QUESTIONS AND ANSWERS for Runway Approach Lights project FA5575-17-B-0003
1. The blue print EA105 shows wiring for the approach lighting, 2 - 12 AWG. Although Item 14 of the solicitation (page 3 of 4), shows 1 cable NYY-0 5x2.5 mm2. Are they the same?, or is the Item listing missing the request for the 12 AWG wiring?
* No, they should be different (note drawings depict 2-8AWG rather than 2 AWG)
En plano EA105 aparece cable en luces empotradas de la zona de aproximación de 2 cables de 12 AWG APPROACH, pero en la partida nº 14 del presupuesto (hoja 3 de 4), aparece un cable NYY-0 5x2.5 mm2.
¿Son los mismos? ¿o falta la partida del presupuesto del cable 12 AWG?
2. Which section of cable on the blue prints corresponds to the segment of cable 5x2.5 mm2? Cable bypass from manholes to the pole of the elevated flashing lights, at the stop or hold zone up to the ILS antenna?
* Yes
A que tramo de cable en el plano, corresponde este cable de 5x2.5 mm2. ¿Derivación de cable desde arquetas hasta mástil de luces de destellos elevada, en zona de parada hasta antena ILS?
3. For the characteristics and supply of the 10 KVA we need to know what eco-design standard applies: European Standard: UE548 or IEC Standard:
* 60076 Worldwide.
Para las características y suministro del 10 KVA necesitamos saber con qué norma de eco diseño le aplica:
La Norma Europea: UE548 o a la Norma IEC: 60076 Mundial.
Ref specs (in Spanish) para 2.8 titled Transformadores, Contractor needs to look into FAA AC 150/5345- 47, type L-830.. ..this will give him/her answers he/she may be looking for regarding transformers