QUESTIONS 2: FA462619RA003: REPAIR HEAT PLANT BOILER
Question 9: If we want to propose an alternate burner and blower system, do we need to submit the information for approval?
Answer 9: Contractors can submit on an alternate burner as long as their burner meets “or equal requirements” in spec section 23 52 33. The Government does not do any approvals prior to bid closing.
It is the contractor’s responsibility to ensure their burner meets the specs. Also, alternate submittals should pay close attention to spec section 23 52 33, Part 2 – Products, 2.1, A.