Attch_5_Consolidated_Fire_Alarm_Spec.doc
DOC document 114 KB Posted
- Attached to
- Upgrade SM Gate Federal contract opportunity
- Solicitation number
- FA4610-16-R-5000
About this file
Attch 5 Consolidated Fire Alarm Spec
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Questions_and_Answers.docx | DOCX document | |
| XUMU_07-1218C__-Santa_Maria_Gate_As-Builts_Drawings.pdf | ||
| Site_Visit_Sign-In.pdf | ||
| Attch_6_Specifications.pdf | ||
| FA4610-16-R-5000.pdf | ||
| Attch_1_Davis_Bacon_Wage.docx | DOCX document | |
| Attch_3_Environmental_Specs.docx | DOCX document | |
| Attch_7_-_35__Drawings.pdf | ||
| Attch_8_Force_Protection_Specifications.pdf | ||
| Attch_4_General_Requirements.doc | DOC document | |
| Attch_2_Statement_of_Work.doc | DOC document | |
| Attch_9_UFGS.pdf | ||
| Presolicitation_Notice_Upgrade_Inspection_Facilities_at_Santa_Maria_Gate.doc | DOC document |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FA4610-16-R-5000
Attch 5
INTERIOR FIRE DETECTION AND ALARM SYSTEM
09/2009
PART 1 GENERAL
1.1 REFERENCES
1.2 RELATED REQUIREMENTS
1.3 DESCRIPTION OF WORK
1.4 SYSTEM DESCRIPTION
1.4.1 Design Requirements
1.4.1.1 Power Calculations
1.5 SUBMITTALS
1.6 QUALITY ASSURANCE
1.6.1 Qualifications of Installer
1.6.2 Manufacturer's Representative
1.6.3 Qualifications of System Technician
1.6.4 Drawing Requirements
1.6.4.1 System Floor Plans
1.6.4.2 System Wiring Diagrams
1.6.4.3 System As-Built Drawings
1.6.5 UL Listing or FM Approval
1.7 MAINTENANCE
1.7.1 Spare Parts
1.7.2 Manuals
PART 2 PRODUCTS
2.1 SYSTEM DESIGN
2.1.1 Operation
2.1.1.1 Fire Alarm Signal Initiation
2.1.1.2 Supervisory Signal Initiation
2.1.1.3 Monitoring Integrity of Installation Conductors
2.1.1.4 Walk-Test Mode
2.1.1.6 Elevator Recall
2.1.2 Primary Power
2.1.3 Auxiliary Power
2.1.3.1 Storage Batteries
2.1.3.2 Battery Charger
2.2 COMPONENT DESIGN
2.2.1 Control Panel
2.2.1.1 Main Annunciator
2.2.1.2 Initiating Zones
2.2.1.3 Remote Annunciator Panel
2.2.1.4 Graphic Annunciator Panel
2.2.1.5 Trouble Buzzer
2.2.2 Manual Pull Stations
2.2.3 Heat Detectors
2.2.3.1 Combination Fixed Temperature Rate-Of-Rise Detectors (Spot
Type)
2.2.4 Open-Area (Spot-Type) Smoke Detectors
2.2.4.1 4-Wire Smoke Detectors
2.2.4.2 2-Wire Smoke Detectors
2.2.4.4 Photoelectric Detectors
2.2.4.5 Detector Spacing and Location
2.2.5 Duct Smoke Detectors
2.2.6 Projected Beam Smoke Detector
2.2.7 Notification Appliances
2.2.7.2 Alarm Horns
2.2.7.3 Visible Appliances
2.2.8 Fire Extinguishing Systems
2.2.9 Freeze Protection Thermostatic Switch
2.2.10 Electro-Magnetic Door Holder-Releases
2.2.11 Valve Tamper Switches/Chains
2.2.13 Conduit
2.2.13.1 Rigid Steel Conduit (Zinc-Coated)
2.2.13.2 Intermediate Metal Conduit (IMC)
2.2.13.3 Electrical Metallic Tubing (EMT)
2.2.13.4 Surface Metal Raceway and Fittings
2.2.14 Outlet Boxes
2.2.15 Fittings for Conduit and Outlet Boxes
2.2.16 Wiring
PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Additional Installation Requirements
3.2 FIELD QUALITY CONTROL
3.2.1 Preliminary Testing
3.2.2 Final Acceptance Testing
3.2.2.1 Entire System
3.2.2.2 Supervisory Systems
3.2.3 Additional Tests
3.2.4 Training
NOTE: Both 4-wire and 2-wire smoke detectors are specified in this guide specification. For smoke detectors in new systems, edit this specification to permit the Contractor the option to provide 2-wire detectors. 4-wire smoke detectors are required for mission essential facilities.
NOTE: The following information shall be shown on the project drawings:
1. On electrical power or fire protection floor plans show location of control panel, battery and charger, transmitter, remote annunciator, connection to power source, remote trouble device, alarm notification appliances, and each initiating device including fire extinguishing system switches and manual pull stations.
2. On electrical site plan, show location of master fire alarm box, outside annunciator (if required), circuit run to the connection to the base fire alarm circuit (except radio systems), circuit run into the building and connection to control panel, and circuit run for master box marker light. Circuit runs to the base fire alarm (except radio systems) should show conduit size and numbers and size of conductors.
3. Show single line fire alarm riser diagram. Connection of equipment should be indicated by circuit runs and not conduit runs. Do not indicate number and size of conductors for interconnection of fire alarm components.
NOTE: When an existing system is to be expanded, show the following information:
1. Manufacturer and model of existing control panel.
2. Number of existing initiating circuits (zones), notification appliance circuits, and control circuits served by the control panel.
3. Number of existing alarm notification appliances on the system.
4. Total calculated current draw of all devices served by the existing standby battery under both supervisory (standby) and alarm conditions.
5. Ampere-hour rating and type of existing battery.
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASME INTERNATIONAL (ASME)
ASME A17.1 (2007; Addenda 2008) Safety Code for
Elevators and Escalators
BUILDERS HARDWARE MANUFACTURERS ASSOCIATION (BHMA)
BHMA A156.15 (2006) Closer Holder Release Devices
FM GLOBAL (FM)
FM P7825 (2005) Approval Guide
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE C62.41.1 (2002) IEEE Guide on the Surges
Environment in Low-Voltage (1000 V and
Less) AC Power Circuits
IEEE C62.41.2 (2002) IEEE Recommended Practice on
SECTION 28 31 74.00 20 Page 6
Characterization of Surges in Low-Voltage
(1000 V and Less) AC Power Circuits
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
NEMA C80.1 (2005) Standard for Electrical Rigid Steel
Conduit (ERSC)
NEMA C80.3 (2005) Standard for Electrical Metallic
Tubing (EMT)
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2008; AMD 1 2008) National Electrical
Code - 2008 Edition
NFPA 72 (2006; Errata 2008; Errata 2009) National
Fire Alarm Code
NFPA 90A (2008; Errata 2009) Standard for the
Installation of Air Conditioning and
Ventilating Systems
UNDERWRITERS LABORATORIES (UL)
UL 1242 (2006; Rev thru Jul 2007) Standard for
Electrical Intermediate Metal Conduit --
Steel
UL 1449 (2006; Rev thru Jun 2009) Surge Protective
Devices
UL 1971 (2002; Rev thru Oct 2008) Signaling
Devices for the Hearing Impaired
UL 467 (2007) Standard for Grounding and Bonding
Equipment
UL 497B (2004; Rev thru Oct 2008) Protectors for
Data Communication and Fire Alarm Circuits
UL 5 (2004; Rev thru May 2007) Surface Metal
Raceways and Fittings
UL 514A (2004; Rev thru Aug 2007) Standard for
Metallic Outlet Boxes
UL 514B (2004; Rev thru Aug 2007) Standard for
Conduit, Tubing and Cable Fittings
UL 6 (2007) Standard for Electrical Rigid Metal
Conduit-Steel
UL 797 (2007) Standard for Electrical Metallic
Tubing -- Steel
UL Fire Prot Dir (2009) Fire Protection Equipment Directory
1.2 RELATED REQUIREMENTS
Section 26 00 00.00 20 BASIC ELECTRICAL MATERIALS AND METHODS applies to this section with additions and modifications specified herein.
1.3 DESCRIPTION OF WORK
The work includes [modifying existing] [and] [providing new] interior fire alarm system including material, tools, equipment, installation, and testing necessary for and incidental to the provision of a complete and usable standard system conforming to the applicable requirements of NFPA 70, NFPA 72, and NFPA 90A and this specification. In referenced NFPA publications, the advisory provisions shall be mandatory, as though the word "shall" had been substituted for "should" wherever it appears; reference to the "authority having jurisdiction" shall be interpreted to mean a combination of approval between the base fire department inspector’s office, the base Fire Protection Engineer, and the base alarm shop. The Civil Engineer Squadron Commander is designated as the base Fire Marshall.
Equipment and devices shall be compatible and operable in all respects with, and shall in no way impair reliability or operational functions of, the existing interior fire alarm system and the existing base fire alarm system.
Materials and equipment to be furnished under this contract shall be essentially the current design products of manufacturers regularly engaged in production of such equipment and shall be listed by the Underwriters' Laboratories, Inc. in the UL Fire Prot Dir, or approved by Factory Mutual System and listed in FM P7825.
1.4 SYSTEM DESCRIPTION
1.4.1 Design Requirements
1.4.1.1 Power Calculations
Submit design calculations for the existing system and new work specified herein to substantiate that the battery capacity exceeds supervisory and alarm power requirements. Show comparison of the detector power requirements per zone versus the control panel smoke detector power output per zone in both the standby and alarm modes. Show comparison of the notification appliance circuit alarm power requirements with the rated circuit power output.
1.5 SUBMITTALS
Government approval is required for submittals with a "G" designation; submittals not having a "G" designation are for Contractor Quality Control approval. The following shall be submitted in accordance with
The Authority Have Jurisdiction will review for approval all submittals required by this section.
SD-02 Shop Drawings
System floor plans; G
System wiring diagrams; G
Conductor wire marker schedule; G SD-03 Product Data
Control panel and modules; G
Storage batteries; G
Battery charger; G
Manual pull stations; G
Heat detectors; G
Open-area (spot-type) smoke detectors; G
Duct smoke detectors; G
Alarm horns; G
Visible appliances; G
Main annunciator; G
Remote annunciator panel; G
Graphic annunciator panel; G
Master fire alarm boxes; G Auxiliary transmitter; G Master box pedestal; G Combination auxiliary transmitter and interface panel; G Freeze protection thermostatic switch; G Electro-magnetic door holder-releases; G Wiring; G
Ground rods
Conduit
Outlet boxes
Fittings for conduit and outlet boxes
Trouble [bell] [buzzer]; G Projected beam smoke detector; G Surge suppression devices; G Data which describe more than one type of item shall be clearly marked to indicate which type the Contractor intends to provide. Submit one original for each item and clear, legible, first-generation photocopies for the remainder of the specified copies. Incomplete or illegible photocopies will not be accepted. Partial submittals will not be accepted.
SD-05 Design Data
Power calculations; G SD-06 Test Reports
Preliminary testing; G
Final acceptance testing; G Submit for all inspections and tests specified under paragraph entitled "Field Quality Control."
SD-07 Certificates
Qualifications of installer; G
Qualifications of system technician; G SD-08 Manufacturer's Instructions
Projected beam smoke detector; G SD-10 Operation and Maintenance Data
Fire alarm system, Data Package; G Submit in accordance with Section 01 78 23 OPERATION AND MAINTENANCE DATA.
SD-11 Closeout Submittals
System as-built drawings; G
1.6 QUALITY ASSURANCE
1.6.1 Qualifications of Installer
The Contractor or installer shall have satisfactorily installed fire alarm systems of the same type and design.
1.6.2 Manufacturer's Representative
Provide the services of a representative or technician from the manufacturer of the system, experienced in the installation and operation of the type of system being provided, to supervise installation, adjustment, preliminary testing, and final testing of the system and to provide instruction to Government personnel.
1.6.3 Qualifications of System Technician
Installation drawings, shop drawings and as-built drawings shall be prepared by, or under the supervision of, a qualified technician. Qualified technician shall be an individual who is experienced with the types of work specified herein, and is currently certified by the National Institute for Certification in Engineering Technologies (NICET) as an engineering technician with minimum Level III certification in fire alarm system program for all normal base projects. For complex projects, a state registered Fire Protection Engineer shall be used. Contractor shall submit data showing the name and certification of the technician/engineer at or prior to submittal of drawings.
1.6.4 Drawing Requirements
1.6.4.1 System Floor Plans
Submit shop drawings of the system floor plans showing locations of initiating and indicating appliances and end-of-line supervisory devices.
Show wire color coding, wire counts, and device wiring order. Show candela rating of each visible notification appliance.
1.6.4.2 System Wiring Diagrams
Submit complete wiring diagrams of the system showing points of connection and terminals used for all electrical connections in the system. Show all modules, relays, switches and lamps in the control panel.
1.6.4.3 System As-Built Drawings
Upon completion, and before final acceptance of the work, furnish to the Contracting Officer one complete set of as-built drawings. The as-built drawings shall be "D" size 850 by 550 mm 34 by 22 inches reproducible drawings on mylar film drawn to the same scale as the contract drawings and with title block similar to contract drawings.
1.6.5 UL Listing or FM Approval
Submit copies of UL listing or FM approval data showing compatibility of the smoke detector model being provided with the control panel being provided.
1.7 MAINTENANCE
1.7.1 Spare Parts
10% of the amount of devices installed should be turned over to the base fire alarm shop along with a complete fuse set for new panels.
1.7.2 Manuals
Submit operation and maintenance data in accordance with the applicable OPERATION AND MAINTENANCE DATA spec section. Inscribe the following identification on the cover: the words OPERATION AND MAINTENANCE MANUAL, the location of the building, the name of the Contractor, system manufacturer and the contract number. The instructions shall be legible and easily read, with large sheets of drawings folded in. The manual shall include: circuit drawings; wiring and control diagrams with data to explain detailed operation and control of each item of equipment; a control sequence describing start-up, operation and shutdown instructions; installation instructions; maintenance instructions; safety precautions, diagrams, and illustrations; test procedures; performance data; and parts list.
1.7.3 Software
All software and specialized tools required to maintain the system will be supplied by the installer. All software will include any security devices or codes required to either operate the software are load the software.
PART 2 PRODUCTS
2.1 SYSTEM DESIGN
2.1.1 Operation
NOTE: Shutdown of mechanical (HVAC) systems must be carefully coordinated between this section and mechanical sections. All HVAC systems must be shutdown upon operation of the alarm system unless the shutdown of individual HVAC units separately when smoke is detected in each unit's ductwork is approved by the AHJ. Shutdown of all HVAC systems upon any alarm is desirable from a life safety standpoint, but may not be practical in all cases.
To shut down all HVAC units from the fire alarm control panel retain the reference to HVAC equipment shutdown in paragraph titled "Operation" and delete reference to shutdown in paragraph titled "Duct Smoke Detectors". If it is desired to shutdown systems on an individual unit basis, delete the reference to HVAC equipment shutdown in paragraph titled "Operation", and retain the reference to shutdown in paragraph titled "Duct Smoke Detectors".
Provide a complete, electrically supervised, code 3 temporal common coded, annunciated, fire alarm system as described herein, and as shown on the drawings.
2.1.1.1 Fire Alarm Signal Initiation
Operation shall be such that actuation of any:
a. Manual station
b. Heat detector
c. Smoke detector
d. Automatic fire sprinkler system
e. Fire extinguishing system Shall cause all of the following actions:
a. All building evacuation alarm devices (notification appliances) to operate continuously;
b. The annunciator(s) to properly register;
c. A coded signal to be transmitted over the station fire alarm system;
d. Heating, ventilating, and air conditioning equipment to shut down;
e. Electro-magnetic door holders to de-energize.
All operations shall remain in the alarm mode (except alarm notification appliances if manually silenced) until the system is manually restored to normal. A signal should be transmitted to the ECC (Bldg 13730) and the fire alarm shop (Bldg 11439).
2.1.1.2 Supervisory Signal Initiation
NOTE: Include this paragraph when any of the listed supervisory signal initiating devices are provided by the project or exist in the building and edit accordingly, otherwise delete.
Operation of a sprinkler control valve tamper shall not cause an alarm, but shall cause operation of common system audible trouble signal, and display of a visual indication distinct from that displayed to indicate a fire alarm or a fault in the supervisory circuit and transmission of a distinct supervisory signal to the ECC (Bldg 13730) and the fire alarm shop (Bldg 11439).
2.1.1.3 Monitoring Integrity of Installation Conductors
NOTE: "Class A" monitoring should be specified for buildings with high life hazard such as hospitals and high rise buildings, and for strategically critical or extremely high monetary value facilities. For all other facilities "Class B" monitoring should usually be specified. (Comply with the limitations contained in NFPA 72 on the number of initiating devices permitted per circuit for both "Class A" and "Class B" circuits.) For all
"Class A" circuits, specify separate conduit for return conductors. For additions to existing alarm systems, specify the type of monitoring already in use.
All system circuits shall be electrically monitored for integrity including the following:
a. Initiating circuits.
b. Evacuation alarm (notification appliance) circuits (including both audible and visual notification appliances).
c. Battery power supply (low and no voltage across the standby battery terminals and open battery circuit).
d. Auxiliary transmitter tripping circuits.
Provide Class A or B initiating device circuits, and Class A or B notification appliance circuits as defined by NFPA 72. For
Class A circuits, provide separate conduits for outgoing and return (redundant) conductors as required by NFPA 72. A ground fault condition or single break in any other circuit shall cause operation of the system trouble signals. Loss of AC power, abnormal AC voltage, a break in the standby battery power circuit, or low battery voltage shall also cause operation of system trouble signals. The abnormal position of any switch in the control panel shall also cause operation of the system trouble signals. Audible and visual equipment for supervision of the AC power supply shall be energized from the auxiliary DC power supply and vice versa. Trouble signals shall sound continuously until manually silenced or the system has been restored to normal. Electrical monitoring for integrity of wiring external of control panel for mechanical equipment shut down and magnetic door holding circuits is not required, provided a break in the circuit will cause doors to close and mechanical equipment to shutdown.
2.1.1.4 Walk-Test Mode
Provide system with walk-test mode to allow one person to test alarm and supervisory features of initiating devices. Walk-test mode shall be enabled from the control panel by authorized service personnel. Control panel shall display a unique visual indication when system is in walk-test mode. If testing ceases while in walk-test mode, after a preset delay system shall automatically return to normal standby mode.
2.1.1.6 Elevator Recall
Provide elevator recall system in accordance with ASME A17.1, Section [14 21 00.00 20 ELECTRICAL TRACTION ELEVATORS] [14 24 00 HYDRAULIC ELEVATORS], and as specified herein. Activation of any smoke detector in an elevator shaft, machine room, or lobby (except at designated recall level) shall cause all elevators associated with that shaft, machine room, or lobby to return nonstop to the designated level. Activation of a smoke detector in the lobby or machine room at the designated level shall cause all elevators associated with that lobby to return nonstop to the assigned alternate level. Activation of a detector in an elevator shaft, machine room, or lobby shall also cause complete operation of fire alarm system as specified in paragraph titled "Operation".
2.1.2 Primary Power
Primary power source shall be 120 volts AC service, transformed through a two winding isolation type transformer and rectified to 24 volts DC for operation of all initiating device, notification appliance, signaling line, trouble signal and transmitter tripping circuits. The alarm current draw of the entire fire alarm system shall not exceed 80 percent of the rated output of the system power supply module(s). Obtain AC operating power as shown on contract drawings. Provide an independent properly fused safety switch, with provisions for locking the cover and operating handle in the "POWER ON" position for this connection located adjacent to main distribution panel. Paint the switch box red and identify it by the lettered designation "FIRE ALARM SYSTEM POWER".
2.1.3 Auxiliary Power
Provide secondary DC power supply for operation of system in the event of failure of the AC source. Transfer from normal to emergency power or restoration from emergency to normal power shall be fully automatic and shall not cause transmission of a false alarm. Loss of AC power shall not prevent transmission of a signal to station fire alarm headquarters upon operation of any initiating circuit.
2.1.3.1 Storage Batteries
Provide sealed lead acid batteries and charger. Drycell batteries are not acceptable. House batteries in the control panel or in a well constructed vented steel cabinet with cylinder lock, non-corrosive base, and louvered vents. Provide batteries of adequate ampere-hour rating to operate the system, including audible trouble signal devices, and auxiliary transmitter tripping circuits under supervisory conditions for 24 hours, at the end of which time batteries shall be capable of operating the entire system in a full alarm condition for not less than 5 minutes. Provide calculations substantiating the battery capacity. If calculations required by the paragraph entitled "Power Calculations" show that the total supervisory and alarm power requirements of the modified system exceed the capacity of the existing battery, provide a new battery as specified herein. Provide reliable separation between cells to prevent contact between terminals of adjacent cells and between battery terminals and other metal parts. When a separate battery cabinet is used, provide a fuse block for battery leads within the cabinet. Finish the cabinet on the inside and outside with enamel paint. Locate the top of the batteries not more than 1.2 m 4 feet above floor level.
2.1.3.2 Battery Charger
Provide completely automatic high/low charging rate type capable of recovery of the batteries from full discharge to full charge in 24 hours or less. Provide a trouble light to indicate when batteries are manually placed on a high rate of charge as part of the unit assembly if a high-rate switch is provided. House the charger in the control panel or battery cabinet.
2.2 COMPONENT DESIGN
NOTE: Delete equipment paragraphs not applicable for the project.
2.2.1 Control Panel
The Fire Alarm Control Panel (FACP) shall be completely addressable with all devices given a specific address for clarity during alarm or supervisory signal reporting. All panels shall be capable of reporting via telephone dial up to both the ECC (Bldg 13730) and the fire alarm shop (11439) simultaneously. The system shall be capable of sending daily test reports and be remote accessible from the fire alarm shop for trouble shooting purposes.
For panel construction, provide a modular type panel installed in a surface mounted steel cabinet with hinged door and cylinder lock. Mount with panel centerline 1.5 m 5 feet above finished floor elevation. Switches and other controls shall not be accessible without the use of a key. The control panel shall be a neat, compact assembly containing all parts and equipment required to provide specified operating and supervisory functions of the system. Each control panel component shall be UL listed or FM approved and approved by the control panel manufacturer for use in the control panel. Panel cabinet shall be finished on the inside and outside with factory-applied enamel finish. Provide main annunciator located on the exterior of the cabinet door or visible through the cabinet door. Provide audible trouble signal. Provide permanent engraved rigid plastic or metal identification plates, or silk-screened labels attached to the rear face of the panel viewing window, for all lamps and switches. Provide one set of Form C dry alarm contacts per zone, a common system Form C dry alarm contact, and a common system Form C dry trouble contact. Permanently label all switches. Provide panel with the following switches:
a. Trouble silencing switch which silences audible trouble signals (including remote trouble devices, if provided) without extinguishing trouble indicating lamp(s). For non-self-resetting type switch, upon correction of the trouble condition, audible signals will again sound until the switch is returned to its normal position. For silencing switch of the momentary action, self-resetting type, the trouble signal circuit shall be automatically restored to normal upon correction of the trouble condition.
b. Evacuation alarm silencing switch which when activated will silence all alarm notification appliances without resetting the panel, and cause operation of system trouble signals. Subsequent alarm(s) from additional zone(s) not originally in alarm shall cause activation of the notification appliances even with the alarm silencing switch in the "silenced" position.
c. Individual zone disconnect switches which when operated will disable only their respective initiating circuit and cause operation of the system and zone trouble signals.
d. Reset switch which when activated will restore the system to normal standby status after the cause of the alarm has been corrected, and all activated initiating devices reset. Operation of reset switch shall restore activated smoke detectors to normal standby status.
e. Lamp test switch.
f. HVAC shutdown bypass switch. Operation of the switch shall allow HVAC system to operate with detectors in alarm and shall cause operation of system trouble signals.
2.2.1.1 Main Annunciator
Provide integral with the control panel. Provide separate alarm and trouble lamps for each zone (initiating circuit) as indicated below and 10% spares, located on the exterior of the cabinet door or visible through the cabinet door. Lamps shall be Light Emitting Diode (LED) type. Supervision will not be required provided a fault in the annunciator circuits results only in loss of annunciation and will not affect the normal functional operation of the remainder of the system. Each lamp shall provide specific identification of the area by means of a permanent label. Provide engraved, silk screened, or machine-made labels. Handwritten labels are prohibited.
2.2.1.3 Remote Annunciator Panel
NOTE: Locate panel at or near the building entrance to allow fire department quick access to panel. When both a remote trouble sounder and remote annunciator are required, specify an annunciator with trouble sounder for dry indoor locations. Where a weatherproof enclosure is required, specify a separate trouble bell.
Provide panel located as shown. Mount with panel centerline 1.5 m 5 feet above finished floor elevation. Panel shall duplicate all requirements specified for the control panel annunciator, except that individual zone trouble lamps are not required. Lamps shall be LED type, except lamps used in backlighted panels shall be LED or neon type. Panel shall have a lamp test switch. Panel shall be of the weatherproof type, surface mounted. Provide panel with an integral audible trouble sounder which shall operate in conjunction with control panel audible sounder. Provide panel with trouble silence switch which shall comply with the requirements for a trouble silencing switch as specified in paragraph entitled "Control Panel".
2.2.1.4 Graphic Annunciator Panel
NOTE: Graphic annunciator panels should be provided only when a large number of concealed devices are installed.
Provide panel located as shown. Mount with panel centerline 1.5 m 5 feet above finished floor elevation. Panel shall be of the weatherproof type, surface mounted. Panel shall be provided with the building floor plan, drawn to scale, with alarm lamps mounted to represent the location of each initiating device. Panel graphic shall also show the locations of the annunciator panel and control panel, and shall have a "you are here" arrow showing its location. Orient building floor plan on graphic to location of person viewing the graphic, i.e. the direction the viewer is facing shall be toward the top of the graphic display. Provide a North arrow. Detectors mounted above ceilings, on ceilings, and beneath raised floors and different types of initiating devices shall have different symbols or lamps of different colors for identification. Lamps shall illuminate upon activation of corresponding device and shall remain illuminated until the system is reset. Panel shall have a lamp test switch.
2.2.1.5 Trouble Buzzer
NOTE: Provide a remote trouble bell or buzzer when the control panel is located in a mechanical room, electrical room, or similar space where the possibility of building occupants becoming aware of system trouble is unlikely. Locate remote bell or buzzer in a frequently attended area such as a security/reception desk, office, or main corridor. When a remote annunciator is also specified, specify an annunciator with silenceable trouble sounder. Provide an external trouble bell or buzzer above the control panel when the control panel is located in a high noise area, such as a machine shop, foundry, printing plant, aircraft hangar bay, etc.
Provide a remote system trouble buzzer arranged to operate in conjunction with the panel's integral trouble signal. Locate remote trouble buzzer as indicated. Provide external trouble buzzer at the control panel arranged to operate in conjunction with the panel's integral trouble signal. Provide trouble buzzer with a rigid plastic, white on red engraved identification sign which reads "FIRE ALARM SYSTEM TROUBLE". Lettering on identification sign shall be a minimum 25 mm one inch high.
2.2.2 Manual Pull Stations
Provide non-coded single action type with mechanical reset features. Stations shall be surface mounted and weatherproof type as indicated. For surface mounting provide station manufacturer's approved back box. Back box finish shall match station finish. Equip each station with a terminal strip with contacts of proper number and type to perform functions required. Stations shall be a type not subject to operation by jarring or vibration. Break-glass-front stations are not permitted. Station color shall be red. Station shall provide visible indication of operation. Restoration shall require use of a key. Keys shall be identical throughout the system for all stations and control panel(s). Mount stations with operating lever not more than 1.2 m 4 feet above finished floor. Where weatherproof stations are required, provide stations with cast metal, weatherproof (NEMA 3R) housings with hinged access doors; finish housings with red enamel paint and provide permanently affixed engraved or raised-letter plastic or metal identification signs reading
"FIRE ALARM" with white letters a minimum of 19 mm 3/4 inch high.
2.2.3 Heat Detectors
NOTE: Choose the type of heat detector best suited for application or design. Do not use rate-of-rise detectors in areas subject to rapid temperature changes, such as boiler rooms and shower rooms. Line-type detectors should only be used for specialized industrial-type hazards.
Provide detectors designed for detection of fire by combination fixed temperature rate-of-rise principle. Locate detectors in accordance with their listing by UL or FM and the requirements of NFPA 72, except provide at least two detectors in all rooms of 54 square meters 600 square feet or larger in area. For mounting heights greater than 3 m 10 feet above floor level, reduce actual detector linear spacing from listed spacing as required by NFPA 72; for heights greater than 9 m 30 feet space detectors no farther apart than 34 percent of their listed spacing. Mount detectors at the underside of ceiling or deck above unless otherwise indicated. Temperature rating of detectors shall be in accordance with NFPA 72. No detector shall be located closer than 300 mm 12 inches to any part of any lighting fixture nor closer than 600 mm 24 inches to any part of an air supply or return diffuser. Detectors, located in areas subject to moisture or exterior atmospheric conditions or hazardous locations as defined by NFPA 70, shall be types approved for such locations. Provide with terminal screw type connections. Removal of detector head from its base shall cause activation of system trouble signals if detectors are provided with separable heads and bases.
2.2.3.1 Combination Fixed Temperature Rate-Of-Rise Detectors (Spot Type)
Designed for surface outlet box mounting and supported independently of conduit, tubing or wiring connections. Contacts shall be self-resetting after response to rate-of-rise actuation. Operation under fixed temperature actuation shall result in an external indication. Detector units located in boiler rooms, showers, or other areas subject to abnormal temperature changes shall operate on fixed temperature principle only.
2.2.3.2 Rate Compensating Detector (Spot Type)
Designed for surface outlet box mounting and supported independently of conduit, tubing or wiring connections. Detectors shall be hermetically sealed and automatically resetting type which will operate when ambient air temperature reaches detector setting regardless of rate of temperature rise. Detector operation shall not be subject to thermal time lag.
2.2.4 Open-Area (Spot-Type) Smoke Detectors
NOTE: Both 4-wire and 2-wire smoke detectors arespecified in this specification. For open-area smoke detectors in new systems, edit this specification to permit the Contractor the option to provide 2-wire detectors. For additions to existing 4-wire systems, or when detector auxiliary contacts are used for critical control functions (such as elevator recall or air handler shutdown) edit this specification to require the Contractor to provide 4-wire detectors only.
Provide detectors designed for detection of abnormal smoke densities by the photoelectric principle. Detectors shall be 4-wire or 2-wire type. Provide necessary control and power modules required for operation integral with the control panel. Detectors and associated modules shall be compatible with the control panel and shall be suitable for use in a supervised circuit. Malfunction of the electrical circuits to the detector or its control or power units shall result in the operation of the system trouble signals. Each detector shall contain a visible indicator lamp that shall flash when the detector is in the normal standby mode and shall glow continuously when the detector is activated. [Remote indicator lamp shall be provided for each detector that is located above suspended ceilings, beneath raised floors, or otherwise concealed from view.] Each detector shall be the plug-in type with tab-lock or twist-lock, quick disconnect head and separate base in which the detector base contains screw terminals for making all wiring connections. Detector head shall be removable from its base without disconnecting any wires. Removal of detector head from its base shall cause activation of system trouble signals. Each detector shall be screened to prevent the entrance of insects into the detection chamber(s).
2.2.4.1 4-Wire Smoke Detectors Detector circuits shall be of the 4-wire type whereby the detector operating power is transmitted over conductors separate from the initiating circuit. Provide a separate, fused, power circuit for each smoke detection initiating circuit (zone). Failure of the power circuit shall be indicated as a trouble condition on the corresponding initiating circuit.
2.2.4.2 2-Wire Smoke Detectors
Detector circuits of the 2-wire type whereby the detector operating power is transmitted over the initiating circuit are permitted, provided the detectors used are approved by the control panel manufacturer for use with the control panel provided and are UL listed or FM approved as being compatible with the control panel (copies of the UL or FM listings showing compatibility shall be submitted as specified in paragraph entitled "Submittals"). The total number of detectors on any detection circuit shall not exceed 80 percent of the maximum number of detectors allowed by the control panel manufacturer for that circuit. Additional zones above those specified in the paragraph titled "Initiating Zones" shall be provided if required to meet the above requirements. Calculations showing compliance with the power consumption limitation requirements shall be submitted with the calculations required by the paragraph entitled "Design Data." The manufacturer's data submitted under the paragraph entitled "Manufacturer's Catalog Data" shall clearly indicate the compatibility of the detectors with the control panel provided and the maximum number of detectors permitted per zone.
2.2.4.4 Photoelectric Detectors
Operate on the light scattering principle using a LED light source.
Detector shall respond to both flaming and smoldering fires.
2.2.4.5 Detector Spacing and Location
NOTE: When underfloor detectors are used, the designer must show a mounting detail for underfloor detectors which complies with this paragraph.
Detector spacing and location shall be in accordance with the manufacturer's recommendations and the requirements of NFPA 72, except provide at least two detectors in all rooms of 54 square meters 600 square feet or larger in area. In no case shall spacing exceed 9 by 9 m 30 by 30 feet per detector, and 9 linear m 30 linear feet per detector along corridors. Detectors shall not be placed closer than 1.5 m 5 feet from any air discharge or return grille, nor closer than 300 mm 12 inches to any part of any lighting fixture. In areas without finished ceilings, mount detectors at the underside of deck above unless otherwise indicated. Detectors installed beneath raised floors shall be mounted with the base within 50 mm 2 inches of the underside of the raised floor, with the detector facing per manufacturers recommendations.
2.2.5 Duct Smoke Detectors
NOTE: Choose the type of smoke detector best suited for application or design. Specify duct smoke detectors as required by NFPA 90A.
Provide detectors installed in ducts of the type and listed by UL or FM for duct installation. Control and power modules required for operation shall be integral with the main control panel. Detectors and associated modules shall be compatible with the main control panel and shall be suitable for use in a supervised circuit. Detector circuits shall be of the 4-wire type whereby the detector operating power is transmitted over conductors separate from the initiating circuit. Malfunction of the electrical circuits to the detector or its control or power modules shall cause operation of the system trouble signals. Provide a separate, fused power circuit for each smoke detection initiating circuit (zone). Failure of the power circuit shall be indicated as a trouble condition on the corresponding initiating circuit. Provide duct detectors in accordance with NFPA 90A. Provide duct detectors with an approved duct housing, mounted exterior to the duct, with perforated sampling tubes extending across the width of the duct. Activation of duct detectors shall cause [shutdown of the associated air handling unit,] annunciation at the control panel, and tripping of the [master box] [transmitter] and sounding of building evacuation alarms. Each detector shall have a visible indicator lamp that shall flash when the detector is in the normal standby mode and shall glow continuously when the detector is activated. Provide remote indicator lamp for each detector. Permanently label remote indicator with description or number of associated air handling unit(s). Provide each detector with a remote test switch. Mount switch not more than 1.8 m 6 feet above finish floor. Permanently label test switch with description or number of associated air handling unit(s).
2.2.6 Projected Beam Smoke Detector
NOTE: Projected beam detectors are specialized devices best suited for use in large open areas such as atriums, high bay buildings, and cathedrals.
They also have applications in protection of specialized industrial hazards.
Provide projected beam smoke detectors to protect spaces indicated. Detectors and associated controls shall be compatible with the main control panel and shall be suitable for use in a supervised circuit. Detector circuits shall be of the 4-wire type, whereby the detector operating power is transmitted over conductors separate from the initiating circuit. Provide a separate, fused power circuit for each smoke detection initiating circuit. Failure of the power circuit shall be indicated as a trouble condition on the initiating circuit. Malfunction of the detector or its control unit or blockage of the projected beam shall cause operation of the system trouble signals. Install detectors in accordance with NFPA 72, the manufacturer's instructions, and UL listing or FM approval, with project beams parallel to ceilings. Beam length and distance between adjacent beams, and distance between beams and walls, shall not exceed the maximum permitted by the equipment listing. Do not use mirrors to alter the direction of the projected beam.
2.2.7 Notification Appliances
NOTE: Specify recessed appliances in buildings where tampering is likely (e.g. BEQs).
Provide in accordance with NFPA 72 and as indicated. Do not exceed 80 percent of the listed rating in amperes of any notification appliance circuit. Additional circuits above those shown shall be provided if required to meet this requirement. Submit calculations showing compliance with the above power consumption requirements with the calculations required by the paragraph titled "Design Data". Effective sound levels shall comply with NFPA 72. Provide appliances in addition to those shown if required in order to meet NFPA 72 sound level requirements. Provide appliances specifically listed for outdoor use in locations exposed to weather. Finish appliances in red enamel. For surface mounting provide appliance manufacturer's approved back box. Back box finish shall match appliance finish.
2.2.7.2 Alarm Horns
Surface-mounted or Recessed, vibrating type suitable for use in an electrically supervised circuit and shall have a sound output rating of at least 90 decibels at 3 m 10 feet.
2.2.7.3 Visible Appliances
NOTE: In accordance with the Uniform Federal Accessibility Standards and the Americans With Disabilities Act Accessibility Guidelines provide visible alarm notification appliances in every building subject to civilian occupancy. Determine candela rating based on device spacing in accordance with Section 6-4 of NFPA 72.
Surface mounted assembly of the stroboscopic type suitable for use in an electrically supervised circuit and powered from the notification appliance circuit(s). Lamps shall be protected by a thermoplastic lens and labeled "FIRE" in letters at least 12 mm 1/2 inch high. Provide visible appliances within 300 mm 12 inches of each audible appliance [and as indicated]. Visible appliances may be part of an audio-visual assembly. Where more than two appliances are located in the same room or corridor, provide synchronized operation.
2.2.8 Fire Extinguishing Systems
Activation shall cause complete functional operation of the control panel.
System contacts are specified in other sections.
2.2.10 Electro-Magnetic Door Holder-Releases
Provide where shown. The armature portion shall be mounted on the door and shall have an adjusting screw for setting the angle of the contact plate. Mount the electro-magnetic release on the wall or in a wall recess behind the door. The activation of the fire alarm system shall release all doors on the circuit to close. Total projection of the door holder-release shall not exceed 100 mm 4 inches. Door holders shall not require battery backup power.
2.2.11 Valve Tamper Swithces/Chains
All water shutoff devices shall be chained shut and shall not be tamper switched.
2.2.13 Conduit
2.2.13.1 Rigid Steel Conduit (Zinc-Coated): NEMA C80.1 or UL 6.
2.2.13.2 Intermediate Metal Conduit (IMC): UL 1242, zinc-coated steel only.
2.2.13.3 Electrical Metallic Tubing (EMT): NEMA C80.3 or UL 797.
**Note, Electrical Non-metallic tubing is allowed also.
2.2.13.4 Surface Metal Raceway and Fittings
NOTE: Specify surface raceways only for retrofit projects where concealment of wire is impractical and wiring is not subject to physical abuse.
UL 5, two-piece painted steel, totally enclosed snap-cover type.
2.2.14 Outlet Boxes: UL 514A,zinc-coated steel.
2.2.15 Fittings for Conduit and Outlet Boxes: UL 514B,zinc-coated steel.
2.2.16 Wiring: NFPA 70 and NFPA 72 compliant.
PART 3 EXECUTION
3.1 INSTALLATION
NOTE: Specify surface raceways only for retrofit projects where concealment of wire is impractical and wiring is not subject to physical abuse.
Installation shall be in accordance with the requirements of NFPA 70, NFPA 72 and NFPA 90A. Each conductor used for the same specific function shall be distinctively color coded. Each function color code shall remain consistent throughout the system. Use colors as directed by the Contracting Officer to match existing base color coding scheme. All wiring shall be in steel conduit or electrical metallic tubing, except surface mounted wiring may be in surface mounted metal raceway in finished areas. All circuit conductors shall be identified within each enclosure where a tap, splice or termination is made. Conductor identification shall be by plastic coated self sticking printed markers or by heat-shrink type sleeves. The markers shall be attached in a manner that will not permit accidental detachment. Control circuit terminations shall be properly identified. Wire devices so that their removal will activate system trouble signals. Pigtail or "T" tap connections are prohibited. Wiring for DC circuits shall not be permitted in the same conduit or tubing as wiring for AC circuits. Paint all junction box covers red or provide them with permanent labels reading "FIRE ALARM CIRCUIT." Electrical metallic tubing shall not be installed in exterior or wet locations and shall not be imbedded in masonry or concrete. Provide a written schedule of conductor markings identifying each wire marker, the purpose, the origin, and termination point of each conductor. The conductor wire marker schedule shall be turned over to the Contracting Officer at the time of preliminary testing with as built drawings.
3.2 FIELD QUALITY CONTROL
3.2.1 Preliminary Testing
Notify Contracting Officer prior to performing preliminary testing.
Contractor shall conduct the following tests during installation of wiring and system components. Any deficiency pertaining to these requirements shall be corrected by the Contractor prior to final acceptance testing of the system. Record results of testing. Submit all test results to the Contracting Officer.
a. Ground Resistance: Prior to connecting control panel and transmitter, test grounds for ground resistance value. Use a portable ground testing megger to test each ground or group of grounds. Make ground resistance measurements in normally dry weather, not less than 48 hours after a rainfall. Follow the directions provided by the equipment manufacturer for proper use of the equipment. Measure the resistance of each connection to ground. Resistance of each connection to ground shall not exceed 10 ohms.
b. Operation of Entire System. Operate all initiating and indicating devices.
c. Operation of Supervisory Systems: Operate all portions to demonstrate correctness of installation.
d. Smoke Detector Test: Clean the smoke detectors in accordance with the manufacturer's recommended procedures. Test smoke detectorsusing magnet-activated test switch, manufacturer-provided test card, or smoke. Use of aerosol sprays to test smoke detectors is prohibited. When 2-wire smoke detectors are provided, prior to formal inspection and tests, perform sensitivity tests on each smoke detector. Perform voltage activation sensitivity test on each detector and record the results. Remove detectors with a sensitivity level above or below the UL accepted sensitivity range for that detector and replace with new detectors having the UL accepted sensitivity range. Present recorded data at the formal inspection for verification. Approved copies shall become part of the operation and maintenance manual for the fire alarm system.
e. Duct Detector Differential Pressure Test: Measure and record the observed differential pressure between sampling tubes with completed HVAC system operating normally to verify airflow requirements through detector housing. Perform test on smoke detector heads as specified above for smoke detectors.
3.2.2 Final Acceptance Testing
When the system is ready for final acceptance testing, the contractor shall notify the fire alarm shop to receive an activity code and the required phone numbers for the reporting capability of the system. The contractor shall then notify the Contracting Officer when the system is ready for final acceptance testing. A test plan should be submitted to the AHJ 15 calendar days prior to acceptance testing. This test plan must be signed by the base fire department. Request scheduling for final acceptance testing only after all necessary preliminary tests have been made and all deficiencies found have been corrected to the satisfaction of the equipment manufacturer's technical representative and the Contracting Officer, and written certification to this effect has been received by the AHJ. The system shall be in service at least 15 calendar days prior to final acceptance testing. The Contractor shall allow at least 15 calendar days between the date final testing is requested and the date the final acceptance testing takes place. The Contractor shall furnish all appliances, equipment, instruments, devices and personnel for this test. Furnish a minimum of three two-way radios plus one additional radio for each remote annunciator, all operating on the same frequency. All necessary tests shall be made including the following, and any deficiency found shall be corrected and the system retested.
3.2.2.1 Entire System
Test the entire system by operating all…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .