Site Visit Clarifications to Q&A

View the file

Other files for this federal contract opportunity

Other files attached to PDS Replacement (Fiber Cabling), newest first.
File Type Posted
Amendment_5.pdf PDF
Site_Visit_Questions_and_Answers_4_8_19_CENTCOM_SOCOM.pdf PDF
Amendment_4.pdf PDF
Amendment__3.pdf PDF
Additional_Questions_and_Answers.pdf PDF
Amendment.pdf PDF
Solicitation_Questions_and_Answers.pdf PDF
Attachment_2,_SOW.pdf PDF
Attachment_1,_CLIN_Structure.pdf PDF
Attachment_3,_Clauses.pdf PDF
RFQ.pdf PDF
Show all 11

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MISSION FOCUSED…VALUED AIRMEN

DEPARTMENT OF THE AIR FORCE

6TH AIR MOBILITY WING (AMC)

MACDILL AIR FORCE BASE, FLORIDA

Site Visit Clarifications

1. Is Coalition one of the previous four 144 strand fiber cable in the scope? If not what is the strand count needed? Yes. (4) 144CT SM Fibers for new install (1) UNCLASSIFIED,

(1) COALITION, (1) SECRET, and (1) TS….at this current time, there is NO existing COALITION fiber that is what I meant. The bottom line is (4) 144ct SM fibers.

2. Response states “””From Building 578 (CENTCOM) to Building 501B (then 501D) is 8,600ft. “”” Is this a continuous piece of cable from bldg. bldg. 578 to 501D or does this cable terminate in all three building? If terminates in all three bldgs.. more hardware is required. From Building 578 to Building 501B is 7100ft. The fiber then leaves the datacenter at SOCOM to Building 501D which is 1500 added feet per SOCOM Techs.

Terminates in ALL 3 buildings (578, 501B, and 501D for the Hybrid. Yes, more hardware is required.

3. Are the pathways entering the building to the telecom rooms complete conduit or do the cables freely route in open space/ceilings? The TS and Hybrid fiber are the only cables that go into a conduit (PDS) when it enters the building. The other cables are free in the ceiling or floor to the Building 501b datacenter.

4. Will a transition splice be allowed from indoor to outdoor fiber? NO….Indoor/outdoor cable only

5. Amendment 4 question 14 was answered Corning. Is there a warranty required? No warranty was previously requested. 20 years