY AND
PREPARE FOR NEW
WORK.
1. DISCONNECT SAN AND V PIPING FROM PLUMBING
FIXTURE BACK TO SAN AND V HEADERS OR FLOOR
CONNECTIONS AND PREPARE FOR NEW WORK.
2. DISCONNECT CW AND HW FROM PLUMBING FIXTURES
AND DEMOLISH BACK TO SERVICE HEADERS. PROVIDE
ISOLATION VALVES AS REQUIRED AT HEADERS AND PREPARE
FOR NEW WORK.
3. CUT OPENINGS IN EXISTING WALL WHERE REQUIRED TO
PERFORM NEW WORK.
4. REFER TO FIXTURE SCHEDULE ON SHEET P-001 FOR
FIXTURE PIPING AND VENT SIZES. REFER TO SHEET P-111
FOR SANITARY AND VENT ISOMETRIC.
5. PROVIDE NEW DOUBLE WYE AT FLOOR AND CONNECT
TWO NEW WATER CLOSETS IN VERTICAL. CONNECT 2" V AT
TOP OF RISER TO EXISTING 2" V HEADER ABOVE.
6. PROVIDE NEW DOUBLE WYE AT FLOOR AND CONNECT
NEW UR, HS AND TWO NEW LAVS IN VERTICAL RISER WITH
1-1/2" V AT TOP OF RISER TO EXISTING 2" V HEADER ABOVE.
7. REMOVE PORTION OF EXISTING 4" SAN AND EXTEND 4"
SAN FROM EXISTING HEADER TO NEW PLUMBING FIXTURES.
8. PATCH WALLS AND FLOOR TO MATCH EXISTING AFTER
NEW WORK PASSES TESTING AND INSPECTION.
9. DURING FIELD SURVEY, NOT ALL FLOOR DRAINS WERE
ACCESSIBLE. CONTRACTOR SHALL FIELD VERIFY FLOOR
DRAIN QUANTITY THROUGHOUT THE ENTIRE PROJECT
BOUNDARY PRIOR TO BID. ALL FLOOR DRAINS SHALL BE
CLEARED OF ALL OBSTRUCTIONS AND THEN RECORDED
WITH CAMERA PROVING REMOVAL OF OBSTRUCTIONS.
REPORT ANY/ ALL DRAINS THAT CANNOT BE CLEARED TO
CONTRACTING OFFICER.
10. DROP 1/2" CW DOWN TO EYE WASH STATION WITH
ISOLATION VALVE OVERHEAD. INSTALL INSTANTANEOUS
ELECTRIC WATER HEATER AT SIDE OF EYE WASH, THEN
CONNECT TEPID WATER TO EYE WASH.
11. REMOVE 1-1/4" CW DROP TO EW AND TERMINATE BRANCH
BY CLOSING OVERHEAD ISOLATION VALVE. PREPARE FOR
NEW WORK INCLUDED IN KEYNOTE 12.
12. PROVIDE 1-1/4" X 3/4" REDUCER AT NEAREST CW HEADER
WITH ISOLATION VALVE AND FIELD ROUTE 3/4" CW TO NEW
EYEWASH STATION. INSTALL NEW INSTANTANEOUS ELECTRIC
WATER HEATER AT SIDE OF EW, THEN CONNECT TEPID
WATER TO EW.
13. REMOVE EXISTING CW AND HW BRANCHES TO
RESTROOM FIXTURES AND PREPARE FOR NEW WORK.
EXTEND EXISTING HEADERS FULL SIZE TO NEW FIXTURES
AND PROVIDE INDIVIDUAL BRANCH PIPING PER FIXTURE
CONNECTION SIZES LISTED IN SCHEDULE ON SHEET P-001.
14. TIE INTO EXISTING CA HEADER, PROVIDE REDUCER AND
3/4" CA ISOLATION VALVE AT HEADER, THEN DROP 3/4" CA TO
HOSE STATION PER DETAIL A ON SHEET P-001 AT 3'-0" AFF.
KEYED NOTES
JK
4" FD
4" SAN
MENS ROOM
WOMENS ROOM
AGE OFFICES
WC
UR
LAV
SH
2" SAN (E)
4" SAN
3" SAN (E)
S A
N
E
LAV
WC
SH
3" SAN
CO (E)
FD (E)
2" SAN (E)
2" V
2" SAN
1-1/2" SAN
D
P-001
HS
2" SAN
DRAWING NO.BASE CIVIL ENG.CHIEF ENG. FLIGHT PLATE
SCALE:DATE:PROJECT NO:CHIEF CE OPERATIONS
USING AGENCY
COMMUNICATIONS
BIO ENVIRONMENTAL
ENVIRONMENTAL ENG.
FIRE
SAFETY
SECURITY
ANTI-TERRORISM
CDM SMITH PROJECT #
CHECK BY:
DRAWN BY:
DESIGN BY:
REV. NO. DATE DESCRIPTION BY
REVIEW
COORDINATION DATE
SHEET OF
ISSUED FOR CONSTRUCTION
FOR OFFICIAL USE ONLY
U.S. AIR FORCE
911TH AIRLIFT WING
PITTSBURGH INTERNATIONAL AIRPORT, ARS
MOON TOWNSHIP, PA 15108-5000:
54321 6
B
C
D
E
A
C
D
E
106718-231406
JLSS-17-0011 10/08/2019
GTP 210-168
503 Martindale Street, Suite 400 Pittsburgh, PA 15212-5722 Tel: (412) 201-5500
As indicated2 /2
/2
:5 :0
P
M
RENOVATE/ADD FOR AGE SHOP/OFFICES, B129A. RICKETTS
G. LUISI
TASCARELLA
P-111
PLUMBING FIRST FLOOR DEMOLITION AND
NEW WORK PLAN AREA A
1/8" = 1'-0"M-111
2 BUILDING 129 - PLUMBING FIRST FLOOR NEW WORK PLAN - AREA A
1/4" = 1'-0"M-111
3 BUILDING 129 - ENLARGED PLUMBING FIRST FLOOR PLAN ABOVE GRADE
1/4" = 1'-0"M-111
1 BUILDING 129 - ENLARGED PLUMBING FIRST FLOOR DEMOLITION PLAN - AREA A
N
1/4" = 1'-0"M-111
4 BUILDING 129 - ENLARGED PLUMBING FIRST FLOOR PLAN BELOW GRADE
| Sheets |
| P-111 - PLUMBING FIRST FLOOR DEMOLITION AND NEW WORK PLAN AREA A |