Solicitation Number FA5587-18-Q-0087
Project/Program Name RAF Mildenhall 100th CES 30k, 80k, 250k kVA GENERATORS
Date 29 August 2018
Purchasing Agency 48th Contracting Squadron – 48 CONS/PKA
RAF Lakenheath, Brandon, Suffolk, IP27 9PN, United Kingdom
Subject Amendment 0003: Questions and Answers x
Questions and Answers
Disclaimer: The following question have been received from various interested offerors. Please note, some of the questions received are still under technical review and pending responses. Those questions will be answered and posted on FBO through an amendment at a later date.
Industry Question Reference Government Response
1. Do you want the generators to be silent
(covered with SOUND PROOF Canopy) OR to open style?
Yes. Sound attenuated enclosure.
2. Which frequency required 50 Hz or 60Hz.? Attachment I-
Statement of
Work. 2. Product
Specifications
Requirements:
Please reference to Table 1. Product Technical Specification
Requirements. 2.1.2. Voltage/Frequency: 120/208-240/416 dual voltage 50/60HZ.
Please note: Sockets are enable for 50Hz and disable for 60Hz.
3. Do you want it skid mounted or on trailer? If with trailer what type of trailer required.
Attachment I-
Statement of
Work. 2. Product
Specifications
Requirements:
Skid mounted is a requirement for moving the generator from place to place, however, the trailer is not a requirement for operational use.
Please reference to Table 1. Product Technical Specification
Requirements.
4. Also you did not require any cables. Please clarify.
Cables will not be required.
5. Are you looking to rent/hire the equipment or purchase the equipment?
The Request for Quotes is for the purchase of generators.
Amend 0003, 24 September 2018
6. Could you specify the voltages for each frequency and if there is 3ph or monophasic, This applies to all generators:
The standard is 400V 50Hz 3ph / 480V 60Hz
3ph
3 phase output
The line to line voltage requirement for 60Hz is 208 Volts
The line to line voltage requirement for 50Hz is 416 Volts
File details come from the government source that posted it.