FA6675-18-R-0004 – BUILDING 1628 RENOVATION

Request for Information (RFI) Response

RFI #3

Question: Does BCE have preferred Fire Protection System Contractors?

Response: BCE does not have any preferred Fire Protection System Contractors.

RFI #4

Question: Can the new duplex receptacles in room 114 be wired from an existing circuit or is a new dedicated circuit required?

Response: The receptacle can be run off of an existing receptacle circuit providing it does not overload the circuit per the NEC.

RFI #5 Pending Response

RFI #6

Question: Can the hose bib and drain to be installed be surface mounted or does it have to be in wall?

Response: The hose bib and drain shall be mounted in the wall.

RFI #7

Question: Will the existing drop ceilings that are currently in place need to be replaced?

Response: Existing ceilings will not need to be replaced unless damaged during construction. If damage occurs, contractor will repair/replace damaged ceilings.

RFI #8

Question: Please provide specifications for both the Air Compressor and Refrigerated Dryer.

Response: Existing Air Compressor and existing Air Dryer "installation only" is required for this project. See Statement of Work Revision 2.

RFI #9

Question: Can existing conduits be reused where practical for fire alarm wiring?

Response: Existing FA conduit may be used in its current location only. It shall not be removed and used in other locations.

Question: Does new or existing conduit need to be painted?

Response: Painting the conduit is not required.