8_-_Cost_Estimate_Breakdown.xlsx

XLSX spreadsheet 35 KB Posted

Attached to
Repair/Replace Circuit 7 Electric Distribution Lines, VNVP 1316001
Solicitation number
FA3020-16-R-0001
Issued by

About this file

Cost Estimate Worksheet

View the file

Other files

Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CIRCUIT 7

CONSTRUCTION COST ESTIMATEDATE:
CONTRACTOR:ADDRESS:
PROJECT TITLE: Replace Circuit 7, Overhead to UndergroundPROPOSED TOTAL CONTRACT PRICE:
PURCHASE REQUEST NUMBER:PROJECT NUMBER: VNVP 1310061WORK LOCATION: Sheppard AFB, TX
MATERIALLABOREQUIPMENTTOTAL
Bid ItemDescriptionQty.UnitCost / UnitTotal CostCost / UnitTotal CostCost / UnitTotal CostCost / UnitTotal Cost
CIRCUIT 7
Total Length:15,203LF
Total Bore Length:927LF
Total Trench Length:14,178LF
Total Trench Volume:12,590CY3.008.00
Asphalt Demolition:5,540SY
Concrete Demolition:737SY
Saw cutting Asphalt:4,313LF
Saw cutting Concrete:696LF
1SITE WORK
Pavement
Saw Cut Asphalt PavementLF
Saw Cut Concrete SidewalkLF
Remove Concrete SidewalkSY
Remove Load & Haul Asphalt PavementCY
Scarify Compact Subgrade & Fine GradeSY
Sub Base, Type II AggregateCY
Bituminous Surface - RepairSY
Replace Concrete SidewalkSF
SUB TOTAL
11ELECTRICAL
Demolition
Remove Primary Circuit Pole, Incl. AppurtenancesEA
Remove Primary Circuit AerialLF
Remove Communication Aerial (Tele, Fiber & CATV)LF
Remove Pole Mounted Light FixtureEA
Remove Conductor In Existing ConduitLF
Abandon ManholeEA

Remove Vacuum Circuit Breaker, Class 15kv, Incl Support, Wire & Conduit Termination EA

Transformer, Demolition
Transformer, 5 Or 15 kV Primary, 208/120 V Secondary, 112.5 kVA, Electrical Demolition, Remove, Incl Support, Wire & Conduit TerminationEAR33.55.714
Transformer, 5 Or 15 kV Primary, 208/120 V Secondary, 150 kVA, Electrical Demolition, Remove, Incl Support, Wire & Conduit TerminationEAR33.55.714
Transformer, 5 Or 15 kV Primary, 208/120 V Secondary, 225 kVA, Electrical Demolition, Remove, Incl Support, Wire & Conduit TerminationEAR33.55.714
Transformer, 5 Or 15 kV Primary, 208/120 V Secondary, 300 kVA, Electrical Demolition, Remove, Incl Support, Wire & Conduit TerminationEAR33.55.714
Transformer, 5 Or 15 kV Primary, 208/120 V Secondary, 500 kVA, Electrical Demolition, Remove, Incl Support, Wire & Conduit TerminationEAR33.55.714
Transformer, 5 Or 15 kV primary, 277/480 V Secondary, 150 kVA, Electrical Demolition, Remove, Incl Support, Wire & Conduit TerminationEAR32.77.407
Transformer, 5 Or 15 kV Primary, 277/480 V Secondary, 225 kVA, Electrical Demolition, Remove, Incl Support, Wire & Conduit TerminationEAR32.38.696
Transformer, 5 Or 15 kV Primary, 277/480 V Secondary, 500 kVA, Electrical Demolition, Remove, Incl Support, Wire & Conduit TerminationEAR31.4513.793
Transformer, 5 Or 15 kV Primary, 277/480 V Secondary, 750 kVA, Electrical Demolition, Remove, Incl Support, Wire & Conduit TerminationEAR31.3315.038
Transformer, 5 Or 15 kV Primary, 277/480 V Secondary, 1000kVA, Electrical Demolition, Remove, Incl Support, Wire & Conduit TerminationEA
Apparatus
Transformer, 15kV, 3 Phase, Oil-Filled, Pad Mounted, With Taps
480/277V Secondary, 150 kVAEA
480/277V Secondary, 225 kVAEA
480/277V Secondary, 300 kVAEA
480/277V Secondary, 500 kVAEA
480/277V Secondary, 750 kVAEA
480/277V Secondary, 1000 kVAEA
208/120V Secondary, 500 kVAEA
208/120V Secondary, 300 kVAEA
208/120V Secondary, 225 kVAEA
208/120V Secondary, 150 kVAEA
208/120V Secondary, 112.5 kVAEA
208/120V Secondary,167 kVA SPEA
240V Secondary, 25 kVA SpEA
Switching
Vacuum Circuit Breaker, Class 15kv, Sectionalizing Gear Pedestal & Concrete SurroundEA
Apparatus Grounding
Cad WeldEA
CU Bare Conductor 1/0LF
Ground Rod 3/4" x 10'EA
Trench & Backfill Machine Chain TrencherLF
Transformer & Switch Pads 6'X6'X8"EA
Clear & Excavate For PadEA
Edge FormLF
Reinforcing SteelLB
Place & Finish ConcreteCY
Areal Extension
Utility Pole, 40'EA
Cross Arms w/ Hardware & Insulators, 6'EA
InsulatorsEA
Fused Cut Out 15 KvEA
Pole Riser Conduit Assembly w/ Weather HeadEA
Primary Duct Bank & Distribution
Clearance & Excavation
Excavating, Trench Common Earth, 3/4 C.Y.BCYB13G2120.075
Backfill, 1 C.Y. Bucket, Minimal Haul, Front End Loader, Wheel MountedCYB10R4000.02
For Tamping Backfilled Trenches, 6" Lift, Air Tamped, AddECYA1G1000.08
Backfill & Compact, By Hand, 12" Layers, Compaction In Layers, Hand Tamp, Add To AboveECY1 Clab340.235
Trench Bedding, Dead Or Bank Sand, Spread Excludes CompactionCYB156000.047
Add For Crossing Under UtilityEA
Dewatering, PumpDAYB10H42
Load Haul & WasteLCYB34A880.091
Duct
Underground Tape, Detectable, Reinforced, Aluminum Foil Core, 2"CLF1 Clab1500.053
Electrical Underground Duct Banks Ready For Concrete Fill, PVC, Type EB, 2 @ 5" Diameter, Excludes Excavation, Backfill & ConcreteLF2 Elec1600.1
Electrical Underground Duct Banks Ready For Concrete Fill, PVC, Type EB, 4 @ 4" Diameter, Excludes Excavation, Backfill & ConcreteL.F.2 Elec800.2
Concrete Fill Duct BankCYC6242
Hand Excavate & Connection Existing Long Rad Eles To New Primary @ TransformersEA
Incoming Duct New Configuration @ Existing Transformer PadEA
Manholes
Electrical Underground Manhole, Precast w/Iron Racks & Pulling Irons, C.I. Frame & Cover, 7' x 7' x 7' Deep, Excludes Excavation, BackfillEAB131.925.263
Comm Manhole, Precast w/ Iron Racks & Pulling Irons, C.I. Frame & Cover, 4' x 6' x 7' Deep, Excludes Excavation, BackfillEAB13224
Electrical Manhole Precast Concrete, w/ Concrete Cover, 4'x4'x4' Deep, Excludes Excavation, BackfillEAR31.414.286
Ground Rod & ConnectionEA
Bore & Jack HorizontalLF
Directional Drilling, Mobilization & Demobilization Includes PitsEAB82A132
Directional Drilling, Hard Clay, Cobble Per Linear Feet, 18" DiameterLFB82B1450.221
Directional Drilling, Hard Clay, Per Linear Feet, 24" DiameterLFB82B1050.305
Horizontal Boring, Jack, Casing 1/2" Thick Wall, 24" DiameterLFB42202.8
Conductor
Medium-Cable Single Cable, Copper, XLP Shielding Concetric neutral , 15 kV, 500 kcmil, In Conduit, Excl Splicing & TerminationsCLF3 Elec3.66.667
Medium-Cable Copper, PVC Jacket, 15 kV, single Conductor, XLP Shielding Concetric neutral , 15 kV #2LF2 Elec2600.062
Cable Terminations, Outdoor Systems, 15 kV, 500 kcmil To 750 kcmil StrandedEA1 Elec4.61.739
Cable Terminations, Outdoor Systems, 15 kV, #2 to 4/0 StrandedEA1 Elec4.81.667
Cable Terminations Secondary ReconnectEA

Communication Cable & Fiber By Others NIC

Site Lighting
Light Pole Base 24" Dia X 8'LS
Light Pole 30' SteelEA
Light Pole 20' SteelEA
Ground Rod & LeaderEA
Fixture ArmEA
Underground Street Light Circuit
Trench & Backfill Machine Chain TrencherLF
PVC Conduit w/ FTGS 1-1/4"LF
Conductor #4, Copper, XLP ShieldedLF
Conductor #12, Copper, XLP ShieldedLF
Reinstall Salvaged FixtureEA
Light Fixture ARE-EDG-2M-DA-60-D-BZ-350EA
Light Fixture MLED-BOUL-5K-M-BZ-PRU-SPEA

SUB TOTAL

TOTAL DIRECT COST
SUBTOTAL
OVERHEAD
PROFIT
BONDS
TOTAL PROJECT COST

NOTE: The items listed above are based on recommendation only, and items may be added or deleted as necessary. Page &P of &N

File details come from the government source that posted it. Updated .