Atch_2_Drawings_FTEV_12-1101.pdf

PDF 2 MB Posted

Attached to
Repair HVAC EOD Bldg 90621 Federal contract opportunity
Solicitation number
FA4417-15-R-0015
Issued by
Department of the Air Force Special Operations Command

About this file

Drawings

View the file

Other files for this federal contract opportunity

Other files attached to Repair HVAC EOD Bldg 90621, newest first.
File Type Posted
Question-Answer_FA4417-15-R-0015.docx DOCX document
FA4417-15-R-0015-0001_Amendment_1.pdf PDF
Pre-Proposal_Site_Visit_Memo_ _Sign-In_Sheet.pdf PDF
Pre-Proposal_Site_Visit_Memo_ _Sign-In_Sheet.pdf PDF
Atch_4_-_Past_Performance_Questionnaire.pdf PDF
Atch_5_-_Financial_Reference_Sheet.pdf PDF
FA4417-15-R-0015_REPAIR_HVAC_EOD_BLDG_90621.pdf PDF
Atch_3_-_Wage_Determination.pdf PDF
Atch_1_Specifications_FTEV_12-1101.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ELECTRICAL PLAN - BUILDING 90621 - DEMOLITION

SCALE: 1/8" = 1'-0"

LOCATION OF

BUILDING 90600

ELECTRICAL PLAN - BUILDING 90600 - DEMOLITION

SCALE: 1/8" = 1'-0"

S

R

S

J

M

M

M

J

LARGE SCALE PLAN - MECHANICAL ROOM - DEMOLITION

SCALE: 1/4" = 1'-0"

SEE "LARGE SCALE PLAN - MECHANICAL

ROOM - DEMOLITION," THIS SHEET.

M

M

M

M M

M

M

EXISTING PANEL "MDP"

EXISTING PANEL "P"

EXISTING GAS BOILER

EXISTING HOT WATER PUMP

EXISTING AIR COMPRESSOR

EXISTING AIR HANDLING UNIT

EXISTING UNIT HEATER

EXISTING AIR HANDLING UNIT

EXISTING CONDENSING UNIT

EXISTING CONDENSING UNIT

EXISTING CONDENSING UNIT

EXISTING CONDENSING UNIT

EXISTING AIR HANDLING UNIT

EXISTING AIR HANDLING UNIT

EXISTING 112.5 KVA PAD MOUNTED TRANSFORMER

EXISTING 600 A. AUTOMATIC TRANSFER SWITCH

EXISTING 100 KW/125 KVA EMERGENCY GENERATOR SET

EXISTING DIESEL FUEL STORAGE TANK

J

J

EXISTING PANEL

E

U

P

REMOVE EXISTING METER

REMOVE EXISTING ELECTRICAL CIRCUIT FROM AIR COMPRESSOR

BACK TO MAIN PANEL "MDP."

REMOVE EXISTING ELECTRICAL CIRCUIT

FROM PUMP BACK TO PANEL "P."

REMOVE EXISTING SWITCH & ELECTRICAL

CIRCUIT FROM BOILER BACK TO PANEL "P."

REMOVE EXISTING ELECTRICAL CIRCUIT FROM

AIR HANDLING UNIT BACK TO MAIN PANEL "MDP."

ELECTRICAL LEGEND - DEMOLITION:

J

J

M

RUS

EUP

R

S

EXISTING JUNCTION BOX - TO REMAIN.

EXISTING JUNCTION BOX - REMOVE.

EXISTING DISCONNECT SWITCH - REMOVE.

EXISTING MOTOR STARTER - REMOVE.

EXISTING MOTOR - REMOVE EXISTING ELECTRICAL CONNECTION.

EXISTING BRANCH CIRCUIT CONDUIT & WIRING - REMOVE.

EXISTING FLEXIBLE CONDUIT CONNECTION - REMOVE.

EXISTING UNDERGROUND SECONDARY - REMOVE.

EXISTING UNDERGROUND PRIMARY - TO REMAIN.

EXISTING DUCT SMOKE DETECTOR - SUPPLY DUCT - REMOVE.

EXISTING DUCT SMOKE DETECTOR - RETURN DUCT - REMOVE.

EXISTING PANELBOARD - TO REMAIN.

FACP

FACP

EXISTING FIRE ALARM CONTROL PANEL - TO REMAIN.

R

U

S

REMOVE EXISTING C.T. CABINET. REMOVE EXISTING SECONDARY

WIRING FROM PANEL "MDP" TO PAD MOUNTED TRANSFORMER

VIA EXISTING AUTOMATIC TRANSFER SWITCH.

REMOVE EXISTING 120 VOLT CONNECTION

TO EXISTING UNIT HEATER.

S

ELECTRICAL DEMOLITION NOTE:

THE CONTRACTOR SHALL REMOVE ALL EXISTING CONDUIT & WIRING ASSOCIATED WITH DEMOLITION WORK. CONDUIT

SHALL BE REMOVED WHERE EXPOSED ON WALLS, OVERHEAD STRUCTURE, AND ABOVE EXISTING LAY-IN CEILINGS.

ALL PANELBOARDS SHALL RECEIVE NEW TYPEWRITTEN DIRECTORIES TO REFLECT THE LOADS CONNECTED TO THE

CIRCUIT BREAKERS. ALL CIRCUIT BREAKERS WHERE LOADS HAVE BEEN REMOVED SHALL BE LABELED AS SPARES

AND SHALL HAVE HANDLES TRIPPED TO THE OFF POSITION.

ELECTRICAL PHASING NOTE:

ELECTRICAL WORK (NEW WORK AND DEMOLITION) SHALL BE PHASED IDENTICALLY TO THE MECHANICAL PHASING

SCHEME INDICATED ON THE MECHANICAL DRAWINGS. POWER OUTAGES TO THE BUILDING SHALL BE KEPT TO A

MINIMUM, AND WHEN REQUIRED, SHALL BE CLOSELY COORDINATED WITH THE CONTRACTING OFFICER AND THE

FACILITY USERS 30 DAYS IN ADVANCE OF THE PROPOSED OUTAGE.

E-1

E L E

C T

R I C

A L

P

L A

N

D

E M

O L I T

I O

N

17 FEB 2015

R E

P A

I R

H

V A

C

E

O D

F F

I C

E

B U

I L

D I N

G

OF 15

FTEV 12-1101

JRH/EWW

JRH

90621

ELECTRICAL PLAN - BUILDING 90621 - NEW WORK

SCALE: 1/8" = 1'-0"

LOCATION OF

BUILDING 90600

ELECTRICAL PLAN - BUILDING 90600 - NEW WORK

SCALE: 1/8" = 1'-0"

EXISTING PANEL "MDP"

EXISTING PANEL "P"

M

NEW CHILLER ACC-1

COMPR. (2) 53 RLA, 208 V., 3Ø

FANS (3) 6.2 FLA, 208 V., 3Ø

VAV-1

VAV-2

VAV-3

VAV-4

(3) 3 HP, 208 V., 3Ø

FIRE ALARM SYSTEM - CONDUIT & WIRING - ALL FIRE ALARM CONDUITS SHALL BE RED IN COLOR.

FIRE ALARM SYSTEM - EXISTING CONTROL PANEL - TO REMAIN.

MOTOR STARTER - BY MECH. - CONNECTION BY ELECT. CONTRACTOR.

S

FACP

MOTOR - BY MECH. - CONNECTION BY ELECT. CONTRACTOR.

NOTE: TICKMARKS INDICATE NO. OF CONDUCTORS; " " INDICATES FULL SIZE GROUND CONDUCTOR; ARROW INDICATES

HOMERUN TO PANEL; "LP:1" INDICATES PANEL AND CIRCUIT NO.; WIRE IS # 12; CONDUIT IS 1/2" & BREAKER IS 20 A., 1 P., UNLESS NOTED OTHERWISE. ( INDICATES CONCEALED OVERHEAD OR IN WALLS; INDICATES CONCEALED IN

ELECTRICAL LEGEND - NEW WORK:

POWER PANEL - SEE SCHEDULE.

BRANCH CIRCUIT CONDUIT & WIRING:

OR BELOW FLOOR; INDICATES EXPOSED.)

FLEXIBLE CONDUIT & WIRING CONNECTION.

LP:1

JUNCTION BOX - SIZE AS REQUIRED.

DISCONNECT SWITCH - HEAVY DUTY - NON-FUSIBLE.

M

F

J

BRANCH CIRCUIT CONDUIT & WIRING:

CONDUIT IS 1/2", UNLESS NOTED OTHERWISE. ( INDICATES CONCEALED OVERHEAD OR IN WALLS; INDICATES EXPOSED.)

NOTE: TICKMARKS INDICATE NO. OF CONDUCTORS; " " INDICATES FULL SIZE GROUND CONDUCTOR; WIRE IS # 12;

EXISTING PANELBOARD - TO REMAIN.

S

FACP

EXISTING PANEL

FACP

M

NEW AHU-3

2 HP, 208 V., 3Ø

30 A., 3 P., NEMA 1

200 A., 3 P., NEMA 3R

NEW CHWP-1

3 HP, 208 V., 3Ø

M

2 HP, 208 V., 3Ø

NEW AHU-2

30 A., 3 P., NEMA 1

TO 20 A., 3 P. BKR. IN NEW

PANEL "M," CKT. # 3.

U

S

U

S

J

J

J

J

NEW PANEL "M"

NEW BOILER

120 V., 1Ø

F

NEW H.W. CIRC. PUMP

1 1/2 HP, 208 V., 3Ø

M

M

J

M

LARGE SCALE PLAN - MECH. ROOM

SCALE: 1/4" = 1'-0"

TOGGLE TYPE SWITCH - HORSEPOWER RATED.

EXISTING PAD MOUNTED TRANSFORMER

EXISTING AUTOMATIC TRANSFER SWITCH

EXISTING GENERATOR SET

NEW ENCLOSED CIRCUIT BREAKER - SEE

"SINGLE LINE DIAGRAM," SHEET E-3.

US NEW UNDERGROUND SECONDARY - SEE "SINGLE LINE DIAGRAM," SHEET E-3.

NEW AHU-1

100 A., 3 P., NEMA 1

3 # 6 & 1 # 8 GND. - 1" C.

TO 20 A., 3 P. BKR. IN EXISTING

PANEL. INSTALL NEW BREAKER IN

EXISTING SPACE. EXISTING PANEL IS

A G.E., A SERIES PANELBOARD.

HOMERUN TO EXISTING 20 A., 1 P.

BKR. IN EXISTING PANEL "P."

SEE "LARGE SCALE PLAN -

MECHANICAL ROOM," THIS SHEET.

EXISTING PANEL "MDP"

EXISTING PANEL "P"

NEW PANEL "M"

HOMERUN TO 30 A., 3 P. BKR.

IN NEW PANEL "M," CKT. # 7.

NEMA SIZE 00 STARTER

W/ H-O-A SWITCH

NEMA SIZE 0 STARTER

W/ H-O-A SWITCH

MOTOR STARTER - FURNISHED AND INSTALLED BY ELECT. CONTRACTOR.

DDC PANEL

120 V., 1Ø

J

T

EXISTING TELECOMM.

EQUIPMENT ROOM

T

DATA OUTLET - W/ CATEGORY 6 DATA JACK - WALL MOUNTED 48" A.F.F. TO TOP OF BOX.

DATA CONDUIT & WIRING - CATEGORY 6 UNSHIELDED TWISTED PAIR IN 3/4" CONDUIT.

EXTEND CONDUIT & WIRING TO

EXISTING TELECOMM. DATA RACK.

HOMERUN TO EXISTING 20 A., 1 P.

BKR. IN EXISTING PANEL "P."

3 # 6 & 1 # 8 GND. - 1" C. TO 70 A., 3 P.

BKR. IN NEW PANEL "M," CKT. # 2.

CONNECT TO EXISTING DUCT SMOKE

DETECTOR ZONE IN EXISTING FIRE

ALARM CONTROL PANEL.

FIRE ALARM SYSTEM - DUCT SMOKE DETECTOR - PHOTO-ELECTRIC TYPE - "S" = SUPPLY; "R" = RETURN.

DETECTOR SHALL BE COMPATIBLE W/ EXISTING FCI FIRE ALARM CONTROL PANEL.

S

F

CONNECT TO EXISTING DUCT SMOKE

DETECTOR ZONE IN EXISTING FIRE

ALARM CONTROL PANEL.

WALL OUTLET - W/ EXIT LIGHT - WALL MTD. ABOVE DOOR - SEE DETAIL, SHEET E-3.

EXISTING PENDANT MOUNTED INDUSTRIAL

FLUORESCENT STRIP TO REMAIN (TYP.)

CONNECT CIRCUIT TO NEW EXIT

LIGHT AHEAD OF LOCAL SWITCHING

IN EXISTING LIGHTING FIXTURE.

J

CONNECT TO UV LIGHTING

IN NEW AHU-1.

HOMERUN TO 20 A., 1 P. BKR. IN

NEW PANEL "M," CKT. # 8.

ELECTRICAL PHASING NOTE:

ELECTRICAL WORK (NEW WORK AND DEMOLITION) SHALL BE PHASED IDENTICALLY TO THE MECHANICAL PHASING

SCHEME INDICATED ON THE MECHANICAL DRAWINGS. POWER OUTAGES TO THE BUILDING SHALL BE KEPT TO A

MINIMUM, AND WHEN REQUIRED, SHALL BE CLOSELY COORDINATED WITH THE CONTRACTING OFFICER AND THE

FACILITY USERS.

EXISTING DUCT SMOKE

DETECTOR TO REMAIN.

HOMERUN TO EXISTING 20 A., 1 P. SPARE

BREAKER IN EXISTING PANEL "P."

3 # 2/0 & 1 # 6 GND. - 2" C. TO 175 A., 3 P.

BKR. IN NEW PANEL "M," CKT. # 5.

EXTEND 120 V. CIRCUIT TO UV

LIGHTING CONNECTION AT AHU-2.

J

EXTEND 120 V. CIRCUIT TO

J-BOX IN MECHANICAL ROOM.

CONNECT TO UV LIGHTING

IN NEW AHU-2.

J

CONNECT TO UV

LIGHTING IN NEW AHU-3.

TO 20 A., 1 P. BKR. IN EXISTING

PANEL. INSTALL NEW BREAKER IN

EXISTING SPACE. EXISTING PANEL IS

A G.E., A SERIES PANELBOARD.

3 # 10 & 1 # 10 GND. - 3/4" C.

TO 30 A., 3 P. BKR. IN NEW

PANEL "M," CKT. # 4.

R

F

INSTALL AIR HANDLING UNIT

SHUTDOWN RELAY FOR AHU-1.

R

INSTALL AIR HANDLING UNIT

SHUTDOWN RELAY FOR AHU-2.

F

R

INSTALL AIR HANDLING UNIT SHUTDOWN

RELAY FOR AHU-3 & CONNECT TO

EXISTING DUCT SMOKE DETECTOR.

F

R

FIRE ALARM SYSTEM - AHU SHUT DOWN RELAY - MUST BE COMPATIBLE W/ EXISTING FCI FIRE ALARM CONTROL PANEL.

J

HOMERUN TO 20 A., 1 P. BKR.

IN NEW PANEL "M," CKT. # 10.

EXHAUST FAN - BY MECH. - DISCONNECT EXISTING ELECTRICAL CONNECTION FROM EXISTING FAN & RECONNECT TO NEW FAN.

F

F

F

F

EXHAUST FAN ON ROOF

EXHAUST FAN ON ROOF

EXHAUST FAN MOUNTED ABOVE LAY-IN CEILING

E-2

E L E

C T

R I C

A L

P

L A

N

N

E W

W

R

K

17 FEB 2015

R E

P A

A

C

E

F

I C

E

B U

I L

D I N

G

EXISTING SERVICE LOAD CALCULATION:

EXISTING DEMAND LOAD HISTORY (METER HISTORY APRIL 2013): 67.7 KW

TOTAL ELECTRICAL LOAD OF HVAC EQUIPMENT BEING DEMOLISHED: 54.4 KW

SUB-TOTAL - EXISTING ELECTRICAL LOAD ON BUILDING SERVICE: 13.3 KW

NEW ELECTRICAL LOAD OF HVAC EQUIPMENT BEING INSTALLED: 63.6 KW

TOTAL - ELECTRICAL LOAD ON BUILDING SERVICE: 76.9 KW

A

P

A

P

SS

"MDP"

PANEL

NEW MAIN PANEL "M"

M

US

NO SCALE

EUP

SINGLE LINE DIAGRAM

S U

R G

E

S

U P

P R

E S

S O

R

S E

E

N

O T

E

T

H

S

S

E

E T

US

EXISTING

EXTERIOR WALL

EXISTING 600 A., 4 P. AUTOMATIC TRANSFER

SWITCH W/ BYPASS/ISOLATION.

WEATHERPROOF

"LB" FITTING

CORE DRILL EXISTING EXTERIOR WALL FOR

NEW CONDUIT ENTRANCE. SEAL AROUND

CONDUIT PENETRATION W/ NON-SHRINK GROUT.

SURGE PROTECTIVE DEVICE NOTE:

SURGE PROTECTIVE DEVICES (SPD) SHALL BE LISTED IN ACCORDANCE W/ UL 1449, 3RD

EDITION AND SHALL BE A TYPE 1 DEVICE. SPD SHALL PROVIDE PROTECTION OF

LINE-NEUTRAL, LINE-GROUND, NEUTRAL-GROUND AND LINE-LINE. EACH MODE OF

PROTECTION SHALL BE FUSED W/ 200 KAIC SURGE RATED FUSES. SPD SHALL BE

FURNISHED W/ AN AUDIBLE ALARM, AN ALARM ON/OFF SWITCH AND AN ALARM PUSH TO

TEST SWITCH. MINIMUM SHORT CIRCUIT CURRENT RATING SHALL BE 200kA. MINIMUM

SURGE CURRENT RATING PER PHASE SHALL BE 300kA. VOLTAGE PROTECTION RATINGS

SHALL BE 700 VOLTS FOR LINE-NEUTRAL, LINE-GROUND AND NEUTRAL-GROUND. VOLTAGE

PROTECTION RATING SHALL BE 1200 VOLTS FOR LINE-LINE. SPD SHALL HAVE A MINIMUM

EMI/RFI FILTERING OF -50dB AT 100kHz WITH AN INSERTION RATIO OF 50:1 USING

MIL-STD-220A METHODOLOGY. SPD SHALL BE PROVIDED WITH ONE SET OF NO/NC

CONTACTS, AND SHALL HAVE A FULL 10 YEAR WARRANTY. SPD SHALL HAVE A NEMA 1

ENCLOSURE FOR INDOOR APPLICATIONS.

EXISTING METER

EXISTING PAD MOUNT TRANSFORMER -

112.5 KVA, 12.47 KV PRIMARY TO

208Y/120 V. SECONDARY.

AMP

BREAKER

PANELBOARD SCHEDULE

TOTAL CONNECTED LOAD:

HWP-1

ACC-1

143.0

143.0

143.0

239.4

A

2"

B C

AMP

NEW PANEL "M"

EXISTING PANEL "MDP"

LOAD SERVED

36.9

36.9

36.9

LOAD (AMPS)

120/208 V., 3Ø, 4 W.S.N., "WYE"

A B

400 A., 3 P. MAIN BREAKER

C

CKT. #

300 3 1

WIREPOLE

BREAKER BRANCH

2 #6 1" 70

BRANCH

WIRE

CKT. #

1 AHU-1 & 2 UV LIGHTS

CHWP-13

3 33.0

33.0

33.0

SURFACE MOUNTED PANEL W/ GROUND BUS

POLE A

BONDED TO NEUTRAL BUS.

LOAD (AMPS)

B C

AHU-1

LOAD SERVED

22 KAIC INTERRUPTING RATING

MCM

3"

#2/0

239.4 237.4

#10 3/4" 30 11.0

11.0

11.0

1/2"#12

7.8

7.8

7.8 20AHU-2

EXISTING PRIMARY - 3 # 2 (15 KV)

TAPE SHIELDED TYPE "EPR" W/

CONCENTRIC NEUTRAL

WEATHERPROOF

"LB" FITTING

4 - 500 MCM - 3 1/2" PVC, SCH. 40

4 - 500 MCM & 1 # 2 GND. - 3 1/2" PVC, SCH. 40

4 - 500 MCM & 1 # 2 GND. - 3 1/2"

RIGID GALV. STEEL

4 - 500 MCM & 1 # 2 GND. -

3 1/2" RIGID GALV. STEEL

4 - 500 MCM & 1 # 2 GND. -

3 1/2" EMT

4 - 350 MCM & 1 # 3 GND. - 3" EMT

# 1/0 BARE COPPER - 1" PVC, SCH. 80 TO

3/4" X 20'-0" COPPERCLAD GROUND ROD

# 1/0 BARE COPPER - 1" PVC, SCH. 80 TO

METALLIC COLD WATER PIPE.

#6 1" 50 SURGE PROTECTIVE

DEVICE

5.7

5.7

5.7 1/2"#1220

SPACE ONLY 93

3 SPACE ONLY

DETAIL - FIXTURE "X"

N.T.S.

13"±

TEST SWITCH

READY LIGHT

UNIVERSAL CANOPY FOR TOP OR BACK MOUNTING. SINGLE FACED, SELF-CONTAINED

COMBINATION NORMAL AND EMERGENCY LIGHTING EXIT SIGN WITH AUTOMATIC

6-VOLT LED LAMPS OPERATING FROM LEAD ACID BATTERY PROVIDING 90 MINUTES OF

CONTINUOUS SERVICE. DIE-CAST ALUMINUM HOUSING AND MOUNTING BRACKET

WITH BRUSHED FINISH, RED LETTERS ON WHITE BACKGROUND, 120 VOLT OPERATION.

HIGH INTENSITY LED LAMPS CONCEALED BEHIND A CLEAR PANEL AND OPTICAL

DIFFUSER THAT PROVIDES UNIFORM ILLUMINATION AND BRIGHTNESS. THE

PRONOUNCED "DOT EFFECT" FROM PROTRUDING LED'S WILL NOT BE ACCEPTED.

STANDARD EMERGENCY ELECTRONICS SHALL PROVIDE SELF-TEST/SELF DIAGNOSTIC

CIRCUITRY THAT COMPLIES WITH ALL THE LATEST UL 924 AND NFPA 101

REQUIREMENTS. THE MANAGEMENT SYSTEM CONTROLS TEST PARAMETERS WITHIN

THE EMBEDDED MICROCONTROLLER TO VERIFY ALL SYSTEM COMPONENTS ARE

FUNCTIONING PROPERLY. ALL EMERGENCY UNITS SHALL HAVE BUILT-IN CIRCUITRY

PROTECTION/LOW-VOLTAGE BATTERY DISCONNECT AND TRANSFORMER ISOLATION.

SOLID STATE CHARGER, TEST SWITCH AND GREEN LED AC STATUS INDICATOR,

ALONG WITH RED FAULT INDICATOR LIGHTS.

HEAT TAPE

SPARE

#12 1/2" 20 2.0

PROVIDE BREAKER WITH NEMA 3R ENCLOSURE. MOUNT BREAKER ON

REAR OF EXISTING ATS. INSTALL PHENOLIC ENGRAVE NAMEPLATE ON

BREAKER READING "MAIN DISCONNECT MEANS FOR BUILDING 90621."

400 A., 3 P., 22

KAIC MAIN BKR.

SELF TEST/SELF DIAGNOSTIC

CONVERT PVC TO RIGID GALV.

STEEL CONDUIT BELOW GRADE.

SPACE ONLY 113 3 SPACE ONLY16

REMOVE EXISTING SERVICE GROUND CONDUCTORS

& REMOVE BONDING JUMPER FROM GROUND BUS TO

NEUTRAL BUS IN EXISTING PANEL "MDP."

#12 1/2" 2.0

229.7

NOTE :

THE ELECTRICAL CONTRACTOR SHALL COORDINATE WITH THE MECHANICAL

CONTRACTOR PRIOR TO INSTALLATION TO VERIFY THE HORSEPOWER RATINGS OF

THE AHU THAT THE MECHANICAL CONTRACTOR FURNISHES. CIRCUIT BREAKER,

DISCONNECT SWITCH, CONDUIT & WIRING FOR AHU-1 IS SIZED BASED UPON THREE

MOTORS RATED AT 3 HP, EACH.

E-3

S I N

G L E

L

N

E

D

I A

G R

A M

17 FEB 2015

R E

P A

A

C

E

F

I C

E

B U

I L

D I N

G

T-1
A-1
A-2
M-1
M-2
M-3
M-4
M-5
M-6
M-7
M-8
M-9
FTEV 12-1101 E1
FTEV 12-1101 E2
FTEV 12-1101 E3

File details come from the government source that posted it. Updated .