FA4659-10-R-0043-0001.doc
DOC document 39 KB Posted
- Solicitation number
- FA4659-10-R-0043_Synopsis
About this file
Amendment to incorporate changes provided by the project designers.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Amendment 0004 Due Date Extension.docx | DOCX document | |
| Amendment 0003.rtf | RTF text file | |
| FA4659-10-R-0043-0002.doc | DOC document | |
| Atth 1 - Technical Specs.pdf | ||
| Atth 5 - Financial Institution Reference Sheet.doc | DOC document | |
| Atth 6 - Climatological Data.pdf | ||
| Atth 2 - Drawings.pdf | ||
| Solicitation FA4659-10-R-0043.doc | DOC document | |
| 410 RFP Letter.pdf | ||
| Atth 4 - Past Performance Questionnaire.doc | DOC document | |
| Atth 3 - Submittal Schedule.pdf |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SECTION SF 30 BLOCK 14 CONTINUATION PAGE
SUMMARY OF CHANGES
Summary of changes:
a. Section 04 20 00 Page 8, Lines 50-59, and Page 04 20 00-9, Lines 1 and 2. Delete in their entirety and replace with the following:
1. At cavity wall construction, build flashing into masonry construction as indicated on the drawings. Stop flashing 1/4 inch back from outside face of wall and adhere flashing to substrate below.
2. At brick veneer/stud wall construction, extend flashing up behind rigid wall insulation and seal top edge with mastic as shown on the Drawings.
3. At lintels and shelf angles, extend flashing a minimum of 4 inches into masonry at each end. At heads and sills, extend flashing 4 inches at ends and turn flashing up not less than 2 inches to form a pan.
4. Care shall be taken not to puncture flashing material and to keep cavity completely free of mortar droppings. Joints shall be avoided to the maximum extent possible, but where they occur, they shall be lapped a minimum of 6-inches and sealed with the manufacturer’s recommended joint adhesive. All flashing steps and corner turns shall be thoroughly sealed. Gaps in thru-wall flashing or unsealed lapped joints will not be acceptable.
b. Section 04 20 00 Page 7, Line 50. Delete the following: “at exterior steel stud/brick veneer walls”.
c. Section 32 16 13, Page 1, Lines 15-19. Delete in their entirety.
(End of Summary of Changes)