ADDENDUM_FOR_QJKL_07_-_0008.pdf
PDF 79 KB Posted
- Attached to
- Repair Roof Bldg 805
- Solicitation number
- FA6633-17-Q0001
About this file
Addendum #1
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Amendment_0004.docx | DOCX document | |
| Addendum__4.doc | DOC document | |
| ADDENDUM_3_FOR_QJKL_07_-_0008(20170425).pdf | ||
| Amendment__3.pdf | ||
| Amendment_02.pdf | ||
| ADDENDUM__2_FOR_QJKL_07_-_0008(20170413).pdf | ||
| QUESTIONS-RESPONSES_2.doc | DOC document | |
| QUESTIONS-RESPONSES.doc | DOC document | |
| Amendment_01.docx | DOCX document | |
| FA6633-17-Q0001.docx | DOCX document | |
| Drawings.pdf | ||
| Technical__Specifications_(1).pdf | ||
| wage_determination.doc | DOC document |
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ADDENDUM FOR
QJKL 07 – 0008 Replace Roof, Building 805
1. Technical Drawing sheet A2 – Caged ladder concrete slab requirement note:
Change to: Place a 36” (W) x 4” (D) x 10’ (L) unreinforced concrete slab.
The new slab must fit between the existing building wall and sidewalk with the felt installed.”
2. As a general note: The current roof insulation is 4.5” thick, with one ¾” thick fire-rated board between the steel deck and insulation, another 3/4 “ fire-rated board between the insulation and the membrane. Since the new high density board is ½” thick maximum, use two layers of 2.5” Poly-isocyanurate board with two layers of ½” thick fire-rated high-density (HD) board. Use high-density fire-rated board that meets UL 790 standard. The high-density board provides good adherence for the membrane when attached with bond adhesive.
3. Add: Apply ½” slope tapered insulation to crickets for positive drainage.
4. Section 07 60 Part 3 Execution: Use aluminum instead of copper for new coping metal.
5. Use 3/8” laminated plywood and attach it to the wall. The plywood will provide good adherence for the membrane flashing covering the exterior wall when applied with bonding adhesive.