SOLICITATION NO. FA4417-15-R-0015
Repair HVAC EOD, Bldg 90621
QUESTIONS & ANSWERS
22 April 2015
Question 1: Plans specify 2'-6" of spray foam insulation around the perimeter of the building where the roof/wall join. However, the floor plan is not to scale and no dimensions are given. So, there is no accurate way to calculate area of foam insulation.
Answer: The reflective ceiling plan shown on sheet A-1 is drawn to scale, 1/8" = 1'-0. If they plot the drawing out to actual size they will be able to scale the drawing.
-END QUESTIONS & ANSWERS -